Professional Documents
Culture Documents
Bus Protection Fundamentals - Chang (Final)
Bus Protection Fundamentals - Chang (Final)
©ABB
September 30, | Slide 4
2013
Learning objectives
©ABB
September 30, | Slide 5
2013
Why bus protection?
©ABB
September 30, | Slide 6
2013
Bus fault protection
Easy to detect because of robust nature
Easy to protect for internal faults (87B)
Summation of currents not equal to zero for internal fault
External faults can cause current transformer saturation
which results in unwanted differential currents
Infrequent, but must be cleared with high speed
Substation is well shielded
Protected environment
©ABB
September 30, | Slide 7
2013
Bus configurations
Single bus *
Main and transfer bus
Double bus, single breaker *
Double bus, double breaker
Breaker and a half *
Ring bus *
©ABB
September 30, | Slide 8
2013
Single bus
©ABB
September 30, | Slide 9
2013
Main and transfer bus
©ABB
September 30, | Slide 10
2013
Double bus single breaker
©ABB
September 30, | Slide 11
2013
Double bus, double breaker
©ABB
September 30, | Slide 12
2013
Breaker and one half
©ABB
September 30, | Slide 13
2013
Ring bus
©ABB
September 30, | Slide 14
2013
Main-Tie-Main
©ABB
September 30, | Slide 15
2013
Some issues
©ABB
September 30, | Slide 16
2013
Zones of protection
Station A Station B
G
G
G
Station C
Bus
Station D
protection
M
©ABB
September 30, | Slide 17
2013
Zones of protection
CT for CT for
Green Zone Blue Zone
Green Zone
Blue Zone
Dead tank breaker,
two CTs
©ABB
September 30, | Slide 18
2013
Zones of protection
CT for
Green Zone CT for
Blue Zone
Green Zone
Blue Zone
Live tank breaker,
single CT
©ABB
September 30, | Slide 19
2013
Current transformer
Ratings of concern for bus protection
Ratio: 200/5, 1200/5, …500/1
Burden capability: VA burden
Accuracy Class: C800, K200, T400
Knee point, saturation voltage (can be derived from
chart in C class CTs)
CT availability
IEEE Standard C57.13-1993 (R2003), IEEE Standard
Requirements for Instrument Transformers
IEEE Standard C37.110-1996, IEEE Guide for the
Application of Current Transformers Used for
Protective Relaying Purposes
©ABB
September 30, | Slide 20
2013
ANSI current transformer accuracy class
©ABB
September 30, | Slide 21
2013
ANSI accuracy class
Standard chart for class C current transformers
©ABB
September 30, | Slide 22
2013
Knee point voltage
Knee point
Log-log plot
Square decades
I.e. (.01,1) – (.1,10)
Tangent 45º line (knee pt)
©ABB
September 30, | Slide 23
2013
Differential measurement difficulties
©ABB
September 30, | Slide 24
2013
CT saturation
©ABB
September 30, | Slide 25
2013
CT saturation
CT secondary model
a perfect current source (infinite impedance) in parallel
with an exciting impedance branch that drives
proportional current
Exciting impedance is normally very high
At saturation, exciting impedance drops to a very low value
the CT appears short-circuited
neither delivers nor resists current flow
Time to saturation is important in low impedance bus
protection
©ABB
September 30, | Slide 26
2013
Issues effecting bus protection selection
Bus arrangement
Fixed
Switchable
Availability and characteristics of current transformers
Performance requirements
Speed
Dependability
Security
Sensitivity (for high impedance grounded system)
©ABB
September 30, | Slide 27
2013
Types of bus protection
Differential
Differentially connected overcurrent
Percentage-restrained differential (low Z)
High impedance differential
Partial differential
Zone interlocked scheme
Back up schemes (eg. remote over-reaching zones)
©ABB
September 30, | Slide 28
2013
Differentially connected overcurrent relay
51
©ABB
September 30, | Slide 29
2013
External fault case
Protected Bus
= FAULT
LOCATION
IE
IT TOTAL OUT OF
TOTAL INTO BUS BUS MINUS IE
TOTAL OUT
OF BUS
Relay Id = I E
©ABB
September 30, | Slide 30
2013
Internal fault case
Protected Bus
I1 I2 I3 I4
Id
I d = I1 + I2 + I3 + I4
Overcurrent relay bus differential
Application OK if:
Protected bus
Symmetrical CT secondary current
less than 100
Burden less than rated
Typical pickup setting IPU > 10A
Trip delay greater than 3 x primary
time constant (L/R)
Id
©ABB
September 30, | Slide 32
2013
Resistor added to relay branch
External fault
Stabilizing
Total primary contribution resistor Rd
RS
to external fault IF (out) ZE = 0 Overcurrent
through saturated ct Id Relay
RS
I d = I F (in ) ⋅
RS + Rd IF (in) total from other
V (acc class)
Rd = CL cts
4 ⋅ I pu (min)
©ABB
September 30, | Slide 34
2013
Multiple restraint Percentage Differential (Legacy)
PROTECTED BUS
A B C D
©ABB
September 30, | Slide 35
2013
Torque for typical multi-restraint relay
Operating
Torque
Two Restraint
One Restraint
0 20 40 60 80 100
Amperes
©ABB
September 30, | Slide 36
2013
Torque for typical multi-restraint relay
55 A. of restraint overcomes 7 A
Operating of operating current with one
Two Restraint restraint winding
Torque
One Restraint
0 7 20 40 55 60 80 100
Amperes
©ABB
September 30, | Slide 37
2013
Multi-restraint percentage differential
Good sensitivity
Good security
Allows other relays on the same CT core
Different CT ratios with Aux CTs.
Slow compared to high impedance
Number of feeders limited by restraint windings
Each CT is wired to relay
©ABB
September 30, | Slide 38
2013
High impedance bus protection
High resistor (R > 1500 ohm) in
series with relay coil and a MOV to
prevent over-voltages
High voltage develops for internal
faults. lower Voltage will develop on
external faults where with ct
saturation
Voltage unit must be set higher than
the maximum junction point voltage
for any external fault
The lowest achievable sensitivity R
must verified for the application
Proven reliability and very sensitive
Operating times of less than one
cycle for internal faults
©ABB
September 30, | Slide 39
2013
High impedance bus protection
EXTERNAL FAULT - SECURITY
Setting VR > (IF / N ) ( RL +R S)
CTR
K = margin factor
IF = Max external fault current
RS = Ct secondary resistance
RL = Lead resistance to junction box
N = ct turns ratio
X = number of circuits N
IE = Ct exciting current at VR
IR = resistor current at VR
IV = Varistor current at VR R
R > 1500 W
©ABB
September 30, | Slide 40
2013
High impedance bus protection
Criteria to be met
Objective: Keep VR and Imin low
Ct secondary loop resistance kept low
Impedance from junction point to relay is of no consequence so
good practice to parallel the CTs as close to the CTs as possible.
Theoretically no limitations in the number of parallel CTs but
sensitivity reduced.
All cts should have the same ratio and magnetizing characteristics
©ABB
September 30, | Slide 41
2013
High impedance bus protection
Criteria to be met
Tapped CT’s may be interconnected with fixed ratio ct’s if
attention is given to the autotransformer effect and the
overvoltage protective characteristics of the relay
A voltage setting higher than the lowest of all of the relaying
accuracy class voltages of the CT’s used in the scheme (400 V
for a C400 CT). IE obtained from the excitation character
contains large errors
Voltage setting can be lowered by reducing CT lead resistance
©ABB
September 30, | Slide 42
2013
Differential comparator (Legacy, Static type)
RADSS/REB103
Developed to lessen restrictions
imposed by high impedance
All CT secondary circuits connected via
interposing cts
Connection made using a special diode
circuit producing rectified incoming,
outgoing and differential currents
AUX CTs
IOUT SR
IDIFF
DR
IIN
©ABB
September 30, | Slide 43
2013
Differential comparator
Single phase connection
AUX CTs
Start
IDIFF VOp
IOUT
VRes Trip
IIN
©ABB
September 30, | Slide 44
2013
Differential comparator
L1 L1
L2 L2
Internal
L3 L3
L4 L4
L1 L2 L3 L4
X
IIN IIN
External
IOUT IOUT
IDIFF IDIFF
External Internal
©ABB
September 30, | Slide 45
2013
Differential comparator
Single phase connection
IDIFF is typically small (normally 0) for
external fault and restraint voltage, VRes, is
greater than operating voltage, VOp.
IDIFF is typically large for an internal fault
and operating voltage, VOp, is greater than
restraining voltage, VRes. This produces
voltage across trip relay.
AUX CTs
Trip / LO
Start
IDIFF VOp Start
Trip
IOUT
VRes Trip
IIN
©ABB
September 30, | Slide 46
2013
Differential comparator
Lower ct requirements
Allows much higher ct loop resistances
Accommodate different CT ratios / auxiliary CTs
Fast operating times for internal faults
Detects internal 1 - 3 ms
Before ct saturation
©ABB
September 30, | Slide 48
2013
Numerical differential comparator
Analog input currents are instantaneously sampled and
quantized to numerical number
Similar technique to legacy differential comparator, but
with measured sampled data
Secondary circuit loop resistance no longer a critical
factor
Critical factor is time available to make the
measurement, i.e. time to saturation. (only 3ms
required to properly restrain for heavy external faults)
Algorithms for Ct saturation Detection and CT state
supervision
©ABB
September 30, | Slide 49
2013
Differential comparator
©ABB
September 30, | Slide 50
2013
Quick operation for internal fault
Internal Fault
16
14
0
1
6
11
16
21
26
31
36
41
46
51
56
61
66
71
76
81
Samples
©ABB
September 30, | Slide 51
2013
Proper & secure restrain during external fault
External Fault REB 670 detects this short
interval when i_in=i_out
(after every fault current
16
zero crossing) and restrain
properly during external
14 fault
0
1
13
17
21
25
29
33
37
41
45
49
53
57
61
65
69
73
77
81
Samples
©ABB
September 30, | Slide 52
2013
Fast open CT algorithm
REB 670 detects that
I_IN doesn't change while Open CT
I_OUT goes down when
1,6 some of the CTs is
open/short circuited
1,4
1,2
1
i_in
Diff Operation Level
Current
i_out
0,8 Must be set to higher
I_IN
ID>Open CT Level value than Open CT Level
0,6 I_OUT
second condition
fulfilled & REB is
0,4 blocked
0,2
0
1
13
17
21
25
29
33
37
41
45
49
53
57
61
65
69
73
77
81
Samples
©ABB
September 30, | Slide 53
2013
Other Features in Modern Numerical Bus IEDs
Each device capable of connecting multiple bays (eg. CTs) in 3-
ph or 1-ph design
Multiple differential zones, dynamic bay switching, zone
interconnection, and check zone logics
External fault/CT saturation detection, open CT detection
algorithms
Blind zone protection (see next 2 slides)
End zone protection (see next 2 slides)
Backup protection (eg. 50/51, 50BF) for each connected bay
Modern substation automation communication (DNP 3.0,
IEC61850)
©ABB
September 30, | Slide 54
2013
Blind zone detection
Blind zone between live tank CT and breaker
A fault in the blind zone makes operation in
ZA unnecessary (tie breaker normally open)
ZB cannot detect the fault
Solution: connect BKR NC (open) status to
the bay to remove this CT from ZA, ZB
(software)
Remove CT dynamically can force operation
of ZB
©ABB
September 30, | Slide 55
2013
End Zone Protection
Regions not overlapped by both red and
blue boundaries are blind zones
CTs are used for both feeder and bus
protection measurement (live tank CTs)
Common in HV 1-1/2 stations
Requires local backup (eg. BF) to trigger
DTT for 3
Requires remote back up (eg. zone 2) to
open local breaker and disconnect the CT
to clear bus zone for 4
©ABB
September 30, | Slide 56
2013
Other distribution (MV) bus protection methods
Partial differential
Blocking on feeder fault
©ABB
September 30, | Slide 57
2013
Partial differential
©ABB
September 30, | Slide 58
2013
Blocking scheme
©ABB
September 30, | Slide 59
2013
Conventional Blocking Scheme
Zone of protection
T+100 ms
Traditional busbar
I> 100 ms protection based on
I>> upstream blocking
blocking
Dedicated hard-wire
I> signal paths needed
I>> Signal path delay needs
to be considered, input
Delay setting with inst. O/C protection and output delay +
(conventional approach)
auxiliary relays
Safety marginal, e.g. delay in operation 20…40 ms
due to CT saturation.
Changes in the protection
O/C protection start delay + output relay’s <40 ms
delay scheme may require re-
Start delay with receiving relay + retarding <40 ms wiring
time for the blocking signal *)
©ABB
September 30, | Slide 62
2013
Questions?
Recommended reading
©ABB
September 30, | Slide 63
2013
Relion® REB650/670 Advanced Busbar Protection
Reliable protection and control of busbars
REB650 REB670
One IED for a wide range of high State of the art protection for medium
impedance differential protection to extra high voltage levels
applications
Selective, reliable and fast fault clearance for all types of internal phase-to-phase and
phase-to-ground faults in solidly earthed or low-impedance earthed power systems
Significant savings in configuration and commissioning with efficient system integration
and optimum “off-the-shelf” solutions and settings
Do more with less - the advanced logic and multipurpose functionality allow you to
customize protection schemes for multiple zones with a single IED
Maximize flexibility and performance with powerful application and communication
capabilities that allow you to integrate these IEDs into new or retrofit substation
automation systems or use them as stand-alone multifunctional units
©ABB
September 30, | Slide 64
2013
Thank you for your participation
Shortly, you will receive a link to an archive of this presentation.
To view a schedule of remaining webinars in this series, or for more
information on ABB’s protection and control solutions, visit:
www.abb.com/relion
©ABB
September 30, | Slide 65
2013