Use case: Exchange current easYgen with an equivalent easYgen-XT control
The tables below compare easYgen-3000XT terminals with those of easYgen-3000. The XT-P2 comparison covers terminals 1-160. Terminals 1 to 80 (PCB one) are available in all variants, terminals 81 to 160 (second PCB) are available only in two-PCB "P2" variants e.g., easYgen-3400XT-P2, and easYgen-3500XT-P2(-LT). easYgen-3000XT Pin/ easYgen-3000 Required wiring changes Required software configuration terminal description Terminal terminal description of current 3000 System changes in 3000XT control 1 Mains/GND Current AC Mains/GND Current AC 2 3 4 Configure as 1A or 5A. 5 Generator Current AC Generator Current AC 6 7 8 9 10 11 Configure inputs as Analog Inputs Analog Inputs 12 resistance/current/voltage. 13 14 No short-cut between pin 15/16! 15 Move wire from pin 15 to pin 16. Move wire from pin 62 to pin 15. 16 Configure output as (Leave pin 62 unconnected) voltage/current/PWM. 17 Analog Outputs Analog Outputs 18 Move wire from pin 18 to pin 19. Configure output as 19 Leave pin 18 not connected. voltage/current/PWM. 20 21 22 23 Notes Mains Voltage AC 24 Mains Voltage AC (21, 23, 25, 27 - NC) 25 easYgen-3100XT/3200XT-P1(-LT): 26 upto 480 Vac 27 28 easYgen-3400XT/3500XT-P1/ 29 P2(-LT): 30 upto 690 Vac. 31 Generator Voltage AC 32 Connect only four terminals Range change is configured by Generator Voltage AC (29, 31, 33, 35 - NC) 33 in each block defined transformer ratio. 34 for L1, L2, L3, and N respectively. 35 36 These terminals together with 37 terminals 117 to 120 form full three phase busbar measurement (P2 38 Busbar Voltage AC only). Busbar Voltage AC (37, 39 - NC) Notes for P2 only 39 P1 busbar terminal "N" (pin 40) becomes "L2". Pin 120 is 3phase 40 busbar terminal "N"!
terminal description Terminal terminal description of current 3000 System changes in 3000XT control 81 Sinking Output SO1 Sinking Output SO1 82 83 84 85 86 Analog Inputs 0 to 10 V | Analog Inputs 0 to 10 V | 87 0/4 to 20 mA 0/4 to 20 mA 88 89 90 91 92 93 94 95 96 Analog Inputs 0 to 250 Ohm 97 Analog Inputs 0 to 250 | 0 to 2.5 kOhm 98 Ohm | 0 to 2.5 kOhm 99 100 101 102 103 104 N. C. 105 106 N. C. 107 Additional analog output can be Analog Output AO3 0/4 to wired here. Use 500 Ohm resistor 20 mA 108 for voltage mode. Analog Output AO4 0/4 to 109 Analog Output AO4 0/4 to 20 mA 110 20 mA Analog Output AO5 0/4 to 111 Analog Output AO5 0/4 to 20 mA 112 20 mA Analog Output AO6 0/4 to 113 Analog Output AO6 0/4 to 20 mA 114 20 mA 115 N. C. 116
117 These terminals together with
terminals 37..40 form full three 118 N. C. phase busbar measurement. Busbar Voltage AC Range change is configured by Notes (117, 119 - NC) defined transformer ratio. 119 P1 busbar terminal "N" (pin 40) becomes "L2" only. Pin 120 is 120 3phase busbar terminal "N"!