You are on page 1of 2

Doc.

No: CSPL/wld/03012013
WLD
Date: 14-JUN-2013
C Systems Pvt Ltd
Water Leak Detector MODBUS Issue Rev.: 1.01
Address Specification Page 1 of 1
Modbus Address:

Description Modbus Address Function Code R/W

4000 –

ZONE-1 Faulty/Healthy/ Isolate/ 0x03 R

Disable/Alarm

4001 –

ZONE-2 Faulty/Healthy/ Isolate/ 0x03 R

Disable/Alarm

4002 –

ZONE-3 Faulty/Healthy/ Isolate/ 0x03 R

Disable/Alarm

4003 –

ZONE-4 Faulty/Healthy/ Isolate/ 0x03 R

Disable/Alarm

Modbus Values:

Faulty - 0

Healthy - 1

Isolate - 2

Disable - 3

Alarm - 4
Doc. No: CSPL/wld/03012013
WLD
Date: 14-JUN-2013
C Systems Pvt Ltd
Water Leak Detector MODBUS Issue Rev.: 1.01
Address Specification Page 2 of 1

Gnd

A+

B-

Water Leak detection system mother board :

The product supports Modbus RTU protocol.

Default Speed is 9600 bps, stop bit 1, parity none, 8 data bit.

Set the slave ID in the site information menu.