RELACAO DE CARGA — DEMANDA
aTDE pescrigso. =| | POT. UNIT KW] POT TOTAL KW | DEM KVA
25 | motor 1 cv 4.13 KW 28.25 KW 20.75 KVA
12 | woToR 2 cv 1.94 KW 23.28 KW 17.28 KVA
15 | motor 3 cv {2.91 KW 43.65 KW 32.70 KVA
10 | MOTOR 5 cv 4.78 KW 47.78 KW 33.70 KVA
07 | woToR 10 cv 9.68 KW 67.76 KW 45.22 KVA
03 | MOTOR 25 cv 22.44 KW 67.32 KW 44.40 KVA
TOTAL 278.04 KW 194.05 KVA
280 | LAMPADAS FLUORESCENTE 0.06 KW 11.20 KW
1400 | LAMPADAS FLUORESCENTE 0.02 KW 28.00 KW
300 | LAMPADAS INCANDESCENTE 0.06 KW 18.00 KW
250 walpaoas INCANDESCENTE 0.1 KW 25.00 KW
82 REFLETOR 0.25 KW 20.50 KW
87 Rehlevon 0.4 KW 22.80 KW
250 | TOMADAS. 0.1 KW 25.00 KW
150 | TOMADAS 0.3 KW 45.00 KW
80 | TONADAS 0.5 KW 40.00 KW
20 | TOMADAS 1.5 KW 30.00 KW
10 | TOWADAS 4.0 KW 40.00 KW
TOTAL 305.50 KW 164.75 KVA
25 | AQUECEDORES 2.0 KW 50.00 KW 19.00 KVA
22. | cHUvEIROS 5.4 KW 118.80 KW 46.33 KVA
15 | MAQUINAS DE SOLDA 10.0 KVA 150.00 KW 57.00 KVA
TOTAL 902.34 KW 481.13 KVAMEMGRIA DE CALCULO PARA AJUSTE
AJUSTE DE PROTEGAQ SECUNDARIA
DADOS ELETRICOS ;
01 - POTENCIA INSTALADA
‘QTDE| POTENCIA (KVA] IN(A) INDIV, IN(A) TOTAL,
4 75 3.14 12.56
mea 7125 471 9.42
2 150, 628 72.58
TOTAL] 82s [3456]
02 ~ DEMANDA
DEMANDA A SER CONTRATADA: 185 KW
03 - PROVETO DE LIGACAD .
8 TRASFORMADORES
4X 75 KVA ~ 13,8 KV - 220v
2 X 1125 kVA ~ 13,8 kV - 220v
2 X 150 KVA ~ 13,8 KV - 220V
04 - CALCULD DA CORRENTE NOMINAL - ¢ In >.
In = ( DEMANDA (KW) / 1.73 X 138 CKV > xX 092.
tes kW / (173X 138X092 > = 842A
05 - C4LCULO DA CORRENTE DE PARTIDA - ¢ Ip >
Ip = MXIn
Ip = Mx 842 = 9264
06 - CALCULO DA CORRENTE DE MAGNETIZACAD DOS TRAFOS - ¢ Im)
Im = 8 X Ini DO TRAFO DE 150 KVA + In DO TRAFO 150 KVA + In DOS 2 TRAFOS 1125 KVA
+ In DOS 4 TRAFOS 75 KVA
Int = PCKVA) = 150KVA = 628A
v3 xv 173 x 138
In@= PCKVA> = 125KVA = 4210
va xv 173 x 138
In3= PCKVAD = 75 kVA 314 8
“VaxV (173 x8
IM=B X 628+ 628+ 042+ 1256 = 7754 para + = 01 seg
07 - CALCULO DO PONTO ANSI DO TRAFO ¢ 1 ANSI >
1 ANSI CORRENTE M4XIMA QUE 0 TRANSFORMADOR SUPORTA DURANTE UM PERIODO DEFINIDO DE TEMPO, SEM SE DANIFI|
1 ANSI DE FASE = ¢ 10072 %> X IN DO TRANSFORMADOR
1 ANSI DO NEUTRO = 058 X I ANSI DE FASE07 - CALCULO DO PONTO ANSI DD TRAFO ¢ I ANSI >
1 ANSI CORRENTE MAXIMA QUE 0 TRANSFORMADOR SUPORTA DURANTE UM PERIODO DEFINIZO DE TEMPO, SEM SE DANIF
1 ANSI DE FASE = ¢ 100 / 2%) X IN DO TRANSFORMADOR
1 ANSI DO NEUTRO = 058 XI ANSI DE FASE
ONDE Z % € A IMPEDANCIA PERCENTUAL DO TRANSFORMADOR
PARA TRANSFORMADORDE"SOO KVANINZ 9S
PARA TRANSFORMADOR DE 300 KVA Z%= 5%
PaRA TRANSFORMADOR DE 1S0KVA 2% = 5%
PARA TRANSFORMADOR DE 1125 kVA Z%= 5 %
TEMPO MAXIMO 3 SEGUNDOS
1 ANSI DE FASE 10075X 6.28 A
I aNsi DE FASE = 20 X 6. 28= 125.64
1 ANSI DE NEUTRO = 058X 125.6 = 72,84 A TRAFD 150 KVA
TANS DE FASE 10075X 4.21 A
1 ANSI DE FASE = 20X 4.21 = 84.20
T ANSI DE NEUTRO = 058X 84.2 = 48.844 TRAFO 125 KVA
T ANSI DE FASE 10075X 3.14 A
I ANSI DE FASE = 20X 3.14 = 628A
I ANSI DE NEUTRO = 058X 62.8 = 36.42 — TRAFO 75 KVA
08 - DEFINIGAD DA RELAGAD DE TRANFORMAGAO DOS TC S
‘A CORRENTE DE CURTO CIRCUITO TRIFASICA NO PONTO DERIVAGAD DA REDE CEMIG = 3500 A
RECOMENDA SE QUE A MAIDR CORRENTE DE CURTO CIRCUITO ¢ TRIFASICO > NAD EXCEDA EM MAIS DE 50 VEZES A Ct
DE ACORDO COM AS RELACHES DE TRANFORMACAD PADRONIZADAS, SERAD INSTALADOS TCS DE 75/5
09 - DIMENSIONAMENTO DO ELOS FUSIVEIS PRIMARIO
FUSIVEL DE PROTEGAD DO RAMAL DE LIGAGAO
DE ACORDO COM A ND 5.3 PARA DEMANDA DE 185 KW DEVERA SER INSTALADO CHAVE FUSIVEL DE 15 KV 71 KA It
FUSIVEL DE PROTEGAD DOS TRAFO 150 kVA 8 K
FUSIVEL DE PROTEGAO DOS TRAFD 1125 KVA 6 K
FUSIVEL DE PROTECAD DOS TRAFO 75 KVA SH10 - AJUSTE DO RELE
RELE DE PROTECAD
FOI ADOTADO O RELE URPE 7104 ¢ V 21 / 311 > DA PEXTRON
FUNGAO INSTANTANEA SO / SON PROTEGAD DE SOBRE CORRENTE INSTANTANEA
FUNGAD INSTANTANEA Si / SiN PROTECAO TE SOBRE CORRENTE TEMPORIZADA
4 FUNG&D INSTANTANEA SO
4 UNIDADE INSTANTANEA SO SERA AJUSTADA A UM VALOR SUPERIOR ¢ MAXIMO 5% >
‘A CORRENTE DE MAGNETIZAGAO CI RUSH > QUE € IGUAL A 77.5 4 ENTAD SERS AJUSTADA
PARA CORRENTE PRIMARIA DE 81 A
A FUNCAO INSTANTANEA SON.
‘A UNIDADE INSTANTANEA SO N SERA AJUSTADA EM 33 % DO VALOR DA UNIDADE INSTANTANEA SO 81 X 33 % = 267,
A FUNGAD TEMPORIZADA Si
FOL ESCOLHIDA A CURVA DO RELE COM CARACTERISTICA EXTREMAMENTE INVERSA,
AJUSTE DA CORRENTE DE PARTIDA (IP >= 9. 26 A
@ FUNGAD TEMPORIZADA Sl N
AJUSTE DA CORRENTE = 33 % DE IP 926 x 33 %
AJUSTE DE TEMPO DE FASE
T= KX DIAL / CIP INST / IP TEMP >? 1
Teexo1s@ s9.e6F -1
T=0,1 Seg
DIAL = 0.1
AJUSTE DE TEMPO DE NEUTRO
kX DIAL / ¢ IP INST NEUTRO / IP TEMP NEUTRO>® - 1
80 xX 01/@6.7 73.06% -1
20,1 Seg ~
DIAL 1
PARAMETROS € RESPECTIVOS AJUSTES
RTC = 15
| inDICE DESCRIGAO ‘AJUSTES|
[Ip Corrente de partida de tempo dependente de fase [3.26K |
Curva __|Tipo de curva de atuago de fase El
Dt___[Ajuste de tempo de fase e neutro OF
TDef.__ [Corrente de partida de tempo idependente de fase MAXIMA
| T. Def. Tempo da unidade independente de fase 2408
—L'inst._— [Corrente da unidade intantanea de fase = BIA
|. partida -N Corrente de partida de tempo dependente de neutro 3.064,
Curva [Tipo de curva de atuagde do neuro EI
Corrente de partida da unidade de tempo
|__| Bef. independente de neutro noes
[_-T.Def.__ [Tempo da unidade dependente de neutro [240s]