ALSTOM
Protection & Control
Course PC3, Dubai
Application of Protective Relaying to
- Distribution and Sub-Transmission Systems
25" - 29" March 2000
Analysis of Unbalanced Faults
~ (Additional Notes)
AISTOM TSO Protection & Conta id
Ragintred Ofc
ngland No. 959256Page 2
ANALYSIS OF UNBALANCED FAULTS
2.1
INTRODUCTION
In a balanced three-phase system, each of the three phases of any
part of the system will have currents and voltages which are equal
and 120° displaced with respect to each other. To maintain balanced
operation, each item of system plant must be symmetrical: i.e. have
identical impedances tn each line, equal mutual impedances between
phases and ground, and equal shunt admittances to ground. This is
the case for machines and transformers, and it is also valid for
Vines if they are fully transposed.
Three phase faults with symmetrical fault impedances leave the system
in balanced operation. Such faults can be analysed using the simple
single phase representation. However» these faults are rare.
The majority of faults occur between one line and ground, or between
two lines and ground. These are asymmetrical or unbalanced faults.
They arise from lightning discharges and other overvoltages which
initiate flashovers followed by power arcs ; or they may arise from
mechanical causes such as birds on overhead lines or mechanical
damage to cables, etc. Another type of unbalanced fault which is of
interest are the open circuit faults. They can arise from broken
conductor, maloperation of single phase switchgear or the operation
of fuses.
During unbalanced faults, the symmetry of the system is lost and the
single phase representation used for three phase balanced faults no
longer applies.
SYMMETRICAL COMPONENTS METHOD
Fortescue discovered a property of unbalanced phasors and introduced
the method of symmetrical conponents.
phasors may be resolved into (n-1) sets of balanced n-phase systems
of different phase sequence and one set of zero-phase sequence or
unf-directional phasor systen.
Consider n-dimensional system of phasors.
Where Vay» Vpjr etc.» are phasors of the first set of balanced
n-phase system. Phasors are single spaced.
Vagt Vyge @te-s are phasors of the second set of balanced
n=phase system. Phasors are double spaced.Page 3
-
And so on.
Van? Vpn? etc-» are phasors of the uni-directional phasor
system.
Take for example an unbalanced S-phase system. V+ Vur Vor Vgr Ver
% Var Vos
V3
he Ve he . he Ves
J Ve
Va, Vow Vex Vow Ves Go ~
FIRST SET OF SECOND SET OF THIRD SET OF
BALANCED PHASORS BALANCED PHASORS BALANCED PHASORS
Va
hack Vas
%
Vow Nes
ea. “fy Nas
Gm
Vea Vie
FOURTH SET OF FIFTH SET OF
BALANCED PHASORS ZERO SEQUENCE PHASORS
2.2 Now consider an unbalanced three phase system. V.» Vir
Ya = Yar * Yan + Vag
y,
bt * Yo2 * Yb3
Yo = Vey + Veg + ¥,
c 3
Van Var Vas
Z Mo 3
Vey Vey Ver, Mer
POSITIVE NEGATIVE ZERO
SEQUENCE ‘SEQUENCE SEQUENCE —Page 4
Three unbalanced phasors have been resolved into nine phasors.
Choose "at phase as the reference phase and replace V3 by Vag-
Ya = Yan * Yar + Yao
2,
Vy = Var t Yao * Vag
2,
Yo = Mar * “Yaz * Yao
where == 1.0 £120°
It is convenient to delete subscript 'a' for the symmetrical
components.
Var tly tM 1
1 tay + Vo 2
Vee ay t22V) + Uy 3
Add equations 1, 2 and 3
Vat My to = 3%
4
te Wy =z Wty +)
Multiply equation 2 by sand equation 3 by x” and add the resulting
equations to equation l,
2,
VY, te¥y to2V, = 3Vy
= 2,
fe MEMS tay + o2¥)
Multiply equation 2 by a2 and equation 3 by x and add the resulting
equations to equation 1,
2, :
Vat 7, + eV, = BY)
= 2, a
se Wye 3 + c7V, tev)
Equations 1 to 6 can be re-written in matrix form.Yo
8
&
R
x
2
wr
g
v.
v
y,
v
Ry k
|
Re-write matrix equations 7 and 8 respectively as
[re] =f] [vs]
“1
Es} “La}L]
Where Vp
10
phase components
= sequence components
hia
A» 1 of «
ria &
Raid
=afir ia 2
Plo
2.3. Example
Resolve the following 3-phase unbalanced voltages into their
symmetrical components.
o Ve
Ye = 120% °
120
= 1,5 290°
oo
= 0.5 /4120°
Page 5Solution :
V,= 1+ 40
ly = O- ils
Yo = 0.5 (-0.5 +j0.86)
= -0.25 + j0.433
Yap Vy CV tay + fv 7
ar 3 CV, tah + eV,
= 3 C (1 + JO) + (-0.5 450.866) (0 = 1.5) +
(-0.5 ~J0.866)(-0.25 +50.433) J
= V3 (2.798 + 50.75) = 0,965 15°
2
a2 V3 CV, + fv, tov]
= 3 C (1D + (-0.5 ~j0.866)(-J1.5) +
(-0.5 +40.866)(-0.25 +J0.433) J]
(3 (-0.548 +j0.318) = 0.211 150°
Yo M3 Wt ¥y + Vd
20 ~ 3
= Wz C (1 + JO) + (0 ~ j1.5) + (-0,25 440.433) ]
= 1/3 (0.75 = §1.067) = 0.434 7-55°
2
Yor = Mar
= 1 240° x 0.965 715° = 0.965 255°
Yoo = “Mar
= 1 £120° x 0,211 750° = 0.211 £270?
Yoo = Yao
= 0.434 /-55°
Yor = “Yar
= 1 20° x 0.965 715° = 0.965 135°
2d
Nog * Vaz
= 1 @40® x 0.211 150° = 0,211 390°
Yeo = Yao
= 0.434 /-55°
Figure 1 shows the sequence components of the phase voltages.
Page 6Page 7
Fig. |
STMMETR ICAL
COMPONENTS3.
Page 8
SYMMETRICAL COMPONENT TRANSFORMATION
Zs
\Yo——As 4 }—_—__——_o
2,
2s yen eum
Vo- Ze
Bm
on)
—_——_ +
FIGURE 2
Take a set of symmetrical three phase impedances (equally spaced,
fully transposed, etc.) carryng unbalanced phase currents I, I, and
I
We may write the following equations.
Zlqt %qly + Zale
Zl t Zelp + Zale
Vo = Zqla + Zqly + Zl
Where Z. = self impedance per phase
2, = mutual impedance between any
m phase pair
Or, in matrix formPage 9
Re-arrange
ll
Therefore, if the system 1s symmetrical in its normal state the
eyametr ical component impedance becomes diagonal (equation 11) and,
Gherefore, isolated sequence networks are obtained with impedences
211 Zz and Zp. These three networks will become intercomecten
sper an unbalance such as a fault or unbalanced loading is
iatreduced. The manner of interconnection will depend’on the new
constraints: i.e, the additional system connections.41
42
Page 1¢
PLANT IMPEDANCE DATA
For static networks i.e. non-rotating plants, the positive and
negative sequence impedances are the same. These are the leakage
impedance of the transformers and the normal phase impedance of the
transmission circuits.
Zero sequence impedance of overhead line and cable circuits ts
determined by the return path of the zero sequence currents through
earths earth wires or cable sheaths. The zero sequence impedance is
generally greater than the positive and negative sequence impedance,
being usually of the order of two to three tines the positive
sequence value in the case of overhead lines.
For transformers, if zero sequence currents have an available path
and can flow, they wil] again see the leakage reactance in each
phase. If no path exists, an open circuit mst be shown for the
particular windings in the zero sequence network. The flow of zero
sequence current in any winding is possible only if other windings
provide @ path for the flow of balancing zero sequence currents.
Consider the transformer equivalent circuit in Figure 3 overleaf. The
magnetising. impedance Z, is of the order of 20008, compared to the
Teakage Impedance 2), + 2,, of about 10%, Therefore, magnetising
impedance can be ignored and the transformer can be represented in
the positive and negative sequence networks by a series impedance
G2, +2.)
z Zeus 21) = primary winding
P Jeakage impedance
21, = secondary winding
Zam Teakage impedance
Z, = magnetising
‘impedance
FIGURE 3. TRANSFORMER EQUIVALENT CIRCUIT
In the zero sequence network, although the leakage impedance is
identical to the positive sequence value (when zero sequence path is
available) the zero sequence magnetising impedance is dependent upon
the transformer core construction and can be much lower. In
three-phase banks of single phase transformers and in three-phase
shell cored transformers, the zero sequence magnetising impedance is
large and can be ignored as in the positive and negative sequence
networks. In three-limb core type transformers, however, the zero
sequence flux must be completed through the oi] or tank. Owing to
the high reluctance of the flux path, zero sequence magnet ising
impedance is of the order of only 1008 to 400%. However, this is
stil] high enough to be neglected in most fault studies, particularly
when a delta winding is present.
Therefore, consider zero sequence circuit of transformer as a series
impedance Z,. The mode of connection of Z, to the external circuit
is determined by taking account of each winding arrangement and its
connection or otherwise to ground.Page 11
Imaginary Tinks ‘a! and 'b! (see Figure 4) are used to derive the
windings res gif z@r@ sequence currents can flow into and ove eros
{indingy for example a solidly earthed star windings the winding
iqgasga! 1s connected to the external circuit, that ts Tink warts
closed,
Ze a
I I oO
B “BI
FIGURE 4
Tf zero sequence currents can circulate in the winding without
flowing in the external circuit, for example a delts winding, the
wpneao terminal 1s directly connected to the zero busy ther fe Vink
'b' 1s closed.
Example 1
Transformer Connections
Zero Sequence Equivalent
Circuit Connections
The zero sequence impedance of a neutral earthing impedance z, 1s
32,- The reason for this can be read!ly understood from Figure 5
below
ae nt
b nm
= 3to a2
Y, By =~ Zero Sequence Circuit
FIGURE 5. NEUTRAL EARTHING IMPEDANCE4.3
Page 12
At the neutral point the zero sequence currents I, in the three
phases combine to give 31, in the netural earthing impedance. The
zero sequence voltage at fhe neutral point 1s given by
3 Van * Yon * Yon? . Yn
Example 2
+ Transformer Connect {ons
a Ze a BR
b b
Zero Sequence Equivalent
Circuit Connections
The positive sequence impedance of synchronous machines is the normal
nachine reactance, There are three defined values of positive
sequence impedances, namely the synchronous transient and
subtranstent impedances and they are used according to whether steady
state, transient or initial short-circuit values of current are
required.
Unlike the non-rotating networks» the negative sequence impedance of
the rotating plants {s not equal to the positive sequence impedance.
It relates to mmf at synchronous speed travelling in the opposite
direction to the rotor. Its value is usually less than that of the
positive sequence impedance.
In the zero sequence network» the winding connection and earthing
arrangement mst be considered as for transformers. Any earthing
impedance will be seen by each phase and therefore the correct
voltages will be obtained if three times the impedance value 1s
included in the zero sequence network.Page 13
Typical turbo-generator sequence reactances are :
synchronous reactance = 1.0 p.u.
transtent reactance = 0.15 pews
subtranstent reactance = 0.10 pews
negative sequence impedance = 0.13 p.u.
zero sequence impedance = 0,04 pu.
CONNECTION OF SEQUENCE NETWORKS TO REPRESENT UNBALANCED FAULTS
(a) For any given fault there are six quantities to be considered
at the fault point 5 Vir Vie Vio Igy Ie IQ+ If any
three are known (provided they are not all voltages or all
currents) or if any two are known and two others known to have
a specific relationship» then a relationship between V,, V> and
Vg and I,» I, and Ip can be established.
These relationships are called the circuit constraints.
From the circu{t constraints we can determine the manner in
which the isolated sequence networks can be interconnected.
(b) The relationships are derived with phase 'a! as the reference
phase and the faults are selected to be balanced relative to
the reference phase. This yields the simplest interconnection
of the sequence networks. If this is not done the
interconnections of the sequence networks require additional
transformations which are achieved by the introduction of phase
shifting transformers. This will be apparent in the case of
simultaneous faults where it 1s not possible for both the
faults to be symmetrical about the reference phase.
5.1 Shunt Faults
Line-to-ground faults, line-to-1ine faults, 1ine-to-1ine to ground
faults and three phase faults all fall into the category of shunt
faults.
(a) Figure 6 shows a system with a fault at F. The positive,
negative and zero sequence networks of the system are shown in
Figure 7. The fault terminals for the posttive sequence
network are F, and Ny» and the corresponding fault terminals
for the negattve and?zero sequence networks are For Ny and For
No respectively. It is at these terminals that the
iRterconnection of the networks will occur. In the derivation
of sequence network interconnections, it is convenient to show
the sequence networks as blocks with fault terminals F and N
for external connections (Figure 8).(b)
Page 14
A
S|
Cc
Tey 7 Ie
NOV, Oye.
FIGURE 9Page 15
(O-@ = 1-0,
FiG.6 SINGLE LWE DIAGRAM OF Two AMCHINE SYSTEM
96
OS
Tn,
POS\TWE SEQUENCE NETWORK OF SYSTEM
Fe
1-1
RR
NEGATE SEQUENCE NETWORK OF SYSTEW
-——-—___
—
Ne
ZERO SEQUENCE NETWORK OF SYSTEM
FIG] SEQuENCE NETWORKS OF FAULTED SYSTEM
30 : 0
VE eB ve F 2 Fe
ees ete ieee
‘| ow Pest. ARS.
FiG.8 SEQuENCE EQUIVALENT NETWORK BLOCK SsPage 16
Line To Ground Fault On Phase "At
At fault point + A FE
1 6
2 <
TeYEVLa
Vow
We know from section (2.2) that
Vat Wty +p T
But
+e Wty + Vy 20 3
We know from section (2.2) that
peg y+ i tip
But I,=1,=0
se gel 1,
= ya
Also, I) = W/3 (1, texel, + TL) = 3 1,
: 2, =
Ip = Vy T+ 7D, tet = 3 1,
eae
pilgt igs Vz 1, ca 4
Equations 3 & 4 are the CIRCUIT CONSTRAINTS. They suggest that the
sequence networks are connected in series.Page 17
5-1.2. Line to Ground Fault Through Fault Impedance 2
At fault point +
We know from section (2.2) that
pt Us Uti tip
t+ Ine V3 Tye stance 1, = 1
Similarly,
Yar My ti + Vy
But V, = 1,2, from constraint 2
Ltt Y= 1Z,
But I, = 31 from equation 3
- 4
ne MHD # Vy = 1932)
Equations 3 and 4 suggests the following interconnections.
ZFPage 18
5.1.3. Line to Line Fault on Phases 'B! and 'Ct
At fault point
We know Ty = 1/, (I, +1, + 1.)
Substituting equations 2 and 3 into equation 4,
Ip 20 5
Simslarly,
Tp = Vy (1, tot, + 071) = 1s, (eee)
17 M3 (1, + oct, io) = M3 >
2, 2.
= V3 (I, tect, tel.) = -1/, (oe -0%) 1,
oe Itt
0 wassennaee 6
2
' = 2
He know Vy = 1/3 (Vt oeV, tec2V_) =~
7
Substituting equation 1 into equation 7,
v= 3 Wa vy)
2, = 7
Similarly V2 = 1/3 (V, tocW, toc¥.) = 3 (V, - V4)
oe WEY, —
7 8
From equations 5, 6 and 8, the positive and negative sequence
networks are in parallel but the zero sequence network is
unconnected.Page 19
5.1.4 Line to Line Fault on Phases '8" and 'C! Through Fault Impedance Zp
At point of faulty
1 A —
2 s —
e
3 |
Tepe pre
OM Oe Ova
V3 I, +I, +I) =0
oan oe?
17 M3 U1, tect, + ec?t) = V5 (oc-ee?) 1,
2, 5
I= V3 (1, + ee*l, toc I)
2,
Wg (o-ee") 1,
4
yy + I, oO
* 2,
We know q, Ty to Ty tecI,) 5
Substituting equation 4 in 5
1, = (oc? -00 1) 6
2
No toe vy + ey
2,
Vp tae + 0070,
. = 20 . 20
te Vy - ve = (oe ~ex) yy (es® ~0¢) Vy 7
Substitute equation 3 and 6 into 7,
2 = (ee? wee
(ec -ee) 1,2, = (09% -o¢) yy (oe ) Vo
oe nz 8
vePage 20
5.1.5 Line to Line to Ground Fault on Phases 'B! and 'C!
At fault point :
A
oe
Weve L a FE
1,0 2 a
Le Yief Lo
Qe GMa om
5 . A
re MEMS OV, tect, te = 5 vy
2 :
Wg = Wz WV, tee, toe¥.) = V5 Vy
Yor Ms VtWy ti) =U y,
lo = 3%,
I, +I,+Ig=0
From equation 3 and 4, it can be concluded that the sequence networks
are connected in parallel.Page 21
5.1.6 Line to Line to Ground Fault on Phases '8! and 'C!
Through Fault Impedance Z,
At fault point :
I,=0 ~ L
(tp Zp 2
. 1 N
ar 1tigtIy=o ee) ~
V3 I, +T, +1 sv; ay +1)
se Ty t IQs 3ty 0 see 4
Yor Ms Wy tM FV) 2; + ayy)
2 ne 2 ls -
Vpn M3 Vy tee, to07V.) Us OV + OE ted T= 1/5 WA YD)
2 = Z . -
Wg 2 M3 Vt, ta) = 1/g CV, + (od #00) Vo 1 = 1/5 (V, ~ YQ)
lo Vp M3 Vt Vy =,
FU tty z 6
Subsitute equation 4 in 6
Vg ~ Vy = 31g2y
+ WA Mg = Ip 3Zp seceeennne 7
Equations 3, 5 and 7 suggest the following interconnect fons.5.1.7
Page 22
Thevenin Equivalent Method
One method of reducing or simplifying a complicated sequence network
is to derive the Thevenin equivalent circuit. The Thevenin
equivalent voltage of the positive sequence network is the pre-fault
voltage at the fault location F,. The positive sequence equivalent
impedance is the impedance seenvacross the fault terminals F, and
Ny when all the sources are de-activated.
It should be realised, however, that if the Thevenin method is used
to calculate the various branch currents, these values will represent
only the current changes in each branch due to the fault. The
pre-fault currents of the system has to be added to the fault current
changes to derive the total current for the fault condition.
Electricity Training Association. - Institution of Electrical Engineers-Power System Protection (Vol 2 - Systems and Methods) - Institution of Electrical Engineers (1995) PDF