FUNCTIONAL TEST RTU LBS

MERK Kwang Myung


TIPE
PROTOCOL DNP 3. comm : 9600 bps 8N1 solicited

ADDRESS DEFAULT HASIL TEST


No. FUNGSI A/NA CLASS
TM TSS TSD TC INTERNAL VALUE OK NOT KETERANGAN

A. TELE STATUS
1 LOCAL / REMOTE 0 1 L/R
2 STATUS CB (NO/NC/INV) 1/2 1 OPEN/CLOSE/INV NO/NC/INVALID
3 SF6 GAS PRESSURE LOW (DI_6) 3 1 NORMAL/ALARM
4 FAULT INDICATOR PHASA R 4 1 NORMAL/ALARM OC set arus 300A
5 FAULT INDICATOR PHASA S 5 1 NORMAL/ALARM EF set arus 40 A dan 2A
6 FAULT INDICATOR PHASA T 6 1 NORMAL/ALARM
7 FAULT INDICATOR PHASA N 7 1
8 FAULT INDICATOR UNBALANCE 8 1 NORMAL/ALARM
9 LOCK MEKANIK (DI_5) 9 1 LOCK/UNLOCK
10 110/220 AC FAULT 10 1 NORMAL/ALARM Supply AC hilang, Tegangan Battery Normal

11 24 VDC BATTERY = 0 11 1 NORMAL/ALARM Supply AC normal, Tegangan Battery 0

12 24 VDC BATTERY DROP <80% 12 1 NORMAL/ALARM Supply AC hilang, Tegangan Battery drop

13 DOOR SWITCH (DI_7) 13 1 BUKA/TUTUP


14 HOT LINE TAG * 14 1 ON/OFF
B. TELE CONTROL 1 Maksimal 6 detik
1 CONTROL OPEN/CLOSE 0 Obj : 12 Var :1 Pulse on / pulse on close Direct
2 CONTROL RESET / AUTORESET 1 Obj : 12 Var :1 Pulse off / pulse on trip Direct
3 CONTROL HOT LINE TAG * 2

C. TELE METERING
1 CURRENT PHASA R 0 2 DESIMAL Floating point
2 CURRENT PHASA S 1 2 DESIMAL Floating point
3 CURRENT PHASA T 2 2 DESIMAL Floating point
4 CURRENT AVERAGE * 3 2 DESIMAL Floating point
5 VOLTAGE PHASA R-N 4 2 DESIMAL Floating point
6 VOLTAGE PHASA S-N 5 2 DESIMAL Floating point
7 VOLTAGE PHASA T-N 6 2 DESIMAL Floating point
5 VOLTAGE PHASA R-S 7 2 DESIMAL Floating point
6 VOLTAGE PHASA S-T 8 2 DESIMAL Floating point
7 VOLTAGE PHASA T-R 9 2 DESIMAL Floating point
8 COUNTER OPERATION 10 2 DESIMAL Floating point
9 FAULT CURRENT PHASA R 11 2 DESIMAL Floating point
10 FAULT CURRENT PHASA S 12 2 DESIMAL Floating point
11 FAULT CURRENT PHASA T 13 2 DESIMAL Floating point
12 FAULT CURRENT PHASA N 14 2 DESIMAL Floating point

D. LAIN - LAIN
1 SECTIONALIZER (Volt dan Fault Count) sensing arus dan tegangan
2 MAPPING DATABASE CONFIGURABLE Menyeleksi point aktif
3 SYNC TIME PROTOCOL
4 RECORD 32 EVENT

Catatan :
Address RTU : 1 / 2
: Untuk diisi dengan address point SCADA
Tgl uji : Bandung : 26 Mei 2016
Software uji : PENGUJI PLN APD JBB
Alat Uji :

Supplier / vendor : PENGUJI 1 :


PT. MARINA ...............................

PENGUJI 2 :
...............................

(Dimas Lintang A.N S.Kom) PENGUJI 3:


...............................