Professional Documents
Culture Documents
Post Pandemic Hvac Systems Strategies For High Rise Office Buildings
Post Pandemic Hvac Systems Strategies For High Rise Office Buildings
org/papers
Authors: Mehdi Jalayerian, PE, Managing Director, Environmental Systems Design, Inc.
Tyler Jensen, PE, Studio Leader, Environmental Systems Design, Inc.
Kenneth Griffin, MBS, Senior Building Analyst, Environmental Systems Design,
Inc.
Subjects: COVID
MEP
Sustainability/Green/Energy
© Council on Tall Buildings and Urban Habitat / Mehdi Jalayerian; Tyler Jensen; Kenneth Griffin
MEP
“
Beyond disease mitigation, many building
operators have yet to focus on the Properly-designed air filters are highly
challenges of having low occupancy in
buildings, especially during the cold winter effective at removing airborne viruses. MERV
5 filters, typically used for residential
months, as many office workers continue to
work from home.
”
equipment and plug loads will be reduced
because the majority of the workforce is at percent of airborne particles.
home. Toilets will not be flushed as often,
E
AHU AHU
E
AHU AHU
E
AHU AHU
E
AHU AHU
E
AHU AHU
Decentralized Air Handling with Decentralized Air Handling with Centralized Air Handling System
Central Dedicated Outside Air System Local Air Intake and Exhaust
Figure 2. Three typical configurations for air-handling systems in commercial office buildings. © Environmental Systems Design, Inc., redrawn by CTBUH
Recirculated Air
Fresh Air AHU
Fresh Air
Supply
Supply Air
Air
Exhaust Air
Figure 3. Floor-by-floor air-handling units (AHUs) with central dedicated outside air (DOAS) and central exhaust systems. Left: Full floor-wide system view; Right: Detail at intake.
© Environmental Systems Design, Inc., redrawn by CTBUH
Although typically installed in the air 2). At the zone level, these arrangements They should consider air delivery schemes
handling unit, BPIs can also kill pathogens in can be coupled with conventional overhead that reduce local air mixing within the space.
the air and on surfaces in the space, not just or underfloor air-distribution systems.
at the AHU. Two configurations look to have the best
Traditionally, many tall office buildings have odds of achieving success. The decentralized
However, some BPI products generate utilized central air-handling systems with floor-by-floor AHUs eliminate air recirculation
harmful ozone, and there is a lack of scientific dedicated mechanical floors incorporating between floors and still enable air
data and testing protocols with which to large, built-up systems that serve groups of economizer/purge capability. They also
evaluate and compare technologies. These 20 to 30 floors. This approach reduces the provide the most rentable square footage
risks must be evaluated, but can be mitigated mechanical footprint on tenant floors, compared to other options. Underfloor air
to some extent. If BPI is used, proper centralizes maintenance, and delivers good distribution increases the number of space
specification to ozone-free Underwriters energy performance with a cost-efficient air changes per hour (ACH), while enabling
Laboratory (UL) standards is critical. Field HVAC system. High-performing buildings of air economizer/purge capability during
performance testing and validation to the future should be designed to address greater number of hours per year;
confirm the efficacy and proper operation of shifting demands—with the flexibility to significantly increases space ventilation
the installed product is also essential. efficiently respond to future pandemics, and effectiveness, with a single-pass airflow from
with HVAC systems that prioritize occupant floor to ceiling; and minimizes local air
health and wellness. (Of course, building mixing compared to the traditional overhead
Changes Ahead for Air-Handling Systems codes differ across the world and have mixing system.
limitations, so the following information may
A high-rise office building typically includes not represent “one-size-fits-all” solutions.) Other options are not as effective, but have
either a centralized or decentralized their benefits. In the traditional centralized
arrangement of its air handling systems. A To achieve these goals, high-performing AHU configuration, air is filtered prior to
centralized system provides ventilation and buildings should be configured with redistribution to the space, but it is recirculated
air conditioning to multiple floors. A mechanical systems that minimize or between all floors in the office stack that the
decentralized system arrangement will eliminate air mixing between floors. They air handling unit serves. With dedicated
include dedicated or direct outside air, as should optimize ventilation effectiveness outside air system (DOAS) and floor-by-floor
well as a relief/exhaust air system, and limits within the space, maximize fresh air volume systems, air recirculation is minimized to
the air recirculation to each floor (see Figure and provide economizer/purge capability. individual floors only (see Figure 3).
Figure 4. Decentralized floor-by-floor AHUs, with local outside air and exhaust with perimeter fan room.
Flexibility is also increasingly important
© Environmental Systems Design, Inc., redrawn by CTBUH
with so much uncertainty in the world.
Floor-by-floor systems provide the best
flexibility for single tenants and single floors
to operate their systems independently.
Recirculated Air
Ventilation, filtration, and advanced air
cleaning enhancements can be
implemented flexibly, depending on
individual tenant needs. And floor-by-floor
Supply
systems will be best-positioned to respond Air
and adapt to unknown future requirements. AHU
Excellent energy
Good energy Great energy performance
Good energy performance performance
Energy performance Full economizer
Reasonable economizer Full economizer capability
Performance Full economizer capability capability
capability Reduced fan energy
Reduced fan energy Reduced fan energy
Efficient zone distribution
Figure 6. View of a typical floor-by-floor AHU. Good system turndown
Great system turndown
© Environmental Systems Design, Inc. Low performing system Simple, efficient, cost
Simple, efficient, cost Adequate system
turndown effective afterhours
Operation effective afterhours turndown
Need to operate multiple operation
Flexibility operation Depends on system
floors to serve a single Need to run central DOAS
Fully independent from configuration
floor afterhours to serve a single floor
other floors
afterhours
Enables individual floor Enables individual floor
Operation
Figure 7. Three-dimensional view of an overhead Series flow FPBs provide Series flow FPBs provide Series flow FPBs provide Excellent thermal comfort
Thermal Comfort
good thermal comfort good thermal comfort good thermal comfort and local control
supply air system, showing air flow and temperature
Reduced AHU space
performance in a compartmented office space. Large AHU space Reduced AHU space
No AHU space required at required at mechanical
© Environmental Systems Design, Inc. required at mechanical required at mechanical
mechanical floors floors
floors floors
AHU room required at Small air column unit
Architectural Impact
Induced Return
Typical Floor Swirl Diffuser
Typical Return Air
Primary Air Return Riser
Air Column Mixing Box
Supply Fan
Primary Air Supply Riser
Figure 8. Diagram of an underfloor air-distribution (UFAD) system with a ceiling-based return air plenum. © Environmental Systems Design, Inc., redrawn by CTBUH
“
predominantly for owner-occupied buildings.
Rethinking the tenant improvement While overall installation cost is typically equal
or even less than traditional approaches,
allowance allocation could make UFAD systems UFAD systems push much of the first cost to
the base building rather than the tenant
feasible even in tall core-and-shell office buildout, which can be challenging from a
”
leasing standpoint.
buildings, and the IAQ benefits are clear.
Rethinking the tenant improvement
allowance allocation could make UFAD
systems feasible even in tall core-and-shell
contaminants and pathogens accumulate office buildings, and the IAQ benefits are clear.
above the occupants, limiting potential
exposure duration.
Intelligent IAQ Monitoring
With UFAD systems, particulates and
pathogens travel much more directly out of The COVID-19 pandemic has highlighted the
the space compared to traditional overhead importance of HVAC systems and indoor air
systems, where the air swirls and mixes as it quality as something that is front-of-mind for
leaves the space. CFD analysis shows the air all occupants in tall office buildings. The way
path of potential pathogens exhaled by an people live and work may forever be
occupant for both systems, with clear changed as a result of the pandemic, and
performance improvements for the UFAD office buildings will need to adapt in order
system (see figures 10 and 11). to prioritize the health, safety, and wellness
of tenants.
Raised-floor air distribution systems have
Figure 9. Three-dimensional view of an underfloor air been used since the 1950s in computer Even after the pandemic subsides, occupants
distribution (UFAD) system, showing air flow and tem-
perature performance in a compartmented office space. rooms to accommodate wiring distribution will be more finely attuned to a building’s
© Environmental Systems Design, Inc. as well as cooling. The system has also been IAQ, and will demand higher-performing