Table 22.4.2.1
4 3

Table 22.4.2.1 — Shell to Shell Spacing


Fixed Roof & Horizontal
Diameter, ft. Floating Roof Tanks Class I /II Class IIIA
≤ 150 1/
6 ∑ adjacent diameters 1/
6 ∑ adjacent diameters
150 w/
remote 1/ ∑ adjacent diameters
1/
4 ∑ AD 1/
6 ∑ AD
6
impounding
open dike 1/
4 ∑ adjacent diameters 1/
3 ∑ AD 1/
4 ∑ AD

In no case is the separation allowed to be less than 3 ft.