General information
Hardware product version 01
Engineering with
Programming package STEP 7 V5.4 SP2
Supply voltage
Rated value (DC) 24 V
24 V DC Yes
Input current
Current consumption (rated value) 650 mA
I²t 1 A²·s
Memory
Type of memory other
Work memory
integrated 256 kbyte ; For program and data
expandable No
Load memory
Plug-in (MMC) Yes
Backup
present Yes ; Guaranteed by MMC (maintenance-free)
CPU-blocks
Number of blocks (total) 1024 ; (DBs, FCs, FBs); the maximum number of loadable blocks
can be reduced by the MMC used.
DB
Number, max. 1023 ; Number band: 1 to 1023
FB
Number, max. 1024 ; Number range: 0 to 2047
FC
Number, max. 1024 ; Number range: 0 to 2047
OB
Size, max. 16 kbyte
Nesting depth
per priority class 8
S7 counter
Number 256
Retentivity
adjustable Yes
lower limit 0
preset 8
Counting range
adjustable Yes
lower limit 0
IEC counter
present Yes
Type SFB
S7 times
Number 256
Retentivity
adjustable Yes
lower limit 0
preset No retentivity
Time range
lower limit 10 ms
IEC timer
present Yes
Type SFB
Flag
Number, max. 2048 byte
Retentivity preset MB 0 to MB 15
Data blocks
Number, max. 1023 ; Number band: 1 to 1023
Local data
per priority class, max. 1024 byte ; per block max. 510
Address area
Outputs 2 kbyte
of which distributed
Inputs 2 kbyte
Outputs 2 kbyte
Process image
Inputs 2048 byte
Subprocess images
Number of subprocess images, max. 1
Digital channels
Inputs 16384
Outputs 16384
Analog channels
Inputs 1024
Outputs 1024
Hardware configuration
Expansion devices, max. 3
Number of DP masters
integrated 1
via CP 4
CP, point-to-point 8
CP, LAN 10
Rack
Racks, max. 4
Time of day
Clock
Hardware clock (real-time clock) Yes
Number/Number range 0
Granularity 1 hour
Clock synchronization
supported Yes
Digital inputs
integrated channels (DI) 0
Digital outputs
integrated channels (DO) 0
Analog outputs
integrated channels (AO) 0
Interfaces
Number of parallel interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Functionality
MPI Yes
DP master Yes
DP slave Yes
Point-to-point connection No
MPI
Number of connections 16
Services
PG/OP communication Yes
Routing Yes
S7 communication Yes
S7 communication, as client No
DP master
Transmission rate, max. 12 Mbit/s
Services
PG/OP communication Yes
Routing Yes
S7 communication Yes
S7 communication, as client No
SYNC/FREEZE Yes
DPV1 Yes
Address area
Inputs, max. 2 kbyte
DP slave
Transmission rate, max. 12 Mbit/s
Services
PG/OP communication Yes
S7 basic communication No
S7 communication Yes
S7 communication, as client No
DPV1 No
Transfer memory
Inputs 244 byte
2. Interface
Interface type PROFINET
isolated Yes
Functionality
DP master No
DP slave No
PROFINET IO Device No
Point-to-point connection No
PROFINET IO Controller
Transmission rate, max. 100 Mbit/s
Send cycles 1 ms
Services
PG/OP communication Yes
Routing Yes
S7 communication Yes ; With loadable FBs, max. configurable connections: 14, max.
number of instances: 32
Address area
Inputs, max. 2 kbyte
PROFINET CBA
acyclic transmission Yes
Communication functions
PG/OP communication Yes
S7 basic communication
User data per job (of which consistent), max. 76 byte ; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT
or X_GET as server)
S7 communication
supported Yes
as server Yes
User data per job, max. See online help of STEP 7 (shared parameters of the SFBs/FBs and
of the SFCs/FCs of S7 Communication)
S5 compatible communication
supported Yes ; via CP and loadable FC
Open IE communication
TCP/IP Yes ; via integrated PROFINET interface and loadable FBs
Data length, max. 1460 byte ; with connection type 01H; 8192 bytes with connection
type 11H
ISO-on-TCP (RFC1006) Yes ; via integrated PROFINET interface and loadable FBs
Number of connections
overall 16
usable for routing X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave
(active): max. 14; X2 as PROFINET: 24 max.
S7 message functions
Number of login stations for message functions, max. 16 ; Depending on the configured connections for PG/OP and S7
basic communication
Number of breakpoints 2
Status/control
Status/control variable Yes
Forcing
Forcing Yes
Diagnostic buffer
present Yes
adjustable No
Configuration
Configuration software
STEP 7 Yes ; V5.4 SP2 or higher
Programming
Command set see instruction list
Nesting levels 8
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
CFC Yes
GRAPH Yes
HiGraph® Yes
Know-how protection
User program protection/password protection Yes
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 460 g