Project:

Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model GFY
Wye-delta Open
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers covered under our standard
offering. Actual AS BUILT drawings may differ from what is shown in this package. 2018-2019

August 2018
Technical Data
Model GFA Electric Fire Pump Controller

3L3 1M T3
From normal incoming 3L2 T2
power through 3L1 T1
Disconnecting Means
M
CR4
(IS/CB) 1M 2M T5 2018-2019
CR5 1S T4
2M
T6
CR5 2M
3L1
1S
1S

3L2

Standard & Built to NFPA 20 (latest edition)


Certification □ CE Mark: Various EN, IEC & CEE directives and standards
Protection Rating
IP55

Enclosure Paint Specifications


Accessories • Red RAL3002
• Bottom entry gland plate • Powder coating
• Glossy textured finish

• Isolating switch and circuit breaker:


Isolating switch rated not less than 115% of motor full load current
Disconnecting Circuit breaker continuous rating not less than 115% of motor full load current
Means Overcurrent sensing non-thermal type, magnetic only
Instantaneous trip setting of not more than 20 times the motor full load current
• Individual operating handles
• Flange mounted
Emergency Start • Pull and latch activation
Handle • Integrated limit switch
• Across the line start (direct on line)
• Operate shunt trip to open circuit breaker
Locked Rotor • Factory set at 600% of motor full load current
• Trip between 8 and 20 seconds
Electrical • Voltage phase to phase (normal power)
Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings

This is a Marketing document. Please consult factory for more information.


August 2018 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GFA Electric Fire Pump Controller

• Pressure readings with date stamp


Pressure and • Event recording with date stamp
Event recorder • Under regular maintained operation, events can be stored in memory for up to 5 years.
• Data viewable on operator interface display screen
• Pressure transducer for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (calibrated at 0-300psi)
• Externally mounted with protective cover
• Power available • Phase unbalance • Deluge valve start
• Phase reversal • Locked rotor • Remote automatic start
• Motor run • Fail to start • Remote manual start
Visual Indications
• Pump room alarm • Low discharge pressure • Overcurrent
& Alarms
• Motor trouble • Pump on demand/Automatic start • Undercurrent
• Phase loss • Emergency start • Undervoltage
• Low water level • Manual start • Overvoltage
SPDT-8A-250V.AC
• Power available
• Phase reversal
Remote Alarm • Motor run
Contacts • Common pump room alarm
• Overvoltage • Undervoltage • Phase unbalance
• Common motor trouble
• Overcurrent • Undercurrent • Fail to start
• Embedded microcomputer with software PLC logic
• 4.2” color touch screen (HMI technology)
ViZiTouch Light
• Upgradable software
Operator Interface
• Expandable storage
• Multi-language
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Start pushbutton
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer **
• Minimum run timer **(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Manual test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

** Can only be used if approved by the AHJ

August 2018 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GFA Electric Fire Pump Controller

D14 Anti-condensation heater & thermostat

L01 Other language and English (bilingual)


L02 French
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


August 2018 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GFA Electric Fire Pump Controller

ViZiTouch Light Operator Interface

3
1

BLACK PANTONE 82-3-2 C

4 5 6 7 8
8

9
10

11 12

1 - Power on LED 8 - USB port


2 - Color touch screen 9 - START button
3 - Alarm LED 10- Contextual navigation pad
4 - HOME page button 11 - STOP button
5 - ALARM page button 12 - RUN TEST button
6 - CONFIGURATION page button
7 - HISTORY page button

August 2018 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
0 1 2 3 4 5 6 7 8

Electric Fire Pump Controller Optional

A
Reduced Voltage / Wye Delta (Open Transition) Model: GFY
REV.
0. FIRST ISSUE
DESCRIPTION DD/MM/YY
04/02/16 Drawing No.
A
1. TITLE BLOCK INFORMATION CHANGED 11/11/16
Dimension Built as per NFPA 20-2013 standard GFY-DI501 /E
GFX-S1-ViZi

834 [33"]
300 [113
4"]
19 [3
4"]
B 1"]
750 [292 B

25 [1"]

C C
See Notes

PT1
Power Table
1"]
900 [352
D D
1"]
1002 [392
Voltage Min Max
1

1"]
493 [192 O .

50 HP 100 HP
E 220 - 240 E

30 kW 55 kW

75 HP 150 HP
Door Swing 380 - 400 - 415
F F
988 [39"] 55 kW 110 kW
1"]
85 [34

29"]
23 [32
1"]
80 [34

G G
194 [73
4"]
325 [123
Notes:
4"] 1"]
140 [52
- IP55 assembly.
- All dimensions are in millimeters [Inches].
- Center of ViZiTouch screen: 582 [23"] from bottom.
- Paint: textured red RAL 3002.
H - Bottom conduit entrance through removable gland plate recommended. H
350 [133
4"] 200 [8"] - Use watertight conduit and connectors only.
- Protect equipment against drilling chips.
- Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
I I
PROJECTION

0 1 2 3 4 5 6 7 8
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
P.1
0 1 2 3 4 5 6 7 8

ELECTRIC FIRE PUMP CONTROLLER


VER DESIGNED BY

A
REDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION) Model: GFY
REV.
0. FIRST ISSUE
DESCRIPTION DATE
12/09/12 Drawing No.
A
Wiring schematic BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
1.
2.
REMOVED SURGE ARRESTER
Révision du logo
13/04/23
18/06/15 GFY-WS500 /E
GFX-S1-ViZi

1L1
1L2 J11 P1 To I/O Relay Board P1
B RS485
1L3

J6 P1
(P.2 / G5)
3
To J45
(P.2 / F4)
2
Main Board
C P2 C
J3

(+) J16
(-)

D
J13 J14
3L3

COM

COM

COM

COM

COM

COM

COM

COM
GND
24V
3L2
To J57 (P.2/F8)

DI0

DI1

DI2

DI3

DI4

DI5

DI6

DI7
3L1

E
3L1
3L2
3L3
20 21

17 18 19
F

3L1 (P.2/D5)
64 Black
65 White
G G
66 Black
67 White To J76 (P.2/F6)

68 Black
69 White

I Drawing for information only.


Manufacturer reserves the right to modify this drawing whitout notice.
Contact manufacturer for "As Built" drawing.
** Contact closes when emergency starts is in "ON" position.
0 1 2 3 4 5 6 7 8
P.2
0 1 2 3 4 5 6 7 8

ELECTRIC FIRE PUMP CONTROLLER


VER DESIGNED BY

A
REDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION) Model: GFY
REV.
0. FIRST ISSUE
DESCRIPTION DATE
12/09/12 Drawing No.
A
Wiring schematic BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
1.
2.
REMOVED SURGE ARRESTER
Révision du logo
13/04/23
18/06/15 GFY-WS500 /E
GFX-S1-ViZi

C C

D XTR1
1
X1 H2
24VAC
3L2 To
1M White 3 X2 H1 3L1-2-3
3L1 (P.1 / D1)
Green

Black
White
Black

To
To ST
Red

CT1-2-3
1M Red
E (P.1 / C1) (P.1 / G3)
3L1 To CR4
(P.1 / F1)
Green

White

White
White
Black

Black

Black

3L2
3L2

3L1
3L1
3L3
Red
Red

Red

1
3
3
2

67
69
68

66
65
64
7 5 3 1 7 6 5 4 3 2 1
PT1-IN

PT2-IN

2 1
14
11
12

12
11
14

12
11
14

AI4-IN

AI3-IN

SV1

GND

GND

REC
J8
(+)

(+)

(+)

(+)

ST2
(-)

(-)

(-)

(-)

N
L
J57

+
8 6 4 2
G

F
J18 J36 J38 J1
J76 J53
J14 J15 J16 J17 J43 J45 J44 J47

I/O Relay Board To ViZiTouch P1


(P.1 / H5)
Main Board
G G
(Fail Safe)
J25
J19 J40 J42 J37 J39 J41
TB1 TB2 TB3 TB4 TB5 21 23 25 27 29 31 33 35 37
22 24 26 28 30 32 34 36 38
14
11
12

14
11
12

14
11
12

14
11
12

14
11
12

14
11
12

LS1 White White


H
Black Black
J1* J2*

e
t
ou

rt

w
rt

alv
Sta
Sta

Lo
ck
rm

eV
v.
n

le
ble

Lo
Ru

ir
Re

ub

al

to

rvo
A la

lug
ila

nu

Au
Tro
tor

se
De
se

Ma
va

te
om

Re
Mo

mo
a
rA

te
tor
Ph

Ro

ter
mo

Re
we

Mo

Wa
Re
mp
Po

I
Pu

* Remove this jumper to use this feature


** Contact closes when emergency starts is in "ON" position.
0 1 2 3 4 5 6 7 8
P.3
0 1 2 3 4 5 6 7 8

ELECTRIC FIRE PUMP CONTROLLER


VER DESIGNED BY

A
REDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION) Model: GFY
REV.
0. FIRST ISSUE
DESCRIPTION DATE
12/09/12 Drawing No.

Terminals diagram BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD


1.
2.
REMOVED SURGE ARRESTER
Révision du logo
13/04/23
18/06/15 GFY-WS500 /E

Field Connections Field Connections Alarm Contacts


GFX-S1-ViZi

Terminals Wire Size:


Normal Power Connections Control Connections 12 - 24 AWG
0.5 Nm
B
Terminals Wire Size:
12 - 24 AWG
I/O Relay Board
0.5 Nm
Normally Closed
Opens to alarm J19 - 12
Incoming Power
I/O Relay Board Motor Run Normally Opened J19 - 11
Ground Closes to alarm
J19 - 14
23
Remote Manual Start
24 Normally Opened
Closes to alarm J40 - 12
25
Lockout Normally Closed J40 - 11
C L1 L2 L3 26 Power Available TB1
GND
(Fail Safe) Opens to alarm J40 - 14
IS 27
Remote Auto Start *J1
28 Normally Closed
29 Opens to alarm J42 - 12
2M 1M Deluge Valve *J2 Normally Opened J42 - 11
GND 30 Phase Rev. TB2
T6 T4 T5 T1 T2 T3 J25 Closes to alarm
31 J42 - 14
Water Reservoir Low
32
Normally Closed
33 Opens to alarm J37 - 12
D Normally Opened
34 Pump Room Alarm J37 - 11 TB3
M 35
Closes to alarm
J37 - 14
36
Normally Closed
37 Opens to alarm J39 - 12
38 Motor Trouble Normally Opened J39 - 11 TB4
Closes to alarm
J39 - 14

* Remove this jumper to use this feature

0 1 2 3 4 5 6 7 8