the Conduit A quarterly publication from

M&M Engineering Associates, Inc.


Vol. 10, No. 4

In this Issue
Forgotten Water: Stator Cooling Water Deaerator Vessel Assessment Guideline .... 3

exhausted, but in many systems, it is Interim Amine Guidelines .......................... 4


By David G. Daniels
common for the pressure differential
Principal Scientist Events and News ....................................... 6
across the resin bed (created by
Even utilities that are very diligent accumulated particulates) to require
about treating and monitoring their that the resins be replaced before deposits are copper oxides released
boiler water, demineralized water the ion exchange capacity is reached. from one area of the stator coolers
makeup, and cooling water may and deposited in another. The
Copper contamination
know little about treating one of the amount of dissolved oxygen in the
most critical water systems in the The stator cooling water system’s system, and particularly variations in
plant: stator cooling water. heat transfer surfaces are typically that oxygen concentration,
copper, though some are stainless determines when copper oxides are
Stator cooling water is contained in
steel. The chemistry of copper in released.
a closed loop system that cools the
oxidizing and reducing conditions
copper stator bars in water-cooled Copper forms cuprous oxide
has been the subject of a great deal
generators. The holes though which (Cu2O) under reducing (low-oxygen)
of recent research. One area of
the water flows are narrow. conditions and cupric oxide (CuO)
intense focus has been copper
Unimpeded flow through all stator when dissolved oxygen is high.
corrosion in feedwater systems and
bar openings is critical to operation Either of these oxides can be stable
corrosion product transport into
of the generator. Overheating of and create a passive oxide layer on
the boiler and on to the HP turbine.
stator bars can result in reduced the channels in the stator bars. A
Some of the general metallurgical
generating capacity or even slightly alkaline pH increases the
principles learned in studying copper
catastrophic failure of the generator. stability of the oxide layer.
in feedwater systems can also be
Stator cooling systems contain only applied to stator cooling systems. Study your options
deionized water. The cooling loop As with copper in feedwater
The recommended treatment
removes heat from the stator systems, we know that dissolved
regimes for stator cooling water can
coolers and conveys it away through oxygen and pH play a major role in
be categorized by their levels of
heat exchangers. The water is determining the corrosion product
dissolved oxygen and pH. Of the
continuously passed through a formation rate and transportation
four options illustrated in Figure 1,
mixed bed polisher that removes rate through the stator cooling
three are generally recommended by
any soluble ionic contaminants that system.
treatment experts. Each of the
enter the water. The stator ion
It is important to remember that the recommended options can be found
exchange resins often also act as a
major cause of problems in stator in operating power plants, and each
filter for particulates in the water,
cooling systems has not been has pros and cons that must be
though some systems have a
corrosion per se but, rather, deposit balanced against the particular needs
separate filter. The ion exchange
accumulation in critical areas. These of a plant and its equipment
resin will eventually become
operating history.
Low-O2, neutral pH option. A
thin layer of passive cuprous oxide
forms in a low–dissolved oxygen and
neutral pH regime. This treatment
option is found in about 50% of the
stator water cooling systems in the
power industry. The water is fully
Figure 1. Three real options. Only three of the four possible stator cooling
water treatment options are viable. Source: M&M Engineering (Continued on page 2)

1
oxygenated when the system is first significant, the stator cooling water utilities have turned to oxygen
filled. As the water circulates, it can swing back and forth between removal systems. Some power
reacts with the copper in the low- and high-oxygen conditions. plants use a series of three gas
system, the oxygen is consumed, and These transient conditions release transfer membranes to remove
the dissolved oxygen gradually oxides into the system. dissolved oxygen from any makeup
approaches zero. The dissolved water added to its stator cooling
Air ingress can also cause significant
oxygen is likely to remain at <10 system. The system, which uses
increases in the system’s dissolved
ppb as long as no water is added to only nitrogen purge gas to sweep
oxygen. Putting a nitrogen cap on
the system. Neither oxygen out the oxygen that permeates the
the stator cooling water head tank
scavengers nor reducing agents are membrane, is capable of reducing
can minimize air in-leakage.
commonly added to stator cooling the dissolved oxygen of the makeup
systems. The trick in this treatment Carbon dioxide can enter the water to about 3 ppb.
regime is keeping dissolved oxygen system via the makeup water or
Low-O2, higher pH option.
out. along with the air. As carbon
Increasing the pH of the stator
dioxide is absorbed into the water,
The effect of transient oxygen spikes water to 8–9 significantly reduces
it drops the pH to acidic levels,
is most profound on low–dissolved the corrosive response during
increasing the corrosion rate of
oxygen and neutral pH systems. oxygen transitions (Figure 2). The
copper. Carbon dioxide can form
The corrosion or oxidation rate of most direct method for increasing
bicarbonate and carbonate in the
copper in a system containing 400 pH is to add controlled amounts of
water and exhaust the mixed bed
ppb of dissolved oxygen is more sodium hydroxide to the water.
polisher. If the polisher is not
than five times its rate at low levels Initially, the sodium will be
changed when it is exhausted, the
of oxygen under neutral conditions. exchanged with hydrogen on the
released carbonate can form
cation resin of the mixed bed
Every time makeup water is added insoluble copper carbonate in the
polisher, neutralizing the caustic. If
to the stator system, it receives a stator.
caustic continues to be added,
little shot of dissolved oxygen. If,
To prevent dissolved oxygen eventually, sodium leakage from the
due to leaks in the stator cooling
contamination resulting from resins will allow the water to
water system, makeup rates are
additions of makeup water, some maintain an alkaline pH.
Another treatment method is to add
a sodium exchange polisher on a
side stream and control the amount
of water that passes through the
sodium exchanger to achieve the
desired pH. Some plants have even
replaced the mixed bed polisher
with all strong base anion resins.
However, this polisher will no
longer remove soluble copper.
Raising the pH also makes it easier
to measure the pH of water in the
system.
During shutdown, and particularly
during a major turbine outage,
stator water can become
oxygenated. In a number of cases,
deterioration of the stator cooling
system occurred shortly after the
unit came back on-line from an
extended outage.
Figure 2. Oxygen therapy. The effect of pH on copper corrosion rates is High-O2, neutral pH option. The
significant as oxygen levels increase. Source: Journal of Power Plant Chemistry other treatment alternative is to

2
maintain a high–dissolved oxygen Monitoring the makeup water usage
level in the cooling water at all in a stator cooling system is also Deaerator Vessel
times. It is estimated that 40% of important. If the system is operating
water-based stator cooling systems under a low–dissolved oxygen Assessment Guideline
operate with high–dissolved oxygen regime, an increase in makeup water
and neutral water chemistry. In this may signal a potential problem from By Catherine Noble
treatment regime, CuO is formed oxide accumulations. Monitoring Senior Engineer
on the copper. It will tightly adhere gas flow rates from the stator
to the surface and create a passive cooling water head tank is one way On January 1, 2011, the Deaerator
layer on the metal. This layer tends to detect hydrogen leaks that can Vessel Assessment Guideline
to be thicker than the Cu2O formed deplete dissolved oxygen in the (Report 1021199) will be made
under low-oxygen conditions. water, if you are using the high- available for purchase and download
oxygen regime. by the Electric Power Research
Because the dissolved oxygen will be
depleted by its reaction with copper, Conductivity of the water and Institute (EPRI). M&M Engineering
at least initially, it may be necessary pressure drop across the polisher Associates, Inc. conducted the
to add air to the system to maintain are critical monitoring parameters primary research and
sufficient dissolved oxygen in the and should be monitored documentation for this manual. The
system. continuously with carefully selected report will allow plant engineers,
setpoints. The frequency with plant chemists, and operators/
This chemical treatment is owners to identify the risk in their
which the filter needs to be changed,
impervious to additions of dissolved DA systems and provides sound
due to particulate plugging, is an
oxygen in the feedwater when it is engineering evaluation practices for
indication of corrosive conditions in
operating continuously under high running vessels with damage,
the system. The resins themselves
(>2 ppm) levels of dissolved oxygen. repairing them if necessary or
can be tested to determine the
However, it may still be susceptible replacing them with vessels with
amount and nature of the copper
to low-pH corrosion from carbon greater integrity.
that is being transported through
dioxide and carbonates if these are The goal of this project was to
the system.
not removed by the mixed bed revise and update the EPRI Deaerator
polisher. Generators should also be equipped Vessel Assessment Guideline (DVAG)
with flow and pressure differential to reflect current industry
If there is a hydrogen leak into the
metering of the cooling water technology and approaches. This
stator cooling water system, the
system across the generator. These updated guideline incorporates
hydrogen can replace the dissolved
parameters can also provide an technical input from the NACE
oxygen and create low–dissolved
indication of fouling if they are Standard Practice Document SP0590-
oxygen transients in the system,
monitored regularly and trended. 2007, but is focused on utility
causing oxides to be released.
On-line monitoring for dissolved applications. This document
High-O2, high-pH option. provides a comprehensive guideline
oxygen is recommended if the plant
Operating with high dissolved of today’s “best practices”, including
will be operating under a low-
oxygen and an elevated pH is not information and guidance on the
oxygen regime. Grab sampling is
recommended because it increases following:
not usually recommended for these
the likelihood of clip corrosion.  Design and materials of
systems due to the amount of water
Monitoring stator water required to flush out sample lines construction.
before one can be sure of getting an  Advanced understanding of
Monitoring the health of stator damage: description and
water systems is more about looking accurate sample. This water is then
replaced with oxygenated water, explanation of damage
at a variety of related temperatures mechanisms including examples
and pressures than collecting grab thus changing the analysis.
of failure.
samples and running them for pH or —David G. Daniels  Operational conditions that
dissolved oxygen. Water promote failure.
(david_daniels@mmengineering.com )
temperature is one example: An  Inspection and evaluation.
is a principal of M&M Engineering and
increase in stator cooling water a contributing editor to POWER.  Repair options.
temperature puts the cooling water  Technical criteria for mitigation
system at higher risk for plugging. of damage including

3
recommendations of repair-run- However, corrosion in air cooled
or replacement. This includes condensers and flow accelerated
reference to current fitness-for- corrosion (FAC) concerns,
service best practices such as particularly on the shell-side of David Daniels
ASME FFS-001 and API 579. feedwater heaters has caused some awarded the 2010
fossil plants to reconsider using Paul Cohen
To find more information regarding amines.
the manual, visit www.epri.com. In November, M&M Engineering Award
completed sponsored research of
the use of amines for pH control in On October 25, 2010, David Daniels was
fossil power plant. The research
Interim Amine project surveyed, arranged sampling
presented the 2010 Paul Cohen Award at
Guideline and analysis, and interpreted amine the 71st Annual International Water
stability and amine breakdown
Conference ® in San Antonio, TX. The
products at three power
By David G. Daniels award is presented “In Memory of Paul
plants. This work determined the
Principal Scientist stability of two amines, Cohen, as Testimony to His Invaluable
ethanolamine and
Amines such as cyclohexylamine and methoxypropylamine in actual Contributions to the Power Generation
morpholine were used in many generating plants. It provided some
industrial and fossil power plant Industry and to the International Water
excellent insight into the
steam cycles for years to raise the effectiveness of these amines in Conference ®.” This award was
pH of the feedwater, steam, and actual steam cycles and the
condensate. The nuclear industry presented to Mr. Daniels in recognition
concentration of the breakdown
uses amines to minimize iron products that can be of the “Most Precise and Innovative
corrosion in moisture separators by expected. Proprietary third party
raising the pH of the first Presentation in the field of Power
software was used to calculate the
condensate. Recently the nuclear pH at temperature (pHT) at various Systems Water Technology.” (IWC 09-
power industry pioneered the points throughout the steam
development of what has been 31: “A Review of Hydrogen Damage
cycle. This helps to predict the
termed “advanced amines to replace effectiveness of these amines at and Phosphate Gouging Corrosion
morpholine. These include various points to minimize iron
ethanolamine, methoxypropylamine, Mechanisms.”-70th Annual International
corrosion.
and dimethylamine. Essentially all Water Conference ®).
nuclear power plants in the US now
use one or more of these advanced
amines in their steam cycle.
While nuclear power has been
embracing amines, large fossil plants
have shied away from using them
due to the elevated cation Contact the Authors
conductivity that is produced as
these organic compounds David Daniels
breakdown in the steam cycle. Principal Scientist
These are primarily carbon dioxide, 512-407-3752
acetate, and formate. The affects of david_daniels@mmengineering.com
acetate and formate on the steam
turbine are not fully understood and Catherine Noble
turbine OEM’s have been reluctant Senior Engineer
to move away from the cation
512-407-3771
conductivity limits that have little
room for even ppb levels of acetate catherine_noble@mmengineering.com
and formate.

4
Failures in Steam/Power Generation
Staying Out of Trouble!!!
M&M Engineering Associates, Inc. will be hosting a Two-Day Conference that will focus on the
issues most common in steam generation systems

March 9-10, 2011


Radisson Hotel & Suites Austin/Town Lake
111 East Cesar Chavez at Congress Avenue
Austin, Texas 78701

Conference Registration

$300.00 per day or $500.00 for both days


(Continental Breakfast & Lunch provided)
Registration will close on March 1, 2010
Enrollment cap of 20 people
Please call Candice at (512) 407-8598 to register or for additional information.

Accommodations

Rooms may be reserved by calling (800) 333-3333. Please be sure to mention the M&M Engineering conference
to receive a special rate for attendees.

Confrence Schedule

March 9th

Failure modes that occur in:

8:30-10:00 AM Water Treatment Systems–David Daniels, Principal Scientist

10:30-12:00 PM Water Kissed Furnace Tubing–Jon McFarlen, Consulting Engineer

1:00-2:30 PM Steam Kissed Furnace Tubing–Ron Munson, Corporate Engineer

3:00-4:30 PM High Energy Piping–Ron Munson, Corporate Engineer

March 10th

8:30-9:15 AM Turbines–Mark Tanner, Senior Principal Engineer

9:30-10:15 AM Turbines–Charlie Rutan, Senior Principal Engineer

10:30-12:00 PM Condensers–David Daniels, Principal Scientist

1:00-2:30 PM Feedwater Heaters–Andi Cragen, Mechanical Engineer

3:00-4:30 PM Miscellaneous (Dearators, etc…)–Catherine Noble, Senior Engineer

5
Seminars and Workshops

Ron Lansing and Max Moskal attended the TAPPI Pulping,


Engineering, Environmental, Recycling and Sustainability
conference held October 17-20, 2010, in Norfolk, Virginia.
Mr. Moskal presented a paper entitled Paper Machine Dryer
and Felt Roll Corrosion, which described the corrosion damage
mechanism resulting from increased carryover of bleach plant
oxidants when achieving high paper brightness targets.

Ron Munson and Catherine Noble attended


the EPRI-BRIG (Boiler Reliability Interest
Group) conference in Houston, Texas on
December 7th, 2010. They presented a
summary of EPRI’s updated deaerator
guideline.

John Molloy attended the ASME Gas


Turbine Users Symposium October 4-
7, 2010, in Houston, Texas.

Upcoming Events

Catherine Noble will be attending the CORROSION 2011


Conference hosted by NACE (National Association of
Corrosion Engineers) to be held March 15-16, 2011 in
Houston, Texas. She will be presenting 2 papers on the
16th—Glossary of Boiler Tube Microstructures and Its Use to
Verify Oxide Thickness Temperature Estimations and Damage
Mechanisms in Creep Strength Enhanced Ferritic (CSEF) Steels
(T91 and T23).

Ron Lansing will be giving a presentation entitled Burning Up the


Refinery: Metallurgical Examination After a Fire at the 2011 API
(American Petroleum Institute) Inspection Summit and Expo
January 24-29, 2011 in Galveston, Texas.

Best Wishes for a Happy New Year from all of us


at M&M Engineering Associates, Inc.

6
the Conduit is distributed
free of charge by M&M
Engineering Associates, Inc..
We welcome your comments, __ Please add my name to your mailing list.
questions, and suggestions, and
we encourage you to submit __ Please delete my name from your mailing list.
articles for publication.
__ Please correct my information as listed below.
We grant limited permission
to photocopy all or part of this
publication for nonprofit use I prefer to receive this newsletter by ____ Email _____ Mail
and distribution.

For technical information, Name: ________________________________________


please contact:
Title: _________________________________________
David Daniels
(512) 407-3761 Company: _____________________________________
david_daniels@mmengineering.com
Address: ______________________________________

Ron Munson City: ________________ State: _______ Zip: _______


(512) 407-3762
ron_munson@mmengineering.com
Phone: _______________ Fax: ___________________

Karen Fuentes Email: ________________________________________


(512) 407-3778
karen_fuentes@mmengineering.com

Comments on this issue: __________________________

_____________________________________________

_____________________________________________

_____________________________________________

Texas • Illinois • Oklahoma


Please send or fax this form to :
www.mmengineering.com
M&M Engineering Associates, Inc.
4616 W. Howard Lane Building 2, Suite 500
Austin, TX 78728-6302
Fax: (512) 407-3766

7
the Conduit
M&M Engineering Associates, Inc.
4616 W. Howard Lane, Bldg. 2, # 500
Austin, TX 78728-6302

You might also like