Data sheet 6ES7215-1AG40-0XB0

SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2


PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC
0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4 -
28.8 V DC, PROGRAM/DATA MEMORY: 100 KB

General information
Engineering with
● Programming package STEP 7 V13 SP1 or higher

Display
with display No

Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 5V
● permissible range, upper limit (DC) 250 V

Input current
Current consumption (rated value) 500 mA
Current consumption, max. 1 500 mA
Inrush current, max. 12 A; at 28.8 V DC

Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.

Output current
Current output to backplane bus (DC 5 V), max. 1 600 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W

Memory
Type of memory EEPROM

Work memory
● Integrated 125 kbyte
● expandable No

Load memory
● Integrated 4 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card

Backup
● present Yes; maintenance-free
● without battery Yes

CPU processing times


for bit operations, typ. 0.085 µs; / instruction

for word operations, typ. 1.5 µs; / instruction


for floating point arithmetic, typ. 2.5 µs; / instruction

CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code

Data areas and their retentivity


retentive data area in total (incl. times, counters, 10 kbyte
flags), max.

Flag
● Number, max. 8 kbyte; Size of bit memory address area

Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte

Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules

Time of day
Clock
● Hardware clock (real-time clock) Yes
● Deviation per day, max. +/- 60 s/month at 25 °C
● Backup time 480 h; Typical

Digital inputs
Number of digital inputs 14; Integrated
● of which, inputs usable for 6; HSC (High Speed Counting)
technologicalfunctions

integrated channels (DI) 14


m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14

Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 VDC at 2.5 mA

Input current
● for signal "1", typ. 1 mA

Input delay (for rated value of input voltage)


for standard inputs
— Parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— Parameterizable Yes
for counter/technological functions
— Parameterizable Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz
& 3 at 30 kHz

Cable length
● shielded, max. 500 m; 50 m for technological functions
● Unshielded, max. 300 m; For technological functions: No

Digital outputs
Number of digital outputs 10
● of which high-speed outputs 4; 100 kHz Pulse Train Output
integrated channels (DO) 10
short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 0.5 A

Output delay with resistive load


● "0" to "1", max. 1 µs
● "1" to "0", max. 5 µs

Relay outputs
● Number of relay outputs, integrated 0

Cable length
● shielded, max. 500 m
● Unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Integrated channels (AI) 2
Input ranges
● Voltage Yes

Input ranges (rated values), voltages


● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms

Cable length
● shielded, max. 100 m; twisted and shielded

Analog outputs
Number of analog outputs 2
Integrated channels (AO) 2; 0 to 20 mA
Output ranges, voltage
● 0 to 10 V Yes

Output ranges, current


● 0 to 20 mA Yes

Cable length
● shielded, max. 100 m; shielded, twisted pair

Analog value creation


Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 10 bit
max.
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs

Encoder
Connectable encoders
● 2-wire sensor Yes

1st interface
Interface type PROFINET

Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
● PROFINET IO Device Yes
● PROFINET IO Controller Yes

PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
● Number of connectable IO devices, max. 16
● Prioritized startup
— Number of IO Devices, max.
16
PROFINET IO Device
Services
— Shared device Yes
— Number of IO controllers with 2
shared device, max.

Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes

Number of connections
● overall 16; dynamically

Test commissioning functions


Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters

Forcing
● Forcing Yes

Diagnostic buffer
● present Yes

Traces
● Number of configurable Traces 2; Up to 512 KB of data per trace are possible

Integrated Functions
Number of counters 6

Counter frequency (counter) max. 100 kHz


Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Limit frequency (pulse) 100 kHz
Galvanic isolation
Galvanic isolation digital inputs
● Galvanic isolation digital inputs No
● between the channels, in groups of 1

Galvanic isolation digital outputs


● between the channels No
● between the channels, in groups of 1

Permissible potential difference


between different circuits 500 V DC between 24 V DC and 5 V DC

EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. Yes
to IEC 61000-4-4
● Interference immunity on signal lines acc. Yes
to IEC 61000-4-4

Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes

Immunity against conducted interference induced by high-frequency fields


● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6

Emission of radio interference acc. to EN 55 011


● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011

Degree and class of protection


Degree of protection to EN 60529
● IP20 Yes

Standards, approvals, certificates


CE mark Yes

UL approval Yes
cULus Yes
RCM (formerly C-TICK) Yes
FM approval Yes
Marine approval
● Marine approval Yes

Ambient conditions
Free fall
● Drop height, max. (in packaging) 0.3 m; five times, in dispatch package

Ambient temperature in operation


● Min. -20 °C
● max. 60 °C; Number of simultaneously activated inputs or outputs 7 or
5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or
10 at 55 °C horizontal or 45 °C vertical
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C

Storage/transport temperature
● Min. -40 °C
● max. 70 °C

Air pressure acc. to IEC 60068-2-13


● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
● Permissible operating height -1000 to 2000 m

Relative humidity
● Operation, max. 95 %; no condensation
● Permissible range (without condensation) at 25 95 %
°C

Vibrations
● Vibrations 2G wall mounting, 1G DIN rail
● Operation, checked according to IEC 60068- Yes
2-6

Shock test
● checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g
(peak value), duration 11 ms
Pollutant concentrations
— SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Configuration
Configuration software
● STEP 7 Yes

programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● can be set Yes

Dimensions
Width 130 mm
Height 100 mm
Depth 75 mm

Weights
Weight, approx. 500 g

6ES72151AG400XB0 Subject to change without notice


1.17.2021
Page 7/7 © Copyright Siemens
Data sheet 6ES7223-1PL32-0XB0
SIMATIC S7-1200, Digital I/O SM 1223, 16 DI/16 DO, 16 DI 24 V DC,
Sink/Source, 16 DO, relay 2 A

General information
Product type designation SM 1223, DI 16x24 V DC, DQ 16x relay

Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V

Input current
from backplane bus 5 V DC, max. 180 mA
Digital inputs
● from load voltage L+ (without load), max. 4 mA/input 11 mA/relay

Output voltage
Power supply to the transmitters
● present Yes

Power loss
Power loss, typ. 10 W

Digital inputs
Number of digital inputs 16

6ES7223-1PL32-0XB0 Subject to change without notice


Page 1/4 09/30/2020 © Copyright Siemens
● in groups of 2
Input characteristic curve in accordance with IEC 61131, Yes
type 1
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 16
horizontal installation
— up to 40 °C, max. 16
— up to 50 °C, max. 16
vertical installation
— up to 40 °C, max. 16
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "0", max. (permissible quiescent 1 mA
current)
● for signal "1", min. 2.5 mA
● for signal "1", typ. 4 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable
in groups of four
for interrupt inputs
— parameterizable Yes
Cable length
● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs
Number of digital outputs 16
● in groups of 4
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 2A

● on lamp load, max. 30 W with DC, 200 W with AC


Output voltage
● Rated value (DC) 5 V DC to 30 V DC

● Rated value (AC) 5 V AC to 250 V AC


Output current
● for signal "1" rated value 2A

6ES7223-1PL32-0XB0 Subject to change without notice


Page 2/4 09/30/2020 © Copyright Siemens
● for signal "1" permissible range, max. 2A
Output delay with resistive load
● "0" to "1", max. 10 ms

● "1" to "0", max. 10 ms


Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 8 A; Current per mass
Relay outputs
● Number of relay outputs 16

● Rated supply voltage of relay coil L+ (DC) 24 V

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
— with inductive load, max. 2A

— on lamp load, max. 30 W with DC, 200 W with AC 2 A

— with resistive load, max.


Cable length
● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes
Diagnostics indication LED
● for status of the inputs Yes

● for status of the outputs Yes

Potential separation
Potential separation digital inputs
● between the channels, in groups of 2
Potential separation digital outputs
● between the channels Relays

● between the channels, in groups of 4

● between the channels and backplane bus 1 500 V AC for 1 minute

Permissible potential difference


between different circuits 750 V AC for 1 minute

Degree and class of protection


IP degree of protection IP20

Standards, approvals, certificates


CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes

6ES7223-1PL32-0XB0 Subject to change without notice


Page 3/4 09/30/2020 © Copyright Siemens
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes

Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C; Number of simultaneously activated outputs: 8 (no adjacent
points) at 60 °C horizontal or 50 °C vertical, 16 at 55 °C horizontal or 45
°C vertical
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
● permissible temperature change 5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
● min. -40 °C

● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Storage/transport, min. 660 hPa

● Storage/transport, max. 1 080 hPa


Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %

Connection method
required front connector Yes

Mechanics/material
Enclosure material (front)
● Plastic Yes

Dimensions
Width 70 mm
Height 100 mm
Depth 75 mm

Weights
Weight, approx. 350 g

6ES7223-1PL32-0XB0 Subject to change without notice


Page 4/4 09/30/2020 © Copyright Siemens
Data sheet 6ES7231-4HF32-0XB0

SIMATIC S7-1200, Analog input, SM 1231, 8 AI, +/-10 V, +/-5 V, +/-2.5 V,


or 0-20 mA/4-20 mA, 12 bit+sign or (13 bit ADC)

General information
Product type designation SM 1231, AI 8x13 bit
Supply voltage
Rated value (DC) 24 V
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 90 mA
Power loss
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8; Current or voltage differential inputs
permissible input voltage for voltage input (destruction 35 V
limit), max.
permissible input current for current input (destruction 40 mA
limit), max.
Cycle time (all channels) max. 625 µs
Input ranges
● Voltage Yes; ±10V, ±5V, ±2.5V
● Current Yes; 4 to 20 mA, 0 to 20 mA
● Thermocouple No
● Resistance thermometer No
● Resistance Yes
Input ranges (rated values), voltages
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) ≥9 MOhm
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) ≥9 MOhm
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) ≥9 MOhm
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 280 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 280 Ω
Thermocouple (TC)
Temperature compensation
— parameterizable No
Analog value generation for the inputs

6ES72314HF320XB0 Subject to change without notice


1.17.2021
Page 1/2 © Copyright Siemens
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; + sign
● Integration time, parameterizable Yes
● Interference voltage suppression for interference 40 dB, DC to 60 V for interference frequency 50 / 60 Hz
frequency f1 in Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes
Diagnostics indication LED
● for status of the inputs Yes
● for maintenance Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %

6ES72314HF320XB0 Subject to change without notice


1.17.2021
Page 2/3 © Copyright Siemens
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 180 g

6ES72314HF320XB0 Subject to change without notice


1.17.2021
Page 3/3 © Copyright Siemens
Data sheet 6ES7232-4HD32-0XB0

SIMATIC S7-1200, Analog output, SM 1232, 4 AO, +/-10 V, 14-bit


resolution, or 0-20 mA/4-20 mA, 13-bit resolution

General information
Product type designation SM 1232, AQ 4x14 bit
Supply voltage
Rated value (DC) 24 V
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 80 mA
Power loss
Power loss, typ. 1.5 W
Analog outputs
Number of analog outputs 4; Current or voltage
Output ranges, voltage
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 000 Ω
● with current outputs, max. 600 Ω
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 14 bit; Voltage: 14 bit; Current : 13 bit
Errors/accuracies
Temperature error (relative to output range), (+/-) 25 °C ±0.3%, to 55 °C ±0.6% total measurement range
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses

6ES72324HD320XB0 Subject to change without notice


9.1.2021
Page 1/2 © Copyright Siemens
● Monitoring the supply voltage Yes
● Wire-break Yes
● Short-circuit Yes
Diagnostics indication LED
● for status of the outputs Yes
● for maintenance Yes
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 180 g

last modified: 3/11/2021

6ES72324HD320XB0 Subject to change without notice


9.1.2021
Page 2/2 © Copyright Siemens
Data sheet 6ES7241-1CH32-0XB0

SIMATIC S7-1200, Communication module CM 1241, RS422/485, 9-pole


D-sub (socket) supports Freeport

General information
Product type designation CM 1241 RS 422 / 485
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, max. 220 mA; From backplane bus 5 V DC
Power loss
Power loss, typ. 1.1 W
Interfaces
Number of interfaces 1
Point-to-point connection
● Cable length, max. 1 000 m
Integrated protocol driver
— Freeport Yes
— ASCII Yes; Available as library function
— Modbus RTU master Yes
— MODBUS RTU slave Yes
— USS Yes; Available as library function
Protocols
Integrated protocols
Freeport
— Telegram length, max. 1 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 (Standard), 2
— Parity No parity (standard); even, uneven, mark (parity bit always 1); space
(parity bit always 0)
3964 (R)
— Telegram length, max. 1 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 (Standard), 2
— Parity No parity (standard); even, uneven, mark (parity bit always 1); space
(parity bit always 0)
Modbus RTU master
— Address area 1 through 49 999 (Standard Modbus addressing)
— Number of slaves, max. 247; slave numbers 1 through 247, per MODBUS network segment
maximum 32 devices, additional repeaters needed to expand the

6ES72411CH320XB0 Subject to change without notice


1.17.2021
Page 1/2 © Copyright Siemens
network to maximum configuration
MODBUS RTU slave
— Address area 1 through 49 999 (Standard Modbus addressing)
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnostics indication LED
● for status of the outputs Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %

Dimensions
Width 30 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 155 g

6ES72411CH320XB0 Subject to change without notice


1.17.2021
Page 1/2 © Copyright Siemens
Data sheet 6ES7221-1BF32-0XB0
SIMATIC S7-1200, Digital input SM 1221, 8 DI, 24 V DC,
Sink/Source

General information
Product type designation SM 1221, DI 8x24 V DC

Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V

Input current
from backplane bus 5 V DC, max. 105 mA
Digital inputs
● from load voltage L+ (without load), max. 4 mA; per channel

Output voltage
Power supply to the transmitters
● present Yes

Power loss
Power loss, typ. 1.5 W

Digital inputs
Number of digital inputs 8

6ES72411CH320XB0 Subject to change without notice


1.17.2021
Page 2/2 © Copyright Siemens
● in groups of 2
Input characteristic curve in accordance with IEC Yes
61131, type 1
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
horizontal installation
— up to 40 °C, max. 8
— up to 50 °C, max. 8
vertical installation
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "0", max. (permissible quiescent 1 mA
current)
● for signal "1", min. 2.5 mA

● for signal "1", typ. 4 mA

Input delay (for rated value of input voltage)


for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
for interrupt inputs
— parameterizable Yes
Cable length
● shielded, max. 500 m
● unshielded, max. 300 m

Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes
Diagnostics indication LED
● for status of the inputs Yes

Potential separation
Potential separation digital inputs
● between the channels, in groups of 2

Degree and class of protection


IP degree of protection IP20

Standards, approvals, certificates


CE mark Yes

6ES72411CH320XB0 Subject to change without notice


1.17.2021
Page 3/2 © Copyright Siemens
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes

Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation


● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %

Connection method
required front connector Yes

Mechanics/material
Enclosure material (front)
● Plastic Yes

Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm

Weights
Weight, approx. 170 g

6ES7288-2DT16-0AA0 Subject to change without notice


Page 4/4 03/26/2020 © Copyright Siemens