Process Bus
- How to configure a distributed fault
recording application
Smart Infrastructure
SI EA PLM PROT HV
Humboldtstr. 59
90459 Nuernberg, Germany
Mobile: +49 162 25 82 134
mailto: markus.kraft@siemens.com
Smart Infrastructure
SI EA PLM PROT HV
Humboldtstr. 59
90459 Nuernberg, Germany
Mobile: +49 172 1534595
mailto: jose.malagon@siemens.com
2. Customer applications
a. 7KE85 internal trigger functions
b. 7KE85 starts recording by relay trip
7UT8
Applications
✓ Maintenance work on primary
6MU85
equipment
Feeder1_6MU85
The simulation bit support for GOOSE and SMV is implemented as described in IEC 61850.
1. As an example, the device can be set to
simulation mode using the IEC 61850 browser.
2. In this mode, the device works with the original,
non simulated signals (GOOSE/SMV) for as long
as it receives the same signals with the
simulation bit set generated from a test set.
3. Signals without a set simulation bit are still
processed from the original source.
The simulation signals and the real signals can be present in the network at the same time.
2. Customer applications
a. 7KE85 internal trigger functions
b. 7KE85 starts recording by relay trip
Port F:
Feeder 1
Station Bus
Process Bus
Network #4 14.4 kHz Port J:
Port F:
Port F:
Feeder2_6MU85
Feeder 2
Feeder 1
Station Bus
Process Bus
Network #4 14.4 kHz Port J:
Port F:
Port F:
Port E: Port E:
Process Bus Port F:
Network #2 4 kHz
Feeder2_6MU85
Feeder2 7SJ85
Feeder 2
2. Customer applications
a. 7KE85 internal trigger functions
b. 7KE85 starts recording by relay trip
Sources Destinations
(Publisher) (Subscriber)
7SJ85
6MU85
7KE85
6MU85
7SJ85
GOOSE/
Station Bus
7SJ85
6MU85
1. Customer applications
a. 7KE85 internal trigger functions
b. 7KE85 starts recording by relay trip
GOOSE/
Station Bus
Station Bus
Feeder2 7SJ85
Feeder2_6MU85
Test case 1: 7KE85 voltage max trigger FastScan Fault record visualisation
Test case 2: 7SJ85 OC (I >1.5A) -> GOOSE -> 7KE85 FastScan start in SICAM PQ Analyzer Last update MK 22nd Sept 2022
Test case 3: Communication Supervision -> GOOSE Stop
Page 28 Unrestricted | © Siemens 2022 | SI EA
Benefits on Distributed Fault Recording
Benefits
✓ No dedicated VTs and CTs
✓ No additional wiring
✓ 7KE85 subscribes SMV streams
✓ Pretesting during FAT
✓ Short time to operation
Network design
principles
✓ Process bus IEC 61850-9-2
✓ IEEE 1588v2/PTP
✓ Redundancy Protocol PRP or HSR
✓ IED for central tasks like 7KE85 or
7SS85 connected to process bus
Smart Infrastructure
Electrification & Automation
Mozartstraße 31 C
91052 Erlangen
Germany
For the U.S. published by
Siemens Industry Inc.
100 Technology Drive
Alpharetta, GA 30005
United States
© Siemens 2022
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or
performance features which may not always specifically reflect those
described, or which may undergo modification in the course of
further development of the products. The requested performance
features are binding only when they are expressly agreed upon in
the concluded contract.
All product designations may be trademarks or other rights of
Siemens, its affiliated companies or other companies whose use by
third parties for their own purposes could violate the rights of the
respective owner.