You are on page 1of 297

TECHNICAL PUBLICATIONS

REVIEW REQUEST
6 April 2007
DATE ____________
SENT TO:
PowerCommand MCM3320
TITLE ___________________________________ Kevin Aufderhar
Service Manual
TYPE ___________________________________ Gary Olson
Paul Dahlen
900−0663
LITERATURE NO. _________________________ Rich Scroggins

IMPORTANT
THIS MATERIAL MUST BE RETURNED BY
25 Apr 2007
_____________________ TO MEET SCHEDULES.

PLEASE REVIEW AND APPROVE THIS MATERIAL AND RETURN TO WRITER NO LAT-
ER THAN ABOVE DATE. WE MUST HAVE THIS MATERIAL TO FINALIZE, PRINT,
AND MEET PRODUCT SHIPPING SCHEDULE.
WRITER’S REMARKS TO REVIEWER REVIEWER’S REMARKS TO WRITER

This manual needs to be thoroughly re-


viewed to make sure that it has complete
and accurate information. Although it is
nearly 300 pages, I suspect that more could
be added.
I know that the menu section is missing
some information that I hope you can pro-
vide. This includes some parameter ranges,
default values, and explanations of what is
accomplished with these menus.

Approved By: _____________________


Jim Lobitz, MN OU3K
Writer _________________________
EXT 7343 Date: ___________
PRELIMINARY

Service Manual

PowerCommand
Master Control Module (MCM3320)

Printed in U.S.A. 900−0663 4-2007


Table of Contents
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii

1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How to Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

2. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
MCM3320 Control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Operator Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Bargraph Display (HMI112) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Panel Harness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Converter Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
System Interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Master Control Subsystem Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Application Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Breaker Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Power Transfer Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Priority Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Master Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Load Demand Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Discrete Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Synchronizer Enable Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Utility Source Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Test Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Extended Parallel Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Fault Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Transfer and Retransfer Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Genset Circuit Breaker Position, Monitoring and Control . . . . . . . . . . . . . . . . 2-14
Circuit Breaker Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Utility Circuit Breaker Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Genset Circuit Breaker Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
ModBus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14

i
Table of Contents (Continued)
Discrete Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Utility Main Neutral Contactor 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Genset Main Neutral Contactor 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Genset Main Circuit Breaker Close Relay 1 and 2 . . . . . . . . . . . . . . . . . . . . 2-16
Genset Main Circuit Breaker Open Relay 1 and 2 . . . . . . . . . . . . . . . . . . . . 2-16
N.C. Genset Start Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
COM Genset Start Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
N.O. Genset Start Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Utility Main Circuit Breaker Close Relay 1 and 2 . . . . . . . . . . . . . . . . . . . . . 2-16
Utility Main Circuit Breaker Open Relay 1 and 2 . . . . . . . . . . . . . . . . . . . . . . 2-16
Low Side Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Load Govern Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Load Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Paralleling Genset Breaker Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 1 (Common Warning) . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 2 (Fail to Synchronize) . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 3 (Genset Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 4 (Utility Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 5 (Fail to Disconnect) . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 6 (Synchronized) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Configurable Output 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16

3. MCM3320 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1


AC Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
AC Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Master Synchronizing and Voltage Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Ratings and Typical Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Synchronizing Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Phase Synchronizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Slip Frequency Synchronizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Voltage Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Synchronizer Enabling Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Sync Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Auto / Manual Synchronizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Genset Sensor Operation During Synchronizing . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Synchronizer Polarity Inversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Maximum Allowable Synchronizer Range vs. Load Share Gains . . . . . . . . . . 3-4
Synchronizer Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5

ii
Table of Contents (Continued)
Fail to Synchronize Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Synchronizer Phase Rotation Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Synchronizer Output Limit Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Permissive Sync Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Permissive Close Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Dead Bus Close Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Circuit Breaker Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Breaker Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Breaker Position Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Breaker Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Power Transfer Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Auto/Manual Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
PTC Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Genset Run/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
PTC States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
No Source Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Utility Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Genset Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Paralleled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Undervoltage Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Overvoltage Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Frequency Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Phase Rotation Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Loss of Phase Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Main Breaker Tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Fail to Close . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Position Contact Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Genset Run/Stop Control Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
PTC Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Transfer Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Retransfer Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Transition Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Open Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Hard Closed Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Soft Closed Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11

iii
Table of Contents (Continued)
Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Test Without Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Test With Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Fail to Sync Open Transition Retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
System Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Multiple Transfer Pair Sequencing (External) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Extended Paralleling (Base Load / Peak Shave) . . . . . . . . . . . . . . . . . . . . . . . 3-14
Load Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Number of Gensets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Load Govern Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
ModBus RTU Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
ModBus Activity LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
System Scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
InPower Service Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Load Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Load Add and Load Shed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18

4. System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1


Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Closed Transition Failure Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Closed Transition Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Optional Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Load Demand Operation Using a Fixed Sequence . . . . . . . . . . . . . . . . . . . . . . 4-2
Load Demand Operation Using Run Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
PTC Normal Operating Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Isolated Bus Normal Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Common Bus Normal Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Transfer Pair Normal Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9

5. Setup and Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Meter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Synchronizer Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Setting up the Load Share Gains for Synchronizing . . . . . . . . . . . . . . . . . . . . . 5-5
System Setup with PCC3100 and PCC3200 Genset Controls . . . . . . . . . . . . . 5-6
Conditions Necessary for Synchronizing to Occur . . . . . . . . . . . . . . . . . . . . . . . 5-6
Synchronizing Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7

iv
Table of Contents (Continued)
Voltage Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Slip Frequency Synchronizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Setup the Synchronizer Gains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Synchronizer Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Permissive Close (Sync Check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Synchronizer Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Fail to Synchronize Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Synchronizer Phase Rotation Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Synchronizer Output Limit Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Voltage and Current Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Circuit Breaker Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Circuit Breaker Fail to Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Positions Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Recharge Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Fail to Fault Close Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Fail to Open Fault Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Genset and Utility Voltage and Frequency Sensor Setup . . . . . . . . . . . . . . . . . . 5-13
Undervoltage Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Overvoltage Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Frequency Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Phase Rotation Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Loss of Phase Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Genset and Utility Bus Sensors Settings for Synchronizer Applications . . . . 5-14
Auto / Manual Synchronizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Genset Sensor Operation During Synchronizing . . . . . . . . . . . . . . . . . . . . . . . 5-14
Load Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Master Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Extended Paralleling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Load Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
Number of Gensets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
Scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Program Overlapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Exception Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
Load Add / Load Shed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26

v
Table of Contents (Continued)

6. Operator Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Utility Parallel Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Lockout Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Warning Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Remote Start Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Auto Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Manual Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Operator Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Operator Panel System Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Communication Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Information Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Screen Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
System Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Master Synchronizer Only System Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Isolated Bus With or Without GM System Topology . . . . . . . . . . . . . . . . . . . . . . 6-5
Common Bus or Transfer Pair System Topology . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Default Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
No Source or Synchronizer Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Timers Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Parallel Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
MCM3320 Menu System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Control Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Adjust Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Monitor Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Faults Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
About Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Control Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Viewing Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Viewing and Adjusting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Enter Password Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Adjusting Values/Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Control Test Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Test Start/Stop Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Test Settings Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Control Extended Paralleling Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Extended Paralleling Start/Stop Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Extended Paralleling Settings Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18

vi
Table of Contents (Continued)
Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Control Load Demand Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Load Demand: Generator Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Load Demand: Genset Fixed Sequence Menu . . . . . . . . . . . . . . . . . . . . . . . 6-24
Load Demand: Genset Run Hours Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Load Demand: Next Genset Start-Up/Shut-Down Status Menu . . . . . . . . 6-24
Load Demand: Capacity Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Control Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Load Add Shed Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Add Levels Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Shed Levels Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Capacity Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Adjust Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
Viewing Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
Viewing and Adjusting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-30
Setup Password Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-30
Adjusting Values/Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-30
AC Meter Adjustment Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32
AC Meter Adjust Genset Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32
AC Meter Adjust Utility Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32
AC Meter Genset Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-34
AC Meter Utility Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36
Genset Circuit Breaker Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-38
Utility Circuit Breaker Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-38
Adjust Communications Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-40
Configuration Output Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-42
Adjust Load Control Output Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-44
Load Control Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-46
Miscellaneous Load Control Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . 6-46
Genset Load Control Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-48
Utility Load Control Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-50
Load Control Tuning Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-52
Load Control kW Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-52
Load Control kVAR Tuning Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-54
PTC Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-56
PTC Transfer Time Delay Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-56
PTC Generator Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-58
Miscellaneous PTC Generator Sensor Submenus . . . . . . . . . . . . . . . . . . . . 6-58
PTC Genset Undervoltage Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . 6-60
PTC Genset Overvoltage Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . 6-62
PTC Genset Frequency Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . 6-64

vii
Table of Contents (Continued)
PTC Utility Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-66
Miscellaneous PTC Utility Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . 6-66
PTC Utility Undervoltage Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . 6-68
PTC Utility Overvoltage Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . 6-70
PTC Utility Frequency Sensor Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-72
Sync Check Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-74
Sync Adjust Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-78
Sync Adjust Miscellaneous Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-78
Sync Adjust Frequency Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-80
Sync Adjust Voltage Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-82
System Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-84
System Application Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-84
System kW Ratings Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-88
Scheduler Set Clock Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-90
Scheduler Daylight Savings Time Submenus . . . . . . . . . . . . . . . . . . . . . . . . 6-90
Scheduler Programs Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-92
Scheduler Program Exceptions Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . 6-94
LCD Display Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-96
Screen Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-96
CRC Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-96
Lamp Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-96
Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-98
Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-100
Genset Bus Overload Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-104
Monitor Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-106
Monitor AC Meter Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-108
System AC Meter Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-108
Genset AC Meter Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-110
Utility AC Meter Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-116
System AC Meter Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-122
Monitor Analog In Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-124
Monitor Analog Out Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-124
Monitor Breakers Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-126
Monitor Communication Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-126
Monitor PTC Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-128
Genset Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-128
PTC Status Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-130
PTC Timers Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-132
Utility Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-134
Monitor Load Control Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-136
Monitor Priority Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-136

viii
Table of Contents (Continued)
Monitor Relay Outputs Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-136
Monitor Switch Inputs Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-138
Monitor Sync Check Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-140
Monitor Synchronizer Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-142
Monitor System Status Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-144
Monitor Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-146
Monitor Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-148
Add Level Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-148
Shed Level Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-148
Load Status ATS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-148
Load Status Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-148
Monitor Generator Bus Overload Submenus . . . . . . . . . . . . . . . . . . . . . . . . . 6-150
Monitor Scheduler Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-150
Faults Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Current Fault Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Active Event Table Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Event Occurrence Table Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Active Fault Table Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Fault History Table Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
Fault Occurrence Table Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152

7. Testing and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1


Fault and Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
System Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
System and diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Test and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Bench Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Malfunctioning Lamps, Meters, Gauges, and/or Starter Solenoid . . . . . . . . . . 7-4
Paralleling Breaker Fail-to-Close Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Troubleshooting Using Fault / Event Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Abnormal Scenarios / Fault Reaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Utility Main Fail to Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Utility Main Fail to Close . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Utility Main Breaker Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Utility Main Breaker Tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Utility Main Breaker Disconnected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Genset Main Fail to Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Genset Main Fail to Close . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21

ix
Table of Contents (Continued)
Genset Main Breaker Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Genset Main Breaker Tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Genset Main Breaker Disconnected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Fail to Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Maximum Parallel Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Fail to Synchronize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Genset Bus Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Utility Source Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22

8. Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1

x
List of Figures
Figure Title Page
2-1 MCM3320 Control Board and Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2-2 MCM3320 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2-3 MCM3320 Hardware I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2-4 MCM3320 Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2-5 Bargraph Display (HMI112) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2-6 AUX101 and AUX102 I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2-7 Functional Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
3-1 MCM3320 Features Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3-2 Transfer Pair Topology (System Types 2, 3, 4, 8, 10, and 11) . . . . . . . . . . . . . . . . . . . . . . 3-12
3-3 Common Bus Topology (System Types 9) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3-4 Isolated Bus With GM Topology (System Type 7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3-5 Isolated Bus Without GM Topology (System Types 5 and 6) . . . . . . . . . . . . . . . . . . . . . . . 3-13
3-6 Master Synchronizer Only Topology (Optional Metering) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
5-1 MCM3320 PC Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5-2 Generator and Utility Metering Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5-3 4 Wire Direct Connection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5-4 4 Wire with Transformer Connection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5-5 3 Wire Direct Connection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5-6 3 Wire with Transformer Connection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5-7 Slip Frequency Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5-8 Using the Master Sync Only Feature to Communicate With PowerCommand Controls 5-10
5-9 Voltage and Current Calibration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5-10 Circuit breaker Setup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5-11 Generator Bus Sensor Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5-12 Load Demand Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
5-13 kW Base Load/Peak Shave Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5-14 kVAR Base Load/Peak Shave Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5-15 System Setup Screen (1 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5-16 System Setup Screen (2 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5-17 Transfer pair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5-18 Common Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5-19 Transfer Pair with GM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
5-20 Scheduler Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
5-21 Program Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5-22 Program Exception Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5-23 Examples of Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5-24 Real Time Clock Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
5-25 Load Add / Load shed Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26

xi
List of Figures (Continued)
Figure Title Page
6-1 MCM3320 Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6-2 Establishing Communications Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6-3 Re-Establishing Communications Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6-4 Fault Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6-5 Information Screen for Master Synchronizer Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6-6 Information Screen for Isolated Bus With or Without GM . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6-7 Default Home Information Screen for Common Bus or Transfer Pair . . . . . . . . . . . . . . . . . 6-6
6-8 No Source or Synchronizer Home Information Screen for Common Bus or Transfer Pair 6-6
6-9 Timers Home Information Screen for Common Bus or Transfer Pair . . . . . . . . . . . . . . . . . 6-7
6-10 Parallel Home Information Screen for Common Bus or Transfer Pair . . . . . . . . . . . . . . . . 6-7
6-11 Main Menu and Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6-12 Control Menus − Viewing Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6-13 Control Menus − Viewing and Adjusting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
6-14 Control Test Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
6-15 Control Extended Paralleling Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
6-16 kW Control Extended Paralleling Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-19
6-17 kVAR Control Extended Paralleling Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
6-18 Control Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-25
6-19 Control Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-27
6-20 Adjust Menus − View Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-29
6-21 Adjust Menus − View and Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31
6-22 Adjust Menus − AC Meter Adjust Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-33
6-23 Adjust Menus − AC Meter Genset Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-35
6-24 Adjust Menus − AC Meter Utility Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-37
6-25 Adjust Menus − Breakers Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-39
6-26 Adjust Menus − Communications Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-41
6-27 Adjust Menus − Configuration Output Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-43
6-28 Adjust Menus − Load Control Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
6-29 Adjust Menus − Load Control Miscellaneous setup Submenus . . . . . . . . . . . . . . . . . . . . . 6-47
6-30 Adjust Menus − Load Control Genset Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-49
6-31 Adjust Menus − Load Control Utility setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-51
6-32 Adjust Menus − Load Control kW Tuning Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-53
6-33 Adjust Menus − Load Control kVAR Tuning Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-55
6-34 Adjust Menus − PTC Sensors Submenus and Transfer Time Delay Submenus . . . . . . 6-57
6-35 Adjust Menus − PTC Genset Miscellaneous Sensors Submenus . . . . . . . . . . . . . . . . . . . 6-59
6-36 Adjust Menus − PTC Genset Undervoltage Sensors Submenus . . . . . . . . . . . . . . . . . . . 6-61
6-37 Adjust Menus − PTC Genset Overvoltage Sensors Submenus . . . . . . . . . . . . . . . . . . . . . 6-63
6-38 Adjust Menus − PTC Genset Frequency Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . 6-65
6-39 Adjust Menus − PTC Utility Miscellaneous Sensors Submenus . . . . . . . . . . . . . . . . . . . . 6-67

xii
List of Figures (Continued)
Figure Title Page
6-40 Adjust Menus − ptc Utility Undervoltage sENSORS Submenus . . . . . . . . . . . . . . . . . . . . 6-69
6-41 Adjust Menus − PTC Utility Overvoltage Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . 6-71
6-42 Adjust Menus − PTC Utility Frequency Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . 6-73
6-43 Adjust Menus − Sync Check Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-75
6-44 Adjust Menus − Sync Adjust Miscellaneous Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-79
6-45 Adjust Menus − Sync Adjust Frequency Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-81
6-46 Adjust Menus − Sync Adjust Voltage Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-83
6-47 Adjust Menus − System Application Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-85
6-48 Adjust Menus − System kW Ratings Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-89
6-49 Adjust Menus − Scheduler Set Clock and Daylight Savings Submenus . . . . . . . . . . . . . 6-91
6-50 Adjust Menus − Scheduler Programs Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-93
6-51 Adjust Menus − Scheduler Program Exceptions Submenus . . . . . . . . . . . . . . . . . . . . . . . 6-95
6-52 Adjust Menus − LCD Display Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-97
6-53 Adjust Menus − Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-99
6-54 Adjust Menus − Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-101
6-55 Adjust Menus − Generator Bus Overload Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-105
6-56 Monitor Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-107
6-57 Monitor Menus − AC Meter Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-109
6-58 Monitor Menus − AC Meter Genset Current, Energy, and Frequency Submenus . . . . 6-111
6-59 Monitor Menus − AC Meter Genset Phase and Voltage Submenus . . . . . . . . . . . . . . . . 6-113
6-60 Monitor Menus − AC Meter Genset Power Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-115
6-61 Monitor Menus − AC Meter Utility Current, Energy, and Frequency Submenus . . . . . . 6-117
6-62 Monitor Menus − AC Meter Utility Phase and Voltage Submenus . . . . . . . . . . . . . . . . . 6-119
6-63 Monitor Menus − AC Meter Utility Power Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-121
6-64 Monitor Menus − AC Meter System Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-123
6-65 Monitor Menus − Analog In and Analog Out Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . 6-125
6-66 Monitor Menus − Breakers and Communications Submenus . . . . . . . . . . . . . . . . . . . . . 6-127
6-67 Monitor Menus − PTC Genset Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-129
6-68 Monitor Menus − PTC Status Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-131
6-69 Monitor Menus − PTC Timers Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-133
6-70 Monitor Menus − PTC Utility Sensors Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-135
6-71 Monitor Menus − Load Control, Priority, and Relay Outputs Submenus . . . . . . . . . . . . 6-137
6-72 Monitor Menus − Switch Inputs Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-139
6-73 Monitor Menus − Sync Check Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-141
6-74 Monitor Menus − Synchronizer Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-143
6-75 Monitor Menus − System Status Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-145
6-76 Monitor Menus − Load Demand Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-147
6-77 Monitor Menus − Load Add Shed Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-149
6-78 Monitor Menus − Generator Bus Overload and Scheduler Submenus . . . . . . . . . . . . . . 6-151
6-79 Faults Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-153
7-1 MCM3320 Control Board LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
MCM3320 Wiring Diagram (Sheet 1 of 20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3

xiii
List of Tables
Table Title Page
2-1 Hardware I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2-2 Operator Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2-3 System States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2-4 Discrete Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2-5 Discrete Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
3-1 Typical Synchronizer Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3-2 Recommended Slip Frequency Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3-3 Synchronizing Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3-4 PCC3100 Maximum Allowable Synchronize Range vs Load Share Gains . . . . . . . . . . . . 3-5
3-5 Sync Check Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3-6 PTC Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-7 PTC Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-8 Real Power Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
3-9 Reactive Power Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
4-1 Isolated Bus Normal Sequence of Operation − Test With Load . . . . . . . . . . . . . . . . . . . . . . 4-3
4-2 Isolated Bus Normal Sequence of Operation − Test Without Load . . . . . . . . . . . . . . . . . . . 4-4
4-3 Common Bus Normal Sequence of Operation − Utility Failure/Return . . . . . . . . . . . . . . . . 4-5
4-4 Common Bus Normal Sequence of Operation − Test With Load . . . . . . . . . . . . . . . . . . . . . 4-6
4-5 Common Bus Normal Sequence of Operation − Test Without Load . . . . . . . . . . . . . . . . . . 4-7
4-6 Common Bus Normal Sequence of Operation − Extended Paralleling . . . . . . . . . . . . . . . 4-8
4-7 Transfer Pair Normal Sequence of Operation − Utility Failure/Return . . . . . . . . . . . . . . . . 4-9
4-8 Transfer Pair Normal Sequence of Operation − Test With Load . . . . . . . . . . . . . . . . . . . . 4-10
4-9 Transfer Pair Normal Sequence of Operation − Test Without Load . . . . . . . . . . . . . . . . . 4-11
4-10 Transfer Pair Normal Sequence of Operation − Extended Paralleling . . . . . . . . . . . . . . . 4-12
5-1 Typical Synchronizer Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5-2 Synchronizing Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5-3 PCC3100 Maximum Allowable Synchronize Range vs Load Share Gains . . . . . . . . . . . . 5-6
5-4 PCC3200 Maximum Allowable Synchronize Range vs Load Share Gains . . . . . . . . . . . . 5-6
5-5 typical synchronizer Gain Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5-6 Permissive window Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
5-7 Base Load / Peak Shave Configuration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5-8 Application configuration variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
6-1 Operator Control Navigation buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6-2 PTC Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-130
6-3 PTC States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-144
6-4 Event Numbers and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-152
6-5 Fault Numbers and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-154
7-1 MCM3320 System Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7-2 U51 LED Activity Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7-3 Control Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
8-1 MCM3320 Board Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23

xiv
Foreword
The purpose of this manual is to provide the users with general control operation and fault code information.
Refer to the equipment manufacturer’s product support manuals for important safety precautions.

Manufacturers applying this control are respectfully advised that it is their responsibility to employ competent
persons to carry out any installation work in the interests of good practice and safety. It is essential that the
utmost care is taken with the application of this control device.

Warranty
Warranty: This manual is published solely for information purposes and should not be considered all inclu-
sive. Sale of product shown or described in this literature is subject to terms and conditions outlined in ap-
propriate Cummins Power Generation selling policies or other contractual agreement between the parties.
This literature is not intended to and does not enlarge or add to any such contract. The sole source governing
the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Cum-
mins Power Generation.

NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTIC-


ULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR
USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DE-
SCRIPTIONS CONTAINED HEREIN.

In no event will Cummins Power Generation be responsible to the purchaser or user in contract, in tort (includ-
ing negligence), strict liability or otherwise for any special, indirect, incidental, or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of
capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchas-
er or user by its customers resulting from the use of the information, recommendations, and descriptions con-
tained herein.

xv
THIS PAGE LEFT INTENTIONALLY BLANK

xvi
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS − This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator and batter- • Provide an adequate exhaust system to properly
ies. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
• Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
ator, service personnel, or the equipment.
birth defects, and other reproductive harm.
DANGER This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or
moving parts.
unsafe practice which can result in severe per-
sonal injury or death. • Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or connect starting batteries, negative (−) cable first.
unsafe practice which can result in personal in- This will prevent accidental starting.
jury or product or property damage. • Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result • Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
• DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential • If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
• Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
• Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.

LS-14L

xvii
ELECTRICAL SHOCK CAN CAUSE • Keep multi-class ABC fire extinguishers handy.
SEVERE PERSONAL INJURY OR DEATH Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
• Remove electric power before removing protective and flammable liquid fuels and gaseous fuels; Class
shields or touching electrical equipment. Use rub- C fires, live electrical equipment. (ref. NFPA No. 10).
ber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around • Make sure that rags are not left on or near the en-
electrical equipment. Do not wear damp clothing gine.
(particularly wet shoes) or allow skin surface to be
damp when handling electrical equipment. Do not • Make sure generator set is mounted in a manner to
wear jewelry. Jewelry can short out electrical con- prevent combustible materials from accumulating
tacts and cause shock or burning. under the unit.
• Use extreme caution when working on electrical • Remove all unnecessary grease and oil from the
components. High voltages can cause injury or unit. Accumulated grease and oil can cause over-
death. DO NOT tamper with interlocks. heating and engine damage which present a poten-
• Follow all applicable state and local electrical tial fire hazard.
codes. Have all electrical installations performed by • Keep the generator set and the surrounding area
a qualified licensed electrician. Tag and lock open clean and free from obstructions. Remove any de-
switches to avoid accidental closure. bris from the set and keep the floor clean and dry.
• DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. • Do not work on this equipment when mentally or
Hazardous voltages can flow from the generator set physically fatigued, or after consuming any alcohol
into the utility line. This creates a potential for elec- or drug that makes the operation of equipment un-
trocution or property damage. Connect only safe.
through an approved isolation switch or an ap-
• Substances in exhaust gases have been identified
proved paralleling device.
by some state or federal agencies as causing can-
GENERAL SAFETY PRECAUTIONS cer or reproductive toxicity. Take care not to breath
or ingest or come into contact with exhaust gases.
• Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex- • Do not store any flammable liquids, such as fuel,
changer pressure cap while the engine is running. cleaners, oil, etc., near the generator set. A fire or
Allow the generator set to cool and bleed the system explosion could result.
pressure first.
• Wear hearing protection when going near an oper-
• Used engine oils have been identified by some state ating generator set.
or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil, • To prevent serious burns, avoid contact with hot
take care not to ingest, breathe the fumes, or con- metal parts such as radiator, turbo charger and ex-
tact used oil. haust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

LS-14L

xviii
PRELIMINARY

1. Introduction
ABOUT THIS MANUAL synchronizing, load control, genset start/stop,
diagnostics, load demand, load add, and load
This manual provides operation, troubleshooting, shed. MCM3320 features can also be used in more
and repair information regarding the CumminsR complex systems. The MCM3320 can synchronize
Power Generation (CPG) Master Command Mod- up to a 12-genset bus to another source.
ule 3320 (MCM3320). This manual also includes
fault code information and corrective steps. CERTIFICATIONS
This manual does not have instructions for servic- The MCM3320 meets or exceeds the require-
ing printed circuit board assemblies. After deter- ments of the following codes and standards.
mining that a printed circuit board assembly is
• UL508 Recongnized
faulty, replace it. Do not repair it. Attempts to repair
a printed circuit board can lead to costly equipment • CE Mark
damage. • EN 61000-2
• EN 61000-4
This manual contains basic (generic) wiring dia-
grams and schematics that are included to help in • ISO 7637, pulses #2, 3a, 3b, 5, 7
troubleshooting. Service personnel must use the PowerCommand control systems are designed
actual wiring diagram and schematic shipped with and manufactured in ISO9001 certified facilities.
each unit. The wiring diagrams and schematics
that are maintained with the unit should be updated HOW TO OBTAIN SERVICE
when modifications are made to the unit.
Contact your generator set manufacturer when
Read the Important Safety Precautions (see seeking additional service information or replace-
pages xvii and xviii) and carefully observe all in- ment parts. Provide model and serial number infor-
structions and precautions in this manual. mation.

SYSTEM OVERVIEW WARNINGIncorrect service or replacement of


parts can result in severe personal injury or
The MCM3320 is designed to reduce the complex- death, and/or equipment damage. Service per-
ity of paralleling systems. It is a system component sonnel must be qualified to perform electrical
designed to interface with multiple PowerCom- and mechanical service. Read and follow Im-
mand digital paralleling controls operating on a portant Safety Precautions, on pages xvii and
common bus. xviii.
The MCM3320 can be used to manage simple sys- Information on how to obtain service is also avail-
tems that include such features as breaker control, able at www.cumminspower.com.

Copyright© 2007 Cummins Power Generation. All rights reserved. 1-1


Cummins is a registered trademark of Cummins Inc.
PRELIMINARY

THIS PAGE LEFT INTENTIONALLY BLANK

1-2
PRELIMINARY

2. Description

FIGURE 2-1. MCM3320 CONTROL BOARD AND OPERATOR PANEL

OVERVIEW use of a voltage transformer (VT) to provide control


signals to the device.
The PowerCommandt Master Control Module
(MCM3320) is a microprocessor−based system The control is designed for panel mounting, but can
control component designed for use with Power- be mounted into a large number of physical loca-
Command digital paralleling controls. tions due to its inherent environmental protection.
The MCM3320 is usually powered from the gener-
The control can be used with generator sets that
ator set starting batteries. The module can be con-
have various frequency (50 or 60 Hz operation),
nected to two independent DC sources for redun-
voltage, and power connection configurations from
dancy. The control functions over a voltage range
120 to 35,000 VAC. The MCM3320 simultaneously
from 9 to 32 VDC and requires less than 1 amp.
synchronizes multiple generator sets to a utility or
other system bus. The MCM3320 drives the genset The MCM3320 is designed for connection to a 12
bus to match the phase, frequency, and voltage of or 24 VDC control system.
the reference bus.
The MCM3320 includes on-board diagnostics and
The MCM3320 is suitable for direct connection to can be configured using the RS-485 interface for
alternators and system buses operating at up to communicating with the InPower service tool.
480VAC line-to-line. By default, the synchronizer An MCM3320 installation may include the following
is set up for nominal line-to-line voltages from equipment.
110−139VAC. The synchronizer can also be used
in applications operating at up to 35kV by proper • The MCM3320 control board

2-1
PRELIMINARY

• One or two operator panels (HMI211) (in- • TB6 − Genset (3-Phase plus Neutral) PT In-
cludes six status LED lamps and a screen that puts (480 VAC Max)
can be used to view menus and adjust param- • TB7 − Utility (3-Phase plus Neutral) PT Inputs
eters) (480 VAC Max)
• Two bargraph panels (HMI112) (one for the
• TB8 − Breaker Control and Start Genset
genset bus, one for the utility bus)
• TB9 − Analog I/O
• Harness (as many as needed) to connect op-
erator panel(s) and/or bargraph panel(s) to the • TB10 − Breaker Status (A and B Inputs)
MCM3320 • TB15 − Service Tool or ModBus RTU (RS-485)
• PCCNet I/O Module (AUX101/AUX102) (used • J14 − ModBus RTU (RS-232)
with the Load Add / Load Shed feature)
The MCM3320 control board also includes three
• An RS-485 to RS-232 converter kit (541−1199) genset and three utility current transformers (CTs).
− used for connecting the controller with In- Each CT includes a polarity mark. For a 5 amp CT,
Power, the Setup Tool, or the Engineering Tool the wire must make one pass through the CT. For a
MCM3320 CONTROL BOARD 1 amp CT, the wire must make two passes through
the hole.
The MCM3320 control board (327−1520−01) in-
cludes the following connectors (see Figure 2-2). For detailed information on these connections, see
Table 8-1.
• TB1 − Switch I/O and PCCNet
A block diagram showing the MCM3320 hardware
• TB2 − Switch I/O and DC Power In I/O is shown in Figure 2-3. The hardware I/O is de-
• TB3 − Switch I/O and System Bus (CAN) scribed in Table 2-1.

GENSET CURRENT UTILITY CURRENT


TRANSFORMERS TRANSFORMERS
(1 AMP OR 5 AMP) (1 AMP OR 5 AMP)
TB7

TB6

TB9
TB2

J14

TB15

TB3 TB1 TB8 TB10

FIGURE 2-2. MCM3320 CONNECTORS

2-2
PRELIMINARY

B+ Input1 Master Freq Bias


B+ Input 2 Master Volt Bias
B+ POWER BIDIRECTIONAL
Gnd Master Priority
Gnd
Start Gensets Relay
RELAY OUTPUTS
CAN (Master)
RS-485 PCC Net
COMMUNICATIONS
RS-485/232 Mon/MB
Load Govern Enable
Extended Parallel Start Load Demand Gen1
Sync Enable MCM3320 Load Demand Gen2
Utility Source Failure Load Demand Gen3
Load Demand Gen4
Transfer Inhibit DISCRETE INPUTS Cfg Out1 (Common Warn)
Retransfer Inhibit (Active Low w/Pullup)
Cfg Out2 (Fail to Sync)
Gen CB Tripped DISCRETE OUTPUTS
(Low Side Drivers) Cfg Out3 (Gen Available)
Util CB Tripped
Cfg Out4 (Utility Available)
Gen CB Inhibit Cfg Out5 (Fail to Discon)
Util CB Inhibit
Cfg Out6 (Synchronized)
Auto/Manual
Cfg Out7
Test Start Cfg Out8

Fault Ack/Reset Paralleling Gensets


Breaker Inhibit
Gen1 Available
Gen2 Available
Gen3 Available
Relay Supply
Gen4 Available B+ OUTPUTS
Override

kW Load Setpoint kW Master Load Control


ANALOG ANALOG OUTPUTS
kVAR Load Setpoint kVAR Master Load Control
INPUTS (0−5V)
BREAKER INTERFACE
(Discrete Inputs / Relay BUS/
GEN Outputs) UTIL
V/I V/I
Gen Open
Gen Close
Gen Position A
Gen Position B

Util Open
Util Close
Util Position A
Util Position B

GENSET UTILITY

LOAD

FIGURE 2-3. MCM3320 HARDWARE I/O

2-3
PRELIMINARY

TABLE 2-1. HARDWARE I/O


Hardware Signal Active State* Function
B+ Input1 Battery positive power input for the board. Diode OR’d on the board
with B+ Input2. 9−32V range. Starter dip ride-through capable.
B+ Input2 Battery positive power input for the board. Diode OR’d on the board
with B+ Input1. 9−32V range. Starter dip ride-through capable.
Gnd Battery negative connection for the board.
CAN (Master) Communications bus available for future use.
RS485 PCCNet Communications network for connecting displays, bargraphs, and I/O
modules to the controller.
RS485/232 Mon/MB Communications connection for tools (via Mon) or PLCs, etc. via
ModBus RTU.
Extended Parallel Start Input used to command an extended paralleling session.
Start
Sync enable Enable Sync Input used to manually enable synchronizing if the Auto/Manual input
is in the Manual state.
Utility Source Failure Source Failed Input used to tell the control that the utility source is not available.
This may be used if an external device is used to determine utility
source status. It can also be used to simulate a utility failure.
Transfer Inhibit Inhibit Active Input used to inhibit a transfer to gensets. An active Override input
will cause an active transfer inhibit to be ignored.
Retransfer Inhibit Inhibit Active Input used to inhibit a retransfer to utility. An active Override input will
cause an active retransfer inhibit to be ignored. Also, the failure of the
genset bus while connected to the genset bus will cause an active
retransfer inhibit to be ignored.
Gen CB Tripped Tripped Input used to tell the control that the genset main breaker is tripped
(bell alarm). The control then declares the genset source to be not
available.
Utilit CB Tripped Tripped Input used to tell the control that the utility main breaker is tripped
(bell alarm). The control then declares the utility source to be not
available.
Gen CB Inhibit Inhibit Active Input used to force the genset main breaker to open, or to prevent it
from closing if already open.
Util CB Inhibit Inhibit Active Input used to force the utility main breaker to open, or to prevent it
from closing if already open.
Auto/Manual Manual Input used to put the control in the manual mode. Manual operation
applies to the breaker control and the synchronizer.
Test Start Start Input used to command a test start (with or without load transfer as
configured).
Fault Reset Reset Input used to reset faults AND also to put the on-board 7-segment
LED into the fault readout mode. The fault readout mode is entered
by holding the reset input active for longer than 5 seconds. The fault
readout mode is exited by toggling the reset input active/inactive.
Faults are then reset by an additional toggle of the input.
Gen1 CB Position Closed Input used to tell control that the genset #1 paralleling breaker is
closed. It is used in applications with no gen main and in load
demand applications.
* For discrete inputs, the active state is when the input is connected to a return (gnd). The inactive state is when
the input is open circuit. For discrete low side outputs, the active state is when the low side output is on (gnd)
and the inactive state is when the low side output is off (float).

2-4
PRELIMINARY

TABLE 2-1. HARDWARE I/O (CONT.)


Hardware Signal Active State* Function
Gen2 CB Position Closed Input used to tell control that the genset #2 paralleling breaker is
closed. It is used in applications with no gen main and in load
demand applications.
Gen3 CB Position Closed Input used to tell control that the genset #3 paralleling breaker is
closed. It is used in applications with no gen main and in load
demand applications.
Gen4 CB Position Closed Input used to tell control that the genset #4 paralleling breaker is
closed. It is used in applications with no gen main and in load
demand applications.
Override Override Active Input used to override the transfer inhibit, retransfer inhibit, start
timer, transfer timer, and retransfer timer. It is used to cause
immediate action, bypassing time delays and inhibits.
kW Load Setpoint 0−5V Analog input which can be used to set the base load or peak shave
kW setpoint. Alternatively this can be done via a trim setting or via
the ModBus. The analog input profile of %kW vs. VDC is the same
profile as the PCC genset control.
kVAR Load Setpoint 0−5V Analog input which can be used to set the base load or peak shave
kVAR or Power Factor setpoint. Alternatively this can be done via a
trim setting or via the ModBus. The analog input profile of %kVAR vs.
VDC is the same profile as the PCC3200 genset control. the analog
input profile of Power Factor vs. VDC is covered in the Extended
Paralleling section of this manual.
Master Frequency −2.5 to +5 V This is a bidirectional analog signal which connects to the PCC kW
Bias load share lines for master voltage matching. The MCM3320 moves
the voltage on the kW load share lines to affect the genset bus
frequency for synchronizing.
Master Voltage Bias −2.5 to +5 V This is a bidirectional analog signal which connects to the PCC kW
load share lines for master synchronizing. The MCM3320 moves the
voltage on the kVAR load share lines to affect the genset bus voltage
for voltage matching.
Master Priority This is a bidirectional discrete signal line which can be used in two
different modes.
The first mode (master sync only) is a manual master inhibit input. If
the input is activated (connected to return), the MCM3320 is inhibited
from synchronizing or breaker operation. This allows a PLC to
orchestrate multiple MCM3320s in a retransfer sequence.
The second mode is an automatic priority control mode. In this mode,
this signal is interconnected to all other MCM3320s. Then for a
retransfer, the controls arbitrate as to which one will get to retransfer
first. Sequence order can be set by adjusting the retransfer time
delay differently. the arbitration guarantees that only one MCM3320
will be able to perform the synchronizing and load control functions at
a time.
Start Gensets Relay Form C relay This is a Form C relay which is used to activate the remote start
inputs on all of the gensets simultaneously.
* For discrete inputs, the active state is when the input is connected to a return (gnd). The inactive state is when
the input is open circuit. For discrete low side outputs, the active state is when the low side output is on (gnd)
and the inactive state is when the low side output is off (float).

2-5
PRELIMINARY

TABLE 2-1. HARDWARE I/O (CONT.)


Hardware Signal Active State* Function
Load Govern Enable Enable This is a low side driver output to be connected to all of the utility CB
aux/position inputs on the individual PCC genset controls. This allows
the MCM3320 to tell the gensets control when to go into the load
govern (utility parallel) mode.
Load Demand Gen1 Stop This is a low side driver output to be connected to Genset #1 Load
Demand input.
Load Demand Gen2 Stop This is a low side driver output to be connected to Genset #2 Load
Demand input.
Load Demand Gen3 Stop This is a low side driver output to be connected to Genset #3 Load
Demand input.
Load Demand Gen4 Stop This is a low side driver output to be connected to Genset #4 Load
Demand input.
Cfg Out1 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out2 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out3 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out4 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out5 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out6 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out7 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Cfg Out8 Low This is a low side driver output which is intended to drive a relay coil.
It is configurable in that it can be mapped to any event or fault code.
Paralleling Gensets Inhibit This is a low side driver output to be connected to the Gen CB Inhibit
Breaker Inhibit input for ALL of the individual PCC genset controls. This allows the
MCM3320 to indirectly control the genset paralleling breakers.
Relay Supply B+ This is a B+ output to be used to supply the high side of relay coils
for the Cfg Out 1−8 low side outputs.
kW Master Load 0−5V This is an analog output to be connected to the Load Set / External
Control kW input on all of the individual PCC genset controls. This allows the
MCM3320 to control the genset bus kW output when utility paralleled.
kVAR Master Load 0−5V This is an analog output to be connected to the External kVAR input
Control on all of the individual PCC genset controls. (Input not available on
the PCC3100.) This allows the MCM3320 to control the genset bus
kVAR output when utility paralleled.
Gen Bus PTs The Gen Bus voltage sensing inputs are 3 phase, 3 or 4 wire, and
0−500V direct.
Utility Bus PTs The Utility Bus voltage sensing inputs are 3 phase, 3 or 4 wire, and
0−500V direct.
* For discrete inputs, the active state is when the input is connected to a return (gnd). The inactive state is when
the input is open circuit. For discrete low side outputs, the active state is when the low side output is on (gnd)
and the inactive state is when the low side output is off (float).

2-6
PRELIMINARY

TABLE 2-1. HARDWARE I/O (CONT.)


Hardware Signal Active State* Function
Gen Bus CTs The Gen Bus current transformer inputs are 3 phase, 1 amp or 5
amp secondary, very low burden.
NOTE: There are NO terminals on the MCM3320 for the CT secon-
daries. Wire must be looped through the small CTs on the
board. Locating a short terminal block close to the MCM3320 to
facilitate the connection is recommended.
Utility Bus CTs The Utility Bus current transformer inputs are 3 phase, 1 amp or 5
amp secondary, very low burden.
NOTE: There are NO terminals on the MCM3320 for the CT secon-
daries. Wire must be looped through the small CTs on the
board. Locating a short terminal block close to the MCM3320 to
facilitate the connection is recommended.
Gen Main Breaker ‘a’ Breaker Closed Input from the genset main breaker ‘a’ position contact.
Contact
Gen Main Breaker ‘b’ Breaker Open Input from the genset main breaker ‘b’ position contact.
Contact
Gen Main Breaker Normally open relay contact output for driving the genset main
Open Relay breaker open coil.
Gen Main Breaker Normally open relay contact output for driving the genset main
Close Relay breaker close coil.
Utility Main Breaker ‘a’ Breaker Closed Input from the utility main breaker ‘a’ position contact.
Contact
Utility Main Breaker ‘b’ Breaker Open Input from the utility main breaker ‘b’ position contact.
Contact
Utility Main Breaker Normally open relay contact output for driving the utility main breaker
Open Relay open coil.
Utility Main Breaker Normally open relay contact output for driving the utility main breaker
Close Relay close coil.
* For discrete inputs, the active state is when the input is connected to a return (gnd). The inactive state is when
the input is open circuit. For discrete low side outputs, the active state is when the low side output is on (gnd)
and the inactive state is when the low side output is off (float).

2-7
PRELIMINARY

OPERATOR PANEL Operator Panel Connections


Up to two operator panels can be connected to one
MCM3320 control installations include an operator
MCM3320. Harness 338−4747 is used to connect
panel (HMI211, 300−6090). The display is
an operator panel to the MCM3320. This harness
composed of an adjustable contrast backlit LCD
can be cut to length or extended to 12 feet (3.6 me-
display, with a series of 6 generator status LED
ters).
lamps. The display is accompanied by a set of six
tactile feel membrane switches that are used by the The operator panel is connected via the PCCNet.
operator to navigate through control menus, and to Two connectors (J1 and J2) are located on the
adjust settings. back of the operator panel (see Figure 2-4).
Connections are listed in Table 2-2.
The operator panel includes an information screen
with access to menus that can be viewed and, NOTE: J1 and J2 are identical. Either one can be
when necessary, adjusted. Faults are automatical- used for the harness connection between
ly displayed on the display screen and six LEDs the main control board and the operator
provide status information. panel.

More information and the operator panel and the The PCCNet interface includes 4 wires for B+,
menu system is included in Section 6. GND, RS-485A and RS-485B connections.

1 5
2 6

3 7
4 8
PIN 1
J1 or J2

J2

J1
J1-4

FIGURE 2-4. MCM3320 OPERATOR PANEL

TABLE 2-2. OPERATOR PANEL CONNECTIONS


Connector Pin Signal Name Connect To / Comments
J1-1 RS-485 Data A Network Data A
J1-2 RS-485 Data B Network Data B
J1-3 B+ Network Supply
J1-4 PCCNet System Wake Up System Wakeup
J1-5 Return Network Supply Return
J1-6 Run Output
J1-7 Auto Output
J1-8

2-8
PRELIMINARY

BARGRAPH DISPLAY (HMI112) I/O MODULE


The MCM3320 supports the PCCNet bargraph
(HMI112, 300−6050−01). Two separate bargraphs The MCM3320 supports an AUX101/AUX102
are used to display AC data — one for the utility bus PCCNet I/O Module (kit 541−1342) for feeder
and one for the genset bus. Only one bargraph can breaker control and/or an ATS control (see Figure
be used for each power source. 2-6). These modules are used with the load add /
load shed feature.
The bargraphs include nine bars to display L1, L2,
and L3 current percentage; percentage of total kW;
The AUX101 connects to load devices #1, 2, 3, and
power factor; frequency; and L12, L23, and L31
4. It includes the following.
voltage percentage.
The bargraph includes 4 wires for B+, GND, • J1 − PCCNet and Wakeup
RS-485A and RS-485B connections.
• J2 − Relays
• J3 − Relays
• J4 − Relays
• J10 − Ground for Inputs
• J11 − Inputs
• J14 − B+ / GND
• PCCNet Communications LED (Green = OK,
Red = Not OK)
• Relay LEDs (ON = Energized)
• Device Number LED − The device number
FIGURE 2-5. BARGRAPH DISPLAY (HMI112) must be “0” for MCM3320 applications.

PANEL HARNESS • Pushbutton − Used to change the device num-


ber. Press and hold the pushbutton until the
A 12-foot harness (338−4747) that can be cut to decimal point is illuminated. the press the but-
length is available for connecting each operator ton repeatedly to cycle through the numbers
panels and/or bargraph panels to the MCM3320. until it reads “0.”

J11 J10
DEVICE NUMBER
INDICATOR
S1 (DEV#) J4 (CUSTOMER INPUTS)

J14
J1

J3
J6
DS1 J5
J2

DS2
J1

J2 J3 J4

FIGURE 2-6. AUX101 AND AUX102 I/O MODULES

2-9
PRELIMINARY

The AUX102 connects to load devices #5 and 6. It The MCM3320 is fused externally with a 4 amp
includes the following. fuse.
• J1 − Relays − N.O. MASTER CONTROL SUBSYSTEM
• J2 − Relays − Com FUNCTIONS
• J3 − Relays − N.C. Figure 2-7 is a high-level functional block diagram
• J4 − Inputs of the master control subsystem of the MCM3320.
These functions are described below.
• Relay LEDs (ON = Energized)
• Board Revision Level Barcode − The first letter Application Configuration
(read from left to right) on the barcode must be The application configuration inputs are used to
a “C” or higher letter. define the configuration of the system topology, ex-
• Ground wire − Connected to the grounded tended parallel type, load demand, and priority
chassis control. Different options are available with differ-
ent inputs.
• Ribbon Cable − Connected to the AUX101
System Information
For more information on the AUX101/AUX102, re-
fer to Instruction Sheet C693. Wiring diagrams for System information inputs are used for storing the
the I/O modules are on pages 8-21 and 8-22 of this ratings of the gensets, total capacity, available ca-
manual. pacity, and system operating state determination.
The possible system states are listed in Table 2-3.
CONVERTER KIT Breaker Control
A converter kit is available for connecting the The breaker control subsystem provides open/
MCM3320 to a PC where basic customer adjust- close control of the genset and utility breakers,
ments can be made using InPower. The kit feedback on breaker positions, load govern output,
(541−1199) includes an interface harness and an and breaker diagnostic feedback.
RS-485 to RS-232 network converter. Setup and
Power Transfer Control
calibration information is included in Section 5.
The power transfer control subsystem controls
SYSTEM INTERCONNECTION genset start/stop, transfer/retransfer inhibit capa-
bilities, the sensing of the state of the source, tim-
The MCM3320 connects to switchgear (breakers, ers, AC metering, and power transfer control state
PRs, CTs), genset controls, PLC, HMIs, and other machine. There are four subsystem sets that con-
customer equipment. Interconnection wiring dia- tribute the majority of the information to the power
grams are included in Section 8. transfer control subsystem.
Battery Power Priority Control
The MCM3320 can be powered by a 12 or 24 volt The priority control subsystem sets the master syn-
input. It has an operating range from 9−32 volts and chronizer to external priority control (manual) or in-
has a 1 amp maximum current draw with no load on ternal priority control (automatic).
the B+ outputs. The control is always awake when Master Load Control
B+ is supplied. Power is supplied by two diode Or’d
B+ inputs (battery1 and battery2). Diode or’ing is The master synchronizer control allows for enab-
done on the board. ling of the synchronizer, permissive close function,
diagnostic sensors, and bidirectional information
If just one B+ source is used and that source is the flow on kW load (frequency bias) and kVAR load
genset starting batteries, the board will ride share (voltage bias) to synchronize the genset to
through the starter dip if the distance/wire gauge the load.
between the MCM3320 and the gensets is ade-
Load Demand Control
quate. For a more robust system, it is recom-
mended that both B+ inputs be used, with one of The load demand control subsystem controls
them supplied from a station battery. matching online generating capacity to the load.

2-10
PRELIMINARY

TABLE 2-3. SYSTEM STATES


7-Segment
System State Description LED Output
Character
Not Available The system state is not known. This generally only occurs during − (Center
power up. Segment)
Time Delay Engine Start There is a timing to start the gensets. 1
(TDES)*
Time Delay Engine Stop There is a timing to stop the gensets. 2
(TDEC)*
Time Delay Program There is a timing for programmed transition. 3
Transition (TDPT)*
Time Delay Transfer There is a timing of a transfer delay or the transfer delay has ex- 4
(TDNE)* pired.
Time Delay Retransfer There is a timing of a retransfer delay or the retransfer delay has 5
(TDEN)* expired.
Synchronizing The system is actively synchronizing. 6
Sync Check OK The breaker is ok to close. 7
Inhibit An active inhibit exists (transfer, retransfer, gen main circuit breaker, 8
utility main circuit breaker, or master)
Unassigned Not presently used. 9
Ramp Unload A ramp unload of the genset bus is underway. A
Ramp Load A ramp load of the genset bus in underway. b
Manual The Auto / Manual switch is in the manual position. C
Utility Failure The utility has failed. d
Test A test is underway. E
Standby All is normal. J
Extended Parallel An extended parallel session is underway. H
* For more information on time delays, see “Timers” on page 3-10.

2-11
PRELIMINARY

SETUP TRIMS AND INPUTS


SYSTEM TOPOLOGY
SYSTEM TOPOLOGY
TRANSITION TYPE
TRANSITION TYPE
EXTENDED PARALLEL ENABLE USED BY
APPLICATION EXTENDED PARALLEL ENABLE
CONFIGURATION CONTROL
LOAD DEMAND TYPE
LOAD DEMAND TYPE FUNCTIONS
PRIORITY CONTROL METHOD BELOW
PRIORITY CONTROL METHOD
HARDWARE VERSION

SETUP TRIMS DERIVED VALUES

DEVICE NAME TOTAL SYSTEM CAPACITY USED BY


TOTAL NUMBER OF GENSETS CONTROL
GENX kW RATING (X=1...12) FUNCTIONS
SYSTEM TOTAL ONLINE CAPACITY
SYSTEM PHASE ROTATION INFORMATION BELOW
SYSTEM FREQUENCY
SYSTEM OPERATING STATE

POSITION AND CONTROL


UM GM

BREAKER INHIBITS BREAKER


CONTROL
POSITION

REQUEST
CLOSE/OPEN

AUTO/MANUAL LOAD GOVERN ENABLE (TO GENSETS)


TRANSFER AND RETRANSFER INHIBITS
OVERRIDE

EXTENDED PARALLEL START


START/STOP (TO GENSETS)
TEST START
POWER
MASTER TRANSFER OK TO CLOSE
PRIORITY CONTROL
(TO OTHER MASTER
SYNC ON/OFF
MASTERS) INHIBIT
PRIORITY LOAD
CONTROL DEMAND
STATE INFO
OPERATING

CONTROL
STATUS
RAMP

kW LOAD SETPOINT INPUT kW LOAD SHARE


(FREQUENCY)
kVAR/PF LOAD SETPOINT INPUT MASTER LOAD MASTER
CONTROL SYNCHRONIZER
AND kVAR LOAD SHARE
kW LOAD CONTROL (TO GENSETS) (BASE LOAD / PERMISSIVE (VOLTAGE)
PEAK SHAVE) CLOSE
kVAR LOAD CONTROL (TO GENSETS

SYNC ENABLE (MANUAL)

FIGURE 2-7. FUNCTIONAL BLOCK DIAGRAM

2-12
PRELIMINARY

DISCRETE INPUTS inhibit, transfer time delay and retransfer time


delay.
Table 2-4 lists the 22 discrete inputs labeled as
switches. Utility Source Failure
Synchronizer Enable Switch The Utility source Failure input is used to indicate to
the control that the utility has failed. It is useful in
The synchronizer enable switch is used to enable
applications where it is desirable to have an exter-
synchronizing when in manual mode or when the
nal device determine utility source availability in
module is used only as a synchronizer. Otherwise
addition to internal sensors.
sync enabling is automatically done by the control.

Override Test Start

The Override switch is used to force a transfer or The Test Start input starts and stops a test of the
retransfer to occur as quickly as possible. Activat- system. It can be configured to test with or without
ing this switch overrides transfer inhibit, retransfer load.

TABLE 2-4. DISCRETE INPUTS


Active State Inactive State
Discrete Input Description
(To Gnd) (Open Circuit)
Fault Reset Reset Not Reset Reset faults; engage fault readout
Auto/Manual Manual Auto Manual or auto breaker / sync operation
Test Start Start Stop Test load transfer start / stop
Extended Parallel Start Start Stop Extended paralleling start / stop
Synchronizer Enable Active Inactive Synch enable (applies in manual only)
Utility Source Failure Active Inactive Use if external devices determines a failure
Transfer Inhibit Inhibit No Inhibit Inhibit transfers to gensets (some
exceptions)
Retransfer Inhibit Inhibit No Inhibit Inhibit transfers to utility (some exceptions)
Override Override No Override Override timers and transfer/retransfer
inhibits
Gen Main CB Inhibit Inhibit No Inhibit Open genset main / inhibit closure
Util Main CB Inhibit Inhibit No Inhibit Open utility main / inhibit closure
Gen Main CB Tripped Tripped Not Tripped Genset main breaker tripped; source not
available
Util Main CB Tripped Tripped Not Tripped Utility main breaker tripped; source not
available
Gen1 CB Position Breaker Closed Breaker Open Genset #1 breaker position (‘a’ contact)
Gen2 CB Position Breaker Closed Breaker Open Genset #2 breaker position (‘a’ contact)
Gen3 CB Position Breaker Closed Breaker Open Genset #3 breaker position (‘a’ contact)
Gen4 CB Position Breaker Closed Breaker Open Genset #4 breaker position (‘a’ contact)
Util Main CB PositionA Breaker Closed Breaker Open Utility main breaker position (‘a’ contact)
Util Main CB PositionB Breaker Open Breaker Closed Utility main breaker position (‘b’ contact)
Gen Main CB PositionA Breaker Closed Breaker Open Genset main breaker position (‘a’ contact)
Gen Main CB PositionB Breaker Open Breaker Closed Genset main breaker position (‘b’ contact)
Master Inhibit Inhibit No Inhibit Master Inhibit for multiple pair operation

2-13
PRELIMINARY

Extended Parallel Start Utility Circuit Breaker Position

The Extended Parallel Start input starts and stops Utility CB Position A (TB10-7) is the ‘a’ contact from
the extended parallel mode. It is used for base load the utility main breaker. The MCM3320 uses this to
or peak shave operation. determine breaker position.
Utility CB Position B (TB10-9) is the ‘b’ contact from
Fault Reset the utility main breaker. The MCM3320 uses this
only to determine a breaker circuit failure by
The Fault Reset input acknowledges and resets comparing it to the ‘a’ contact. This feature can be
faults. It is also used to activate the fault flashout on enabled/disabled.
the seven segment display on the MCM3320 con-
trol board (press the button for at least seven five The Utility CB Tripped (TB10-10) is used to indicate
seconds to activate this mode). to the MCM3320 that the utility main breaker is
tripped. When tripped, the control considers the
Transfer and Retransfer Inhibit source to be unavailable.
The Utility CB Inhibit (TB10-11) opens the utility
Transfer Inhibit normally inhibits transferring the main breaker, if closed. It inhibits closure if the util-
load to a genset. Under some conditions, it is ig- ity main breaker is open.
nored. Transfer Inhibit is not the same as Gen CB
Inhibit. Genset Circuit Breaker Position
Genset 1 CB Position (TB10-12) is the ‘a’ contact
Retransfer Inhibit normally inhibits retransferring
from genset #1 breaker. It is required for load de-
the load back to the Utility. Under some conditions,
mand and some other configurations.
it is ignored. Retransfer Inhibit is not the same as
Util CB Inhibit. Genset 2 CB Position (TB10-14) is the ‘a’ contact
from genset #2 breaker. It is required for load de-
Genset Circuit Breaker Position, mand and some other configurations.
Monitoring and Control
Genset 3 CB Position (TB10-15) is the ‘a’ contact
from genset #3 breaker. It is required for load de-
Genset CB Position A is the ‘a’ contact from the
mand and some other configurations.
genset main breaker. This MCM3320 uses this to
determine breaker position. Genset 4 CB Position (TB10-16) is the ‘a’ contact
from genset #4 breaker. It is required for load de-
Genset CB Position B is the ‘b’ contact from the mand and some other configurations.
genset main breaker. the control uses this only to
determine a breaker circuit failure by comparing it ModBus
to the ‘a’ contact. This feature can be enabled/dis-
RS232 DCD (J14) is the ModBus RS-232 DCD in-
abled.
put. This feature is enabled when a device is con-
nected to this port connection.
The Genset CB Tripped is used to indicate to the
MCM3320 that the genset main breaker is tripped. NOTE: This port is shared with TB15.
When tripped, the control considers the source to
be unavailable. DISCRETE OUTPUTS
The Genset CB Inhibit opens the genset main Discrete outputs include low-side outputs, Form-A
breaker, if closed. It inhibits closure if the genset relays, Form-C relays, and power outputs. Some
main breaker is open. low-side outputs are configurable. The available
discrete outputs are listed in Table 2-5.
Circuit Breaker Control Mode Relay Outputs
Auto/Manual (TB10-6) puts the breaker control in There are 15 relay outputs. Descriptions of their ex-
Manual mode. pected signals are included in Table 2-1.

2-14
PRELIMINARY

TABLE 2-5. DISCRETE OUTPUTS


Inactive State
Active State
Discrete Output (High Impedance / Description
(Low / Energized)
De-energized)
Start Gensets Relay Run Stop Form-C relay to start / stop gensets (via a
remote start)
Utility Main CB Close Active Inactive Normally open relay contact for the utility
Relay main close coil
Utility Main CB Open Active Inactive Normally open relay contact for the utility
Relay main open coil
Gen Main CB Close Active Inactive Normally open relay contact for the genset
Relay main close coil
Gen Main CB Open Active Inactive Normally open relay contact for the genset
Relay main open coil
Load Govern Enable Enabled Disabled Low-side driver to the PCC genset’s utility
Driver circuit breaker position input to put the
PCC in load govern mode when the utility
is paralleled
Paralleling Gensets Inhibit All Gensets No Inhibit Low-side drive to the PCC genset’s
Breaker Inhibit Driver paralleling breaker inhibit input
Load Demand Gen1 Load Demand Run Low-side driver to the PCC genset’s #1
Driver Stop load demand input
Load Demand Gen2 Load Demand Run Low-side driver to the PCC genset’s #2
Driver Stop load demand input
Load Demand Gen3 Load Demand Run Low-side driver to the PCC genset’s #3
Driver Stop load demand input
Load Demand Gen4 Load Demand Run Low-side driver to the PCC genset’s #4
Driver Stop load demand input
Configurable Output1 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output2 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output3 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output4 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output5 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output6 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output7 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Configurable Output8 Driver On Driver Off Activated by a programmed event/warning
Driver code.
Relay Supply B+ Output B+ Output B+ output for supplying relay coil high
side. The low side is connected to a
low-side driver output.

2-15
PRELIMINARY

Utility Main Neutral Contactor 1 and 2 Load Govern Enable

These two relay outputs are used for controlling a This driver is connected to the utility circuit breaker
utility neutral contactor. position inputs on the individual genset controls. It
tells the genset controls when they are paralleled to
Genset Main Neutral Contactor 1 and 2 the utility.

These two relay outputs are used for controlling a Load Demand
genset neutral contactor.
This driver is connected to the load demand input
Genset Main Circuit Breaker Close Relay 1 and 2 on genset #1.

These two contacts are used for closing the genset Paralleling Genset Breaker Inhibit
main breaker. They are rated at 8 Amp 30 VDC re- This driver is connected to all of the individual gen-
sistive, 3.5 Amp 30 VDC inductive L/R = 7msec. set circuit breaker inhibit inputs. It allows the con-
They are not rated for AC voltage. trol to treat individual genset breakers in concert as
Genset Main Circuit Breaker Open Relay 1 and 2 a genset main breaker.
Configurable Output 1 (Common Warning)
These two contacts are used for opening the gen-
set main breaker. They are rated at 8 Amp 30 VDC Configurable low side output #1 is intended to drive
resistive, 3.5 Amp 30 VDC inductive L/R = 7msec. a relay coil. It has a Common Warning default set-
They are not rated for AC voltage. ting.
N.C. Genset Start Relay Configurable Output 2 (Fail to Synchronize)

The normally closed contact is used for starting Configurable low side output #2 is intended to drive
gensets. a relay coil. It has a Fail to Sync default setting.

COM Genset Start Relay Configurable Output 3 (Genset Available)

The COM relay is used for starting gensets. Configurable low side output #3 is intended to drive
a relay coil. It has a Gen Available default setting.
N.O. Genset Start Relay
Configurable Output 4 (Utility Available)
The normally open contact is used for starting gen- Configurable low side output #4 is intended to drive
sets. It is connected in parallel to all genset remote a relay coil. It has a Utility Available default setting.
start inputs.
Configurable Output 5 (Fail to Disconnect)
Utility Main Circuit Breaker Close Relay 1 and 2
Configurable low side output #5 is intended to drive
These two contacts are used for closing the utility a relay coil. It has a Fail to Disconnect default set-
main breaker. they are rated at 8 Amps 30 VDC re- ting.
sistive, 3.5 Amp 30 VDC inductive L/R = 7 msec.
They are not rated for AC voltage. Configurable Output 6 (Synchronized)

Utility Main Circuit Breaker Open Relay 1 and 2 Configurable low side output #6 is intended to drive
a relay coil. It has a Synchronized default setting.
These two contacts are used for opening the utility
Configurable Output 7
main breaker. they are rated at 8 Amps 30 VDC re-
sistive, 3.5 Amp 30 VDC inductive L/R = 7 msec. Configurable low side output #7 is intended to drive
They are not rated for AC voltage. a relay coil.
Low Side Drivers Configurable Output 8

The function of each low side driver and each confi- Configurable low side output #8 is intended to drive
gurable low side driver is described below. a relay coil.

2-16
PRELIMINARY

3. MCM3320 Features

MCM3320
AC Metering HMI211
HMI112
Source Failure Operator
Gensets
Gensets Start/Stop Panel #1
Main Breaker Control Bargraph
Sync/Volt Match
Customer I/O Open/Closed Transition
Load Ramping HMI211
Operator HMI112
Extended Paralleling
kW and kVAR Control Panel #2 Utility
Load Demand Bargraph
Load Add / Shed
Scheduler
ModBus
Diagnostics

G1
GM UM
G2

G3
I/O Module
Breakers AUX101
G4 or AUX102
ATS

Load1 Load2 Load3 Load4 Load5 Load6

FIGURE 2-8. MCM3320 FEATURES OVERVIEW

This section describes the features supported by NOTE: Positive values refer to the power ex-
the MCM3320. An overview of the MCM3320 fea- ported by the source and the negative
tures is illustrated in Figure 2-8. values refer to power imported by the
source.
AC METERING The AC metering feature provides pre-calibrated
PT and CT inputs. Field adjustments are available,
The MCM3320 sends three phase metering data of if needed, using the setup tool (see page 5-2) or us-
the genset bus and the utility bus simultaneously ing the digital display (see page 6-33). Monitoring
over the ModBus port. The following data is avail- AC metering functions is also available using the
able for each power source. digital display (see page 6-108).
AC Voltage
• Phase and total/avg V, A, kW, kVAR, kVA, PF,
and Hz The MCM3320 senses genset AC voltage lines L1,
L2, L2, and N via the TB6 connector. The
• Phase and total metering of +kWh, −kWh, MCM3320 senses utility AC voltage via the TB7
+kVARh, and −kVARh connector.

3-1
PRELIMINARY

The on-board power transformers (PTs) accept • Adjustable control loop gains
0−480VLL directly. External PTs are required for
• A sync enable input to be used for Manual
higher voltages (up to 35000V).
Mode or Sync Only applications
AC Current • A synchronizer output limit diagnostic

The MCM3320 senses three phase genset and • An option to lock out the synchronizer if a fail-
utility current. Each phase current wire is threaded to-sync occurs. It is re-enabled upon a fault re-
through an on-board current transformer (CT1 for set.
utility phase A, CT2 for utility phase B, CT3 for utility • An option to invert synchronizer polarity if the
phase C, CT4 for genset phase A, CT5 for genset genset and utility swap positions in a synchro-
phase B, and CT6 for genset phase C). nizer-only application (via the ModBus)
The MCM3320 accepts either a one amp or a five • Adjustable frequency and voltage control out-
amp secondary (up to 10000A primary) and it in- put ramp rates for minimizing disturbance
cludes a high withstand capability for faults. Use when synchronization is activated.
one pass through the hole for a 1 amp secondary or Adjustments to synchronization parameters can
two passes for a five amp secondary. Refer to the be done using the setup tool (see page 5-5). Moni-
wiring diagrams for polarity of CT connections. toring synchronizer functions is also available us-
ing the digital display (see page 6-142).
MASTER SYNCHRONIZING AND
VOLTAGE MATCHING Ratings and Typical Performance

The MCM3320 performs both phase synchroniza- The MCM3320 can synchronize up to a 12-genset
tion and voltage matching. The MCM3320 bus to another source. The output frequency offset
matches frequency, phase, and voltage of a sys- range is from 1.5 Hz minimum, up to 3.0 Hz. It
tem of paralleled gensets to a utility bus. This done has an output voltage offset range of 10 percent.
by driving the kW and kVAR load share lines to ad-
just the genset frequency and voltage. Table 3-1 shows the typical performance of the
phase synchronizer with diesel engines.
The MCM3320 is designed to synchronize gensets
with PCC controls. The MCM3320 can be used TABLE 3-1. TYPICAL SYNCHRONIZER
with gensets that do not have a PCC control but PERFORMANCE
there will be no voltage matching in those applica- Typical Performance
tions. with Diesel Engines
Synchronize Time with 1−5 Seconds
The master synchronizing and voltage matching Phase Match
feature provides the following functions.
Synchronize Time with 3−10 Seconds
• Synchronization of up to 20 gensets to another Frequency Match
source Phase Hold Within 5 percent
• An output frequency offset range of +/−1.5 Hz Maximum Number of Sets 12
minimum, up to +/− 3.0 Hz
Synchronizing Methods
• An output voltage offset range of +/− 10%
• An offset range that is generally independent The MCM3320 provides for two methods of syn-
of genset bus load chronizing.
• Control of frequency and voltage via the PCC • Phase Synchronizing
kW and kVAR load share lines
• Slip Frequency Synchronizing
• Allowance of selectable phase synchroniza-
Phase Synchronizing
tion (default) or slip frequency synchronization
• Adjustable slip frequency (used with the slip Phase synchronizing is the default method and is
frequency synchronization method) suitable for most applications.

3-2
PRELIMINARY

When the phase synchronizing method is selected, TABLE 3-2. RECOMMENDED SLIP FREQUENCY
the synchronizer matches phase, frequency, and SETTINGS
voltage on the generator bus to the utility bus. The Permissive Recommended Time is Seconds
phase match algorithm drives the kW load share Window Slip Frequency Between When
lines to match frequency and phase. The in Hz permissive
MCM3320 quickly matches frequency and then Window
slowly brings the two sources into phase synchro- Conditions are
nization. Met
20 degrees 0.1 10
Slip Frequency Synchronizing 0.5 seconds
10 degrees 0.05 20
Slip frequency synchronizing should be used with 0.5 seconds
difficult to sync applications, such as natural gas.
Voltage Matching
When the slip frequency synchronizing method is
selected, the genset bus frequency is driven to be a The MCM3320 matches the average of the three
fixed frequency high or lower (for example, 0.1 Hz) generator phases to the average of the three utility
than the utility bus frequency. phases. The MCM3320 matches voltage in a simi-
lar way in which it matches frequency. The
The slip frequency method works by governing the MCM3320 drives the kVAR load share lines to
generator bus frequency slightly off of the utility fre- match voltage. Voltage matching is active in both
quency. This frequency is called the slip frequency. the phase and frequency synchronize methods.
The frequency difference produces a constantly
changing phase difference between the two Tuning the voltage matching is done in a similar
sources. If the frequencies are close enough peri- way to frequency matching. There is a proportional
odically, the phase difference will be small enough gain (Kp) and an integral gain (Ki).
that it will meet the permissive conditions for clos-
ing the circuit breaker. Voltage matching gains are generally less critical
than frequency or phase matching gains and typi-
Because it is easier to govern frequency than it is to cally do not need to be adjusted.
match phase, you may wish to use this method on
NOTE: If the genset voltage is increased by volt-
systems that are difficult to match phase or when
age matching, the load on the genset in-
you would like to control the direction of power flow
when the breaker closes frequency synchronizing. creases. If the voltage is raised to 6 per-
cent, then the genset load will increase by
Since the permissive conditions occur periodically 12 percent.
based on the slip frequency, the slip frequency
method takes longer to synchronize than the phase Synchronizer Enabling Conditions
match method. The phase gain has no effect when
The MCM3320 does not start synchronizing unless
using the frequency synchronize method and when
the following conditions are met.
phase synchronizing is selected, the slip frequency
has no effect. Table 3-2 shows the recommended • The system topology must be set to Master
slip frequency settings. The recommended slip fre- Synchronize or, in another topology where the
quency setting is: software requests synchronizing.

Phase Window / (360 * Time in Window) • The generator power source must be avail-
able.
By using the settings in the table, the phase differ- • The utility power source must be available.
ence at the end of the permissive time window
(when the breaker is allowed to close) will be 0 de- • The MCM must either be in Auto mode or else
grees. (For example, at 0.1 Hz slip, it takes 0.5 sec- it is in Manual mode with the sync enable
onds for the phase to change 20 degrees; the switch on.
phase difference is in a 20 degree window for 0.5 • The Fail to Synchronize fault must not be ac-
seconds.) tive or the Fail to Sync lockout is disabled.

3-3
PRELIMINARY

• The generator and bus must have the same Maximum Allowable Synchronizer Range
phase rotation. vs. Load Share Gains
• The MCM3320 must not be inhibited.
The MCM3320 drives the load share lines to syn-
The synchronizer function requires both sources to chronize system frequency/phase, and voltage. In
be considered as “available” in order to be able to order for frequency and voltage matching to work
turn on synchronizing. A source is available when properly, the kW and kVAR load share gains must
all enabled sensors are picked up. be set properly so that all of the controls respond
the same way to the voltage applied to the load
Sync Enable Input share lines. If the system genset controls are all set
the same, the load share gains must be set to the
The sync enable input is used to enable synchro- same values. If your installation includes a mix of
nizing when the control is in Manual mode or when PCC3100 and PCC3200 controls, the controls
the MCM3320 is used as a synchronizer only. (With must be set up so that their gains have the same
the Power Transfer Control (PTC) function, sync effect. The load share gains affect the range of op-
enabling is automatically done by the control.) eration of the frequency, voltage matching, and the
synchronizer gain.
Auto / Manual Synchronizer Operation
The default synchronizing range limits for frequen-
When the synchronizer is set for automatic opera- cy/phase and voltage matching are shown in Table
tion (open circuit), it will start synchronizing when 3-3. These limits are set so the MCM3320 will work
both power sources are available. with the default load share gain settings of the
PCC3100 and PCC3200.
When the synchronizer is set for manual operation
(grounded circuit), it will start synchronizing when NOTE: The PCC3100 and PCC3200 have over-
both power sources are available and the Sync En- voltage shutdowns at 110%. The voltage
able input is grounded. It does not synchronize matching range on the MCM3320 should
when Sync enable is an open circuit. not be set to exceed this value.

Genset Sensor Operation During If a wider range is desired, the load share gains can
Synchronizing be increased. The kW load share gain controls the
frequency matching range and the kVAR load
When the synchronizer is running, the pickup and share gain controls the voltage matching range.
dropout thresholds for undervoltage, overvoltage, The PCC3100 default gain allows a 2.5 Hz fre-
and frequency sensors for the genset bus are tem- quency match range. Maximum match ranges for
porarily expanded in order to allow the synchroniz- PCC3100 and PCC3200 controls are listed in
er to change the bus voltage and frequency without Table 3-4. The maximum voltage and frequency
dropping out a sensor. synchronizing range is not available through the
operator panel; it must be changed using InPower.
Synchronizer Polarity Inversion
NOTE: Higher gains may cause the load sharing to
If the MCM3320 is being used in a sync only ap- become unstable. If the gains are changed,
plication, the operator may invert which source is stable load share operation should be veri-
the genset and which is the utility via the ModBus. fied.

TABLE 3-3. SYNCHRONIZING RANGE


Synchronizer Maximum
Comments
Default Range Allowable Range
Frequency 1Hz 5 Hz Maximum range is only achievable by changing kW
load share
Voltage 6% 9% Default overvoltage shutdown of the genset controls is
110%

3-4
PRELIMINARY

TABLE 3-4. PCC3100 MAXIMUM ALLOWABLE SYNCHRONIZE RANGE VS. LOAD SHARE GAINS
Maximum Frequency Maximum Voltage
kW Load Share Gain kVAR Load Share Gain
Match Range Match Range
PCC3100
3 2.0 Hz 150 4%
6 (Default) 2.5 Hz 300 (Default) 8%
8 3.5 Hz
PCC3200
0.5 0.5 Hz 0.5 4%
1.0 (Default) 1.0 Hz 1.0 (Default) 8%
2.0 2.5 Hz

Synchronizer Diagnostics monitors for permissive sync conditions to be met


when sources are considered acceptable. The fol-
The MCM3320 supports the following synchroniz- lowing permissive sync check features are avail-
er diagnostics. able with the MCM3320.
Fail to Synchronize Warning • An adjustable frequency window, phase win-
dow, voltage window, and window time for per-
A Fail to Synchronize warning is activated if syn- missive check
chronizing does not occur within the time specified.
• A configurable dead bus logic
If the fail to synchronize lockout is disabled, syn- • Sync check output
chronizing will continue while the fault is active. If
the fail to synchronize lockout is enabled, synchro- • A fail-to-synchronize diagnostic
nizing ceases as soon as the fault occurs. If a fail to • A phase rotation mismatch diagnostic (sync
sync fault occurs and the synchronize lockout is check OK is prevented if phase rotations are
enabled, the fault must be reset before normal op- different)
eration can occur.
The MCM3320 sync check function runs indepen-
Synchronizer Phase Rotation Warning dently of the synchronizer. The PTC function uses
the sync check output to determine when to close
A Synchronizer Phase Rotation warning is acti- the circuit breaker. The sync check output can be
vated if the phase rotation of the utility bus does not mapped to one of the MCM3320 configurable out-
match the phase rotation of the generator bus. puts. (It is mapped to configurable output 6 by de-
Synchronizing continues while this fault is active. fault.) Sync check default settings are listed in
The system phase rotation can be set in either the Table 3-5.
generator or utility bus menu (see page ).
TABLE 3-5. SYNC CHECK DEFAULT SETTINGS
Synchronizer Output Limit Warning
Default
The Synchronizer Output Limit warning is active if Voltage 5%
the MCM3320 drive on the load share lines reach- Phase 10 Degrees
es its maximum. This fault occurs when the
Time 0.5 Seconds
MCM3320 cannot reach the desired level needed
to match voltage and frequency. If this fault occurs, Frequency 1.0 Hz
synchronizing stops.
Adjustments to sync check parameters can be
PERMISSIVE SYNC CHECK done using the setup tool (see page 5-9) or using
the digital display (see page 6-74). Monitoring sync
The MCM3320 sync check function is independent check functions is also available using the digital
of the synchronizer. The MCM3320 continuously display (see page 6-140).

3-5
PRELIMINARY

Permissive Close Conditions • Full breaker interface for both genset and util-
ity main breakers
The following conditions must be met before a per-
missive close is allowed. • Close and open control − momentary ener-
gization until desired position is achieved
1. The utility source must be available.
• Breaker position inputs − selectable as dual
2. The generator source must be available. contact (a/b) OR single contact (a) − dual pre-
ferred for robustness and reliability
3. The utility and generator phase rotation must
be identical. • An adjustable breaker recharge time delay to
prevent fail to close due to inadequate charge
4. The highest difference of all the generator time
phase voltages minus the utility phases must
be less than the voltage window. • Utility paralleling enable output to genset con-
trols (connects to utility CB position input)
5. The phase differences must be less that 20 de-
grees and decreasing or less than 10 degrees • Breaker inhibit control input (opens breaker if
with the phase difference less than the phase closed; inhibits closure if open)
window. • Breaker tripped input included in source avail-
ability determination
6. The frequency difference between the
sources must be less than the frequency win- • Breaker diagnostics with appropriate system
dow. control reaction − tripped, contact failure, fail
to close, or fail to open
7. All permissive conditions are met for the time
window. • Adjustable fail-to-close and fail-to-open time
delays
8. The MCM3320 is not inhibited.
• Paralleling fail-to-disconnect diagnostic with
NOTE: The permissive close is removed when the redundant and configurable system control
phase difference is greater than 20 de- reaction
grees or the voltage difference is greater
• Anti-pump avoidance logic − external breaker
than five percent.
position contacts not required in series with
LEDs on the MCM3320 control board display the trip coil
sync check status (see Section 7). • Breaker open and close relay contacts capa-
Dead Bus Close Scenarios ble of directly driving trip and close coils in
some low voltage applications
In synchronizer only applications, sync check can
• Breaker inhibit output to control individual gen-
be enabled individually for the following dead bus
set paralleling breakers in applications with no
scenarios.
genset main, and for backup disconnect
• Dead utility and dead genset protection capability
• Live utility and dead genset Adjustments to circuit breaker parameters can be
• Dead utility and live genset done using the setup tool (see page 5-12).
The dead bus threshold for both the utility bus and
the genset bus are adjustable. the default for both
Breaker Control
busses is 10 percent of nominal.
The MCM3320 controls separate relays for closing
CIRCUIT BREAKER CONTROL and opening genset main and utility main breakers.
INTERFACE The relays are energized until the desired position
is achieved. A breaker recharge time delay is ad-
The breaker control interface feature provides the justable. Breakers can be controlled manually
following functions. when the Auto/Manual switch is set to Manual.

3-6
PRELIMINARY

The MCM3320 has a built-in software interlock for • Fail to Disconnect


open transition applications.
POWER TRANSFER CONTROL
In applications without a genset main breaker, the
The Power Transfer Control (PTC) feature pro-
MCM3320 controls the virtual genset main via the
vides the following functions.
paralleling genset circuit breaker inhibit inputs on
the genset controls. TB3-16 on the MCM3320 con- • Support of open transition with program transi-
trol board is connected to the genset breaker inhibit tion delay, hard closed transition (<100msec),
on each of the genset controls. soft load closed transition
Breaker Position Sensing • Source sensors (undervoltage, overvoltage,
frequency, phase rotation, loss of phase, gen-
The MCM3320 used two contacts (‘a’ and ‘b’) to de- set bus capacity, and breaker failure)
termine breaker position. The default preferred • Adjustable time delays (program transition,
setting is when the ‘a’ contact is used for position transfer, retransfer, max parallel, gensets start
and the ‘b’ contact is used as check. the MCM3320 delay, gensets stop delay)
can be configured for ‘a’ contact only operation, but
this is not preferred. Once the breaker is deter- • Source availability determination for both the
mined to be closed, the source is considered con- utility and the gensets
nected. • Source connected determination for both the
utility and the gensets
The two contacts should always be in opposite
states (one should be open and the other closed). If • Genset start/stop logic with single relay output
this is not the case, the control looks upon this as a • Transfer and retransfer inhibit inputs (note that
contact fault. In this situation, if current on all three these have different action than the breaker in-
phases is greater than the threshold value, the hibit inputs)
breaker is considered closed; otherwise, the • Override input to override timers and transfer/
breaker position is unknown. When the breaker retransfer inhibits for immediate transfer, re-
position is unknown, the source is considered to be transfer or genset start
not available.
• Auto/Manual transfer mode input
In applications without a genset main breaker, a • Test start input
virtual genset main is created by a collection of
genset paralleling breakers. In this case, if one or • Adjustable test with or without load
more genset paralleling breakers is closed, the • Option to do open transition retransfer if a fail-
virtual genset main is considered closed. If your to-sync occurs
installation consists for four or fewer gensets, the The PTC function manages the circuit breakers
individual genset circuit breaker position inputs and normal starting and stopping of the gensets.
should be used. If your installation includes more The PTC function also decides when the master
than four gensets, the circuit breaker contacts synchronizer is needed.
should be connected in parallel to the genset main
position inputs. Adjustments to PTC parameters can be done using
the digital display (see page 6-56). Monitoring PTC
Breaker Diagnostics functions is also available using the digital display
(see page 6-128).
The MCM3320 supports the following breaker
diagnostic functions. Additional information on Auto/Manual Modes
these diagnostic functions is included on page
7-21. Auto/Manual mode can be selected either with a
hardwired input or through the ModBus port. The
• Fail to Close (has an adjustable delay) default is Auto Mode.
• Fail to Open (has an adjustable delay) Selecting Manual puts the breaker and synchroniz-
er control in manual mode. Manual mode bypasses
• Breaker Contacts
all of the PTC functions and allows the circuit
• Breaker Tripped breakers to be controlled manually.

3-7
PRELIMINARY

PTC Operation TABLE 3-6. PTC OPERATING MODES


Mode Description
The Power Transfer Control (PTC) feature deter-
mines the overall system operating mode. It evalu- Normal The is the normal operating condi-
tion. The PTC is attempting to re-
ates utility source status, test start/stop, and ex- transfer to the utility or, if it already
tended parallel start/stop to decide whether or not has transferred to the utility, it stays
to start or stop the gensets and maintains informa- there.
tion on how the transfer switch needs to operate.
Normal This indicates that a problem with
Override the genset source has occurred. The
The PTC tests prioritized conditions. It starts by transfer switch will either stay con-
testing the highest prioritized condition. If the con- nected to the utility or else it will
dition exists, it does not test for any additional con- quickly transfer the load to the utility,
ditions. If the highest prioritized condition does not aborting any retransfer time delay
exist, it then tests to the next highest priority condi- and ignoring any retransfer inhibit.
tion, etc. If none of the conditions exist, the PTC op- Test This indicates that a test input has
erating mode is set to the default. been activated. If set to transfer
“with load”, the PTC is attempting to
transfer the load to the genset. If the
The operating modes available with the PTC are test begins while the load is running
listed in Table 3-6. off of the genset, the load remains
with the genset until the test is over.
If the genset is not powering the
Table 3-7 summarizes the logic used to set the PTC load, the genset runs without load
operating mode. until the test is completed.
Utility Fail The utility has failed and the PTC is
Genset Run/Stop Control attempting to transfer the load to the
genset. Once the load has been
transferred, the load will remain
Time delays are incorporated into the genset start- there until utility power returns.
ing and stopping sequence. If your installation in- Extended An extended parallel start has been
cludes multiple gensets, a single Form-C relay is Parallel initiated. The PTC will start the gen-
used to activate the remote start inputs of all gen- sets, parallel to the utility, and either
sets simultaneously. base load or peak shave.

TABLE 3-7. PTC OPERATION


Priority Conditions PTC Operating Comments
Mode
Highest The utility is not available Utility Fail After the utility fails, the genset starts and the
load is transferred to the genset.
The utility breaker opens Normal Override The genset failed during a test or extended par-
AND the genset becomes allel. The load is immediately transferred to the
available utility, bypassing any time delays and inhibits.
Extended Paralleling is Extended Parallel The transfer switch can be connected to either
requested and at least one the utility or the genset.
source is connected
A test is requested Test The genset starts and, if set to do so, transfers
the load to the genset. When the test is over,
the load is retransferred back to the genset and
the genset is shut down.
Lowest Normal operation Normal If connected to the isolated bus, a test will stop.
If connected to the common bus or transfer
pair, the utility is available. The load is trans-
ferred to the utility and stays there.

3-8
PRELIMINARY

PTC States Paralleled

There are four possible states defined by four pos- The MCM3320 is in Paralleled state when the fol-
sible combinations of GM and UM breaker positions. lowing conditions occur.
Each state determines if the synchronizer should be
• The MCM3320 is in extended paralleling
activated and if a breaker should be opened or
mode.
closed. When a breaker closure is required, the
breaker does not close until all sync check permissive • For a short time, the utility has failed and then
conditions are met. returned.
• A test is running and closed transition has
The four possible PTC states are No Source con- been selected.
nected, Utility Connected, Genset Connected, and
Paralleled. If the PTC switches from Extended Paralleling or
Test mode to Normal or Normal Override mode, the
No Source Connected control will open the genset breaker. If the PTC is in
Test mode and the maximum parallel timer has ex-
pired, the control will open the utility breaker.
During programmed transition, the MCM3320 is
briefly in a No Source Connected state. Sensors

If the PTC is in Normal or Normal Override mode, it An MCM3320 installation provides for monitoring
will try to close the utility breaker. If the PTC is in of generator and utility sensors to determine is the
Utility Fail, Test, or Extended Parallel mode, it will bus voltages and frequencies are in an acceptable
try to close the genset breaker. operating range.

Both power sources have the following sensors.


Utility Connected
• Undervoltage
The normal state for the PTC is the Utility Con- • Overvoltage*
nected state.
• Under/Over Frequency*
If the PTC is in Extended Parallel or Test with Load • Phase Rotation*
mode, the MCM3320 tries to sync and close to the • Loss of Phase*
genset bus. If the utility has failed or an open transi-
tion Test with Load is requested and the genset is • Main Breaker Tripped
not available, the PTC will open the utility breaker. • Fail to Close
Be aware that even if the utility fails, it will not open
the genset breaker unless the genset bus is avail- • Position Contact Failure
able. * These sensors can be enabled using the operator
panel menus.
Genset Connected
The utility source also has a Utility Source Failure
The MCM3320 is typically in the Genset Con- switch input.
nected state during a test or when the utility has The genset source also has a Genset Online Ca-
failed. pacity Sensor. This sensor detects when the online
kW capacity exceeds threshold. Once the genset
When the test is over or utility power returns, the main breaker closes, the sensor stops checking
MCM3320 activates the synchronizer and closes the kW capacity.
the utility breaker so that the load can be trans-
ferred back to the utility. If open transition is se- The undervoltage, main breaker tripped, fail to
lected, the MCM3320 opens the genset breaker close, and position contact failure sensors are al-
when the test ends or utility power is again avail- ways enabled. The other sensors may be enabled,
able. if desired.

3-9
PRELIMINARY

If any sensor is dropped out, the source is consid- ing to either source is inhibited. For more informa-
ered to be not available. tion, see “Breaker Position Sensing” on page 3-7
and “Utility Main Breaker Contacts” on page 7-21.
Undervoltage Sensor
Timers
source availability is determined by the undervol-
tage sensor. This sensor drops out when the volt- The PTC uses the following timers that can be ad-
age falls below the drop-out threshold and picks up justed by using the menus available through the
when the voltage rises above the pickup threshold operator panel or but using InPower connected to
setting. There is a drop out time delay but pick up is the ModBus port.
immediate.
Genset Run/Stop Control Timers
Overvoltage Sensor
The MCM3320 incorporates the following two time
When enabled, this sensor drops out when the volt- delays into the genset starting and stopping se-
age exceeds the drop out threshold and picks up quence.
when the voltage falls below the pick up threshold. • The time delay engine start (TDES) time delay
There is a drop out time delay but pick up is imme- controls how long the engine should run be-
diate. fore the load is transferred to the genset.
Frequency Sensor • The time delay engine cooldown (TDEC) time
delay controls how long the engine should
When enabled, this sensor drops out when the fre- continue to run after the load has been trans-
quency goes beyond drop out thresholds and picks ferred back the the utility.
up when frequency falls within the pick up thresh-
olds. There is a drop out time delay but pick up is It is recommended that TDES and TDEC in the
immediate. genset control be set to zero and that these time
delays be set using the MCM3320’s operator pan-
Phase Rotation Sensor el.

When enabled, this sensor drops out if the phase PTC Timers
rotation of the source does not match the phase
The PTC uses the following four timers but only
rotation setting.
one of these timers can be active at any given time.
Loss of Phase Sensor • The time delay programmed transition (TDPT)
is the amount of time between opening one
When enabled, this sensor detects if the line-to-line
source and closing the other source. This time
voltages are more than 30 degrees from 120 de-
delay can only be active when there is no
grees. There is a drop out time delay but pick up is
source connected.
immediate.
• The TDNE timer is applicable only when the
Main Breaker Tripped utility is connected. It is the time between a
transfer being requested and the transfer be-
The MCM3320 detects a main breaker trip via the ing initiated.
hardwired input from the breaker.
• The TDEN timer is applicable only when the
Fail to Close genset is connected. It is the time between a
transfer being requested and the transfer be-
If a breaker is sent a signal to close but fails to close ing initiated.
within an adjustable time delay, the fail to close
• The time delay maximum parallel (TDMP) is
sensor drops out and the source is considered un-
applicable when two sources are paralleled. It
available.
is the time what the two sources may be paral-
Position Contact Failure leled when the MCM3320 is not in extended
parallel mode. When the timer expires, the
If the MCM3320 cannot determine the breaker genset breaker opens, regardless of whether
position because of a contact position failure, clos- the genset is unloaded or not. The ramp rate

3-10
PRELIMINARY

in the genset controller should be set so that source and, when it gets below the set threshold, it
when transferring the load to the utility, the opens that source’s breaker.
genset will be completely unloaded before the
max parallel timer expires. Test
Transfer Inhibit The MCM3320 can be set to test either with or with-
out load. A test is initiated either by a discrete input
Transfer inhibit prevents the transfer of the load or by the scheduler. The test lasts as long as the ini-
from the utility to the genset. When the utility is con- tiating test commend remains active. If a test is initi-
nected, transfer inhibit prevents a sync enable re- ated by the hardware input, the tool determines if
quest and a genset breaker close request. Trans- the test is to run with or without load. If a test is initi-
ferred inhibit can be set using a discrete input or via ated by the scheduler, the scheduler determines
the ModBus port. whether to run the test with or without load.
Retransfer Inhibit NOTE: A test start command is ignored if the PTC
is in Utility Fail, Normal Override, or Ex-
Retransfer inhibit prevents the transfer of the load
tended Parallel mode.
from the genset to the utility. When the genset is
connected, transfer inhibit prevents a sync enable Test Without Load
request and a utility breaker close request. Re-
transferred inhibit can be set using a discrete input When the control is set to test without load, the gen-
or via the ModBus port. set normally starts without load and continues to
run for the set test period. At the end of a test, the
Override MCM3320 commands the genset(s) to shut down.
The override function overrides all timers and A test is stopped if is interrupted by the PTC switch-
transfer/retransfer inhibits for immediate transfer, ing to Utility Fail, Normal Override, or Extended
retransfer, or genset start. Override can be set us- Parallel mode. This would happen in one of the
ing a discrete input or via the ModBus port. sources fails or an extended parallel command is
Transition Types issued.

The MCM3320 supports the following three transi- Test With Load
tion types. When the control is set to test with load, the gen-
Open Transition set(s) normally start, sync to the utility, and the load
is transferred to the genset using the selected tran-
The MCM3320 performs open transition transfers sition type after the set time delays have expired. At
and retransfers with a programmed transition the end of a test, the load is retransferred back to
delay. the utility and the MCM3320 commands the gen-
set(s) to shut down.
Hard Closed Transition
A test is stopped if is interrupted by the PTC switch-
The MCM3320 performs a hard closed transition ing to Utility Fail, Normal Override, or Extended
with <100msec of overlap. Parallel mode. This would happen in one of the
sources fails or an extended parallel command is
Soft Closed Transition issued.
The MCM3320 performs a soft transition with load Fail to Sync Open Transition Retransfer
ramping for both transfer and retransfers between
live sources. The ramp rate is controlled the the in- If the Fail to Sync Open Transition Retransfer fea-
dividual genset controls. When a source is being ture is enabled, an open transition transfer occurs if
unloaded, the MCM3320 monitors he output of that a fail to synchronize fault is activated.

3-11
PRELIMINARY

SYSTEM TOPOLOGIES used when only the features of AC metering and


synchronizing are needed. Metering is optional.
For utility paralleling applications, the MCM3320
supports transfer pair (UM and GM − see Figure The MCM3320 completely manages the system,
2-9) and common bus (UM only − see Figure 2-10). including breaker control, synchronizing, load con-
trol, diagnostics, etc.
For isolated bus applications, the MCM3320 sup-
ports isolated bus with (see Figure 2-11) or without Setting the system topology can be done using the
(see Figure 2-12) a genset main breaker. setup tool (see page 5-19) or using the digital dis-
play (see page 6-84).
The MCM3320 can also be used as a master syn-
chronizer only (see Figure 2-13). This topology is

G1 G2 G1 G2
MCM3320

UM GM
LOAD

FIGURE 2-9. TRANSFER PAIR TOPOLOGY (SYSTEM TYPES 2, 3, 4, 8, 10, AND 11)

G1 G2 G1 G2
MCM3320

UM
LOAD

FIGURE 2-10. COMMON BUS TOPOLOGY (SYSTEM TYPES 9)

3-12
PRELIMINARY

G1 G2 G1 G2
MCM3320

GM

LOAD

FIGURE 2-11. ISOLATED BUS WITH GM TOPOLOGY (SYSTEM TYPE 7)

G1 G2 G1 G2
MCM3320

LOAD

FIGURE 2-12. ISOLATED BUS WITHOUT GM TOPOLOGY (SYSTEM TYPES 5 AND 6)

G1 G2 G1 G2
MCM3320

SOURCE SYNC
CHECK

FIGURE 2-13. MASTER SYNCHRONIZER ONLY TOPOLOGY (OPTIONAL METERING)

3-13
PRELIMINARY

MULTIPLE TRANSFER PAIR • Load control operates independently of the


SEQUENCING (EXTERNAL) number of gensets that are online.
• Extended paralleling can be used with a maxi-
The multiple transfer pair sequencing feature pro- mum of 20 gensets.
vides the following functions.
• kW base load control is selectable as open
• The master inhibit input inhibits the synchro- loop or closed loop.
nizer and power transfer control functions. • kW peak shave control is closed loop only.
• This feature can be used in complex systems • kVAR control selectable is done by genset
with multiple transfer pairs and multiple controllers, open loop base load, closed loop
MCM3320s. base load, or closed loop peak shave
• An external logic device is required to assert • kVAR control can be either based on kVAR di-
the master inhibit as required (e.g. during a re- rectly, or on the power factor.
transfer sequence of multiple pairs).
• Setpoints can be set from InPower, the opera-
• Future enhancement will allow automatic tor panel, ModBus, or via the analog hardware
priority control through interconnected 0−5V inputs.
MCM3320s (similar to First Start Bus PT log-
ic). • The extended parallel start input starts/stops
the mode.
LOAD CONTROL • A single kW analog output drives all genset kW
load setpoint inputs simultaneously.
The master load control feature performs the fol-
lowing functions. • A single kVAR analog output drives all genset
kVAR load setpoint inputs simultaneously (not
• Controls real and reactive power in extended applicable to PCC3100).
[paralleling operation (base lade / peak shave) • Soft load ramping is available.
• Causes ramp loading and unloading during • Includes an optional load tracking feature to
soft closed transition load transfers prevent utility kW export if building load should
• Operates independently of the number of gen- drop below base load kW setpoint
sets that are online • Separate diagnostics are available for both
• Provides diagnostics in extended paralleling if kW and kVAR if unable to achieve setpoint.
the desired setpoint(s) cannot be achieved Adjustments to load control parameters can be
The master load control function ultimately drives done using the setup tool (see page 5-15) and (see
page 6-16). Monitoring load control functions is
two hardware analog outputs, one for kW control
also available using the digital display (see page
and one for kVAR control. The kW control output is
connected to all of the kW load set inputs on the 6-136).
gensets to be controlled. The kVAR control output Extended Paralleling (Base Load / Peak
is connected to all of the kVAR load set inputs on Shave)
the gensets to be controlled.
Extended paralleling refers to continued operation
NOTE: The PCC3100 genset control does not in parallel with a utility source for the purposes of
have a kVAR load set input. base load and/or peak shave operation.
The following functions are available with the mas- During extended paralleling operation, the kW and
ter load control feature. kVAR of the gensets are controlled in a number of
ways (see Tables 3-8 and 3-9). The kW control type
• Many options available for controlling kW and and the kVAR control type can be set independent-
kVAR in extended paralleling mode. ly of each other. For example, the kW could be con-
• kW and kVAR can be independently controlled trolled at the genset bus (base load) while the kVAR
in any combination of base load (control the could be controlled at the utility bus (peak shave).
power at the genset bus) or peak shave (con- This scenario is useful in applications where, while
trol the power at the utility bus). base loading the gensets, it is desirable to manage

3-14
PRELIMINARY

the utility kVAR to avoid penalties from the utility for Extended paralleling can be enabled/disabled us-
a low power factor. The gensets that are online are ing the digital display (see page 6-84).
limited to what they are capable of putting out;
therefore, it may not always be possible to achieve
Load Ramping
a desired setpoint.

In all installations, the online gensets are limited to During soft closed transition load transfers, load
what they are capable of putting out. Therefore it ramping is done by the individual genset control-
may not always be possible to achieve a desired lers. Therefore, the desired ramp rates must be set
setpoint. in the genset controllers. The ramping direction is
controlled by the MCM3320 by either setting the
The MCM3320 can be configured for open loop or control output value to give +5V (ramp load) or 0V
closed loop base load operation (see page 6-18). (ramp unload) on the analog output.
NOTE: Peak shave always requires closed loop
base load operation. When an extended parallel state is activated, the
ramping of the load is controlled by the MCM3320.
In some cases, open loop operation may be desir- This is necessary because the load control algo-
able due to stability issues with a closed loop base rithm in the MCM3320 operates without knowledge
load operation. Open loop operation may also be of the number of gensets online. When an ex-
required for each genset that is online in order to tended parallel session expires, the ramp loading
put out a fixed percentage of its capability. is done by the individual genset controllers.

TABLE 3-8. REAL POWER CONTROL OPTIONS


Genset Controller
Capability
Parameter Setting Description
3200
3100 3300
3201
Extended Paralleling kW Load Control Type =
Genset Bus % Level n n n The MCM3320 puts out a user adjustable fixed
(Open Loop) − This is percent level on the kW control output. The genset
the default setting. bus kW is a result of whatever gensets are online.
Therefore, it is an open loop on the kW at the
genset.
Genset Bus kW (Closed n n n The MCM3320 drives the kW control output to
Loop) achieve the desired kW setpoint at the GM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.
Genset Bus kW Utility n n n The MCM3320 drives the kW control output to
Constraint (Closed achieve the desired kW setpoint at the GM and
Loop) reduces the this setpoint to keep the kW at the UM
above the programmed level. (This can be used to
prevent tripping a UM reverse power relay because
of the load falling below the GM kW setpoint.
Coordination of the settings in the MCM3320 and
the relay and an understanding of the magnitude of
load fluctuations is critical to the successful use of
this feature.
Utility Bus kW (Closed n n n The MCM3320 drives the kW control output to
Loop) achieve the desired kW setpoint at the UM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.

3-15
PRELIMINARY

TABLE 3-9. REACTIVE POWER CONTROL OPTIONS


Genset Controller
Capability
Parameter Setting Description
3200
3100 3300
3201

Extended Paralleling kVAR Load Control Type =


Genset Controllers − n n n The MCM3320 does nothing. The kVAR control
This is the default output = 0. The genset controllers take care of the
setting. kVAR control, based on their own settings (for
example, a fixed power factor of 0.95).
NOTE: This is the only option that will work with a
PCC3100 control.
Genset Bus Power % n n The MCM3320 puts out a user adjustable fixed
Level (Open Loop) percent level on the kVAR control output. The
genset bus kVAR is a result of whatever gensets
happen to be online.
Genset Bus Power n n The MCM3320 puts out a level on the kVAR control
Factor (Open Loop) based on what is being currently sent on the kW
control output. The relationship between the two is
based upon the Power Factor setting.
Genset Bus kVAR n n The MCM3320 drives the kVAR control output to
(Closed Loop) achieve the desired kVAR setpoint at the GM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.
Genset Bus Power n n The MCM3320 drives the kVAR control output to
Factor (Closed Loop) achieve the desired PF setpoint at the GM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.
Utility Bus kVAR (Closed n n The MCM3320 drives the kVAR control output to
Loop) achieve the desired kVAR setpoint at the UM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.
Utility Bus Power Factor n n The MCM3320 drives the kVAR control output to
(Closed Loop) achieve the desired PF setpoint at the UM. If the
setpoint cannot be achieved within a preset time, a
warning fault occurs.

If an individual genset comes online when ex- Number of Gensets


tended paralleling is already underway, it will ramp
toward whatever the current setpoint is. If the Because the master load control function does not
MCM3320 is using closed loop operation, it will ad- require knowledge of how many gensets are on-
line, your installation can include up to 12 gensets
just its output command to compensate for the new
without needing all of the additional I/O.
genset coming into the group. The same is true if
an individual genset is to ramp unload. For smooth In closed loop mode, the load control function
operation, the ramp load and ramp unload times in drives the control output to attempt to achieve the
the genset controllers should not be set to time val- setpoint target with the available gensets. It is im-
ues less than 60 seconds, if at all possible. portant that the individual genset kW ratings be en-

3-16
PRELIMINARY

tered into the MCM3320 because, in some configu- ModBus communication parameters (address,
rations, the load control function does not need to baud rate, and parity) can be adjusted using the
know what is the total genset bus capacity. digital display (see page 6-40).

If you do not want extended paralleling to start until Modbus Activity LED
a specific number of gensets are online, this can be
accomplished using the genset online capacity The Modbus Activity LED is lit when either the con-
sensor for up to four gensets. If you want more than trol is receiving a ModBus packet or sending a
four gensets to be online, the transfer time delay ModBus packet. It is also lit when the Protocol Tim-
(TDNE) should be set long enough to make sure er is in timer mode. This precedes a protocol switch
that all gensets have come online before extended on the SCI1 port. Otherwise, the LED is off.
paralleling begins. Setting this type of restriction
does not affect the load control function. SYSTEM SCHEDULER
The system scheduler features provides up to 12
Diagnostics
different run schedules with highly configurable
If the desired kW or kVAR setpoint cannot be settings.
achieved within a set amount of time, the The run schedules are configurable for start day,
MCM3320 issues a warning message. start time, duration, repeat interval, and run mode.
The run modes include no load, with load, or ex-
Load Govern Enable
tended parallel.
The MCM3320 activates a load govern enable out- The system scheduler feature provides up to 6 dif-
put when both sources are connected. This signal ferent schedule exceptions. It uses an on-board
should be wired into all of the genset’s utility break- Real Time Clock.
er position inputs. The load govern enable output is
used to put the genset controllers into the load gov- Adjustments to system scheduler parameters can
ern mode. be done using the setup tool (see page 5-23) and
(see page 6-92). Monitoring load control functions
MODBUS RTU INTERFACE is also available using the digital display (see page
6-150).
The ModBus RTU interface allows for easy system
monitoring by many third party devices. It provides Real Time Clock
a standard register map of system data that can be
used for monitoring by a remote PLC. The control board includes a real time clock for use
with the System Scheduler feature. The user must
The ModBus serial communications uses a Re- set the clock on first power-up or if the control board
mote Terminal Unit (RTU) two-wire master/slave has been without power for an extended period of
multi-drop configuration where the PLC is the mas- time.
ter device and the MCM3320 is the ModBus slave.
The clock keeps track of the year, month, day, date,
The ModBus RTU interface feature includes: hour, minute, and second. The clock automatically
accounts for leap years and can be configured for
• A published register map automatic Daylight Savings Time clock correction.
• Read/write access The clock settings will remain valid for at least 24
• Operational data, control, and setup variables hours without B+ supplied to the board.
• Can be configured for an RS-232 or an A diagnostic fault occurs if the clock needs to be set
RS-485 connection (the system scheduler won’t run).
• An adjustable address (default = node 1), al-
The clock settings can be adjusted using the setup
lowing multiple MCM3320 slaves on RS-485
tool (see page 5-25) or the digital display (see page
• Communications setup and diagnostics 6-90).

3-17
PRELIMINARY

INPOWER SERVICE TOOL Use of this feature requires that the paralleling
breaker position ‘a’ contacts be connected to the
The MCM3320 includes a MON RS-485 interface MCM3320.
which is used, along with an RS-485 to RS-232
converter kit, to communicate with a PC that has In- Adjustments to load demand parameters can be
done using the setup tool (see page 5-14) and us-
Power software loaded.
ing the digital display (see page 6-24). Monitoring
load demand functions is also available using the
This feature has standard InPower folders: Adjust-
digital display (see page 6-146).
ments, Faults, Monitor, Test. It can be used to cap-
ture files and download new firmware.
LOAD ADD AND LOAD SHED
The MCM3320 is supported in InPower, starting This feature allows for adding load in steps as the
with software version 5.0. The MCM3320 can be gensets come online. This feature also allows for
partially supported in version 4.5 with some file up- shedding loads to unload an overloaded genset
dates required. bus.
Use of this feature requires that an external I/O
LOAD DEMAND module be installed. Your installation may include
an AUX101/AUX102 PCCNet I/O Module for feed-
Load demand is used to match online generating er breaker control and/or an ATS control.
capacity to the load in order to optimize fuel use
and genset life. This feature can control up to six feeder breakers or
ATSs directly in any combination. This feature sup-
Load demand can be used with up to four gensets. ports up to four gensets.

Load demand can be set up to operate based upon There are six configurable levels of load add and
fixed sequence OR run hours. load shed.
Monitoring of the breaker/ATS position is provided.
This feature includes adjustable shutdown and re-
start levels as well as time delays. Adjustments to load add shed parameters can be
done using the setup tool (see page 5-26) and (see
Four load demand driver outputs are available to page 6-26). Monitoring load add shed functions is
connect to the PCC genset control’s load demand also available using the digital display (see page
inputs. 6-148).

3-18
PRELIMINARY

4. System Operation
This section describes how the MCM3320 oper- 5. The PCC causes the gensets to synchronize
ates. It includes information on how it communi- with the system bus and then close to it at the
cates with and controls gensets and transfer proper time.
switches. 6. When the minimum number of gensets are on-
line, the utility main breaker (52-UM1) opens.
SEQUENCE OF OPERATION
7. The adjustable programmed transition time
An example of a normal system controlled by an delay (TDPT) starts.
MCM3320 is one that consists of one utility source, 8. When the time delay expires, the genset main
two diesel gensets, one transfer pair, and eight breaker (52-GM1) closes and the entire plant
load breakers. The feeder breakers are located on is fed by generator power.
the load bus and are normally fed by the utility
source through the utility main breaker. They are NOTE: If the utility source returns before the
separated from the load by a genset main breaker. TDPT expires, the utility main
(52-UM1) closes and the genset par-
During normal operation, the gensets are in alleling breakers open. The genera-
standby mode (gensets in Auto mode and not tors continue to run without load for a
running) and the genset paralleling breakers are cooldown period. When the time delay
open. The utility source is available and the utility engine cooldown (TDEC) has expired,
main breaker is closed, providing power to the the gensets shut down and the system
feeder breakers, which are closed. The Auto/ returns to normal standby mode.
Manual switch on the transfer switch for the
transfer pair is set to the Auto position. Return of Utility Power
1. When the utility power source returns, the util-
AUTOMATIC OPERATION ity failure contact opens and the adjustable re-
transfer time delay (TDEN) starts.
When the switchgear is placed in Auto Mode, all
connected gensets are available to be automatical- NOTE: If the utility source again fails during
ly started if the utility power source fails. the TDEN, the timer resets and does
not restart until utility power again re-
Closed Transition Failure Operation turns.
2. When the TDEN expires, the master synchro-
Loss of Utility Power nizer between the genset paralleling bus and
1. The system receives a utility failure contact the utility is enabled to synchronize the gen-
closure from the MCM3320. sets to the utility.
2. All gensets automatically and independently 3. When sync check conditions are met, the util-
start. They accelerate to rated frequency and ity main breaker (52-UM1) closes and the gen-
build up to rated voltage. sets ramp down load.
3. The first-start system monitors the gensets 4. when the power across the genset main
and, upon finding a genset at 90% of rated breaker (52-GM1) approaches zero, the gen-
voltage and frequency, automatically closes set main breaker opens.
the ready unit to the bus and disables all other 5. the genset paralleling breakers open and the
units from closing to the bus. gensets operate at no load for a cooldown pe-
4. After the first unit closes to the bus, control of riod.
the remaining units switches to the synchro- 6. When the time delay engine cooldown (TDEC)
nizer in each generator PowerCommand Par- has expired, the gensets shut down and the
alleling Control (PCC). system returns to normal standby mode.

4-1
PRELIMINARY

Closed Transition Test Mode When in Manual Mode, the main breakers
(52-UM1 and 52-GM1) are controlled by a breaker
A Load Test can be initiated through the operator control switch located on the switchgear. The
panel. transfer pair are electrically interlocked to prevent
1. When the system receives a Load Test bus 1 closed transition operation.
signal, all gensets automatically and indepen-
dently start. They accelerate to rated frequen- OPTIONAL MODES OF OPERATION
cy and build up to rated voltage.
Load Demand Operation Using a Fixed
2. Since voltage exists on the load bus, control of Sequence
the units switches to the synchronizer in each
generator PowerCommand Paralleling Con- Load demand allows the gensets to operate closer
trol (PCC). to their rated capacities, resulting in decreased fuel
consumption and less wear on the system. Load
3. The PCC causes the gensets to synchronize demand is set up and enabled through the operator
with the system bus and then close to it at the panel menus (see page 6-24).
proper time.
The load demand mode of operation includes two
4. When all available gensets are online, the time delays.
master synchronizer between the genset par-
alleling bus the the utility source is enabled. • The initial time delay is the amount of time that
the system runs with full genset capacity be-
5. When sync conditions on the genset main
fore monitoring the system load.
breaker (52-GM1) are met, the breaker closes
and the gensets ramp up load. • The shutdown time delay is the amount of time
the system monitors the system load in com-
6. When the power across the utility main break- parison to the load demand settings before
er (52-UM1) approaches zero, the utility main shutting down the genset. The load demand
breaker opens. shutdown sequence determines the order in
7. The gensets now supply power to the loads which the gensets are shut down or restarted,
connected to the load bus. based upon system load.
8. When the Load Test signal is removed, the NOTE: The lead unit never shuts down.
master synchronizer between the genset par-
The load demand settings determine the levels at
alleling bus the the utility source is enabled to
which gensets are shut down and started. The kW
synchronize the gensets to the utility.
restart percent is the percent of load on the running
9. When the sync check conditions are met, the gensets that must be exceeded to start an addition-
utility main breaker (52-UM1) closes, the gen- al genset. The kW shutdown percentage is the per-
sets ramp down load, and the genset main cent of kW capacity of the remaining gensets that
breaker (52-GM1) opens when the load the load just be under for the next genset in the load
across it approaches zero. demand sequence to shut down.
10. The genset paralleling breakers open and the Load Demand Operation Using Run
gensets operate at no load for a cooldown pe- Hours
riod.
Load demand operation using run hours is the
11. When the time delay engine cooldown (TDEC)
same as when using a fixed sequence, but the se-
has expired, the gensets shut down.
quence differs in that the user defines a run-time
threshold on the Load Demand menu included in
MANUAL OPERATION the Adjust series of menus (see page 6-99).
For manual operation, the Auto/Manual switch on When the difference in running hours between the
the switchgear with open transition must be placed gensets exceeds the threshold, the system starts
in Manual position. The gensets then can be indi- up the genset with the lower number of running
vidually started and brought online using the gen- hours and shuts down the one with the highest
set’s PowerCommand Control (PCC). number of hours.

4-2
PRELIMINARY

PTC NORMAL OPERATING SEQUENCES Isolated Bus Normal Operating Sequence


The normal power transfer control operating se-
quence differs, depending on the system topology The Isolated Bus system topology is only used
(isolated bus, common bus, or transfer pair) and
when testing with or without load. This topology
the chosen transfer method (open transition, hard
closed transition, or soft closed transition). can be used with an Open Transition type but not
with Hard Closed or Soft Closed transition types.
Operational priorities in order from highest to low-
est are:
1. Utility Failure The normal operating sequence when using the
Isolated Bus system topology when testing with
2. Extended Parallel load is shown in Table 4-1 and when testing without
3. Test load is shown in Table 4-2.

TABLE 4-1. ISOLATED BUS NORMAL SEQUENCE OF OPERATION − TEST WITH LOAD
Transition Type Action Performed By
# Hard Closed Soft Closed User/ Genset
Open Transition MCM3320
Transition Transition Other Control(s)
1 A test start input is Not Applicable Not Applicable X
activated.
2 Time delay engine start X
3 Activate gensets start X
relay.
4 Gensets start, warm up, X
sync, close, etc.
5 The genset bus becomes X
available.
6 Time delay transfer X
7 Close GM X
8 The loads are powered X X
by the genset bus.
9 The test start input is X
deactivated
10 Time delay retransfer X
11 Open GM X
12 Time delay engine stop X
13 Deactivated gensets start X
relay.
14 The gensets open the X
breakers, cool down, and
stop.

4-3
PRELIMINARY

TABLE 4-2. ISOLATED BUS NORMAL SEQUENCE OF OPERATION − TEST WITHOUT LOAD
Transition Type Action Performed By
# Hard Closed Soft Closed User/ Genset
Open Transition MCM3320
Transition Transition Other Control(s)
1 A test start input is Not Applicable Not Applicable X
activated.
2 Time delay engine start X
3 Activate gensets start X
relay.
4 Gensets start, warm up, X
sync, close, etc.
5 The genset bus becomes X
available.
6 Gensets running X X
unloaded
7 The test start input is X
deactivated
8 Time delay engine stop X
9 Deactivate gensets start X
relay
10 Gensets open breakers, X
cool down, and stop.

Common Bus Normal Operating The normal operating sequence when using the
Sequence Common Bus system topology when there is a util-
ity failure and return is shown in Table 4-3. The nor-
The Common Bus system topology is used when
mal operating sequence when using the Common
there is a utility failure/return, to test with or without
load, and for extended paralleling. For utility failure/ Bus system topology when testing with load is
return and testing with or without load, this topology shown in Table 4-4 and when testing without load is
can be used with Open Transition and Soft Closed shown in Table 4-5. The normal operating se-
Transition types but not with a Hard Closed Transi- quence when using the Common Bus system to-
tion. For extended paralleling, this topology can pology for extended paralleling is shown in Table
only be used with a soft Closed Transition. 4-6.

4-4
PRELIMINARY

TABLE 4-3. COMMON BUS NORMAL SEQUENCE OF OPERATION − UTILITY FAILURE/RETURN


Transition Type Action Performed By
# Hard Closed User/ Genset
Open Transition Soft Closed Transition MCM3320
Transition Other Control(s)
1 Utility failure is detected. Not Applicable Utility failure is detected. (X) X
2 Inhibit genset breakers Inhibit genset breakers X
ON ON
3 Time delay engine start Time delay engine start X
4 Activate Gensets start Activate Gensets start X
relay relay
5 Gensets start and run Gensets start and run X
unloaded unloaded
6 Time delay transfer Time delay transfer X
7 Open UM Open UM X
8 Time delay program Time delay program X
transition (TDPT) transition (TDPT)
9 Inhibit genset breakers Inhibit genset breakers X
OFF (“Close GM”) OFF (“Close GM”)
10 Genset breakers close Genset breakers close X
11 Loads powered by the Loads powered by the X X
genset bus genset bus
12 Utility return is detected. Utility return is detected. (X) X
13 Time delay retransfer Time delay retransfer X
14 Master synchronize X
15 Close UM X
16 Genset ramp unload X
17 Genset bus kW is less X
than threshold
18 Inhibit genset Breakers Inhibit genset Breakers X
ON (“Open GM”) ON (“Open GM”)
19 Genset breakers open Genset breakers open X
20 TDPT X
21 Confirm genset breakers X
open
22 Confirm dead bus X
23 Close UM X
24 Time delay engine stop Time delay engine stop X
25 Deactivate gensets start Deactivate gensets start X
relay. relay.

4-5
PRELIMINARY

TABLE 4-4. COMMON BUS NORMAL SEQUENCE OF OPERATION − TEST WITH LOAD
Transition Type Action Performed By
# Hard Closed User/ Genset
Open Transition Soft Closed Transition MCM3320
Transition Other Control(s)
1 Test start input activated Not Applicable Test start input activated X
2 Inhibit genset breakers Inhibit genset breakers X
ON ON
3 Time delay engine start Time delay engine start X
4 Activate gensets start Activate gensets start X
relay relay
5 Gensets start and run Gensets start and run X
unloaded, synchronizing unloaded, synchronizing
6 Time delay transfer Time delay transfer X
7 Inhibit genset breakers X
OFF (“Close GM”)
8 Genset breakers close X
9 Gensets ramp load X
10 Utility kW less than X
threshold
11 Open UM Open UM X
12 Time delay program X
transition (TDPT)
13 Inhibit genset breakers X
OFF (“Close GM”)
14 Genset breakers close X
15 Loads powered by genset Loads powered by genset X X
bus bus
16 Test start input Test start input X
deactivated deactivated
17 Master load control = 0V X
18 Time delay retransfer Time delay retransfer X
19 Master synchronize X
20 Close UM X
21 Genset ramp unload X
22 Genset bus kW less than X
threshold
23 Inhibit genset breakers Inhibit genset breakers X
ON (“Open GM”) ON (“Open GM”)
24 Genset breakers open Genset breakers open X
25 TDPT X
26 Confirm genset breakers X
open
27 Confirm dead bus X
28 Close UM X
29 Time delay engine stop Time delay engine stop X
30 Deactivate gensets start Deactivate gensets start X
relay relay

4-6
PRELIMINARY

TABLE 4-5. COMMON BUS NORMAL SEQUENCE OF OPERATION − TEST WITHOUT LOAD
Transition Type Action Performed By
# Hard Closed User/ Genset
Open Transition Soft Closed Transition MCM3320
Transition Other Control(s)
1 Test start input activated Not Applicable Test start input activated X
2 Inhibit genset breakers Inhibit genset breakers X
ON ON
3 Time delay engine start Time delay engine start X
4 Activate gensets start Activate gensets start X
relay relay
5 Gensets start and run Gensets start and run X
unloaded, may be unloaded, may be
synchronizing synchronizing
6 Gensets run unloaded Gensets run unloaded X
7 Test start input Test start input X
deactivated deactivated
8 Time delay engine start Time delay engine start X
9 Deactivate gensets start Deactivate gensets start X
relay relay

4-7
PRELIMINARY

TABLE 4-6. COMMON BUS NORMAL SEQUENCE OF OPERATION − EXTENDED PARALLELING


Transition Type Action Performed By
# Hard Closed User/ Genset
Open Transition Soft Closed Transition MCM3320
Transition Other Control(s)
1 Not Applicable Not Applicable Extended parallel start X
input activated
2 Inhibit genset breakers ON X
3 Time delay engine start X
4 Activate gensets start relay X
5 Gensets start and run X
unloaded, synchronizing
6 Time delay transfer X
7 Inhibit genset breakers X
OFF (“Close GM”)
8 Genset breakers close X
9 Gensets ramp load X
10 Loads powered by genset X X
bus and utility bus
11 Extended parallel input X
deactivated
12 Deactivate gensets start X
relay
13 Gensets ramp load X
14 Genset bus kW less than X
threshold
15 Inhibit genset breakers ON X
(“Open GM”)
16 Genset breakers open X
17 Gensets cool down and X
stop

4-8
PRELIMINARY

Transfer Pair Normal Operating Sequence The normal operating sequence when using the
Transfer Pair system topology when there is a util-
The Transfer Pair system topology is used when
ity failure and return is shown in Table 4-7. The nor-
there is a utility failure/return, to test with or without
load, and for extended paralleling. For utility failure/ mal operating sequence when using the Transfer
return and testing with or without load, this topology Pair system topology when testing with load is
can be used with Open Transition, Hard Closed shown in Table 4-8 and when testing without load is
Transition, and Soft Closed Transition types. For shown in Table 4-9. The normal operating se-
extended paralleling, this topology can only be quence when using the Transfer Pair system topol-
used with a Soft Closed Transition. ogy for extended paralleling is shown in Table 4-10.

TABLE 4-7. TRANSFER PAIR NORMAL SEQUENCE OF OPERATION − UTILITY FAILURE/RETURN


Transition Type Action Performed By
# Hard Closed Soft Closed User/ Genset
Open Transition MCM3320
Transition Transition Other Control(s)
1 Utility failure detected Utility failure detected Utility failure detected (X) X
2 Time delay engine Time delay engine Time delay engine X
start start start
3 Activate gensets start Activate gensets start Activate gensets start X
relay relay relay
4 Genset bus available Genset bus available Genset bus available X
5 Time delay transfer Time delay transfer Time delay transfer X
6 Open UM Open UM Open UM X
7 Time delay program Time delay program Time delay program X
transition (TDPT) transition (TDPT) transition (TDPT)
8 Close GM Close GM Close GM X
9 Loads powered by Loads powered by Loads powered by X X
genset bus genset bus genset bus
10 Utility return detected Utility return detected Utility return detected (X) X
11 Master load control = X
0V
12 Time delay retransfer Time delay retransfer Time delay retransfer X
13 Master synchronize Master synchronize X
14 Open GM X
15 TDPT X
16 Close UM Close UM Close UM X
17 Genset ramp unload X
18 Genset bus kW < X
threshold
19 < 100 msec overlap X
20 Open GM Open GM X
21 Time delay engine Time delay engine Time delay engine X
stop stop stop
22 Deactivate gensets Deactivate gensets Deactivate gensets X
start relay start relay start relay
23 Gensets open breaker, Gensets open breaker, Gensets open breaker, X
cool down, and stop cool down, and stop cool down, and stop

4-9
PRELIMINARY

TABLE 4-8. TRANSFER PAIR NORMAL SEQUENCE OF OPERATION − TEST WITH LOAD
Transition Type Action Performed By
# Hard Closed Soft Closed User/ Genset
Open Transition MCM3320
Transition Transition Other Control(s)
1 Test start input Test start input Test start input X
activated activated activated
2 Master load control = X
5V
3 Time delay engine Time delay engine Time delay engine X
start start start
4 Activate gensets start Activate gensets start Activate gensets start X
relay relay relay
5 Genset bus available Genset bus available Genset bus available X
6 Time delay transfer Time delay transfer Time delay transfer X
7 Master synchronize Master synchronize X
8 Close GM Close GM X
9 Genset ramp load X
10 Utility bus kW < X
threshold
11 <100 msec overlap X
12 Open UM Open UM Open UM X
13 Time delay program X
transition (TDPT)
14 Close GM X
15 Loads powered by Loads powered by Loads powered by X X
genset bus genset bus genset bus
16 Test start input Test start input Test start input X
deactivated deactivated deactivated
17 Master load control = X
0V
18 Time delay retransfer Time delay retransfer Time delay retransfer X
19 Master synchronize Master synchronize X
20 Open GM X
21 TDPT X
22 Close UM Close UM Close UM X
23 Genset ramp unload X
24 Genset bus kW < X
threshold
25 < 100 msec overlap X
26 Open GM Open GM X
27 Time delay engine stop Time delay engine stop Time delay engine stop X
28 Deactivate gensets Deactivate gensets Deactivate gensets X
start relay start relay start relay
29 Gensets open breaker, Gensets open breaker, Gensets open breaker, X
cool down, and stop cool down, and stop cool down, and stop

4-10
PRELIMINARY

TABLE 4-9. TRANSFER PAIR NORMAL SEQUENCE OF OPERATION − TEST WITHOUT LOAD
Transition Type Action Performed By
# Hard Closed Soft Closed User/ Genset
Open Transition MCM3320
Transition Transition Other Control(s)
1 Test start input Test start input Test start input X
activated activated activated
2 Time delay engine Time delay engine Time delay engine X
start start start
3 Activate gensets start Activate gensets start Activate gensets start X
relay relay relay
4 Genset bus available Genset bus available Genset bus available X
5 Gensets running Gensets running Gensets running X X
unloaded unloaded unloaded
6 Test start input Test start input Test start input X
deactivated deactivated deactivated
7 Time delay engine Time delay engine Time delay engine X
stop stop stop
8 Deactivate gensets Deactivate gensets Deactivate gensets X
start relay start relay start relay
9 Gensets open breaker, Gensets open breaker, Gensets open breaker, X
cool down, and stop cool down, and stop cool down, and stop

4-11
PRELIMINARY

TABLE 4-10. TRANSFER PAIR NORMAL SEQUENCE OF OPERATION − EXTENDED PARALLELING


Transition Type Action Performed By
# Hard Closed User/ Genset
Open Transition Soft Closed Transition MCM3320
Transition Other Control(s)
1 Not Applicable Not Applicable Extended parallel start input X
activated
2 Master load control = X
setpoint
3 Time delay engine start X
4 Activate gensets start relay X
5 Genset bus available X
6 Time delay transfer X
7 Master synchronize X
8 Close GM X
9 Gensets ramp load X
10 Loads powered by genset X X
bus and utility bus
11 Extended paralleling start X
input deactivated
12 Master load control = 0V X
13 Gensets ramp unload X
14 Genset bus kW < threshold X
15 Open GM X
16 Time delay engine stop X
17 Deactivate gensets start X
relay
18 Gensets open breaker, cool X
down, and stop

4-12
PRELIMINARY

5. Setup and Calibration


INTRODUCTION Kit number 541−1199 is available for use with the
MCM3320. The kit includes the RS-232 to RS-485
converter and the cable used for this application.
A personal computer (PC) based setup tool is pro-
vided on a CD with the module to allow basic cus- The following steps should be followed for setting
tomer set up. This section describes setup and up the MCM3320 using the MCM3320 setup
configuration of the MCM3320 using the CD-based screen.
configuration tool provided with the module. In- 1. Connect to the control.
Power can be used to setup, adjust, monitor, and 2. Select an application type and other system
calibrate the MCM3320. The InPower service con- parameters.
nection from a laptop to the MCM3320 is shown in
3. Set up the metering inputs to match your sys-
Figure 4-1.
tem.
4. Calibrate the metering inputs, if desired.
The MCM3320 requires an RS-232 to RS-485 data
converter and a unique cable. Figure 4-1 shows the 5. Set up the circuit breakers.
MCM3320 InPower connection. 6. Set up the synchronizer.

MASTER CONTROL
MODULE 3320

OPERATOR
PANEL

SERVICE
CABLE

J14
CONNECTOR
SECURITY
DONGLE

RS-232 TO RS-485
CONVERTER

FIGURE 4-1. MCM3320 PC CONNECTIONS

5-1
PRELIMINARY

METER SETUP sary to calibrate the voltage current go the voltage


and current calibration setup tab.

To set up the MCM3320 metering first select the The following connection options are available:
wye or delta configuration for the generator and
• 4 wire direct (see Figure 4-3)
bus at the top of the screen (see the connection op-
tions below). Then enter the system nominal volt- • 4 wire with transformer (see Figure 4-4)
age for the system in Genset nominal system LL • 3 wire direct (see Figure 4-5)
voltage text box. The utility nominal voltage box will
display the same value. This is the voltage that will • 3 wire with transformer (see Figure 4-6)
equal the 100% value referred to in the genset and NOTE: When using one amp CTs, wind two turns
utility bus sensor setup screens. If an external step through the board CTs.
down potential transformer is used then click on the
enable check box in the external transformer frame MCM3320 Range of Operation
and enter the data for the transformer. In all the text Range
boxes the data can either be selected from the drop
down menu or entered in directly. Finally select 1 or Voltage (LL, rms) 0−480V Direct
5 amp for the CT secondary and CT ratio for the 600−34500V w/PT
genset and utility. When the data is entered cor- Current (rms) 5−10000 Amps with 1 or 5
rectly click the save adjustments button to perma- Amp CT
nently save the data. To verify the meter readings Power (total) −32000 to +32000 kW
click on meter data and top menu bar to display the
voltage, current and power readings. If it is neces- Power Factor (true) 0 to +/−1.0

FIGURE 4-2. GENERATOR AND UTILITY METERING SETUP

5-2
PRELIMINARY

FIGURE 4-3. 4 WIRE DIRECT CONNECTION OPTION

FIGURE 4-4. 4 WIRE WITH TRANSFORMER CONNECTION OPTION

5-3
PRELIMINARY

FIGURE 4-5. 3 WIRE DIRECT CONNECTION OPTION

FIGURE 4-6. 3 WIRE WITH TRANSFORMER CONNECTION OPTION

5-4
PRELIMINARY

SYNCHRONIZER SETUP 5. Set up the synchronizer faults.

6. Set up the synchronizer gains.


The MCM3320 matches frequency, phase and
voltage of a system of paralleled generator sets to 7. If necessary, turn the synchronizer.
a utility bus. It does this by driving the kW and kVAR
load share lines to adjust the generator set fre-
Setting up the Load Share Gains for
quency and voltage. There are two synchronize
method options, frequency or phase which can be Synchronizing
selected depending on the application. The match-
ing range of the synchronizer is dependent the The MCM3320 drives the load share lines to syn-
genset kW and kVAR load share gains see setting chronize system frequency/phase and voltage. In
up the load share gains for synchronizing. Table order for frequency and voltage matching to work
5-1 shows the typical performance of the phase properly the kW and kVAR load share gains must
synchronizer with diesel engines. The MCM3320 be set properly so all the controls respond the
LEDs display the status of the generator and utility same way to the voltage applied to the load share
source availability and the status of the synchroniz- lines. If the system genset controls are all the same
er. The MCM3320 can operate in a master syn- the load share gains must be set to the same val-
chronize only mode see ues. If PCC3100 and PCC3200 are mixed in the
same system they must be set up so their gains
have the same effect. The load share gains affect
TABLE 5-1. TYPICAL SYNCHRONIZER
PERFORMANCE the range of operation of the frequency and voltage
matching and the synchronizer gain.
Typical Performance
with Diesel Engines
The MCM3320 default synchronizing range limits
Synchronize time with 1−5 Seconds for frequency/phase and voltage matching are
phase match
shown in Table 5-2. These limits are set so the
Synchronize time with 3−10 Seconds MCM3320 will work with the default load share gain
frequency match settings of the PCC3100 and 3200 controls.
Phase hold Within +/− 5 degrees
Maximum number of sets 12 NOTE: The PCC3100 and PCC3200 controls
have over voltage shutdowns at 110%. The
MCM3320 voltage matching range should
The following steps should be followed for proper
not be set to exceed this value.
synchronizer setup

1. Set up the load share gains. If a wider range is desired the load share gains can
be increased. The kW load share gain controls the
2. Select the synchronize method. frequency matching range and the kVAR load
3. Verify the conditions necessary for synchro- share gain controls the voltage matching range.
nizing to occur. The PCC3100 default gains will allow a +/− 2.5 Hz
frequency match range. The maximum voltage
4. Set up the Permissive Close (sync check) win- and frequency synchronizing range are not avail-
dow. able on the tabbed setup screen.

TABLE 5-2. SYNCHRONIZING RANGE


Synchronizer Maximum Comments
Default Range Allowable Range
Frequency +/−1 Hz +/−5 Hz Maximum range is only achievable by
changing the kW load share gain.
Voltage +/−6 % +/−9 % The default over voltage shutdown of the
genset controls is 110%.

5-5
PRELIMINARY

TABLE 5-3. PCC3100 MAXIMUM ALLOWABLE SYNCHRONIZE RANGE VS LOAD SHARE GAINS

kW Load Share Maximum Frequency kVAR Load Maximum Voltage


Gain Match Range Share Gain Match Range
3 +/−1.0 Hz 150 +/−4 %
6 (default) +/−2.5 Hz 300 (default) +/−8 %
8 +/−3.5 Hz

TABLE 5-4. PCC3200 MAXIMUM ALLOWABLE SYNCHRONIZE RANGE VS LOAD SHARE GAINS

kW Load Share Maximum Frequency kVAR Load Maximum Voltage


Gain Match Range Share Gain Match Range
0.5 +/−0.5 Hz 0.5 +/−4 %
1.0 (default) +/−1.0 Hz 1.0 (default) +/−8 %
2.0 +/−2.5 Hz
System Setup with PCC3100 and 0326−0187 PCC Sentinel 2.03
PCC3200 Genset Controls
0326−6472 QSM 11 2.03
When operating a system with PCC3100 and 0326−6397 PGI Std. P7 2.07
PCC3200 controls the load share gains must be 0326−5853 GPS PCS 1.27
set so they have the same response to voltages on
0326−6049 PGI Sentinal 2.04
the load share lines. Recommended values are
shown in the table. The default kVAR gains are Ok 0326−6052 PGI Ventura 2 2.04
but the PCC3200 must be increased to 2.0 to 0326−6050 PGI Ventura 1 2.03
match the PCC3100.
0326−6393 Astr’l Army 2.11

Recommended kW and kVAR Gain Values Conditions Necessary for Synchronizing


Control kW Gain kVAR Gain to Occur
PCC3100 6 300 The MCM3320 will not start synchronizing unless
PCC3200 2.0 1.0 the following conditions are met:
1. The system topology is set to Master Synchro-
The following change must be made to the nize or in another topology where the software
PCC3100 control for it to match the PCC3200 has requested synchronizing occurs.
kVAR gain. The Reactive Power Scale variable
must be changed and saved using InPower from 2. Generator source is available – see generator
695 to 820. If this is done in PCC3100 software ear- and bus sensors.
lier than the versions listed in the table below the
minimum frequency synchronizing range bus must 3. Utility source is available – see generator and
be set to −1.0 Hz or less. Later versions of the soft- bus sensors.
ware do not have this limitation.
4. MCM3320 is in Auto OR it is in Manual with the
sync enable switch on.
Software P/N Description Version
0326−6047 PGI Std. 2.06 5. The fail to synchronize fault in not active or the
0326−0368 PCC Std. P7 3.01 fail to sync lockout is disabled.

0326−6046 PCC Ventura 1 2.04 6. The generator and bus have the same phase
0326−0198 PCC Ventura 2 2.03 rotation.
0326−0148 PCC Std. P7 2.06 7. The MCM3320 is not inhibited.

5-6
PRELIMINARY

Synchronizing Methods frequency than match phase so on systems that


are difficult to phase match or where you would like
The MCM3320 has two methods of synchronizing: to control the direction of power flow when the
phase synchronizing and frequency synchroniz- breaker closes frequency synchronizing may be
ing. The default method is phase synchronizing desirable. Since the permissive conditions occur
and is suitable for most applications. This synchro- periodically based on the slip frequency the slip fre-
nizes the generator bus phase to the utility. quency method generally takes longer to synchro-
nize than the phase match method. The phase gain
Voltage Matching has no effect when using frequency synchronize
method and when phase synchronizing is selected
The MCM3320 matches the average of the three the slip frequency has no effect. The following table
generator phases to the average to the three utility shows the recommended slip frequency settings.
phases. The MCM3320 matches voltage in a simi- The recommended slip frequency setting = phase
lar way in which it matches frequency. Voltage window / (360 * Time in window). By using the set-
matching is active in both the phase and frequency tings in the table the phase difference at the end of
synchronize methods. Tuning the voltage match- permissive time window (when the breaker is al-
ing is done in a similar way to frequency matching. lowed to close) will be 0 degrees. (For example at
There is a proportional gain Kp and an integral gain 0.1 Hz slip it takes 0.5 seconds for the phase to
Ki. Voltage matching gains are generally less criti- change 20°, the phase difference would be in a +/−
cal than frequency or phase matching gains and 20° window for 0.5 seconds.)
typically do not need to be adjusted.
Recommended Slip Frequency Settings
NOTE: If the genset voltage is increased by volt-
age matching the load on the set will in- Recom- Time in Seconds
crease. If the voltage is raised to 6% then mended between When
Permissive
the genset load will increase by 12%. Slip Permissive
Window
Frequency Window Condi-
Slip Frequency Synchronizing in Hz tions are Met
20_ 0.5 Sec- 0.1 10
The slip frequency method works by governing the onds
generator bus frequency slightly off of the utility fre- 10_ 0.5 Sec- 0.05 20
quency. This frequency difference is called the slip onds
frequency. The frequency difference produces a
constantly changing phase difference between the The graph shown in Figure 4-7 the result of fre-
two sources. If the frequencies are close enough quency synchronizing with a slip frequency of 0.1
periodically the phase difference will be small Hz. The phase difference ramps from −180° to
enough that it will meet the permissive conditions 180°and the permissive conditions are met every
for closing the circuit breaker. It is easier to govern 10 seconds

5-7
PRELIMINARY

FIGURE 4-7. SLIP FREQUENCY EXAMPLE

Setup the Synchronizer Gains NOTE: The stability of the synchronizing improves
as more sets are paralleled. Gas sets are
The synchronizer gains can be set using the values much more stable with load.
in Table 7 Typical synchronizer gain settings based
on the control and engine. These gain values apply
if with the genset controls set to their default load Synchronizer Tuning
share gains. If the load share gains are changed
the frequency gain Kp will need to change. Gener- The synchronizer consists of a proportional inte-
ally the voltage matching gains can be set the gral controller for frequency matching with an input
same for all gensets and can be left at their de- for phase difference matching. When the frequen-
faults. The frequency matching gains will vary de- cy synchronize method is used the phase differ-
pending on the control and engine. For diesel en- ence input is ignored. The frequency matching
gines with PCC3100 and PCC3200 controls the control has two adjustable gains. A proportional
frequency match gains should be set to the stan- gain Kp and an integral gain Ki. Phase matching
dard values listed in the table. If it is necessary to has one proportional gain Kp. The voltage match-
optimize performance or the genset is not one ing control is similar to the frequency control with
listed in the table (Table 5-5), it will be necessary to two adjustable gains. Normally it is only necessary
go through the synchronizing tuning procedure. to adjust the proportional gains.
TABLE 5-5. TYPICAL SYNCHRONIZER GAIN SETTINGS
Control/Set Frequency Frequency Phase Kp Voltage Kp Voltage Ki
Kp Ki
Default Gains 30 20 160 400 50
PCC3200 − Standard 50 20 160 400 50
PCC3100 − Standard 50 20 160 400 50
PCC3100 − QSM11 25 20 160 400 50
PCC3100 − 1250 Gas 9 20 160 400 50

5-8
PRELIMINARY

Permissive Close (Sync Check) The board LEDs display the status of the sync
check.
The following trims are available for the permissive
window: NOTE: The permissive close is removed when
phase difference is greater than 20 de-
TABLE 5-6. PERMISSIVE WINDOW SETTINGS grees or voltage difference is greater than
5%.
Trim Default
Voltage Window 5% Synchronizer Faults
Phase Window 10 Degrees Fail to Synchronize Warning
Time Window 0.5 Seconds
If the permissive conditions are not met in the time
Frequency Window 1.0 Hz specified the fail to synchronize warning is acti-
vated. If the fail to synchronize lockout is disabled
The follow conditions must be met for a permissive synchronizing will continue while the fault is active.
close is allowed: If it is enabled synchronizing will cease when the
fault occurs. If a fail to sync fault occurs and the
1. Utility source is available lockout is enabled the fault must be reset before
normal operation can occur.
2. Generator source is available
If the fail to sync open transition retransfer is en-
3. Utility and generator phase rotation are the abled an open transition transfer will occur when
same the fail to synchronize fault is activated.

4. The highest difference of all the generator Synchronizer Phase Rotation Warning
phase voltages minus the utility phases is less
If the phase rotation of the Utility bus does not
than the voltage window
match the phase rotation of the generator bus this
fault is activated. Synchronizing will continue while
5. Phase difference is less than 20 degrees and
this fault is active but the permissive conditions will
decreasing or less then 10 degrees and phase
not be met. The system phase rotation can be set in
difference is less than the phase window
the either the generator or utility bus menu.
6. The frequency difference between the Synchronizer Output Limit Warning
sources is less than the frequency window
If the MCM3320 drive on the load share lines has
7. Permissive conditions are met for the time win- reached its maximum this fault is activated. This
dow occurs if the MCM3320 is trying to match voltage or
frequency and cannot reach the desired level. Syn-
8. The MCM3320 is not inhibited. chronizing will stop if this fault occurs.

5-9
PRELIMINARY

FIGURE 4-8. USING THE MASTER SYNC ONLY FEATURE TO COMMUNICATE WITH POWERCOMMAND
CONTROLS

5-10
PRELIMINARY

VOLTAGE AND CURRENT CALIBRATION a box labeled Your meter. This is where you enter
the reading from an external meter that you would
The MCM3320 is calibrated at the factory and nor- like the MCM3320 to match. When you click on the
mally does not require calibration in the field. If it is perform auto calibration button the setup pro-
necessary to have the MCM3320 metering match gram will match the MCM3320 reading to the value
another metering instrument a provision is pro- entered in the Your meter box. The scroll bars to
vided for calibration of the voltage and current. The the right of the meter boxes allow an option to
setup program allows for an automatic calibration manually calibrate the voltages and current.
of the MCM3320 through the voltage/current cal-
ibration screen (see Figure 4-9). The shaded NOTE: The voltage and current cannot be cali-
blocks display the voltage and current readings of brated while the MCM3320 is synchroniz-
the MCM3320. Below each of the shaded boxes is ing.

FIGURE 4-9. VOLTAGE AND CURRENT CALIBRATION SCREEN

5-11
PRELIMINARY

CIRCUIT BREAKER SETUP contacts should be selected if you have both the a
and b circuit breaker auxiliary contacts connected
The following setup options are available for the to the MCM3320. When Dual is selected the
circuit breaker. MCM3320 checks the position of both contacts to
verify the breaker position. If single is selected then
Circuit Breaker Fail to Disconnect only one contact is used to detect the breaker posi-
tion.
Fail to Disconnect logic applies to cases where the
genset and utility sources are paralleled. If one of Recharge Delay
the breakers fails to open when commanded to do
so, the fail to disconnect logic will then try to open Sets the time to allow the circuit breaker to re-
the other breaker. If it succeeds, the action is com- charge.
plete and this state is latched until the user resets
the fail to open fault. However, if upon attempting
Fail to Fault Close Delay
to open the second breaker, it too fails to open, then Sets the maximum time after a circuit breaker close
the MCM3320 flags the fail to disconnect fault and is requested that the circuit breaker close position
activates the breaker inhibit line to the individual should be sensed. After that time a fail to close fault
genset controls in a last attempt to disconnect. In will occur. This fault causes a lockout and must be
addition, the Fail to Disconnect fault can be reset before normal operation can occur.
mapped to one of the 8 configurable outputs which
can in turn be used to externally trip a breaker. This Fail to Open Fault Delay
entire logic function can be optionally disabled.
Sets the maximum time after a circuit breaker open
Positions Contacts is requested that the circuit breaker open position
should be sensed. After that time a fail to open fault
This option is available for using dual or single posi- will occur. This fault causes a lockout and must be
tion contacts to detect the breaker position. Dual reset before normal operation can occur.

FIGURE 4-10. CIRCUIT BREAKER SETUP SCREEN

5-12
PRELIMINARY

GENSET AND UTILITY VOLTAGE AND voltage falls below the pick up threshold. The time
FREQUENCY SENSOR SETUP delay is for the drop out time. Pick up is immediate.

The generator and utility bus sensors determine if Frequency Sensor


the bus voltages and frequencies are in an accept-
able operating range. When they are in this range If enabled, this sensor will drop out when the fre-
the source is considerable available. The text quency goes beyond drop out thresholds, and pick
boxes with the white background are used to enter up when frequency falls within the pick up thresh-
the desired range. The shaded boxes display the olds. The time delay is for the drop out time. Pick
voltage or frequency those values correspond to. up is immediate.
Undervoltage Sensor Phase Rotation Sensor
At a minimum, source availability is determined by
the undervoltage sensor. The sensor will drop out If enabled, this sensor will drop out if the phase
when the voltage falls below the drop−out thresh- rotation of the source does not match the phase
old, and pick up when the voltage rises above the rotation setting.
pick−up threshold setting. The time delay is for the
drop out time. Pick up is immediate. Loss of Phase Sensor

Overvoltage Sensor If enabled, this sensor will detect if the line−line


voltages are more than 30 degrees away from 120
If enabled, this sensor will drop out when voltage degrees. The time delay is for the drop out time.
exceeds the drop out threshold and pick up when Pick up is immediate.

FIGURE 4-11. GENERATOR BUS SENSOR SCREEN

5-13
PRELIMINARY

Genset and Utility Bus Sensors Settings smooth transition, avoiding unnecessary voltage
for Synchronizer Applications and frequency transients.) To restart a genset
which has been stopped, total load is compared to
The synchronizer function requires both sources to the online capacity. When load reaches 80% of the
be considered as “available” in order to be able to online capacity (typical setting), the genset will be
turn on synchronizing. A source is available when restarted. (During a restart, the individual genset
all enabled sensors are picked up. The undervol- controller will start the genset, synchronize, close,
tage sensor is always enabled. Other sensors may and ramp on the load for a smooth transition.)
be enabled as desired.
Deciding which genset to shut down next can be
Auto / Manual Synchronizer Operation done in one of two ways. The first is with a fixed
preset sequence. The second is based on genset
When the Auto / Manual input is open circuit, the online hours. The online hours based method will
synchronizer is in automatic. It will start synchro- attempt to equalize run hours on each genset, re-
nizing whenever both sources are “available.” starting one and shutting down another when the
hours differential cross a threshold.
When the Auto / Manual input is grounded, the syn-
chronizer is in Manual mode. It will start synchro- Some fundamental rules for load demand control:
nizing when both sources are “available” and the
Sync Enable input is grounded. It will not synchro- • Load demand only works if the total number of
nize when Sync Enable is open circuit. gensets is 2, 3, or 4. Ratings must only appear
in Gen1 thru Gen4 and all other rating settings
Genset Sensor Operation During must be 0.
Synchronizing • For the load demand function to turn on, the
When the synchronizer is running, the pickup and load demand function must be enabled, the
dropout thresholds for undervoltage, overvoltage, genset bus available, and the genset main
and frequency sensors for the genset bus are tem- breaker closed (or one or more genset paral-
porarily expanded in order to allow the synchroniz- leling breakers closed in case of Common Bus
er to change the bus voltage and frequency without topology).
dropping out a sensor. When the synchronizer is • Load Demand control ends and all gensets
running these temporary expanded voltage thresh- are restarted if a Genset Bus Overload fault
olds are displayed in red on the genset sensor tab. occurs. This condition can only be reset
through user intervention. User must activate
LOAD DEMAND the fault reset and the overload condition must
no longer exist. Then the load demand func-
The load demand function is used to match gener- tion will turn back on if all of the turn on condi-
ation capacity to load so as to optimize fuel efficien- tions are met.
cy, extended service intervals, and prolong genset
life. It works with up to 4 gensets. To shutdown ex- • A genset is considered as part of the load de-
cess capacity, the function monitors the total mand online capacity either if its breaker is
amount of load and compares it to what the capac- closed or if it has been restarted and is waiting
ity would be if one genset were removed from the for the breaker to close. If the breaker does not
online gensets. If the load is less than 60% of this close in a fixed amount of time, the genset is
capacity (typical setting), then that genset will be then considered as failed and will be removed
stopped on load demand. (During a load demand from the load demand capacity.
stop of a genset, the individual genset controller • If a genset does not exist (its kW rating = 0), its
will ramp down that genset’s load, open its breaker, load demand command will be in the Run
cool down, and stop. The load ramp gives a state.

5-14
PRELIMINARY

FIGURE 4-12. LOAD DEMAND SCREEN

MASTER LOAD CONTROL model of genset controller does not have a kVAR
load set input.
The master load control function has the following
primary duties:
Extended Paralleling
Extended paralleling as used here is meant to refer
• Control real and reactive power in extended to intentional continued operation in parallel with a
paralleling operation (base load / peak shave) utility source for the purposes of base load and/or
• Cause ramp loading and unloading to occur peak shave operation. During extended paralleling
during soft closed transition load transfers operation, the kW and kVAR of the gensets must be
controlled. They can be controlled in a number of
• Operate independently of the number of gen- ways. Table 5-7 (Base Load / Peak Shave Configu-
sets that are online ration Options) lists the possible ways in which they
• Provide diagnostics in extended paralleling if can be controlled with this controller. Note that the
the desired setpoint(s) cannot be achieved kW control type and the kVAR control type can be
set independent of one another. For example, the
The master load control function ultimately drives kW could controlled at the genset bus (aka Base
two hardware analog outputs, one for kW control Load), while the kVAR could be controlled at the
and one for kVAR control. The kW control output is utility bus (aka Peak Shave). This scenario would
to be connected to all of the kW load set inputs on be used for applications where while base loading
the gensets to be controlled (= one output con- the gensets, it is desirable to manage the utility
nected to multiple inputs). The kVAR control output kVAR to avoid penalties from the utility for a low
is to be connected to all of the kVAR load set inputs power factor. In any of these scenarios, the gen-
on the gensets to be controlled (= one output con- sets which are online will be limited to what they are
nect to multiple inputs). Note that the PCC3100 capable of putting out, so it may not always be pos-

5-15
PRELIMINARY

sible to achieve a desired setpoint. The configura- cordingly begin to adjust its output command to
tions listed in the table also allow for open loop or compensate as this new genset comes into the
closed loop base load operation. (Peak shave al- group. Same is true if an individual genset is told to
ways requires closed loop.) In some cases open ramp unload. In order to insure that this operates
loop operation may be desirable due to stability is- smoothly, the ramp load and ramp unload times in
sues with closed loop, or just a requirement for the genset controllers should not be set to time val-
each genset that is online to put out a fixed % of its ues less than 60 seconds if at all possible.
capability.
Number of Gensets
Load Ramping
The master load control function does not require
During soft closed transition load transfers, ramp- knowledge of how many gensets are online. This
ing of the load is done by the individual genset con- provides the advantage of being able to do up to 12
trollers themselves. Thus the desired ramp rates gensets without needing all of the additional I/O. In
must be set in the genset controllers. The ramping closed loop mode, the load control function will just
direction is controlled by this controller by either drive the control output to attempt to achieve the
setting the control output value to give +5V (ramp setpoint target with whatever gensets are out
load), or 0V (ramp unload) on the analog output. there. It is important that the individual genset kW
ratings be entered into this controller because in
Upon entry into an extended parallel state, the some configurations, this load control function
ramping on of the load is controlled by this control- does need to know what the total genset bus ca-
ler. (This is required because the load control algo- pacity is. Though it is not required by this load con-
rithm in this controller operates without knowledge trol algorithm, if for some reason it is important that
of the number of gensets online. It could allow the extended paralleling not start until a certain num-
gensets to ramp on their own, but when the control ber of gensets are online, this can be accomplished
point was reached it would not know where to start with the Genset Online Capacity Sensor for up to 4
the control output at, resulting in an undesirable gensets. Beyond 4 gensets, the Transfer Time
transient.) At the end of an extended parallel ses- Delay (TDNE) should be set long enough to insure
sion, the ramp unloading is done by the individual that all available gensets have come online.
genset controllers themselves.
Diagnostics
If an individual genset should come online when
extended paralleling is already underway, it will If the desired kW setpoint cannot be achieved with-
ramp toward whatever the current setpoint is. If in a certain amount of time, a diagnostic warning
this controller is operating closed loop, it will ac- will be generated. Same for the kVAR setpoint.

5-16
PRELIMINARY

TABLE 5-7. BASE LOAD / PEAK SHAVE CONFIGURATION OPTIONS


Parameter Setting Genset Controller Description
Capability
3100 3200 3300
3201
REAL POWER CONTROL OPTIONS
Extended Paralleling kW Load Control Type =
Genset Bus % Level X X X MCM3320 puts out a user adjustable % level on the kW
(Open Loop) control output. Genset bus kW will be a result of whatever
[DEFAULT SETTING] gensets are online. (Thus it is open loop on the kW at the
GM.)
Genset Bus kW (Closed X X X MCM3320 drives the kW control output to achieve the de-
Loop) sired kW setpoint at the GM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.
Genset Bus kW Utility X X X MCM3320 drives the kW control output to achieve the de-
Constraint (Closed Loop) sired kW setpoint at the GM, but will reduce this setpoint to
keep the kW at the UM above a programmed level. (This
can be used to prevent tripping a UM reverse power relay
because of load falling below the GM kW setpoint. Coor-
dination of the settings in this controller and the relay and
an understanding of the magnitude of load fluctuations is
critical to successful use of this feature.)
Utility Bus kW (Closed X X X MCM3320 drives the kW control output to achieve the de-
Loop) sired kW setpoint at the UM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.
REACTIVE POWER CONTROL OPTIONS
Extended Paralleling kVAR Load Control Type =
Genset Controllers X X X MCM3320 does nothing. kVAR control output = 0. Genset
[DEFAULT SETTING] controllers take care of the kVAR control based on their
own settings...e.g. fixed power factor of 0.95.
Genset Bus % Level (Open X X MCM3320 puts out a user adjustable % level on the kVAR
Loop) control output. Genset bus kVAR will be a result of whatev-
er genset happen to be online.
Genset Bus Power Factor X X MCM3320 puts out a level on the kVAR control output
(Open Loop) based on what is being currently put out on the kW control
output. The relationship between the two is determined by
the PF setting.
Genset Bus kVAR (Closed X X MCM3320 drives the kVAR control output to achieve the
Loop) desired kVAR setpoint at the GM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.
Genset Bus Power Factor X X MCM3320 drives the kVAR control output to achieve the
(Closed Loop) desired PF setpoint at the GM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.
Utility Bus kVAR (Closed X X MCM3320 drives the kVAR control output to achieve the
Loop) desired kVAR setpoint at the UM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.
Utility Bus Power Factor X X MCM3320 drives the kVAR control output to achieve the
(Closed Loop) desired PF setpoint at the UM. If the setpoint cannot be
achieved within a preset time, a warning fault will occur.

5-17
PRELIMINARY

FIGURE 4-13. KW BASE LOAD/PEAK SHAVE SCREEN

FIGURE 4-14. KVAR BASE LOAD/PEAK SHAVE SCREEN

5-18
PRELIMINARY

SYSTEM SETUP often if ever. System Topology may only be set


when the System State is in Manual or Factory
Configuration of the system application consists of Test. The remaining variables are Transition
setting four variables. The primary setting is the Type, Extended Parallel Enable, and Test With
System Topology. This defines the breaker con- Load Enable. See Table 5-8 for details on the vari-
figuration and is not expected to be changed very ables.

TABLE 5-8. APPLICATION CONFIGURATION VARIABLES


Application Possible Values Description
Configuration Variable
System Topology Master Synchronize Control only does AC metering and synchronizing
Only
Isolated Bus without Control will support an isolated bus topology with no genset
GM main breaker.
Isolated Bus w/GM Control will support an isolated bus topology with a genset
main breaker.
Common Bus Control supports a utility parallel system with no genset main
breaker, only a utility main breaker.
Transfer Pair Control supports a utility parallel system with both genset and
utility main breakers.
Transition Type Open Transition Control performs open transition transfers and retransfers with
a programmed transition delay.
Hard Closed Transi- Control performs a hard transition parallel with <100msec of
tion overlap.
Soft Closed Transi- Control performs a soft transition with load ramping for both
tion transfers and retransfers between live sources.
Extended Parallel Enable Disabled Extended paralleling is disabled.
Enabled Extended paralleling is enabled.
Test With Load Enable Disabled When test is activated, test will be without load.
Enabled When test is activated, test will be with load.

5-19
PRELIMINARY

FIGURE 4-15. SYSTEM SETUP SCREEN (1 OF 2)

FIGURE 4-16. SYSTEM SETUP SCREEN (2 OF 2)

5-20
PRELIMINARY

FIRST START SENSOR


LOAD SHARE LINES

PCC PCC PCC

G G G

3 3 3
3 3 3
UTILITY

FAILED XXX XXX XXX

25
PMT 3 3 3 3
3 3
3

XXX XXX

LOADS

FIGURE 4-17. TRANSFER PAIR

FIRST START SENSOR


LOAD SHARE LINES

PCC PCC PCC

G G G

3 3 3
3 3 3
UTILITY

FAILED XXX XXX XXX

25
PMT 3 3 3 3
3 3
3

XXX

LOADS

FIGURE 4-18. COMMON BUS

5-21
PRELIMINARY

FIRST START SENSOR


LOAD SHARE LINES

PCC PCC PCC

G G G

3 3 3
3 3 3

XXX XXX XXX

25
PMT 3 3 3 3
3

XXX

LOADS

FIGURE 4-19. TRANSFER PAIR WITH GM

5-22
PRELIMINARY

SCHEDULER Program Overlapping


The scheduler (see Figure 4-20) operates based Do not overlap programs; overlapped program will
on up to 12 programs and 6 exceptions. be ignored (see Figure 4-21).
Each program specifies a day of the week/time to Exception Operation
start, how long to run, how often to repeat, and
what mode to run in. The timing of an exception will determine whether
Run modes are: test without load, test with load, or not a program will run (see Figure 4-22).
and extended parallel.
Priorities
Each exception is defined by a start date/time,
duration, and repeat interval. A Utility Failure will supersede any scheduler pro-
gram.
An exception will block a scheduled program from
starting during the exception period. An active program will resume when the utility
source has become available again
Scheduler will not run if real time clock has not
been set. Two examples are shown in Figure 4-23.

FIGURE 4-20. SCHEDULER SCREEN

5-23
PRELIMINARY

Example 1: This illustrates an example that must be avoided.


Program 1
Program 1 runs for its entire duration.
Program 2 Program 2 does not run.

Example 2: This illustrates an acceptable example of two programs with a break between them.
Program 1 Program 2 Program 1 runs and ends. Some time
later, Program 2 runs and ends.
Example 2: This illustrates an acceptable example of two programs without a break between them.
Program 1 Program 2 Program 1 runs and ends. Program 2
starts immediately after Program 1 ends.

FIGURE 4-21. PROGRAM EXAMPLES

Example 1: This illustrates when the program will not run because of when the exception is set up.
Program 1
Program 1 does not run.
Exception 1

Example 2: This illustrates when a program will run even though the exception is scheduled during
the program.
Program 1
Program 1 runs and ends. Some time
Exception 1 later, Program 2 runs and ends.

FIGURE 4-22. PROGRAM EXCEPTION EXAMPLES

Example 1: The utility fails while the gensets are running


Program 1 (No Load) with no load due to Program 1. The system
transfers the load to the gensets. When the
Utility utility returns, the system retransfers the
loads to the utility. The gensets then contin-
ue to run until Program 1 ends.
Example 2: The utility fails while the gensets are run-
Program 1 (Extended Parallel) ning in parallel to the utility due to Program
1. The system OPENS the utility main
Utility breaker. When the utility returns, the sys-
tem syncs across the utility main, CLOSES
the utility main, and continues in parallel
until Program 1 ends.

FIGURE 4-23. EXAMPLES OF PRIORITIES

5-24
PRELIMINARY

REAL TIME CLOCK hours without B+ power


• Fault will indicate when clock needs to be set
• Scheduler will not run if real time clock is not • Real Time Clock handles leap year automati-
set cally
• Clock will retain correct time for at least 24 • Daylight Savings Time is fully configurable

FIGURE 4-24. REAL TIME CLOCK SCREEN

5-25
PRELIMINARY

LOAD ADD / LOAD SHED operated circuit breakers. This function provides
Load Add Shed Control manages the load control six Form C outputs for controlling the adding of
devices to maintain proper genset loading while loads and six Form C contacts for controlling the
managing genset overload conditions. The load shedding of loads. These Form C contacts are
control devices can be automatic transfer switches physically located on the SID and Expansion
equipped with load add shed option or electrically Board.

FIGURE 4-25. LOAD ADD / LOAD SHED DIALOG

5-26
PRELIMINARY

6. Operator Panel Operation

LED
INDICATORS
DISPLAY
SCREEN

INFORMATION
SCREEN
BUTTON

OPERATOR MENU PREVIOUS MENU


SELECTION BUTTONS BUTTON

FIGURE 6-1. MCM3320 OPERATOR PANEL

This section describes the operator panel and the The digital display is also used to view the menus
menu system available through the digital display. available in the menu-driven operating system
The menus display status information, events, and and, when appropriate, adjust settings. The bottom
setup menus. The setup menus include parame- of the graphical display indicates the functions that
ters that can be adjusted if the appropriate pass- are available by pressing the four selection but-
word is entered. tons. Refer to the menu trees later in this section.
System messages (communication and fault) are
OPERATOR PANEL shown on the digital display. For more information,
All indicators, control buttons, and the digital dis- see page 6-4.
play are located on the face of the optional control Utility Parallel Indicator
panel. Figure 6-1 shows the features of the front
panel. It includes the graphical digital display, six This green lamp indicates that both sources of
LED indicators, and six buttons used to navigate power (utility and generator) are connected in ex-
through the menus and adjust settings. tended parallel or are in the middle of a soft transi-
tion.
Digital Display
Lockout Indicator
The digital display is used to select the appropriate
information screen for your system topology and to This red lamp indicates that a shutdown fault has
view system status information (see page 6-4). occurred and that the MCM3320 can take no fur-

6-1
PRELIMINARY

ther action until the fault condition has been cor- Auto Indicator
rected.
The Lockout LED is lit whenever one of the follow- This green lamp indicates that the system is in Auto
ing faults occur. Mode.
• The utility breaker fails to close.
Manual Indicator
• The utility breaker fails to open.
• There is a utility breaker position contact fault.
This amber lamp indicates that the system is in
• The genset breaker fails to close. Manual Mode. Manual Mode is for emergency
• The genset breaker fails to open. breaker operation only. When in Manual Mode,
synchronization is not permitted.
• There is a genset breaker position contact
fault.
• There is a failure to synchronize when the Fail
Operator Control Buttons
to Sync feature is enabled.
• There is a maximum parallel time fault. Four momentary (soft-key) buttons are used to
step through the various menu options and to ad-
• There is a genset bus overload fault when ei- just generator set parameters. These selection
ther the Load Demand or the Load Add Shed buttons are “active” when a word or symbol in the
feature is enabled. digital display is displayed above the button. Some
Warning Indicator submenus do not include any active buttons. The
function of the four selection buttons varies with
This amber lamp indicates that a warning fault has each menu.
occurred that has not yet been acknowledged.
Two additional buttons are used to return to the In-
Remote Start Indicator
formation screen or to return to the previous menu.
This green lamp indicates that a remote start com-
mand has been sent from the MCM3320 to the The operator control buttons are described in Table
gensets. 6-1.

6-2
PRELIMINARY

TABLE 6-1. OPERATOR CONTROL NAVIGATION BUTTONS


Symbol Function
Navigate to the previous menu (see Note 1)
Navigate to the next menu (see Note 1)
MENU Return to the Home screen
Navigate to the previous main menu (see Note 2)
Navigate to the Information screen (see Note 2)
SAVE Saves changes made to the current menu
ADJUST Navigate to an menu where values/parameters can be changed. When the ADJUST
button is pressed, the first adjustable parameter or value in the submenu is highlighted.
CTRL Navigate to the associated Control menu
Navigate to an editable field within a menu
− Decrease a parameter or value shown on the screen
+ Increase a parameter or value shown on the screen
VIEW Navigate to the associated viewing menus
RESET Clears all faults
BACK Navigate to associated viewing menu
CAP Navigate to the Capacity Information screen
ADD Add load levels manually
SHED Shed load levels manually
REST Restore shed load levels manually
START Starts an operation on the screen
STOP Stops an operation on the screen
When this black box is displayed, the navigation button has no function.
Some menus include a list of numbered subjects. These menus include numbers in parenthesis (for
example, (1)) displayed above the selection buttons. The selection buttons are then used to display
submenus of the subjects included in the list.
Note 1: Only the symbol is displayed in the first submenu of the series and only the symbol is
displayed in the last submenu of the series. Both symbols are displayed in the rest of the
submenus.
Note 2: If you have made changes to the settings within a menu and this button is pressed before
the SAVE button is pressed, the changes will not be saved.

6-3
PRELIMINARY

OPERATOR PANEL SYSTEM MESSAGES If either communication message remains dis-


played (cannot view other menus), this is an in-
A system pop-up message is displayed when the dication that communications between the op-
event it is displaying becomes active. These pop- erator panel and the control logic is lost. Con-
up messages remain displayed until pre-empted tact an authorized service center for service.
by another pop-up message or until the or the
display buttons is pressed or the event has ex- Fault Messages
pired. Once the or the button is pressed, the A Fault message is an indicator of a Warning or
previous screen is redisplayed. Shutdown condition that is also announced with a
lamp indicator. Text fault messages include the
Communication Messages fault code number and a short description.
System messages are displayed for initial power-
up or when there is a subsequent loss of commu-
nications. Auto and Manual Run modes can also
be selected when communication messages are
displayed (for more information, see page ).
Upon initial power-up, the message “Establishing
communication with control” is displayed (see Fig-
ure 6-2). This menu also displays the screen’s soft-
ware number and version. FIGURE 6-4. FAULT MESSAGE

INFORMATION SCREENS
The MCM3320 includes an information screen that
shows the current system status and any timer that
is currently running. This screen is displayed when-
ever the button is pressed.

Screen Operation
FIGURE 6-2. ESTABLISHING COMMUNICATIONS
Under normal conditions, the information (home)
MESSAGE
screen shows the system in standby mode. This
screen provides information in a one-line format
When the display detects that it is no longer com- relevant to the current system operating state, in-
municating with the control, the Shutdown, Warn- cluding source availability, source connected sta-
ing, and Remote Start LEDs are turned off. tus, voltage, frequency, and power data.
If communications are lost, the message “Re-es- Two soft-key buttons are available when the infor-
tablishing communication with control” is displayed mation screen is displayed. The Menu button al-
until communications have been re-established lows you to access the MCM3320 menu system
(see Figure 6-3). The LEDs then return to the state (see page 6-8). The Reset button allows you to re-
determined by the control. set any active faults.

System Topology
The information that is displayed is dependant
upon the system topology. The system topology is
the primary setting and must be set before making
any other adjustments. It defines the breaker con-
figuration and is not expected to be changed very
often, if ever.
FIGURE 6-3. RE-ESTABLISHING The system topology can only be set when the
COMMUNICATIONS MESSAGE Auto / Manual switch is in the Manual position.

6-4
PRELIMINARY

The system topology can be changed if your instal- Isolated Bus With or Without GM System
lation includes a second keypad display. Once the Topology
display knows what is the current system topology,
the Adjust System submenu can be used to If the system topology is set for either Isolated Bus
change it (see Figure 6-47). InPower can also be W/O GM or Isolated Bus W/GM, the Information
used to change the system topology. screen shown in Figure 6-6 is displayed. This
screen includes the following:
The system topology can be set to:
• The top line displays the system state.
• Master Synchronizer Only (default setting) • The generator circuit breaker position status:
• Isolated Bus with GM If the symbol is down, the circuit breaker is
closed. If the symbol is up, the circuit breaker
• Isolated Bus Without GM is open.
• Common Bus • The symbol shows the Genset Availability
Status. A “1” below this symbol indicates that
• Transfer Pair
generator power is available and a “0” indi-
Master Synchronizer Only System cates that it is not available.
Topology • If the Genset Available Status is available and
the generator circuit breaker is closed, then
If the system topology is set for Master Synchroniz-
the L-L average VAC is displayed. Otherwise
er Only, the Information screen shown in Figure 6-5
no VAC value is displayed.
is displayed. This screen includes the following:
• If a VAC value is displayed, then the AC Meter
• The top line displays the system state. System Total kW is also displayed.
• The symbol shows the Utility Availability • Pressing the Menu button takes you to the
Status. A “1” below this symbol indicates that main menu.
utility power is available and a “0” indicates • Pressing the Reset button clears the current
utility power is not available. fault.
• The symbol shows the Sync Status. A “1”
below this symbol indicates that synchroniza-
tion is on and a “0” indicates synchronization
is not on.
• The symbol shows the Genset Availability
Status. A “1” below this symbol indicates that
genset power is available and a “0” indicates
genset power is not available. FIGURE 6-6. INFORMATION SCREEN FOR
• Pressing the Menu button takes you to the ISOLATED BUS WITH OR WITHOUT GM
main menu.
Common Bus or Transfer Pair System
• Pressing the Reset button clears the current
fault. Topology
If the system topology is set for either Common Bus
or Transfer Pair, one of four different Information
screens can be displayed, depending on how the
Home screen parameter is set. This parameter can
be set to:
• Default
• No Source or Synchronizer
• Timers
FIGURE 6-5. INFORMATION SCREEN FOR
MASTER SYNCHRONIZER ONLY • Parallel

6-5
PRELIMINARY

Default Home Screen No Source or Synchronizer Home Screen


If the Home screen is set to Default, the screen If the Home screen is set to No Source or Synchro-
shown in Figure 6-7 is displayed. This screen in- nizer, the screen shown in Figure 6-8 is displayed.
cludes the following: This screen includes the following:
• The top line displays the system state.
• The top line displays the system state.
• The symbol shows the Utility Availability
Status. A “1” above this symbol indicates that • The symbol shows the Utility Availability
utility power is available and a “0” indicates Status. A “1” above this symbol indicates that
utility power is not available. utility power is available and a “0” indicates
utility power is not available.
• The Generator circuit breaker position status:
If the symbol is down, the circuit breaker is • The Generator circuit breaker position status:
closed. If the symbol is up, the circuit breaker If the symbol is down, the circuit breaker is
is open. closed. If the symbol is up, the circuit breaker
• The Utility circuit breaker position status: If the is open.
symbol is down, the circuit breaker is • The Utility circuit breaker position status: If the
closed. If the symbol is up, the circuit breaker symbol is down, the circuit breaker is
is open. closed. If the symbol is up, the circuit breaker
• The symbol shows the Genset Availability is open.
Status. A “1” above this symbol indicates that • The symbol shows the Genset Availability
genset power is available and a “0” indicates Status. A “1” above this symbol indicates that
genset power is not available. genset power is available and a “0” indicates
• If the Utility Available Status is available and genset power is not available.
the utility circuit breaker is closed, then the L-L
average voltage and the utility frequency is • The utility L-L average voltage and utility fre-
displayed. Otherwise no voltage value or utility quency is displayed on beneath the Utility
frequency is displayed. symbol.

• If the Genset Available Status is available and • The generator L-L average voltage and gener-
the generator circuit breaker is closed, then ator frequency is displayed beneath the Gen-
the L-L average voltage and the genset fre- erator symbol.
quency is displayed. Otherwise no voltage val- • The synchronizer phase differential degrees is
ue or genset frequency is displayed. displayed near the bottom center of the
• If the average voltage is displayed, then the screen.
AC Meter System Total kW and the System To-
tal PF values are also displayed. • Pressing the Menu button takes you to the
main menu.
• Pressing the Menu button takes you to the
main menu. • Pressing the Reset button resets the control
after a fault condition is acknowledged.
• Pressing the Reset button resets the control
after a fault condition is acknowledged.

FIGURE 6-8. NO SOURCE OR SYNCHRONIZER


FIGURE 6-7. DEFAULT HOME INFORMATION HOME INFORMATION SCREEN FOR COMMON
SCREEN FOR COMMON BUS OR TRANSFER PAIR BUS OR TRANSFER PAIR

6-6
PRELIMINARY

Timers Home Screen Parallel Home Screen


If the Home screen is set to Timers, the screen
shown in Figure 6-9 is displayed. This screen in- If the Home screen is set to Parallel, the screen
cludes the following: shown in Figure 6-10 is displayed. This screen in-
• The top line displays the system state. cludes the following:
• A countdown of any active timer is displayed
next to the system state. • The top line displays the system state.
• The symbol shows the Utility Availability • The symbol shows the Utility Availability
Status. A “1” above this symbol indicates that Status. A “1” above this symbol indicates that
utility power is available and a “0” indicates utility power is available and a “0” indicates
utility power is not available. utility power is not available.
• The Generator circuit breaker position status:
If the symbol is down, the circuit breaker is • The Generator circuit breaker position status:
closed. If the symbol is up, the circuit breaker If the symbol is down, the circuit breaker is
is open. closed. If the symbol is up, the circuit breaker
• The Utility circuit breaker position status: If the is open.
symbol is down, the circuit breaker is • The Utility circuit breaker position status: If the
closed. If the symbol is up, the circuit breaker symbol is down, the circuit breaker is
is open. closed. If the symbol is up, the circuit breaker
• The symbol shows the Genset Availability is open.
Status. A “1” above this symbol indicates that
genset power is available and a “0” indicates • The symbol shows the Genset Availability
genset power is not available. Status. A “1” above this symbol indicates that
• If the Utility Available Status is available and genset power is available and a “0” indicates
the utility circuit breaker is closed, then the L-L genset power is not available.
average voltage and the utility frequency is
displayed. Otherwise no voltage value or utility • The utility L-L average voltage and AC Meter
frequency is displayed. utility power total kW is displayed on beneath
the Utility symbol.
• If the Genset Available Status is available and
the generator circuit breaker is closed, then • The generator frequency and AC Meter gener-
the L-L average voltage and the genset fre- ator power total kW is displayed beneath the
quency is displayed. Otherwise no voltage val- Generator symbol.
ue or genset frequency is displayed.
• If the average voltage is displayed, then the • Pressing the Menu button takes you to the
AC Meter System Total kW and the System To- main menu.
tal PF values are also displayed.
• Pressing the Reset button resets the control
• Pressing the Menu button takes you to the after a fault condition is acknowledged.
main menu.
• Pressing the Reset button resets the control
after a fault condition is acknowledged.

FIGURE 6-10. PARALLEL HOME INFORMATION


FIGURE 6-9. TIMERS HOME INFORMATION SCREEN FOR COMMON BUS OR TRANSFER PAIR
SCREEN FOR COMMON BUS OR TRANSFER PAIR

6-7
PRELIMINARY

MCM3320 MENU SYSTEM OVERVIEW Monitor Menus


The MCM3320 menu system can be accessed by The Monitor menus provide an organized access
pressing the Menu button on the home screen. Af- to all controller data.
ter entering the menu system, press the button The Monitor menus are available by pressing the
at any time to return to the Home screen. Whenev- (3) button on the Main menu. The Monitor menus
er you are viewing a submenu, press the button include the following 17 categories.
to return to the previous main menu. • AC Meter
The Main menu provides access access to five ma- • Analog In
jor categories of menus listed below (see Figure • Analog Out
6-11). • Breakers
Control Menus • communication
• PTC
The Control menus provide for viewing and, when
appropriate, allow adjustment of relevant operat- • Load Control
ing setpoints. • Priority
• Relay Outputs
The Control menus are available by pressing the
(1) button on the Main menu. The Control menus • Switch Inputs
include the following 4 categories. • Sync Check
• Test • Synchronizer
• System Status
• Extended Paralleling
• Load Demand
• Load Demand
• Load Add Shed
• Load Add and Load Shed
• Generator Bus Overload
Adjust Menus • Scheduler
The Adjust menus allow complete configuration, Faults Menus
setup, and fine-turning of the controller settings.
Pop-up diagnostic messages are displayed when
The Adjust menus are available by pressing the (2) they occur and can be acknowledged with a single
button on the Main menu. The Adjust menus in- button. In addition to any current message, histori-
clude the following 15 categories. cal information on faults and events can be viewed
• AC Meter Adjust with the Faults menus.
• AC Meter Setup The Faults menus are available by pressing the (4)
button on the Main menu. The Monitor menus in-
• Breakers
clude the following 6 categories.
• Communication
• Current Fault
• Configuration Output
• Active Event Table
• Load Control
• Event Occurrence Table
• PTC • Active Fault Table
• Sync Check • Fault History
• Sync Adjust • Fault Occurrence Table
• System
About Menu
• Scheduler
The About menus are available by pressing the (5)
• LCD Display
button on the Main menu (see Figure 6-11).
• Load Demand
The first menu displays the software version and
• Load Add / Load Shed the calibration part number. The second menu dis-
• Generator Bus Overload plays the controller on-time value.

6-8
PRELIMINARY

MAIN MENU AND SUBMENUS

MONITOR MENUS
SEE PAGE 6-107

ADJUST MENUS
SEE PAGE 6-31

FAULTS MENUS
SEE PAGE 6-153

CONTROL MENUS
SEE PAGE 6-13

FIGURE 6-11. MAIN MENU AND SUBMENUS

6-9
PRELIMINARY

CONTROL MENUS The Control menus include one level of security. If


the correct password in not entered, the Control
The Control menus are available by pressing the menus can be viewed but not changed.
(1) button on the Main menu (see Figure 6-11).
Control menus can be viewed and, if the correct Viewing Only
password is entered, values/parameters on these
menus can be changed. Figure 6-12 is a block representation of the Control
menus that are available when a password is not
The Control menus are used to initiate a test, ex- entered (or an incorrect password is entered) in the
tended parallel, load demand, and load add/load Enter Password menu.
shed operations. These menus can also be used to
To only view these menus, press the VIEW button
make adjustments for relevant operating setpoints.
in the Enter Password menu. The word “View” ap-
The Control menu provides access to the following pears at the top of the five available submenus.
submenus: When the VIEW button is selected without entering
the correct password, the ADJUST button is not
• Test displayed on any of the subsequent menus; there-
• Extended Parallel fore, no adjustments can be made.
• Load Demand
• Load Add/Load Shed

6-10
PRELIMINARY

CONTROL MENUS − VIEWING ONLY

CONTROL TEST CONTROL EXTENDED CONTROL LOAD CONTROL LOAD ADD/


MENUS PARALLELING MENUS DEMAND MENUS LOAD SHED MENUS
SEE FIGURE 6-14 SEE FIGURE 6-15 SEE FIGURE 6-18 SEE FIGURE 6-19

FIGURE 6-12. CONTROL MENUS − VIEWING ONLY

6-11
PRELIMINARY

Viewing and Adjusting 5. Press the button below the + or − symbols until
the value reads “4.”
Figure 6-13 is a block representation of the Control
menus that are available from the Main Menu after 6. After you have completed entering the pass-
the correct password has been entered. The AD- word, press the arrow selection button .
JUST button is available on these submenus; The first main Setup menu is displayed.
therefore, adjusting the settings is allowed. Once the correct password is entered, the word
Enter Password Menu “Adjust” appears on all submenus with adjustable
values.
Changing the Control menus is restricted to service
personnel and a password must be entered to NOTE: The password timer expires after 15 min-
modify these menus. utes of button inactivity.

When the Enter Password menu is displayed, the Adjusting Values/Parameters


first numeric character (0) is highlighted (see Fig-
ure 6-13). Once the correct password has been entered, ad-
justable values/parameters can be changed.
NOTE: When selected (highlighted), each charac-
ter initially turns to “0” and the remaining 1. Press the buttons above the and sym-
characters turn to “X”. bols in the digital display to navigate between
submenus.
NOTE: Make sure that each numeric character is
correct before you move to the next char- 2. Press the ADJUST selection button to select
acter. If a wrong character is entered, you the first parameter or value to be changed.
will not be able to go back and correct it.
3. Press the + or − selection buttons to adjust val-
You will not be notified if a wrong password
ues or select parameters.
is entered. Instead, the word VIEW will be
displayed instead of ADJUST. 4. Press the arrow selection button to navi-
To enter the password: gate to the next or previous adjustable value
or parameter.
1. With the first character highlighted, press the
button below to the + or − symbols until the val- 5. After adjusting values/selecting parameters,
ue reads “5.” press the SAVE button to save your settings.
2. Press the arrow selection button to move
to the next numeric character. NOTE: If the button is pressed before
pressing the SAVE button, the
3. Press the button below the + or − symbols until changes are not saved.
the value reads “7.”
4. Press the arrow selection button to move 6. Press the button to return to the previous
to the next numeric character. Menu.

6-12
PRELIMINARY

CONTROL MENUS − ADJUSTING AND VIEWING

ENTER THE
PASSWORD “574”

CONTROL TEST CONTROL EXTENDED CONTROL LOAD CONTROL LOAD ADD/


MENUS PARALLELING MENUS DEMAND MENUS LOAD SHED MENUS
SEE FIGURE 6-14 SEE FIGURE 6-15 SEE FIGURE 6-18 SEE FIGURE 6-19

FIGURE 6-13. CONTROL MENUS − VIEWING AND ADJUSTING

6-13
PRELIMINARY

Control Test Submenus The Test Start/Stop submenu displays the informa-
tion included in the Test Settings submenu.
The Control Test submenus are available by press-
1. Before starting a test, verify that these settings
ing the (1) button on the Test menu (see Figure
are correct. To start a test, press the START
6-14).
button. The message “Confirm?” is displayed.
The Control Test submenus include menus for 2. To confirm that you want the test to start, press
starting and stopping a test, for selecting the transi- the YES button. The Test Start/Stop menu is
tion type, and for selecting to test with or without redisplayed with the STOP button activated.
load.
3. Press the STOP button to stop the test.
The Control Test submenu provides access to the
following submenus: Test Settings Submenu

• Test Start/Stop The Test Settings submenu is available by press-


ing the (2) button on the Control Test submenu.
• Test Settings
• Transition Type: The transition type can be set
Test Start/Stop Submenus to Open Transition, Hard Closed Trans, or Soft
Closed Trans (default = ____________).
The Test Start/Stop submenus are available by • Test With Load: The Test With Load feature
pressing the (1) button on the Control Test subme- can be Enabled or Disabled (default = Dis-
nu. abled).

6-14
PRELIMINARY

CONTROL TEST MENUS

FIGURE 6-14. CONTROL TEST SUBMENUS

6-15
PRELIMINARY

Control Extended Paralleling Submenus 1. Before starting extended paralleling, verify


that these settings are correct. These settings
The Control Extended Paralleling submenus are can be adjusted using the kVAR Control Ex-
available by pressing the (2) button on the Control tend Paralleling submenus (see Figure 6-17).
menu (see Figure 6-15).
2. To start extended paralleling, press the
The Control Extended paralleling submenu pro-
START button. The message “Confirm?” is
vides access to the following submenus:
displayed.
• Extended Paralleling Start/Stop
3. To confirm that you want extended paralleling
• Extended Paralleling Settings to start, press the YES button. The ExtPar
Extended Paralleling Start/Stop Submenus Start/Stop menu is redisplayed with the STOP
button activated.
The Extended Paralleling Start/Stop submenus
are available by pressing the (1) button on the Con- 4. Press the STOP button to terminate this func-
trol Extended Paralleling submenu. tion.

6-16
PRELIMINARY

CONTROL EXTENDED
PARALLELING SUBMENUS

A B
kW CONTROL MENUS kVAR CONTROL MENUS
(SEE FIGURE 6-16) (SEE FIGURE 6-17)

FIGURE 6-15. CONTROL EXTENDED PARALLELING SUBMENUS

6-17
PRELIMINARY

Extended Paralleling Settings Submenu it reduces this setpoint to keep the kW at the
Utility Main (UM) above a programmed level.
The Extended Paralleling Settings submenu is This can be used to prevent tripping of a UM
available by pressing the (2) button on the Control reverse power relay due to load falling below
Extended Paralleling submenu. the GM kW setpoint. Coordination of the set-
The Control Extended Paralleling Settings subme- tings in this controller and the relay (plus an
nu provides access to the following submenus: understanding of the magnitude of load fluc-
tuations) is critical to the successful use of this
• kW Control Settings (see Figure 6-16) feature.
• kVAR Control Settings (see Figure 6-17) This screen shows the utility and genset circuit
breaker positions, the AC meter utility and
To view the kW Control Settings submenus, press
genset total kWs, the utility bus kW constraint
the (1) button. It allows access to the following four
different types of kW controls in extended parallel. level, and the genset bus kW setpoint. The
genset bus setpoint can be adjusted from
• Genset Bus % Level (Open Loop): This is the −32768 to 32767 kW.
default setting. When this type of extended
paralleling is selected, the MCM3320 pro- • Utility Bus kW (Closed Loop): The MCM3320
duces a user-adjustable percent level for the drives the kW control output to achieve the de-
kW control output. The genset bus kW value sired kW setpoint at the UM. If the setpoint is
displayed is the total of the online gensets − it not reached with a preset time period, a warn-
is an open loop on the kW at the Genset Main ing fault occurs.
(GM). This screen shows the utility and genset circuit
This screen shows the utility and genset circuit breaker positions, the AC meter utility and
breaker positions, the AC meter utility and genset total kWs, and the utility bus kW set-
genset power total kW, and the genset bus point. The genset bus setpoint can be ad-
percentage kW setpoint. The kW control out- justed from −32768 to 32767 kW.
put level can be adjusted from −.05 to 105 per- To select a specific kW Control screen,
cent.
1. Press the ADJUST button.
• Genset Bus kW (Closed Loop): The MCM3320
drives the kW control to achieve the desired 2. Use the + or − buttons to scroll through the
kW setpoint at the GM. If the setpoint cannot available screens.
be achieved within a preset time period, a
warning fault occurs. To change kW values,
This screen shows the utility and genset circuit 1. Press the ADJUST button.
breaker positions, the AC meter utility and
genset total kW, and the genset bus kW set- 2. Press the to navigate to the value you wish
point. The genset bus setpoint can be ad- to change.
justed from 00000 to 32767 kW.
3. Use the + or − buttons to increase or decrease
• Genset kW w/Util Const (Closed Loop): The the highlighted value.
MCM3320 drives the kW control output to
achieve the desired kW setpoint at the GM, but 4. Press the SAVE button to save your settings.

6-18
PRELIMINARY

kW CONTROL EXTENDED PARALLELING SUBMENUS


A

FIGURE 6-16. kW CONTROL EXTENDED PARALLELING SUBMENUS

6-19
PRELIMINARY

To view the kVAR Control Settings submenus, If the setpoint is not reached within a preset
press the (2) button on the Control Extended Par- time period, a warning fault occurs.
alleling Settings submenu.
This screen shows the utility and genset circuit
• Genset Controls (Information Only): This is breaker positions, the AC meter utility and
the default setting. With this setup, the genset total kVARs, and the genset bus kVAR
MCM3320 performs no action. The kVAR con- setpoint. The genset bus setpoint can be ad-
trol output is zero. The genset controllers man- justed from 00000 to 32767 kVAR.
age the kVAR control base on their own set- • Genset Bus PF (Closed Loop): The
tings (for example, a fixed power factor of MCM3320 drives the output to achieve the de-
0.95). sired PF at the GM. If the setpoint is not
This screen shows the utility and genset reached within a preset time period, a warning
breaker positions and the AC meter utility and fault occurs.
genset power total kVAR. This screen shows the utility and genset circuit
breaker positions, the AC meter utility and
• Genset Bus % Level (Open Loop): The
genset total power factor (PF), and the genset
MCM3320 sends out a user-adjustable per-
bus power factor setpoint. The setpoint can be
cent level on the kVAR control output. The
adjusted from 0.70 to 1.00.
genset bus kVAR value displayed is the result
of whatever gensets happen to be online. • Utility Bus kVAR (Closed Loop): The
MCM3320 drives the kVAR control output to
This screen shows the utility and genset circuit
achieve the desired kVAR at the UM. If the set-
breaker positions, the AC meter utility and
point is not reached within a preset time peri-
genset total kVARs, and the genset bus per-
od, a warning fault occurs.
centage kVAR setpoint. The kVAR control out-
put level can be adjusted from −.05 to 105 per- This screen shows the utility and genset circuit
cent. breaker positions, the AC meter utility and
genset total kVARs, and the utility bus kVAR
• Genset Bus PF (Open Loop): The MCM3320 setpoint. The genset bus setpoint can be ad-
sends a reading to the kVAR control output justed from −32768 to 32767 kVAR.
based on the current kW control output. the
relationship of these two is determined by the • Utility Bus PF (Closed Loop): The MCM3320
power factor (PF) setting. drives the kVAR control output to achieve the
desired power factor (PF) setpoint at the utility
This screen shows the utility and genset circuit main (UM). If the setpoint is not reached within
breaker positions, the AC meter utility and a preset time period, a warning fault occurs.
genset total power factor (PF), and the genset
bus power factor setpoint. The setpoint can be The Utility Bus Power Factor screen shows the
adjusted from 0.70 to 1.00. utility and genset circuit breaker positions, the
AC meter utility and genset total power factor
• Genset Bus kVAR (Closed Loop): The (PF), and the utility bus power factor setpoint.
MCM3320 drives the kVAR control output to The setpoint can be adjusted from 0.70 to
achieve the desired kVAR setpoint at the GM. 1.00.

6-20
PRELIMINARY

kVAR CONTROL EXTENDED PARALLELING SUBMENUS

kVAR OPTIONS
(SEE PAGE 6-21)

FIGURE 6-17. kVAR CONTROL EXTENDED PARALLELING SUBMENUS (SHEET 1 OF 2)

6-21
PRELIMINARY

To select a specific kVAR Control screen, 1. Press the ADJUST button.

1. Press the ADJUST button. 2. Press the to navigate to the value you wish
to change.
2. Use the + or − buttons to scroll through the 3. Use the + or − buttons to increase or decrease
available screens. the highlighted value.

To change kVAR values, 4. Press the SAVE button to save your settings.

6-22
PRELIMINARY

kVAR CONTROL EXTENDED PARALLELING SUBMENUS

FIGURE 6-17. kVAR CONTROL EXTENDED PARALLELING SUBMENUS (SHEET 2 OF 2)

6-23
PRELIMINARY

Load Demand Submenus 3. Use the + or − buttons to change the genset


order.
The Control Load Demand submenus are avail-
able by pressing the (3) button on the Control menu 4. Press the SAVE button to save your settings.
(see Figure 6-18). Load Demand: Genset Run Hours Menu
Control Load Demand Menu NOTE: This menu is displayed when the Load De-
• Ld Enable:The Load Demand feature can be mand Type is set to “None” or “Run Hours.”
Enabled or Disabled (default = Disabled). This menu shows the order, as set by the operator,
• Ld Type: The Load Type can be set to None, in which the gensets are shut down and restarted.
Fixed Sequence, or Run Hours (default = In the example shown in Figure 6-18, genset D is
None). the first to shut down, followed by genset C, then B,
and finally A. The gensets are restarted in the op-
Load Demand: Generator Status Menu posite order (A, B, C, D). The HRS column indi-
This menu provides status information only for up cates how many hours each genset has been run-
to four generators. The status displayed can be ning. This number is reset to zero when a genset
one of the following. shuts down.

• Offline − The control has sent a STOP signal To change hours of the gensets,
to the genset and has shut down or is in the 1. Press the ADJUST button. The first generator
process of shutting down. in the HRS column is highlighted.
• Online − The genset is running or has been 2. Press the to scroll through the HRS en-
signaled to run. tries.
• Waiting − The genset has been signaled to run 3. Use the + or − buttons to change the values.
and the system is waiting for it to come online.
4. Press the SAVE button to save your settings.
• Failed − The genset was signaled to run by the
control but it done not come online within a Load Demand: Next Genset Start-Up/Shut-
specified time period. Down Status Menu
• NoExist − The genset is not part of the system This information-only menu provides information
(does not exist). For example, if your installa- on the next genset designated to shut down, the
tion includes three gensets, genset #4 would next genset designated to restart, and how much
be displayed as “NoExist.” power (in kW) the gensets are currently providing.
The Load (LD) column indicates whether or not the
• The Off generator is the next genset desig-
genset is running (”Run” or “Stop”).
nated to shut down. If a genset is identified in
Load Demand: Genset Fixed Sequence Menu the Off row, the threshold (THRESH) column
displays the kW value that the genset total
NOTE: This menu is displayed when the Load De- (Gen Tot) must drop below for the generator
mand Type is set to “None” or “Fixed Se- (in this example, gen 2) to stop, following the
quence.” shutdown time delay.
This menu shows the order, as set by the operator, • The On generator is the next genset desig-
in which gensets are shut down and restated. In the nated to restart. If a genset is designated in the
example shown in Figure 6-18, genset D is the first On row, the threshold (THRESH) column dis-
to shut down, followed by genset C, then B, and fi- plays the kW value that the genset total (Gen
nally A. The gensets are restarted in the opposite Tot) must go above for the generator to receive
order (A, B, C, D). a run command.
To change the shut down and restart sequence, • The Gen Tot value indicated how much power
(in kW) the gensets are currently providing.
1. Press the ADJUST button. The first generator
in the NEW column is highlighted. Load Demand: Capacity Menu
2. Press the to scroll through the list of NEW This information-only menu shows the total online
gensets. capacity and the total spare online capacity.

6-24
PRELIMINARY

CONTROL LOAD DEMAND SUBMENUS


NOTE: If “Ld Type” is set to “Run Hours,” the “Gen
Now New” screen is not available.
If “Ld Type” is set to “Fixed Sequence Adjust,”
the “Gen Now Hrs” screen is not available.

FIGURE 6-18. CONTROL LOAD DEMAND SUBMENUS

6-25
PRELIMINARY

Control Load Add Shed Submenus NOTE: The CTRL button is only displayed if the
Load Add Shed Control is set to “Manual.”
The Control Load Add Shed submenus are avail-
able by pressing the (4) button on the Control menu
To modify the Add status of each level, press the
(see Figure 6-19).
CTRL button. Level 1 through Level 6 can be set to
Six levels of load add shed are possible. The load Add or Off.
add shed level must be set for each distribution de-
vice at the System Control screen. Level 1 Add is 1. Press the to scroll to select an add level.
the first load connected to the bus and Level 6 Add 2. Press the Add button to add the loads on that
is the last load connected to the bus. Level 1 shed is level.
the first load that is shed from the bus and Level 6
Shed is the last load that is shed from from the bus. To view the total online capacity and the total spare
Load 0 Shed is never shed from the system. online capacity, press the CAP button.
Loads are added to the system automatically Shed Levels Menu
based upon the number of gensets online. If all
gensets are successfully running on the bus, the
system automatically continues adding loads up to The Shed Levels menu allows you to set the six
Level 6 or until a bus overload occurs. shed levels to Shed or Off (default = Off).

If the genset capacity is sufficiently greater that the NOTE: The CTRL button is only displayed if the
loads added, additional loads can be added. If a Load Add Shed Control is set to “Manual.”
load is shed due to insufficient system capacity,it
can be restored manually by using the Restore To modify the Shed status of each level, press the
buttons. CTRL button. Level 0 through Level 5 can be set to
Shed or Off.
Load Add Shed Control Menu
1. Press the to scroll to select a shed level.
• Load Add Shed Control: The control can be set
for Manual or Auto(matic) load add restore op- 2. Press the Shed button to shed the loads on
eration (default = Auto). that level.
To change the Load Add Shed Control,
NOTE: Level 0 can never be set to shed load. It
1. Press the ADJUST button. The first generator cannot be selected and is always set to
in the HRS column is highlighted. “Off.”
2. Use the + or − buttons to toggle between Auto
and Manual. Capacity Menu
3. Press the SAVE button to save your settings.
To view the total online capacity and the total spare
NOTE: If this function is set to “Manual,” a CTRL online capacity, press the CAP button on either the
button is displayed in the Add Levels and Add Levels or the Shed Levels menu.
Shed Levels menus.
• Total Online Cap: This shows the total online
Add Levels Menu capacity.
The Add Levels menu allows you to set the six add • Spare Online Cap: The shows the total spare
levels to Add or Off (default = Off). online capacity.

6-26
PRELIMINARY

CONTROL LOAD ADD SHED SUBMENUS

NOTE: The CTRL button is only


available when the Load
Add Shed Control is set
to “Manual.”

FIGURE 6-19. CONTROL LOAD ADD SHED SUBMENUS

6-27
PRELIMINARY

ADJUST MENUS Viewing Only


The Adjust menus are available by pressing the (2) Figure 6-20 is a block representation of the Adjust
button on the Main menu (see Figure 6-11). These menus that are available when a password is not
menus can be viewed and, if the correct password entered (or an incorrect password is entered) in the
is entered, values/parameters on these menus can Adjust Password menu.
be changed.
The Adjust menus are used to configure, set up, To only view these menus, press the VIEW button
and fine-tune the controller settings. in the Adjust Password menu. The word “View” ap-
pears at the top of the five available submenus.
The first Adjust menu provides access to the fol-
lowing submenus: When the VIEW button is selected without entering
the correct password, the ADJUST button is not
• AC Meter Adjust displayed on any of the subsequent menus; there-
• AC Meter Setup fore, no adjustments can be made.
• Breakers Menu Navigation
The second Adjust menu provides access to the
following submenus: 1. Press the buttons above the and sym-
• Communication bols in the digital display to navigate between
submenus.
• Configuration Output
• Load Control 2. To return to the main View menu from any of
The third Adjust menu provides access to the fol- the submenus, press the button.
lowing submenus:
3. To return to the Information screen from the
• PTC
Adjust menu, press the button.
• Sync Check
• Sync Adjust
The fourth Adjust menu provides access to the fol-
lowing submenus:
• System
• Scheduler
• LCD Display
The fifth Adjust menu provides access to the fol-
lowing submenus:
• Load Demand
• Load Add / Load Shed
• Generator Bus Overload

6-28
PRELIMINARY

ADJUST MENUS − VIEW ONLY

SEE PAGE 6-33


SEE PAGE 6-35
SEE PAGE 6-39

SEE PAGE 6-41


SEE PAGE 6-43
SEE PAGE 6-45

SEE PAGE 6-57


SEE PAGE 6-75
SEE PAGE 6-79

SEE PAGE 6-85


SEE PAGE 6-91
SEE PAGE 6-97

SEE PAGE 6-99


SEE PAGE 6-101
SEE PAGE 6-105

FIGURE 6-20. ADJUST MENUS − VIEW ONLY

6-29
PRELIMINARY

Viewing and Adjusting 5. Press the button below the + or − symbols until
the value reads “4.”
Figure 6-21 is a block representation of the Adjust
menus that are available from the Main Menu after 6. After you have completed entering the pass-
the correct password has been entered. The AD- word, press the arrow selection button .
JUST button is available on these submenus; The first main Setup menu is displayed.
therefore, adjusting the settings is allowed. Once the correct password is entered, the word
“Adjust” appears at the top of the five available sub-
Setup Password Menu
menus.
Changing the Adjust menus is restricted to service
NOTE: The password timer expires after 15 min-
personnel and a password must be entered to
utes of button inactivity.
modify these menus.
When the Password menu is displayed, the first nu- Adjusting Values/Parameters
meric character (0) is highlighted (see Figure Once the correct password has been entered and
6-21). one of the Adjust categories of menus is selected,
NOTE: When selected (highlighted), each charac- the desired parameters can be changed.
ter initially turns to “0” and the remaining 1. Press the buttons above the and sym-
characters turn to “X”. bols in the digital display to navigate between
submenus.
NOTE: Make sure that each numeric character is
correct before you move to the next char- 2. Press the ADJUST selection button to select
acter. If a wrong character is entered, you the first parameter or value to be changed.
will not be able to go back and correct it. If
the wrong password is entered, you will be 3. Press the + or − selection buttons to adjust val-
able to view the Adjust menus but you ues or select parameters.
won’t be able to change them.
4. Press the arrow selection button to navi-
To enter the password: gate to the next or previous adjustable value
or parameter.
1. With the first character highlighted, press the
button below to the + or − symbols until the val- 5. After adjusting values/selecting parameters,
ue reads “5.” press the SAVE button to save your settings.
2. Press the arrow selection button to move
to the next numeric character. NOTE: If the button is pressed before
pressing the SAVE button, the
3. Press the button below the + or − symbols until
changes are not saved.
the value reads “7.”
4. Press the arrow selection button to move 6. Press the button to return to the Previous
to the next numeric character. Menu.

6-30
PRELIMINARY

ADJUST MENUS − VIEW AND ADJUST

ENTER THE
PASSWORD “574”

SEE PAGE 6-33


SEE PAGE 6-35
SEE PAGE 6-39

SEE PAGE 6-41


SEE PAGE 6-43
SEE PAGE 6-45

SEE PAGE 6-57


SEE PAGE 6-75
SEE PAGE 6-79

SEE PAGE 6-85


SEE PAGE 6-91
SEE PAGE 6-97

SEE PAGE 6-99


SEE PAGE 6-101
SEE PAGE 6-105

FIGURE 6-21. ADJUST MENUS − VIEW AND ADJUST

6-31
PRELIMINARY

AC Meter Adjustment Submenus • L1: The Genset L1 Current Adjustment can be


set from −1 to +1 amps.
The AC Meter Adjustment submenus are available
by pressing the (1) button on the first Adjust menu • L2: The Genset L2 Current Adjustment can be
(see Figure 6-22). set from −1 to +1 amps.

The AC Meter Adjustment submenus consist of six • L3: The Genset L3 Current Adjustment can be
basic submenus. set from −1 to +1 amps.

• AC Meter Adjust Genset AC Meter Adjust Utility Submenus


• AC Meter Adjust Utility The AC Meter Adjust Utility menus display
• AC Meter Genset Setup
• L1L2: The Utility L1L2 Voltage Adjustment can
• AC Meter Utility Setup
be set from 0.9 to 1.1 volts.
• Genset Circuit Breakers
• L2L3: The Utility L2L3 Voltage Adjustment can
• Utility Circuit Breakers be set from 0.9 to 1.1 volts.
AC Meter Adjust Genset Submenus • L3L1: The Utility L3L1 Voltage Adjustment can
The AC Meter Adjust Genset menus display be set from 0.9 to 1.1 volts.

• L1L2: The Genset L1L2 Voltage Adjustment • L1: The Utility L1 Current Adjustment can be
can be set from 0.9 to 1.1 volts. set from −1 to +1 amps.

• L2L3: The Genset L2L3 Voltage Adjustment • L2: The Utility L2 Current Adjustment can be
can be set from 0.9 to 1.1 volts. set from −1 to +1 amps.
• L3L1: The Genset L3L1 Voltage Adjustment • L3: The Utility L3 Current Adjustment can be
can be set from 0.9 to 1.1 volts. set from −1 to +1 amps.

6-32
PRELIMINARY

ADJUST AC METER ADJUST SUBMENUS

FIGURE 6-22. ADJUST MENUS − AC METER ADJUST SUBMENUS

6-33
PRELIMINARY

AC Meter Genset Setup Submenus • PT Secondary Volt: The AC Meter Genset PT


Secondary Voltage can be set from 110 to 500
• Connection Type: The AC Meter Genset Con- volts (default = 120 volts).
nection Type can be set to either Wye or Delta
(default = Wye).
• CT Primary Curr: The AC Meter Genset CT
• Nominal Voltage: The AC Meter Genset Nomi- Primary Current can be set from 5 to 10000
nal Voltage can be set from 110 to 45000 volts amps (default = 100 amps).
(default = 480 volts).
• PT Primary Volt: The AC Meter Genset PT Pri- • CT Secondary Curr: The AC Meter Genset CT
mary Voltage can be set from 110 to 45000 Secondary Current can be set to either 1 or 5
volts (default = 480 volts). amps (default = 5 amps).

6-34
PRELIMINARY

ADJUST AC METER GENSET SETUP SUBMENUS

SEE FIGURE 6-24

FIGURE 6-23. ADJUST MENUS − AC METER GENSET SETUP SUBMENUS

6-35
PRELIMINARY

AC Meter Utility Setup Submenus • PT Secondary Volt: The AC Meter Utility PT


Secondary Voltage can be set from 110 to 500
• Connection Type: The AC Meter Utility Con- volts (default = 120 volts).
nection Type can be set to either Wye or Delta
(default = Wye).
• CT Primary Curr: The AC Meter Utility CT Pri-
• Nominal Voltage: The AC Meter Utility Nomi- mary Current can be set from 5 to 10000 amps
nal Voltage can be set from 110 to 45000 volts (default = 100 amps).
(default = 480 volts).
• PT Primary Volt: The AC Meter Utility PT Pri- • CT Secondary Curr: The AC Meter Utility CT
mary Voltage can be set from 110 to 45000 Secondary Current can be set to either 1 or 5
volts (default = 480 volts). amps (default = 5 amps).

6-36
PRELIMINARY

ADJUST AC METER UTILITY SETUP SUBMENUS

FIGURE 6-24. ADJUST MENUS − AC METER UTILITY SETUP SUBMENUS

6-37
PRELIMINARY

Genset Circuit Breaker Submenus Utility Circuit Breaker Submenus

• CB Fail to Close Delay: The Circuit Breaker • CB Fail to Close Delay: The Circuit Breaker
Fail to Close Time Delay can be adjusted from Fail to Close Time Delay can be adjusted from
0.1 to 1.0 seconds, in 0.2 second increments 0.1 to 1.0 seconds, in 0.2 second increments
(default = 0.26 second). (default = 0.26 second).
• CB Fail to Open Delay: The Circuit Breaker • CB Fail to Open Delay: The Circuit Breaker
Fail to Open Time Delay can be adjusted from Fail to Open Time Delay can be adjusted from
0.2 to 5.0 seconds, in 0.2 second increments 0.2 to 5.0 seconds, in 0.2 second increments
(default = 1.0 second). (default = 1.0 second).
• CB Recharge Delay: The Circuit Breaker Re- • CB Recharge Delay: The Circuit Breaker Re-
charge Time Delay can be adjusted from 0.0 charge Time Delay can be adjusted from 0.0
to 60.0 seconds, in 0.2 second increments to 60.0 seconds, in 0.2 second increments
(default = 10.0 seconds). (default = 10.0 seconds).
• Breaker Position Contacts: The Circuit Break- • Breaker Position Contacts: The Circuit Break-
er Position Contacts can be set to either Single er Position Contacts can be set to either Single
or Dual (default = __________). or Dual (default = __________).

6-38
PRELIMINARY

ADJUST BREAKERS SUBMENUS

FIGURE 6-25. ADJUST MENUS − BREAKERS SUBMENUS

6-39
PRELIMINARY

Adjust Communications Submenus • Modbus Baud: The ModBus baud rate can be
set to 2400, 4800, 9600, or 19200 (default =
____________).
• Modbus Address: The ModBus Node Address • Modbus Parity: The ModBus parity can be set
can be set from 1 to 247 (default = ________). to Even, Odd, or None (default = _________).

6-40
PRELIMINARY

ADJUST COMMUNICATIONS SUBMENUS

FIGURE 6-26. ADJUST MENUS − COMMUNICATIONS SUBMENUS

6-41
PRELIMINARY

Configuration Output Submenus • Config Output 1 Fault # thru Config Output 8


Fault #: Each of the eight Configuration Output
Fault Codes can be set from 1 thru 65535.
Up to eight Configurable Outputs can be assigned • Start Gensets Relay Active State: The Start
fault codes. In addition, the Start Gensets Relay Gensets Relay Active State can be set to En-
can be energized or deenergized. ergized or Deenergized (default = ________).

6-42
PRELIMINARY

ADJUST CONFIGURATION OUTPUT SUBMENUS

FIGURE 6-27. ADJUST MENUS − CONFIGURATION OUTPUT SUBMENUS

6-43
PRELIMINARY

Adjust Load Control Output Submenus • Load Control Setup (see page 6-47) − In-
cludes miscellaneous, genset, and utility set-
The Adjust Load Control menus are available by up menus.
pressing the (6) button on the Adjust menu (see
Figure 6-28). The Adjust Load Control menu is di- • Load Control Tuning (see page 6-53) − In-
vided into two categories. cludes kW and kVAR tuning menus.

6-44
PRELIMINARY

ADJUST LOAD CONTROL SUBMENUS

ADJUST LOAD CONTROL ADJUST LOAD CONTROL


SETUP MENUS TUNING MENUS
SEE PAGE 6-47 SEE PAGE 6-53

FIGURE 6-28. ADJUST MENUS − LOAD CONTROL SUBMENUS

6-45
PRELIMINARY

Load Control Setup Submenus • Extend Par kVAR Load Cntl Type: This sets
how and where the kVAR will be controlled for
The Load Control Setup Submenus are divided an extended parallel operation. The Extended
into three categories: Paralleling kVAR Load Control Type can be
• Miscellaneous set as Genset Controllers, Genset Bus % Lev-
el − Open Loop, Genset Bus Power Factor −
• Genset Open Loop, Genset Bus kVAR − Closed Loop,
• Utility Genset Bus Power Factor − Closed Loop, Util-
ity Bus kVAR − Closed Loop, or Utility Bus
The Load Control Setup submenus are available
Power Factor − Closed Loop (default = Genset
by pressing the (1) button on the Adj Load Control
Controllers).
menu (see Figure 6-28).
Miscellaneous Load Control Setup Submenus • kW Load Cntl Max % Out: The kW Load Con-
trol Maximum % Output can be adjusted from
The Miscellaneous Load Control Setup submenus 0 to 100 percent, in 0.01% increments (default
are available by pressing the (1) button on the Adj = _________).
Load Setup menu (see Figure 6-29).
• kVAR Ld Cntl Max % Out: The kVAR Load
• Extend Par kW Load Cntl Type: This sets how Control Maximum % Output can be adjusted
and where the kW will be controlled for an ex- from 0 to 60 percent, in 0.01% increments (de-
tended parallel operation. The Extended Par- fault = _________).
alleling kW Load Control Type can be set as
Genset Bus % Level − Open Loop, Genset • Extend Par Ramp Ld Time: This sets the ramp
Bus kW − Closed Loop, Genset Bus kW w/Utl load time for extended paralleling. The Ex-
Constraint − Closed Loop, or Utility Bus kW − tended Parallel Ramp Load Time can be ad-
Closed Loop (default = Genset Bus % Level − justed from 10 to 900 seconds, in 0.1 second
Open Loop). increments (default = 60.0 seconds).

6-46
PRELIMINARY

ADJUST LOAD CONTROL MISCELLANEOUS SETUP SUBMENUS

FIGURE 6-29. ADJUST MENUS − LOAD CONTROL MISCELLANEOUS SETUP SUBMENUS

6-47
PRELIMINARY

Genset Load Control Setup Submenus • kVAR SetPoint: This sets the base load kVAR
setpoint in closed loop extended paralleling.
The Genset Load Control Setup submenus are The Genset Bus kVAR Setpoint can be set
available by pressing the (2) button on the Adj Load from 0 to 32767 kVAR (default = 0 kVAR).
Setup menu (see Figure 6-30).
• Power Factor SetPt: This sets the desired gen-
• kW SetPt Source: This is used to select where set bus power factor in closed loop extended
the genset kW setpoint will come from for ex- paralleling. The Genset Bus Power Factor
tended paralleling. The Genset Bus kW Set- Setpoint can be set from 0.7 to 1.0, in 0.1 incre-
point Source can be set to Analog Input or In- ments (default = 1.00).
ternal (default = Internal). • % kW SetPoint: This sets the %kW genset out-
• kVAR SetPt Source: This is used to select put level for open loop base load extended
where the genset kVAR setpoint will come paralleling. The Genset Bus Percent kW Set-
from for extended paralleling. The Genset Bus point can be set −5 to 105 percent, in 0.01 per-
kVAR Setpoint Source can be set to Analog In- cent increments (default = 80.00%).
put or Internal (default = Internal). • % kVAR SetPoint: This sets the %kVAR gen-
• kW SetPoint: This sets the base load kW set- set output level for open loop base load ex-
point in closed loop extended paralleling. The tended paralleling. The Genset Bus Percent
Genset Bus kW Setpoint can be set from 0 to kVAR Setpoint can be set −5 to 105 percent,
32767 kW (default = 0 kW). in 0.01 percent increments (default = 0.00%).

6-48
PRELIMINARY

ADJUST LOAD CONTROL GENSET SETUP SUBMENUS

FIGURE 6-30. ADJUST MENUS − LOAD CONTROL GENSET SETUP SUBMENUS

6-49
PRELIMINARY

Utility Load Control Setup Submenus Utility Bus kW Setpoint can be set from
−32768 to 32767 kW (default = 100 kW).
The Utility Load Control Setup submenus are avail-
able by pressing the (2) button on the Adj Load Set- • kVAR SetPoint: This sets the peak shave
up menu (see Figure 6-31). kVAR setpoint in closed loop extended paral-
leling. The Utility Bus kVAR Setpoint can be
• kW SetPt Source: This selects where the utility set from −32768 to 32767 kVAR (default =
kW setpoint will come from for extended paral- _________).
leling. The Utility Bus kW Setpoint Source can
be set to Analog Input or Internal (default = In- • Power Factor SetPt: This sets the desired util-
ternal). ity bus power factor in closed loop extended
• kVAR SetPt Source: This selects where the paralleling. The Utility Bus Power Factor Set-
utility kVAR setpoint will come from for ex- point can be set from 0.7 to 1.0, in 0.1 incre-
tended paralleling. The Utility Bus kVAR Set- ments (default = 1.00).
point Source can be set to Analog Input or In- • kW Constraint Level: This sets the utility kW
ternal (default = Internal). constraint level for base load extended paral-
• kW SetPoint: This sets the peak shave kW set- leling. The kW Constraint Level can be set
point in closed loop extended paralleling. The from −32768 to 32767 kW (default = 100 kW).

6-50
PRELIMINARY

ADJUST LOAD CONTROL UTILITY SETUP SUBMENUS

FIGURE 6-31. ADJUST MENUS − LOAD CONTROL UTILITY SETUP SUBMENUS

6-51
PRELIMINARY

Load Control Tuning Submenus The kW Kp can be set from 0 to 1000 (default
= 60).
The Load Control Setup submenus are available
• kW Adaptive Gain Slope: The kW Adaptive
by pressing the (2) button on the Adj Load Control
Gain Slope can be set from 0 to 50 percent, in
menu (see Figure 6-28).
.001 percent increments (default = _______).
Load Control kW Tuning • kW Adaptive Gain Error Threshold: The kW
Adaptive Gain Error Threshold can be set from
The Load Control kW Tuning submenus are avail- 0 to 110 percent, in 0.01 percent increments
able by pressing the (1) button on the Adj Load (default = _________).
Tuning menu (see Figure 6-32).
• kW Ki: This sets the integral gain for kW closed
• kW Kp: This sets the proportional gain for kW loop control in extended paralleling. The kW Ki
closed loop control in extended paralleling. can be set from 0 to 255 (default = 60).

6-52
PRELIMINARY

ADJUST LOAD CONTROL kW TUNING SUBMENUS

FIGURE 6-32. ADJUST MENUS − LOAD CONTROL KW TUNING SUBMENUS

6-53
PRELIMINARY

Load Control kVAR Tuning Submenus cent, in .001 percent increments (default =
_________).
The Load Control kVAR Tuning submenus are
available by pressing the (2) button on the Adj Load • kVAR Adaptive Gain Error Threshold: The
Tuning menu (see Figure 6-33). kVAR Adaptive Gain Error Threshold can be
set from 0 to 110 percent, in 0.01 percent in-
• kVAR Kp: This sets the proportional gain for
crements (default = _________).
kVAR closed loop control in extended parallel-
ing. The kVAR Kp can be set from 0 to 1000 • kW Ki: This sets the integral gain for kVAR
(default = 120). closed loop control in extended paralleling.
• kVAR Adaptive Gain Slope: The kVAR Adap- The kVAR Ki can be set from 0 to 255 (default
tive Gain Slope can be set from 0 to 50 per- = 50).

6-54
PRELIMINARY

ADJUST LOAD CONTROL kVAR TUNING SUBMENUS

FIGURE 6-33. ADJUST MENUS − LOAD CONTROL KVAR TUNING SUBMENUS

6-55
PRELIMINARY

PTC Sensors Submenus • Transfer Delay (TDNE): The Time Delay Nor-
mal to Emergency (TDNE) can be set from 0
The PTC Sensors menus are available by pressing to 120 seconds, in 0.1 second increments (de-
the (7) button on the PTC Sens menu (see Figure fault = 10.0 seconds).
6-21).
PTC Transfer Time Delay Submenus • Retransfer Delay (TDEN): The Time Delay
Emergency to Normal (TDNE) can be set from
The PTC Transfer Time Delay submenus are avail- 0 to 1800 seconds, in 0.1 second increments
able by pressing the (2) button on the PTC Sens (default = 600.0 seconds.
menu (see Figure 6-34).
• Programmed Trans (TDPT): The Time Delay
• Start Time Delay (TDES): The Time Delay En- Programmed Transition (TDPT) can be set
gine Start (TDES) can be set from 0 to 3600 from 0 to 60 seconds, in 0.1 second incre-
seconds, in 0.1 second increments (default = ments (default = 3.0 seconds).
0.0 seconds).
• Stop Time Delay (TDEC): The Time Delay En- • Max Paralleled (TDMP): The Time Delay Max-
gine Cooldown (TDEC) can be set from 0 to 20 imum Parallel (TDMP) time can be set from 0
seconds, in 0.1 second increments (default = to 1800 seconds, in 0.1 second increments
0.0 seconds). (default = 20.0 seconds.

6-56
PRELIMINARY

ADJUST PTC SENSORS SUBMENUS


TRANSFER TIME DELAY SUBMENUS

ADJUST PTC GENSET ADJUST PTC UTILITY


SENSORS MENUS SENSORS MENUS
SEE PAGE 6-59 SEE PAGE 6-67

FIGURE 6-34. ADJUST MENUS − PTC SENSORS SUBMENUS AND TRANSFER TIME DELAY SUBMENUS

6-57
PRELIMINARY

PTC Generator Sensor Submenus • Online Cap Sensr Enable: The Genset Online
Capacity Sensor Enable can be set to either
The PTC Transfer Time Delay submenus are avail- Disable or Enable (default = Disable).
able by pressing the (1) button on the PTC Sens • Loss Phase Drop Delay: The Genset Loss of
menu (see Figure 6-34). Phase Drop-Out Time Delay can be set from
1.0 to 10.0 seconds, in 0.1 second increments
Miscellaneous PTC Generator Sensor (default = _________).
Submenus • Phase Rot Sensor Enable: The Genset Phase
Rotation Sensor Enable can be set to either
The Miscellaneous PTC Generator Sensor sub- Disable or Enable (default = Disable).
menus are available by pressing the (1) button on • Online Cap Sensr Enable: The Genset Online
the Adj PTC Gen Sens menu (see Figure 6-35). Capacity Sensor Enable can be set to either
Disable or Enable (default = Disable).
• Volt Sensr Type: The Genset Voltage Sensor • Unloaded Level: The Genset Unloaded Level
Type can be set to either Line to Line or Line can be set from −32768 to 32767 kW (default
to Neutral (default = _________). = _________).
• Loss Phase Sensr Enable: The Genset Loss • Dead Bus Thresh: The Genset Dead Bus
of Phase Sensor Enabled can be set to either Threshold can be set from 20 to 50 percent
Disable or Enable (default = Disable). (default = _________).

6-58
PRELIMINARY

ADJUST PTC GENSET MISCELLANEOUS SENSORS SUBMENUS

FIGURE 6-35. ADJUST MENUS − PTC GENSET MISCELLANEOUS SENSORS SUBMENUS

6-59
PRELIMINARY

PTC Genset Undervoltage Sensor Submenus percent, in 0.1 percent increments (default =
_________).
The PTC Genset Undervoltage Sensor submenus • Dropout Delay: The Genset Undervoltage
are available by pressing the (2) button on the Adj Dropout Delay can be set from 0.1 to 30.0 sec-
PTC Gen Sens menu (see Figure 6-36). onds, in 0.1 second increments (default =
_________).
• Dropout Percent: The Genset Undervoltage • Dropout Threshold: The Genset Undervoltage
Dropout Percentage can be set from 75 to 98 Threshold is displayed but cannot be ad-
percent, in 0.1 percent increments (default = justed.
_________).
• Pickup Threshold: The Genset Undervoltage
• Pickup Percent: The Genset Undervoltage Threshold is displayed but cannot be ad-
Pickup Percentage can be set from 85 to 100 justed.

6-60
PRELIMINARY

ADJUST PTC GENSET UNDERVOLTAGE SENSORS SUBMENUS

FIGURE 6-36. ADJUST MENUS − PTC GENSET UNDERVOLTAGE SENSORS SUBMENUS

6-61
PRELIMINARY

PTC Genset Overvoltage Sensor Submenus percent, in 0.1 percent increments (default =
_________).
The PTC Genset Undervoltage Sensor submenus
are available by pressing the (3) button on the Adj • Dropout Delay: The Genset Overvoltage
PTC Gen Sens menu (see Figure 6-37). Dropout Time Delay can be set from 0.5 to 120
• Sensor Enable: The Genset Overvoltage Sen- seconds, in 0.1 second increments (default =
sor Enable can be set to Disabled or Enabled _________).
(default = Disabled).
• Drpout Threshold: The Genset Overvoltage
• Dropout Percent: The Genset Overvoltage Dropout Threshold is displayed but cannot be
Dropout Percentage can be set from 105 to adjusted.
135 percent, in 0.1 percent increments (de-
fault = _________). • Pickup Threshold: The Genset Overvoltage
• Pickup Percent: The Genset Overvoltage Pickup Threshold is displayed but cannot be
Pickup Percentage can be set from 95 to 99 adjusted.

6-62
PRELIMINARY

ADJUST PTC GENSET OVERVOLTAGE SENSORS SUBMENUS

FIGURE 6-37. ADJUST MENUS − PTC GENSET OVERVOLTAGE SENSORS SUBMENUS

6-63
PRELIMINARY

PTC Genset Frequency Sensor Submenus percent, in 0.1 percent increments (default =
_________).
The PTC Genset Undervoltage Sensor submenus
• Dropout Delay: The Genset Frequency Drop-
are available by pressing the (4) button on the Adj
out Time Delay can be set from 0.1 to 15.0 sec-
PTC Gen Sens menu (see Figure 6-38).
onds, in 0.1 second increments (default =
• Sensor Enable: The Genset Frequency Sen- _________).
sor Enable can be set to Disabled or Enabled. • Lower Dropout Thresh: The Genset Frequen-
• Center Frequency: This is used to set the cen- cy Lower Dropout Threshold is displayed but
ter frequency for the genset frequency sensor cannot be adjusted.
bandwidth settings. The Genset Center Fre- • Lower Pickup Thresh: The Genset Frequency
quency can be set from 45 to 65 Hz, in 0.1 Hz Lower Pickup Threshold is displayed but can-
increments (default = 60.0 Hz). not be adjusted.
• Drpout Bandwidth: The Genset Frequency • Upper Pickup Thresh: The Genset Frequency
Dropout Bandwidth can be set from 0.3 to 5.0 Upper Pickup Threshold is displayed but can-
percent, in 0.1 percent increments (default = not be adjusted.
_________).
• Upper Dropout Thresh: The Genset Frequen-
• Pickup Bandwidth: The Genset Frequency cy Upper Dropout Threshold is displayed but
Pickup Bandwidth can be set from 0.3 to 20.0 cannot be adjusted.

6-64
PRELIMINARY

ADJUST PTC GENSET FREQUENCY


SENSORS SUBMENUS

FIGURE 6-38. ADJUST MENUS − PTC GENSET FREQUENCY SENSORS SUBMENUS

6-65
PRELIMINARY

PTC Utility Sensor Submenus • Loss Phase Drop Delay: The Utility Loss of
Phase Drop-Out Time Delay can be set from
The PTC Transfer Time Delay submenus are avail-
1.0 to 10.0 seconds, in 0.1 second increments
able by pressing the (3) button on the PTC Sens
(default = _________).
menu (see Figure 6-34).
Miscellaneous PTC Utility Sensor Submenus • Phase Rot Sensor Enable: The Utility Phase
Rotation Sensor Enable can be set to either
The Miscellaneous PTC Utility Sensor submenus
Disable or Enable (default = Disable).
are available by pressing the (1) button on the Adj
PTC Util Sens menu (see Figure 6-39).
• Unloaded Level: The Utility Unloaded Level
• Volt Sensr Type: The Utility Voltage Sensor can be set from −32768 to 32767 kW (default
Type can be set to either Line to Line or Line = _________).
to Neutral (default = _________).
• Loss Phase Sensr Enable: The Utility Loss of • Dead Bus Thresh: The Utility Dead Bus
Phase Sensor Enabled can be set to either Threshold can be set from 20 to 50 percent
Disable or Enable (default = Disable). (default = _________).

6-66
PRELIMINARY

ADJUST PTC MISCELLANEOUS UTILITY SENSORS SUBMENUS

FIGURE 6-39. ADJUST MENUS − PTC UTILITY MISCELLANEOUS SENSORS SUBMENUS

6-67
PRELIMINARY

PTC Utility Undervoltage Sensor Submenus cent, in 0.1 percent increments (default =
_________).
The PTC Utility Undervoltage Sensor submenus • Dropout Delay: The Utility Undervoltage Drop-
are available by pressing the (2) button on the Adj out Delay can be set from 0.1 to 30.0 seconds,
PTC Util Sens menu (see Figure 6-40). in 0.1 second increments (default =
_________).
• Dropout Percent: The Utility Undervoltage • Drpout Threshold: The Utility Undervoltage
Dropout Percentage can be set from 75 to 98 Threshold is displayed but cannot be ad-
percent, in 0.1 percent increments (default = justed.
_________).
• Pickup Threshold: The Utility Undervoltage
• Pickup Percent: The Utility Undervoltage Pick- Threshold is displayed but cannot be ad-
up Percentage can be set from 85 to 100 per- justed.

6-68
PRELIMINARY

ADJUST PTC UTILITY UNDERVOLTAGE SENSORS SUBMENUS

FIGURE 6-40. ADJUST MENUS − PTC UTILITY UNDERVOLTAGE SENSORS SUBMENUS

6-69
PRELIMINARY

PTC Utility Overvoltage Sensor Submenus cent, in 0.1 percent increments (default =
_________).
The PTC Utility Overvoltage Sensor submenus are
available by pressing the (3) button on the Adj PTC • Dropout Delay: The Utility Overvoltage Drop-
Util Sens menu (see Figure 6-41). out Time Delay can be set from 0.5 to 120 sec-
• Sensor Enable: The Utility Overvoltage Sen- onds, in 0.1 second increments (default =
sor Enable can be set to Disabled or Enabled _________).
(default = Disabled).
• Drpout Threshold: The Utility Overvoltage
• Dropout Percent: The Utility Overvoltage Dropout Threshold is displayed but cannot be
Dropout Percentage can be set from 105 to adjusted.
135 percent, in 0.1 percent increments (de-
fault = _________). • Pickup Threshold: The Utility Overvoltage
• Pickup Percent: The Utility Overvoltage Pick- Pickup Threshold is displayed but cannot be
up Percentage can be set from 95 to 99 per- adjusted.

6-70
PRELIMINARY

ADJUST PTC UTILITY OVERVOLTAGE SENSORS SUBMENUS

FIGURE 6-41. ADJUST MENUS − PTC UTILITY OVERVOLTAGE SENSORS SUBMENUS

6-71
PRELIMINARY

PTC Utility Frequency Sensor Submenus cent, in 0.1 percent increments (default =
_________).
The PTC Utility Frequency Sensor submenus are
available by pressing the (4) button on the Adj PTC • Dropout Delay: The Utility Frequency Dropout
Util Sens menu (see Figure 6-42). Time Delay can be set from 0.1 to 15.0 sec-
onds, in 0.1 second increments (default =
• Sensor Enable: The Utility Frequency Sensor _________).
Enable can be set to Disabled or Enabled (de-
fault = Disabled). • Lower Dropout Thresh: The Utility Frequency
Lower Dropout Threshold is displayed but
• Center Frequency: This is used to set the cen- cannot be adjusted.
ter frequency for the utility frequency sensor
bandwidth settings. The The Utility Center • Lower Pickup Thresh: The Utility Frequency
Frequency can be set from 45 to 65 Hz, in 0.1 Lower Pickup Threshold is displayed but can-
Hz increments (default = 60.0 Hz). not be adjusted.
• Drpout Bandwidth: The Utility Frequency • Upper Pickup Thresh: The Utility Frequency
Dropout Bandwidth can be set from 0.3 to 5.0 Upper Pickup Threshold is displayed but can-
percent, in 0.1 percent increments (default = not be adjusted.
_________). • Upper Dropout Thresh: The Utility Frequency
• Pickup Bandwidth: The Utility Frequency Pick- Upper Dropout Threshold is displayed but
up Bandwidth can be set from 0.3 to 20.0 per- cannot be adjusted.

6-72
PRELIMINARY

ADJUST PTC UTILITY FREQUENCY


SENSORS SUBMENUS

FIGURE 6-42. ADJUST MENUS − PTC UTILITY FREQUENCY SENSORS SUBMENUS

6-73
PRELIMINARY

Sync Check Submenus tion. This parameter can be set from 0.5 to
10.0 percent, in 0.1 percent increments (de-
The Sync Check submenus are available by press- fault = 6.0 percent).
ing the (8) button on the Adjust menu (see Figure
6-43). • Permissive Volt Time: The Permissive Voltage
Time sets the permissive acceptance window
• Permissive Freq Window: The Permissive window dwell time for the synch check func-
Frequency Window sets the maximum fre- tion. This parameter can be set from 0.50 to
quency difference allows for permissive close. 5.00 seconds, in 0.02 second increments (de-
This parameter can be set from 0.001 to 1.000 fault = 0.50 seconds).
Hz, in .001 Hz increments (default = 1.000 Hz). • Fail To Sync Time: This parameter sets the
• Permissive Phase Window: The Permissive fail-to-synchronize diagnostic time delay. The
Phase Window sets the permissive +/− phase Failure to Synchronize Time Delay can be set
angle window for the sync check function. This from 10.0 to 900.0 seconds, in 0.2 second in-
parameter can be set from 0.10 to 20.00 de- crements (default = 120.0 seconds).
grees, in .01 degree increments (default = • Fail Sync Lckout Enable: The Failure to Syn-
10.00 degrees). chronize Lockout Enable can be set to En-
• Permissive Volt Window: The Permissive Volt- abled or Disabled (default = Disabled). This
age Window sets the permissive +/− voltage feature should be enabled if you want syn-
acceptance window for the sync check func- chronizing to stop if a fail-to-sync occurs.

6-74
PRELIMINARY

ADJUST SYNC CHECK SUBMENUS

A
CONTINUED ON
PAGE 6-77

FIGURE 6-43. ADJUST MENUS − SYNC CHECK SUBMENUS (SHEET 1 OF 2)

6-75
PRELIMINARY

• Fail To Sync Open Transition Retransfer En- erator Enable can be set to Disabled or En-
able: The Failure to Synchronize Open Transi- abled (default = Disabled).
tion Retransfer Enable can be set to Disabled • Dead Util Live Gen: The Dead Utility Live Gen-
or Enabled (default = Disabled). erator Enable can be set to Disabled or En-
• Dead Util Dead Gen: The Dead Utility Dead abled (default = disabled).
Generator Enable can be set to Disabled or • Live Util Live Gen: The Live Utility Live Gener-
Enabled (default = Disabled). ator Enable can be set to Disabled or Enabled
• Live Util Dead Gen: The Live Utility Dead Gen- (default = Disabled).

6-76
PRELIMINARY

ADJUST SYNC CHECK SUBMENUS

A RETURN TO
PAGE 6-75
B

FIGURE 6-43. ADJUST MENUS − SYNC CHECK SUBMENUS (SHEET 2 OF 2)

6-77
PRELIMINARY

Sync Adjust Submenus • Sync Method: The Sync Method can be set to
be either Phase Match or Slip Frequency (de-
The Sync Adjust submenus are available by press- fault = Phase Match). To determine which is
ing the (9) button on the Adjust menu (see Figure the appropriate synchronization method for
6-44). you application, see “Synchronizing Methods”
on page 3-2.
The Sync Adjust Submenus are divided into three
• Slip Frequency: The Slip Frequency can be
categories:
set from −3.000 to +3.000 Hz (default = 0.1).
This feature is used when the using the slip
• Miscellaneous
sync method.
• Frequency • Sync Phase Offset: This function sets a sync
• Voltage phase offset to accommodate synchronizing
across the transformer with phase shift. The
Sync Adjust Miscellaneous Submenus Sync Phase Offset can be set from −50.00 to
+50.00 degrees, in 0.1 degree increments (de-
The Sync Adjust Miscellaneous submenus are fault = 0.00 degrees).
available by pressing the (1) button on the Adj Sync
• Phase Match Kp: The Phase Match Kp can be
Adjust menu (see Figure 6-44).
set from 10 to 1500 (default = _________).
• System Frequency: The System Frequency • Volt Match Test Offset: The Voltage Match
can be set from 45.0 to 65.0 Hz (default = 60 Test Offset can be set from −10 to +10 percent
Hz). (default = _________).

6-78
PRELIMINARY

ADJUST SYNC ADJUST


MISCELLANEOUS SUBMENUS

FIGURE 6-44. ADJUST MENUS − SYNC ADJUST MISCELLANEOUS SUBMENUS

6-79
PRELIMINARY

Sync Adjust Frequency Submenus • Freq Match Ramp Rate: The Frequency
Match Ramp Rate can be set from 0.00 to
The Sync Adjust Frequency submenus are avail- 60.00 seconds (default = _________).
able by pressing the (2) button on the Adj Sync Ad-
just menu (see Figure 6-45). • Freq Match Lower Limit: The Frequency
Match Lower Limit can be set from −5 to 0
• Freq Match Kp: The Frequency Match Kp can hertz (default = _________).
be set from 1 to 300 (default = _________). • Freq Match Upper Limit: The Frequency
• Freq Match Ki: The Frequency Match Ki can Match Upper Limit can be set from 0 to 5 hertz
be set from 0 to 255 (default = _________). (default = _________).

6-80
PRELIMINARY

ADJUST SYNC ADJUST FREQUENCY SUBMENUS

FIGURE 6-45. ADJUST MENUS − SYNC ADJUST FREQUENCY SUBMENUS

6-81
PRELIMINARY

Sync Adjust Voltage Submenus • Volt Match Ramp Rate: The Voltage Match
Ramp Rate can be set from 0 to 60 (default =
The Sync Adjust Voltage submenus are available _________).
by pressing the (3) button on the Adj Sync Adjust
menu (see Figure 6-46). • Volt Match Lower Limit: The Voltage Match
Lower Limit can be set from −15.00 to 0.00
• Volt Match Kp: The Voltage Match Kp can be percent (default = _________).
set from 10 to 800 (default = _________). • Volt Match Upper Limit: The Voltage Match
• Volt Match Ki: The Voltage Match Ki can be set Upper Limit can be set from 0 to 15.00 percent
from 0 to 255 (default = _________). (default = _________).

6-82
PRELIMINARY

ADJUST SYNC ADJUST VOLTAGE SUBMENUS

FIGURE 6-46. ADJUST MENUS − SYNC ADJUST VOLTAGE SUBMENUS

6-83
PRELIMINARY

System Submenus Bus w/out GM, Isolated Bus w/GM, Common


Bus, or Transfer Pair (default = Master Syn-
The System submenus are available by pressing chronize Only). For more information, see
the (10) button on the Adjust menu (see Figure page 6-4.
6-47).
• Transition Type: The Transition Type can be
The System submenus are divided into two cate- set to be Open Transition, Hard Closed Transi-
gories: tion, or Soft Closed Transition (default = Open
Transition).
• Application
• Extended Parallel Enable: The Extended Par-
• kW Ratings alleling operation can be Enabled or Disabled
System Application Submenus (default = Disabled).
• Load Demand Typ: The Load Demand Type
The System Application submenus are available can be set to None, Fixed Sequence, or Run
by pressing the (1) button on the Adj System Setup Hours (default = None).
menu (see Figure 6-47).
• Priority Control Method: The Priority Control
• System Topology: The System Topology can Method can be set to Manual or Automatic (de-
be set to be Master Synchronize Only, Isolated fault = Manual).

6-84
PRELIMINARY

ADJUST SYSTEM APPLICATION SUBMENUS

SYSTEM kW RATINGS
SETUP MENUS ARE
SHOWN ON PAGE 6-89

A
CONTINUED ON
PAGE 6-87

FIGURE 6-47. ADJUST MENUS − SYSTEM APPLICATION SUBMENUS (SHEET 1 OF 2)

6-85
PRELIMINARY

• Sys Phase Rot: The System Phase Rotation • Fail to Sync Lockout Enable: The Fail to Sync
can be set to L1-L2-L3 or L1-L3-L2 (default = Lockout Enable can be set to Disabled or En-
L1-L2-L3). abled (default = Disabled).
• Fail to Sync Open Transition Retransfer En-
• Test With Load: The Test With Load can be set able: The Fail to Sync Open Transition Retran-
to Disable or Enable (default = Disable). sfer Enable can be set to Disabled or Enabled
(default = Disabled).
• Fail to Disconnect Enable: The Fail to Discon- • System Frequency: The System Frequency
nect Enable can be set to Disabled or Enabled can be set from 45 to 650 Hz (default =
(default = Disabled). _________).

6-86
PRELIMINARY

RETURN TO
ADJUST SYSTEM A
PAGE 6-85
APPLICATION SUBMENUS B

FIGURE 6-47. ADJUST MENUS − SYSTEM APPLICATION SUBMENUS (SHEET 2 OF 2)

6-87
PRELIMINARY

System kW Ratings Submenus • Gen 01 thru Gen 12: The Generator Rating for
The System kW Ratings submenus are available each of the 12 possible generators can be set
by pressing the (2) button on the Adj System Setup from 0 to 32000 kW (default = 0 kW).
menu (see Figure 6-48).

6-88
PRELIMINARY

ADJUST SYSTEM kW RATINGS SUBMENUS

FIGURE 6-48. ADJUST MENUS − SYSTEM KW RATINGS SUBMENUS

6-89
PRELIMINARY

Scheduler Set Clock Submenus • Start Wk: The week that daylight savings time
is to begin can be set to First, Second, Third,
The Scheduler Set Clock submenus are available Fourth, or Last (default = _________).
by pressing the (1) button on the Adj Scheduler
• Start Day: The day of the week that daylight
menu (see Figure 6-49).
savings time is to begin can be set Sunday,
• MM/DD/YYYY: The correct month, day, and Monday, Tuesday, Wednesday, Thursday,
year can be set. Friday, or Saturday (default = Sunday).

• HH/MM/SS: The correct hour, minute and sec- • Start Hour: The starting hour that daylight sav-
ond can be set. ings time is to begin can be set from 1 thru 24
(default = _________).
Scheduler Daylight Savings Time Submenus
• End Month: The month that daylight savings
The Scheduler Daylight Savings Time submenus time is to end can be set from 1 thru 12 (default
are available by pressing the (2) button on the Adj = _________).
Scheduler menu (see Figure 6-49). • End Wk: The week that daylight savings time
is to end can be set to First, Second, Third,
• Daylite Saving Enable: The Daylight Savings Fourth, or Last (default = _________).
Time feature can ben Enabled or Disabled
(default = Disabled). • End Day: The day of the week that daylight
savings time is to end can be set to Sunday,
• Time Adjustment: This value can be set from Monday, Tuesday, Wednesday, Thursday,
___ to ___ minutes (default = _________). Friday, or Saturday (default = _________).
• Start Month: The month that daylight savings • End Hour: The hour that daylight savings time
time is to begin can be set from 1 thru 12 (de- is to end can be set from 1 thru 24 (default =
fault = _________). _________).

6-90
PRELIMINARY

ADJUST SCHEDULER SET CLOCK AND DAYLIGHT SAVINGS SUBMENUS

FIGURE 6-49. ADJUST MENUS − SCHEDULER SET CLOCK AND DAYLIGHT SAVINGS SUBMENUS

6-91
PRELIMINARY

Scheduler Programs Submenus • Prog Select: This allows you to select a sched-
uler program (1 to 12) to view or edit (default
The Scheduler Programs Time submenus are = 1).
available by pressing the (3) button on the Adj • Enable: The Program Select Enable feature
Scheduler menu (see Figure 6-50). can be Disabled or Enabled (default = Dis-
abled).
• System Scheduler Enable: This allows you to • Program Run Mode: The Program Run Mode
Enable or Disable the selected program (de- Parameter can be set to No Load, With Load,
fault = Disable). or Extended Parallel (default = No Load).
• RunCmd: This shows the current Run Com- • Start Day HH:MM: Enter the Hour (0 to 23, de-
mand coming from the scheduler function. It fault = 0) and Minute (0 to 59, default = 0) the
can be Off, No Load, With Load, or Extended program is to begin.
Parallel. • Duration HH:MM: Enter the Hour (0 to 23, de-
• ActiveSch: This shows the current Active fault = 0) and Minute (0 to 59, default = 0) the
Scheduler program or exception. It can be program is to stop.
None, Program 1, Program 2, Program 3, Pro- • Repeat Interval: The program can be set to re-
gram 4, Program 5, Program 6, Program 7, peat Once, Every Week, Every 2 Weeks, Ev-
Program 8, Program 9, Program 10, Program ery 4 Weeks, Every 5 Weeks, First Week of
11, Program 12, Exception 1, Exception 2, Ex- Month, Second Week of Month, Third Week of
ception 3, Exception 4, Exception 5, or Excep- Month, Fourth Week of Month, or Last Week
tion 6. of Month (default = Once).

6-92
PRELIMINARY

ADJUST SCHEDULER PROGRAMS SUBMENUS

FIGURE 6-50. ADJUST MENUS − SCHEDULER PROGRAMS SUBMENUS

6-93
PRELIMINARY

Scheduler Program Exceptions Submenus 23, default = 0), and Minute (0 to 59, default =
0) for a period of time that you do not wish to
The Scheduler Program Exceptions Time subme- have a programmed exercise operating.
nus are available by pressing the (4) button on the
Adj Scheduler menu (see Figure 6-51). • Dur Days HH MM: Enter the length of time, in
• Exceptn Select: This allows you to select an Days (0 to 44, default = 0), Hours(0 to 23, de-
exception (1 to 6) to view or edit (default = 1). fault = 0), and Minutes (0 to 59, default = 0) that
you do not wish the scheduled program to op-
• Exceptn Enable: This allows you to Enable or erate.
Disable the selected exception (default = Dis-
able). • Repeat Interval: The Repeat Interval can be
• Month DD HH MM: Enter the Month ( to 12, de- set to either Only Once or Every Year (default
fault = 1), Date ( to 31, default = 1), Hour (0 to = Once Only).

6-94
PRELIMINARY

ADJUST SCHEDULER PROGRAM EXCEPTIONS SUBMENUS

FIGURE 6-51. ADJUST MENUS − SCHEDULER PROGRAM EXCEPTIONS SUBMENUS

6-95
PRELIMINARY

LCD Display Submenus • Contrast and Brightness: Press the + or −


selection buttons to adjust the screen’s con-
The LCD Display submenus are available by trast and brightness. Changing the brightness
pressing the (12) button on the Adjust menu (see setting also affects the brightness of the LEDs
Figure 6-52). on the control panel.
• Display Symbols: Press the + or − selection
The LCD Display submenus are divided into three buttons to select whether or not you want Sym-
categories: bols to be displayed (default = No).
• Screen CRC Submenu
• CRC The CRC submenu is available by pressing the (2)
button on the LCD Display menu (see Figure 6-52).
• Lamp Test This menu displays the bootload, firmware,
Screen Submenu screens, and fonts versions.
Lamp Test
The Screen submenu is available by pressing the
(1) button on the LCD Display menu (see Figure The six LEDs on the control panel should light as
6-52). long as the Lamp Test button (3) is pressed.

6-96
PRELIMINARY

ADJUST LCD DISPLAY SUBMENUS

Lamp Test − The six LEDs


on the control panel should
light until the Previous
Menu button is pressed.

FIGURE 6-52. ADJUST MENUS − LCD DISPLAY SUBMENUS

6-97
PRELIMINARY

Load Demand Submenus • RestartDly: The Restart Time Delay sets a


genset restart delay time to avoid nuisance re-
The five Load Demand submenus are available by starts due to load transients. This value can be
pressing the (13) button on the Adjust menu (see sec from 0.00 to 25.00 seconds (default = 1.00
Figure 6-53). second).
• Load Demand Enable: The Load Demand fea- • GenFailTime: The Genset Failure Time Delay
ture can be Enabled or Disabled (default = Dis- sets how long to wait for a genset to come on-
abled). line before declaring it failed. This value can be
set from 10 to 900 seconds (default = 60 sec-
• Load Demand Typ: The Load Demand Type onds).
can be set to Fixed Sequence, Run Hours, or
None (default = _________). • GenA: This sets GenA for fixed sequence load
demand. This parameter can be set to Gen1,
• Min Cap: This value sets how much the load Gen2, Gen3, or Gen4 (default = Gen1).
demand Minimum Capacity must always be
online regardless of what the load is. This val- • GenB: This sets GenB for fixed sequence load
ue can be set from 0 to 32767 kW (default = 0 demand. This parameter can be set to Gen1,
kW). Gen2, Gen3, or Gen4 (default = Gen2).
• Shutdown: The load demand Shutdown • GenC: This sets GenC for fixed sequence load
threshold should be smaller than the Restart demand. This parameter can be set to Gen1,
percentage. This value can be set from 20 to Gen2, Gen3, or Gen4 (default = Gen3).
100 percent (default = 60 percent). • GenD: This sets GenD (the first to stop) for
• Restart: The Restart can be set from 20 to 100 fixed sequence load demand. This parameter
percent (default = 80 percent). can be set to Gen1, Gen2, Gen3, or Gen4 (de-
fault = Gen4).
• Hrs Diff: The Hours of Differential sets the run
hours differential for restarting a genset • Gen1: This
stopped due to load demand. This parameter
can be set from 1 to 500 hours (default = 50
hours). • Gen2: This
• Init Delay: The Initial Time Delay can be set
from 1 to 60 minutes (default = 5 minutes).
• ShutdwnDly: The Shutdown Time Delay sets • Gen3: This
the delay time between stopping gensets due
to load demand. This parameter can be set
from 1 to 60 minutes (default = 5 minutes) • Gen4: This

6-98
PRELIMINARY

ADJUST LOAD DEMAND SUBMENUS

FIGURE 6-53. ADJUST MENUS − LOAD DEMAND SUBMENUS

6-99
PRELIMINARY

Load Add Shed Submenus ture can be Enabled or Disabled (default = Dis-
abled).
The nine Load Add Shed submenus are available • Genset Bus Load Add Delay: The Genset Bus
by pressing the (14) button on the Adjust menu Load Add Shed Time Delay can be set from 0
(see Figure 6-54). to 60 seconds (default = 1 second).
• Utility Bus Load Add Delay: The Utility Bus
• Ld Add Shed Enable: The Load Add Shed fea- Load Add Shed Time Delay can be set from 0
ture can be Enabled or Disabled (default = Dis- to 60 seconds (default = 1 second).
abled).
• Load Shed Delay: The Load Shed Time Delay
• Open Transition Retransfer Load Shed: The can be set from 1.0 to 10.0 seconds, in 0.1 sec-
Open Transition Retransfer Load Shed fea- ond increments (default = 1.0 seconds).

6-100
PRELIMINARY

ADJUST LOAD ADD SHED SUBMENUS

A
CONTINUED ON
PAGE 6-103

FIGURE 6-54. ADJUST MENUS − LOAD ADD SHED SUBMENUS (SHEET 1 OF 2)

6-101
PRELIMINARY

• Load Add Shed Required Online Capacity: − Load 2: The add level can be set from 1 to
The Load Shed Required Online Capacity can 6 (default = 2) and the shed level can be set
be set from 0 to 32000 kW (default = 0 kW). from 0 to 5 (default = 1)
This value is the genset kW capacity that must
be online to start a timed load add. This func- − Load 3: The add level can be set from 1 to
tion is disabled when set to 0. 6 (default = 3) and the shed level can be set
from 0 to 5 (default = 2)
• Type: The two Type menus are used to set the
load type for each of the available six loads − Load 4: The add level can be set from 1 to
connected to the load add shed shed control 6 (default = 4) and the shed level can be set
and status I/O. The load Type can be set to from 0 to 5 (default = 3)
None, Breaker, or ATS (default = None).
• LVL ADJ: The two Level Adjust Add Shed me- − Load 5: The add level can be set from 1 to
nus are used to set the add and shed level for 6 (default = 5) and the shed level can be set
each load. from 0 to 5 (default = 4)

− Load 1: The add level can be set from 1 to − Load 6: The add level can be set from 1 to
6 (default = 1) and the shed level can be set 6 (default = 6) and the shed level can be set
from 0 to 5 (default = 0) from 0 to 5 (default = 5)

6-102
PRELIMINARY

ADJUST LOAD ADD SHED SUBMENUS


A RETURN TO
PAGE 6-101
B

FIGURE 6-54. ADJUST MENUS − LOAD ADD SHED SUBMENUS (SHEET 2 OF 2)

6-103
PRELIMINARY

Genset Bus Overload Submenus • kW OL Delay: The genset bus kW Overload


Time Delay can be adjusted from 0 to 120 sec-
The two Genset Bus Overload submenus are avail- onds (default = 60 seconds).
able by pressing the (15) button on the Adjust
menu (see Figure 6-55). • UnderFreq OverLd Threshld: The genset bus
Underfrequency Overload Threshold can be
• Method: The Method of determined a genset adjusted from 0.1 to 10.0 hertz, in .1 hertz in-
bus overload is kW Only. This information is crements (default = 3.0 Hz).
displayed but cannot be changed. • UnderFreq OverLd Delay: The genset bus Un-
• %kW OL Thrs: The Percentage of genset bus derfrequency Overload Time Delay can be ad-
kW Overload Threshold can be adjusted from justed from 0 to 20 seconds (default = 3 sec-
80 to 140 percent (default = 105 percent). onds).

6-104
PRELIMINARY

ADJUST GENERATOR BUS OVERLOAD SUBMENUS

FIGURE 6-55. ADJUST MENUS − GENERATOR BUS OVERLOAD SUBMENUS

6-105
PRELIMINARY

MONITOR MENUS • Load Control


The Monitor menus are available by pressing the • Priority
(3) button on the Main menu (see Figure 6-11). • Relay Outputs
The Monitor menus are used to view all controller The fourth Monitor menu provides access to the
data, including AC data, load demand status infor- following submenus:
mation, breaker position information, and analog
and discrete I/O readings. • Switch Inputs
The first Monitor menu provides access to the fol- • Sync Check
lowing submenus:
• Synchronizer
• AC Meter The fifth Monitor menu provides access to the fol-
• Analog In lowing submenus:
• Analog Out • System Status
The second Monitor menu provides access to the
• Load Demand
following submenus:
• Load Add Shed
• Breakers
The sixth Monitor menu provides access to the fol-
• Communication lowing submenus:
• PTC
• Generator Bus Overload
The third Monitor menu provides access to the fol-
lowing submenus: • Scheduler

6-106
PRELIMINARY

MONITOR MENUS
SEE PAGE
6-109
SEE PAGE 6-125
SEE PAGE
6-125

SEE PAGE 6-127


SEE PAGE 6-127
SEE PAGE 6-129

SEE PAGE 6-137


SEE PAGE 6-137
SEE PAGE 6-137

SEE PAGE 6-139


SEE PAGE 6-141
SEE PAGE 6-143

SEE PAGE 6-145


SEE PAGE 6-147
SEE PAGE 6-149

SEE PAGE 6-151


SEE PAGE
6-151

FIGURE 6-56. MONITOR MENUS

6-107
PRELIMINARY

Monitor AC Meter Submenus • Utility AC Meter − includes of the following six


categories.
The AC Meter submenus include of the following − Current − see page 6-117
three categories.
− Energy − see page 6-117
• Genset AC Meter − includes of the following − Frequency − see page 6-117
six categories.
− Phase − see page 6-119
− Current − see page 6-111
− Power − see page 6-121
− Energy − see page 6-111
− Voltage − see page 6-119
− Frequency − see page 6-111 • System AC Meter
− Phase − see page 6-113 System AC Meter Submenu
− Power − see page 6-115
The system AC Meter submenu displays the total
− Voltage − see page 6-113 kW, kVAR, kVA, and power factor.

6-108
PRELIMINARY

MONITOR AC METER SUBMENUS

AC METER GENSET MENUS AC METER UTILITY MENUS


SEE PAGE 6-111 SEE PAGE 6-117

FIGURE 6-57. MONITOR MENUS − AC METER SUBMENUS

6-109
PRELIMINARY

Genset AC Meter Submenus The genset AC meter energy submenus list the
___________________________.
the Genset AC Meter submenus are available by
pressing the (1) button on the Monitor AC Meter • Reset Gen Energy Meters: The Reset Genset
menu. Energy Meters can be set to Nothing, Reset,
or ________________ (default =
Genset AC Meter Current submenu _________).
The genset AC meter current submenu lists the Genset AC Meter Frequency submenus
genset L1, L2, L3, and average current (in amps).
The Genset Frequency submenu displays the gen-
Genset AC Meter Energy submenus set frequency.

6-110
PRELIMINARY

MONITOR AC METER GENSET


CURRENT, ENERGY, AND
FREQUENCY SUBMENUS

ADDITIONAL MENUS
ON PAGE 6-113

FIGURE 6-58. MONITOR MENUS − AC METER GENSET CURRENT, ENERGY, AND


FREQUENCY SUBMENUS

6-111
PRELIMINARY

Genset AC Meter Phase submenus The first Genset Voltage menu displays the genset
L1N voltage, L2N voltage, L3N voltage, and LN av-
The Genset Frequency submenus display the erage voltage.
phase rotation ____________ ____________
The second Genset Voltage menu displays the
Genset AC Meter Phase submenus genset L1L2, L2L3, L3L1, and LL average voltage.

6-112
PRELIMINARY

MONITOR AC METER GENSET PHASE AND VOLTAGE SUBMENUS

AC METER
POWER MENUS
SEE PAGE 6-115

FIGURE 6-59. MONITOR MENUS − AC METER GENSET PHASE AND VOLTAGE SUBMENUS

6-113
PRELIMINARY

Genset AC Meter Power submenus The third Genset Power menu displays the genset
L1, L2, L3, and total kVA.
The first Genset Power menu displays the genset
The fourth Genset Power menu displays the gen-
L1, L2, L3, and total kW.
set L1, L2, L3, and total power factor.
The second Genset Power menu displays the gen- The fifth Genset Power menu displays the genset
set L1, L2, L3, and total kVAR. total kW, kVAR, kVA, and power factor.

6-114
PRELIMINARY

MONITOR AC METER GENSET POWER SUBMENUS

FIGURE 6-60. MONITOR MENUS − AC METER GENSET POWER SUBMENUS

6-115
PRELIMINARY

Utility AC Meter Submenus The utility AC meter energy submenus list the
___________________________.
the Utility AC Meter submenus are available by
pressing the (2) button on the Monitor AC Meter • Reset Gen Energy Meters: The Reset Genset
menu. Energy Meters can be set to Nothing, Reset,
or ______________ (default = _________).
Utility AC Meter Current submenu
The utility AC meter current submenu lists the utility Utility AC Meter Frequency submenus
L1, L2, L3, and average current (in amps).
The Utility Frequency submenu displays the utility
Utility AC Meter Energy submenus frequency.

6-116
PRELIMINARY

MONITOR AC METER UTILITY


CURRENT, ENERGY, AND
FREQUENCY SUBMENUS

FIGURE 6-61. MONITOR MENUS − AC METER UTILITY CURRENT, ENERGY, AND FREQUENCY
SUBMENUS

6-117
PRELIMINARY

Utility AC Meter Phase submenus


The Utility Frequency submenus display the phase The first Utility Voltage menu displays the utility
rotation ____________ ____________ L1N voltage, L2N voltage, L3N voltage, and LN av-
Utility AC Meter Phase submenus erage voltage.

The Utility Voltage submenus display the The second Utility Voltage menu displays the utility
____________ ____________ L1L2, L2L3, L3L1, and LL average voltage.

6-118
PRELIMINARY

MONITOR AC METER UTILITY PHASE AND VOLTAGE SUBMENUS

AC METER
POWER MENUS
SEE PAGE 6-121

FIGURE 6-62. MONITOR MENUS − AC METER UTILITY PHASE AND VOLTAGE SUBMENUS

6-119
PRELIMINARY

Utility AC Meter Power submenus The third Utility Power menu displays the utility L1,
L2, L3, and total kVA.
The first Utility Power menu displays the utility L1,
The fourth Utility Power menu displays the utility
L2, L3, and total kW.
L1, L2, L3, and total power factor.
The second Utility Power menu displays the utility The fifth Utility Power menu displays the utility total
L1, L2, L3, and total kVAR. kW, kVAR, kVA, and power factor.

6-120
PRELIMINARY

MONITOR AC METER UTILITY POWER SUBMENUS

FIGURE 6-63. MONITOR MENUS − AC METER UTILITY POWER SUBMENUS

6-121
PRELIMINARY

System AC Meter Submenus • Total kW: This shows the sum of the genset
bus and utility bus kW.
the System AC Meter submenu is available by • Total kVA: This shows the sum of the genset
pressing the (3) button on the Monitor AC Meter bus and utility bus kVA.
menu. • Total PF: This shows the system total power
factor (utility bus plus genset bus).
This menu lists the total Kw, total kVA, total power • Total kVAR: This shows the sum of the genset
factor, and total kVAR available on the system. bus and utility bus kVAR.

6-122
PRELIMINARY

MONITOR AC METER SYSTEM SUBMENUS

FIGURE 6-64. MONITOR MENUS − AC METER SYSTEM SUBMENUS

6-123
PRELIMINARY

Monitor Analog In Submenus Monitor Analog Out Submenus


The Monitor Analog In submenus are available by The Monitor Analog Out submenus are available
pressing the (2) button on the Monitor menu. These by pressing the (3) button on the Monitor menu.
menus display the following. These menus display the following.
• kW Load Set Point Percentage − This displays • kW Master Load Control − This displays the
the value for the kW load setpoint analog input. voltage level sent to the kW master load con-
trol analog output.
• Battery Voltage − This displays the value for
the battery voltage analog input. • Master Frequency Bias − This displays the
voltage level sent to the master frequency bias
• Power Factor Set Point − The power factor
analog output.
setpoint analog input value displayed here
uses a kVAR load setpoint analog input. • Master Voltage Bias − this displays the master
voltage level send to the master voltage bias
• kVAR Load Share Level −
analog output.
• kVAR Load Set Point − This displays the value • kVAR Master Load Control − This displays the
for the kVAR load setpoint analog input. voltage level sent to the kVAR master load
• kW Load Share Level − control analog output.

6-124
PRELIMINARY

MONITOR ANALOG IN AND ANALOG OUT SUBMENUS

FOR ADDITIONAL
MONITOR MENUS
SEE PAGE 6-127

FIGURE 6-65. MONITOR MENUS − ANALOG IN AND ANALOG OUT SUBMENUS

6-125
PRELIMINARY

Monitor Breakers Submenus Monitor Communication Submenus


The Monitor Breakers submenus are available by The Communication submenus are available by
pressing the (4) button on the Monitor menu. These pressing the (5) button on the Monitor menu. These
menus display the following. menus display the following.
• Genset Circuit Breaker Position Status • Bus Message Count
• Genset Circuit Breaker Inhibit Status • Slave Message Count
• Genset #1 Circuit Breaker Position
• No Response Count
• Genset #2 Circuit Breaker Position
• Exception Count
• Genset #3 Circuit Breaker Position
• CRC Error Count
• Genset Circuit Breaker Position
• Clear Counters: When the password is en-
• Utility Circuit Breaker Position tered, this parameter can set set to Do Noth-
• Utility Circuit Breaker Inhibit Status ing, or ____________________.

6-126
PRELIMINARY

MONITOR BREAKERS AND COMMUNICATIONS SUBMENUS

MONITOR PTC
MENUS
SEE PAGE 6-129

FIGURE 6-66. MONITOR MENUS − BREAKERS AND COMMUNICATIONS SUBMENUS

6-127
PRELIMINARY

Monitor PTC Submenus • Undervoltage Sensor Status: The status of the


genset undervoltage sensor may be Drop-out
The PTC submenus are available by pressing the or Picked-Up.
(6) button on the Monitor menu. This series of me- • Overvoltage Sensor Status: The status of the
nus includes the following four categories. genset overvoltage sensor may be Drop-out
or Unknown.
• PTC Genset Sensors
• Frequency Sensor Status: The status of the
• PTC Status genset frequency sensor may be Drop-out or

• PTC Timers • Loss of Phase Sensor Status: The status of


the genset loss of phase sensor may be Drop-
• PTC Utility Sensors out or

Genset Sensors Submenus • Phase Rotation Sensor Status: The status of


the genset phase rotation sensor may be
Drop-out or
The Genset Sensors submenus are displayed by
pressing the (1) button on the Mon PTC menu. • Online Cap Sensor Status: The status of the
These menus display the following. genset online cap sensor may be Drop-out or
• Genset Bus Status: The status of the genset
• Genset Availability: bus may be Drop-out, Live, or Unavailable.

6-128
PRELIMINARY

MONITOR PTC GENSET SENSORS SUBMENUS

FIGURE 6-67. MONITOR MENUS − PTC GENSET SENSORS SUBMENUS

6-129
PRELIMINARY

PTC Status Submenus • Utility Availability: This shows the availability


of the utility for loading (Available, Not Avail-
The PTC Status submenus are displayed by press- able, or Unknown), as determined by the utility
ing the (2) button on the Mon PTC menu. These sensors.
menus display the following.
• Active Transition Type: The Active Transition
• PTC Status: This shows the status of the con- timer type may be Programmed Transition,
nected Power Transfer Control (Util Con- Transfer, Retransfer, Max Parallel, or None.
nected, Genset Connected, No Source Con-
• Active Transition Timer: This shows the count-
nected, Paralleled, or Not Enabled).
down timer (in seconds) value of the active
• PTC Operating Mode: This variable indicates timer.
what direction the system is trying to go (if
• Transfer Inhibit Sw: The status of the Transfer
any). The current PTC Operating Mode may
Inhibit Switch may be Inhibit or No Inhibit (de-
be Normal, Normal Override, Test, Utility Fail,
fault = No Inhibit).
or Extended Parallel. The PTC operating
modes are listed in order of priority from high- • Retransfer Inhibit Sw: The status of the Re-
est to lowest in Table 6-2. transfer Inhibit Switch may be Inhibit or No In-
hibit (default = No Inhibit).
• Genset Availability: This shows the availability
of the genset for loading (Available, Not Avail- • Override Sw: The status of the Override
able, or Unknown), as determined by the gen- Switch may be Override or No Override (de-
set sensors. fault = No Override).
TABLE 6-2. PTC OPERATING MODES
PTC Operating Mode Description
Utility Fail The utility has failed and the load is transferred to the gensets.
Normal Override The genset bus has failed and the load is immediately retransferred to the utility.
Extended Parallel Extended parallel mode
Test Test mode (with or without load)
Normal Stay on the utility, or if not there, retransfer to the utility.

6-130
PRELIMINARY

MONITOR PTC STATUS SUBMENUS

FIGURE 6-68. MONITOR MENUS − PTC STATUS SUBMENUS

6-131
PRELIMINARY

PTC Timers Submenus • Transfer Timer: Displays the countdown value


of the transfer timer, in seconds.
The PTC Timers submenus are displayed by • Retransfer Timer Status: The status of the Re-
pressing the (3) button on the Mon PTC menu. transfer Timer may be Timing, Not Timing, or
These menus display the status and the time al- Expired.
lowed for each PTC timer function. These menus
display the following. • Retransfer Timer: Displays the countdown
value of the retransfer timer.
• Start Timer Status: The status of the Start Tim- • Programmed Transfer Timer Status: The sta-
er can be Timing, Not Timing, or Expired. tus of the Programmed Transfer Timer may be
Timing, Not Timing, or Expired.
• Start Timer: Displays the countdown value for
the genset start timer. • Programmed Transfer Timer: Displays the
countdown value of the programmed transi-
• Stop Timer Status: The status of the Stop Tim- tion timer, in seconds.
er may be Timing, Not Timing, or Expired.
• Maximum Paralleling Timer Status: The status
• Stop Timer: Displays the countdown value for of the Maximum Paralleling Timer may be Tim-
the genset stop timer. ing, Not Timing, or Expired.
• Transfer Timer Status: The status of the • Maximum Paralleling Timer: Displays the
Transfer Timer may be Timing, Not Timing, or countdown timer of the maximum parallel tim-
Expired. er, in seconds.

6-132
PRELIMINARY

MONITOR PTC TIMERS SUBMENUS

FIGURE 6-69. MONITOR MENUS − PTC TIMERS SUBMENUS

6-133
PRELIMINARY

Utility Sensors Submenus • Frequency Sensor Status: The status of the


Frequency Sensor may be Drop-out or Un-
The PTC Utility Sensors submenus are displayed known.
by pressing the (4) button on the Mon PTC menu.
These menus display the status of the PTC utility • Loss of Phase Sensor Status: The status of
sensors. These menus display the following. the Loss of Phase Sensor may be Drop-out or
Unknown.
• Utility Availability: The status of the Utility
Availability sensor may be Available or Not • Phase Rotation Sensor Status: The status of
Available. the Phase Rotation Sensor may be Drop-out
or Unknown.
• Undervoltage Sensor Status: The status of the
Undervoltage Sensor status may be Drop-out • Utility Source Failure Sw Status: The status of
or Picked-Up. the Utility Source Failure Switch sensor may
be Drop-out or Unknown.
• Overvoltage Sensor Status: The status of the
Overvoltage Sensor may be Drop-out or Un- • Utility Bus Status: The status of the Utility Bus
known. sensor may be Unavailable, Live, or Dead.

6-134
PRELIMINARY

MONITOR PTC UTILITY SENSORS SUBMENUS

FIGURE 6-70. MONITOR MENUS − PTC UTILITY SENSORS SUBMENUS

6-135
PRELIMINARY

Monitor Load Control Submenu menus show the status of the various relay outputs
available with an MCM3320 installation. These
The Monitor Load control submenu is available by menus display the following.
pressing the (7) button on the Monitor menu. This
menu displays the following. • Genset Circuit Breaker Close Relay Status:
• kVAR Load Ref The status of the Genset Circuit Breaker Close
Relay may be Inactive or On.
• kW Load Ref
• Genset Circuit Breaker Open Relay Status:
Monitor Priority Submenu
The status of the Genset Circuit Breaker Open
The Monitor Priority submenu is available by Relay may be Inactive or On.
pressing the (8) button on the Monitor menu. This
• Utility Circuit Breaker Close Relay Status: The
menu displays the following.
status of the Utility Circuit Breaker Close Relay
• Master Inhibit Status: The status of the Master may be Inactive or On.
Priority Inhibit function may be Inhibit or No In-
• Utility Circuit Breaker Open Relay Status: The
hibit.
status of the Utility circuit Breaker Open Relay
Monitor Relay Outputs Submenus may be Inactive or On.
The Relay Outputs submenus are available by • Start Gensets Relay Status: The status of the
pressing the (9) button on the Monitor menu. These Start Genset Relay may be Inactive or On.

6-136
PRELIMINARY

MONITOR LOAD CONTROL, PRIORITY, AND RELAY OUTPUTS MENUS

FIGURE 6-71. MONITOR MENUS − LOAD CONTROL, PRIORITY, AND RELAY OUTPUTS SUBMENUS

6-137
PRELIMINARY

Monitor Switch Inputs Submenus • Util CB Inhibit Sw: The status for the Utility Cir-
cuit Breaker Inhibit input switch may be Inhibit
or No Inhibit.
The Switch Inputs submenus are available by
pressing the (10) button on the Monitor menu. • Util Source Fail Sw: The status for the Utility
These menus show the status of the various Source Failure input switch may be Active or
switches that the MCM3320 monitors. These me- Inactive.
nus display the following. • Test Start Sw: The status for the Test Start in-
put switch may be Start or Stop.
• Genset #1 Circuit Breaker Position Switch
• Extend Parallel Start Sw: The status for the
Status: The status of the Circuit Breaker Posi-
Extended Parallel Start input switch may be
tion input switch for Genset #1 may be Breaker
Start or Stop.
Open or Breaker Closed.
• Auto/Manual Sw: The status for the Auto/
• Genset #2 Circuit Breaker Position Switch Manual input switch may be Manual or Auto.
Status: The status of the Circuit Breaker Posi- • Transfer Inhibit Sw: The status for the Transfer
tion input switch for Genset #2 may be Breaker Inhibit input switch may be Inhibit or No Inhibit.
Open or Breaker Closed.
• Retransfer Inhib Sw: The status for the Re-
• Genset #3 Circuit Breaker Position Switch transfer Inhibit input switch may be Inhibit or
Status: The status of the Circuit Breaker Posi- No Inhibit.
tion input switch for Genset #3 may be Breaker • Override Sw: The status for the Override input
Open or Breaker Closed. switch may be Override or No Override.
• Genset #4 Circuit Breaker Position Switch • Sync Enable Sw: The status for the Synchro-
Status: The status of the Circuit Breaker Posi- nizer Enable input switch may be Active or In-
tion input switch for Genset #4 may be Breaker active.
Open or Breaker Closed. • Fault Reset Sw: The status for the Fault Reset
• Gen CB Inhibit Sw: The Genset Circuit Break- input switch may be Reset or Not Reset.
er Inhibit input switch status may be Inhibit or • RS232 DCD Sw: The status for the RS232
No Inhibit. DCD switch may be Active or Inactive.

6-138
PRELIMINARY

MONITOR SWITCH INPUTS SUBMENUS

FIGURE 6-72. MONITOR MENUS − SWITCH INPUTS SUBMENUS

6-139
PRELIMINARY

Monitor Sync Check Submenus • Util Bus Stat: The status of the Utility Bus may
be Unavailable or Dead.
The Monitor Sync Check submenus are available
by pressing the (11) button on the Monitor menu. • Gen Bus Stat: The status of the Genset Bus
These menus show the status of the various sync may be Unavailable or Dead.
check functions. These menus display the follow- • Util Phase Rot: The Utility Phase Rotation may
ing. be either L1-L2-L3 or L1-L3-L2.
• Sync Status: The status of the synchronizer • Gen Phase Rot: The Genset Phase Rotation
may be Synchronizer On or Synchronizer Off. may be either L1-L2-L3 or L1-L3-L2.
• Master Inhibit: The status of the master inhibit • Phase Match Err:
function may be Inhibit or No Inhibit. • Time in Window: The Time in Window value
• Util Avail Stat: The status of the utility may be may be from _____ to ____ seconds.
Available or Not Available. • Sync Check Close Allow: This shows whether
• Gen Avail Stat: The status of the genset may or not any sync check conditions have been
be Available on Not Available. met.

6-140
PRELIMINARY

MONITOR SYNC CHECK SUBMENUS

FIGURE 6-73. MONITOR MENUS − SYNC CHECK SUBMENUS

6-141
PRELIMINARY

Monitor Synchronizer Submenus • Phase Match Err:

The Monitor Synchronizer submenus are available


by pressing the (12) button on the Monitor menu. • Volt Match Err:
These menus show the status of the various sync
check functions. These menus display the follow- • Master Freq Bias Cmd:
ing.
• Sync Status: The status of the synchronizer • Master Volt Bias Cmd:
may be Synchronizer On or Synchronizer Off.
• Freq Match Err: • Sync Enable Sw: This shows the status of the
synchronizer enable input (Active or Inactive).

6-142
PRELIMINARY

MONITOR SYNCHRONIZER SUBMENUS

FIGURE 6-74. MONITOR MENUS − SYNCHRONIZER SUBMENUS

6-143
PRELIMINARY

Monitor System Status Submenus Connected, No Source Connected, Paral-


leled, or Not Enabled.
The Monitor System Status submenus are avail- • Gen Avail Stat: The genset availability status
able by pressing the (13) button on the Monitor may be Available, Not Available, or Unknown.
menu. These menus show the status of the various • Util Avail Stat: The utility availability status
system functions. These menus display the follow- may be Available, Not Available, or Unknown.
ing.
• Auto/Manual Sw: The status for the Auto/
Manual start switch may be Manual or Auto.
• System State: This variable is intended to give
an indication of the most relevant current con- • Test Start Sw: The status of the Test Start
troller activity. It should only be used for indica- switch my be Start or Stop.
tion purposes and not be used in any control • Extend Parallel Start Sw: The status of the Ex-
logic. The state the control currently is in may tended Paralleling Start switch my be Start or
be TD Start, TD Stop, TD Programmed Transi- Stop.
tion, TD Transfer, TD Retransfer, Synchroniz-
ing, Sync Check OK, Inhibit, Unassigned, • Sync Status: The Synchronizer status may be
Ramp Unload, Ramp Load, Manual, Utility Synchronizer On or Synchronizer Off.
Failure, Test, Standby, Factory Test, Extended • Total Number of Gensets: This lists the total
Parallel, or Not Available. A description of number of gensets with non-zero ratings con-
these states is included in Table 2-3. nected to the MCM3320 (maximum of 16).

• PTC State: This variable indicates what the • Total Sys Cap: This shows the sum of the gen-
utility and genset main breaker states are. set kW ratings.
Possible combinations are shown in Table 6-3. • Total Online Cap: This shows the sum of the
The PTC state may be Util Connected, Genset genset kW ratings for gensets that are online.
TABLE 6-3. PTC STATES
PTC State Description
No Source Connected Both breakers are open.
Utility Connected The utility main breaker is closed and the genset main breaker is open.
Genset connected The utility main breaker is open and the genset main breaker is closed.
Paralleled Both breakers are closed.

6-144
PRELIMINARY

MONITOR SYSTEM STATUS SUBMENUS

FIGURE 6-75. MONITOR MENUS − SYSTEM STATUS SUBMENUS

6-145
PRELIMINARY

Monitor Load Demand Submenus • Gen4Avail: This shows the status of Gen5.
The status may be Gen Does Not Exist, Of-
The Monitor Load Demand submenus are avail- fline, Waiting for Gen, Online, or Failed.
able by pressing the (14) button on the Monitor
menu. These menus show the status of the various • Gen1Cmd:
load demand functions. These menus display the
following.
• Gen2Cmd:
• LD State: This indicates the operating state
(Off, Initial Delay Timing, or Load Monitor) of
the load demand control. • Gen3Cmd:

• Nxt ShutDn: This shows which genset (Gen1,


Gen2, Gen3, Gen4, or None) will be stopped • Gen4Cmd:
if load conditions are met.
• Nxt Restrt: This shows which genset (Gen1, • GenA: This shows which genset (Gen1, Gen2,
Gen2, Gen3, Gen4, or None) will restart if load Gen3, or Gen4) is currently GenA for load de-
conditions are met. mand.
• Gen Total kW: • GenB: This shows which genset (Gen1, Gen2,
Gen3, or Gen4) is currently GenB for load de-
• Total LD Online Cap: mand.
• GenC: This shows which genset (Gen1,
• Nxt Gen Shutdown Thrshld: This shows the Gen2, Gen3, or Gen4) is currently GenC for
kW threshold for the genset bus at which the load demand.
next genset will load demand stop.
• GenD: This shows which genset (Gen1,
• Nxt Gen Restart Thrshld: This shows the kW
Gen2, Gen3, or Gen4) is currently GenD for
threshold for the genset bus at which the next
load demand.
genset will restart.
• Gen1Avail: This shows the status of Gen1. • Gen1: This shows the status of the load de-
The status may be Gen Does Not Exist, Of- mand Gen1 driver output.
fline, Waiting for Gen, Online, or Failed.
• Gen2: This shows the status of the load de-
• Gen2Avail: This shows the status of Gen2. mand Gen2 driver output.
The status may be Gen Does Not Exist, Of-
fline, Waiting for Gen, Online, or Failed. • Gen3: This shows the status of the load de-
mand Gen3 driver output.
• Gen3Avail: This shows the status of Gen3.
The status may be Gen Does Not Exist, Of- • Gen4: This shows the status of the load de-
fline, Waiting for Gen, Online, or Failed. mand Gen4 driver output.

6-146
PRELIMINARY

MONITOR LOAD DEMAND SUBMENUS

FIGURE 6-76. MONITOR MENUS − LOAD DEMAND SUBMENUS

6-147
PRELIMINARY

Monitor Load Add Shed Submenus Load Status ATS

The Monitor Load Add Shed submenus are avail- The two Load Status ATS menus show the position
able by pressing the (15) button on the Monitor status of the six transfer switches. The status can
menu. These menus show the status of the various be Not Available, No Source connected, Source 1
load add and load shed functions. These menus Connected, Source 2 Connected or Paralleled (de-
display the following. fault = Not Available).
Add Level Status Load Status Breaker
The Add Level Status menu shows the status (Do
The two Load Status Breaker menus show the
Nothing or Add Level, default = No Nothing) of the
position and the trip status of the six breakers. The
six add levels.
position can be Open, Closed, or Not Available (de-
Shed Level Status fault = Not Available). The trip status can be Not
Available, Normal, or Tripped (default = Not Avail-
The Shed Level Status menu shows the status (Do able).
Nothing or Shed Level, default = No Nothing) of the
six shed levels.

6-148
PRELIMINARY

MONITOR LOAD ADD SHED SUBMENUS

FIGURE 6-77. MONITOR MENUS − LOAD ADD SHED SUBMENUS

6-149
PRELIMINARY

Monitor Generator Bus Overload • UnderFreq OverLd Thres: This shows the un-
Submenus derfrequency offset threshold for a genset
overload condition. the Underfrequency Over-
The Monitor Generator Bus Overload submenus load threshold can be 0.1 to 10.0 Hz.
are available by pressing the (16) button on the • Genset Freq: This shows _____________
Monitor menu. These menus show the status of the ___________.
various load add and load shed functions. These
• System Freq: This shows the system nominal
menus display the following.
frequency.
• kW Stat: This shows whether or not the genset Monitor Scheduler Submenu
bus is overloaded based upon kW. The kW
status may be No Overload or Overload. The Monitor Scheduler submenu is available by
pressing the (17) button on the Monitor menu. This
• kW Thres: This shows the calculated kW over- menu shows the scheduler functions.
load threshold based on online capacity and
the % setting. • Run Command: This shows the current Run
Command coming from the scheduler func-
• Gen Tot: This shows how many of the defined tion. It can be Off, No Load, With Load, or Ex-
Gen1 thru Gen4 gensets are online. tended Parallel.
• SpareCap: This shows the difference between • Active Schedule: This shows the current Ac-
the online capacity of the four gensets and the tive Scheduler program or exception. It can be
genset bus total kW. None, Program 1, Program 2, Program 3, Pro-
gram 4, Program 5, Program 6, Program 7,
• UnderFreq OverLd Status: This shows wheth- Program 8, Program 9, Program 10, Program
er or not the genset bus is overloaded, based 11, Program 12, Exception 1, Exception 2, Ex-
on frequency. The Underfrequency Overload ception 3, Exception 4, Exception 5, or Excep-
Status may be No Overload or Overload. tion 6.

6-150
PRELIMINARY

MONITOR GENERATOR BUS OVERLOAD SUBMENUS


AND SCHEDULER SUBMENU

FIGURE 6-78. MONITOR MENUS − GENERATOR BUS OVERLOAD AND SCHEDULER SUBMENUS

6-151
PRELIMINARY

Faults Menus Fault History Table Submenus

The Faults menus are available by pressing the (4)


The Fault History Table submenus can be viewed
button on the Main menu (see Figure 6-11). These
by pressing the (5) button on the Faults submenu.
menus provide information on both fault and non-
They display information on all faults. These me-
fault events. There are six categories of Fault sub-
nus also include the fault number, a brief descrip-
menus.
tion, and the amount of time (in seconds) that the
Current Fault Submenu controller has been powered (COT = controller On
Time). Information on these faults can be viewed
The Current Fault submenu can be viewed by by pressing the and buttons. Information on
pressing the (1) button on the Faults submenu. It any of the faults can be cleared by pressing the
displays information on only the most recent fault CLR button.
that is still active. The fault number and a brief de-
scription is displayed. Fault Occurrence Table Submenus
Active Event Table Submenus
The Fault Occurrence Table submenus can be
The Active Event Table submenus can be viewed viewed by pressing the (6) button on the Faults
by pressing the (2) button on the Faults submenu. submenu. They provide information on how many
They display all active events (non-fault events). times each fault has occurred. These menus also
The event number and a brief description of the include the fault number and a brief description. In-
most recent event is displayed first. Use the and formation on these faults can be viewed by press-
buttons to scroll through the list. ing the and buttons. Press the CLR button to
clear the entire history of a fault and return to the
Event Occurrence Table Submenus
Faults main menu. The faults that are available
The Event Occurrence Table submenus can be with the MCM3320 are listed in Table 6-5.
viewed by pressing the (3) button on the Faults
submenu. They provide information on how many
TABLE 6-4. EVENT NUMBERS AND
times each event has occurred. These menus also DESCRIPTIONS
include the event number and a brief description.
Information on these events can be viewed by Event Number Event Description
pressing the and buttons. Information on any 1222 Not In auto
of the events can be cleared by pressing the CLR
button. The events that are available with the 1483 Common warning
MCM3320 are listed in Table 6-4. 2965 Genset Bus Available

Active Fault Table Submenus 2328 Utility Bus Available


2333 Genset Bus Connected
The Active Fault Table submenus can be viewed by
pressing the (4) button on the Faults submenu. 2332 Utility Bus Connected
They list all active faults. The fault number and a 2971 Test Extended Parallel
brief description of the most recent fault is dis-
played first. Use the and buttons to scroll 1916 Sync Check OK
through the list. 1534 Load Control Output Enable

NOTE: An active fault cannot be reset until the NOTE: The events listed in this table are listed in
condition causing the fault is cleared and the order they are shown on the display
the RESET button is pressed. screen.

6-152
PRELIMINARY

FAULTS MENUS X

FIGURE 6-79. FAULTS MENUS

6-153
PRELIMINARY

TABLE 6-5. FAULT NUMBERS AND


DESCRIPTIONS
Fault Number Event Description
1455 Util Main Pos Contact Fail
2396 Util Main Fail to Close
2397 Util Main Fail to Open
1219 Util Main Tripped
1914 Util Bus Phase Rotation
1912 Util Bus Loss of Phase
2331 Util Bus Under Voltage
2358 Util Bus Over Voltage
1223 Util Bus Frequency
2648 Remote I/O Comm Failure
1689 Real Time Clock Power Interrupt
1335 AC Metering Time Reached
1999 Max Parallel Time Reached
343 Hardware Failure
1456 Sync Output Limit
2416 Calibration Checksum Error
353 EEPROM Write Error
1454 Gen Main Pos Contact Fail
1452 Gen Main Fail to Close
1453 Gen Main Fail to Open
1328 Gen Main Tripped
1915 Gen Bus Phase Rotation
1913 Gen Bus Loss of Phase
1225 Gen Bus Under Voltage
1224 Gen Bus Over Voltage
1226 Gen Bus Frequency
1541 Genset Failed to Come Online
2647 Load Demand Setup Invalid
1444 Genset Bus Overload
1989 kW Load Control Output Limit
1991 kVAR Load Control Output Limit
1121 Fail to Disconnect
1458 Phase Rotation Mismatch
1457 Fail to Sync
NOTE: The faults listed in this table are listed in
the order they are shown on the display
screen.

6-154
PRELIMINARY

7. Testing and Troubleshooting


This section describes testing, diagnostics, and SYSTEM AND DIAGNOSTIC INDICATORS
troubleshooting procedures. If any problem occurs
that is not included in these procedures, contact a The MCM3320 control module includes a seven-
Cummins service representative. To troubleshoot segment LED (U51 − see Figure 7-1), used to indi-
gensets and/or transfer switches, refer to the ap- cate the following modes.
propriate equipment manual. • System Mode − When in this mode, the LED
displays a code to indicate current activity. The
FAULT AND STATUS CODES available activity codes are listed in Table 7-2.
An MCM3320 installation includes two means of • Diagnostic Mode − When in this mode, the
viewing faults and status codes. LED displays event and fault codes.
• The 7-Segment LED display located on the The control is normally in the System mode. When
MCM3320 control board in System mode, the decimal point (DP) near the
• The display panel bottom right corner of the seven-segment LED is
off and the LED displays a code to indicate current
The MCM3320 also has nine lamps that indicate activity. When in this mode, the characters listed in
what is happening in the system that is being con- Table 7-2 can be displayed.
trolled.
To switch to Diagnostic mode and view event and
SYSTEM STATUS INDICATORS fault codes, a customer-supplied fault reset switch
connected to TB2-14 must be pressed for at least
The nine lamps (DS1 thru DS9) on the MCM3320 five seconds. When in Diagnostic mode, the
control board (see Figure 7-1) are used to display decimal point near the bottom right corner of the
the system activities listed in Table 7-1. seven-segment LED is lit.

DS4
DS2 DS5
U51
DS1 DS9
DS3
DS8
DS7 DS6

DECIMAL POINT (DP)

FIGURE 7-1. MCM3320 CONTROL BOARD LEDS

7-1
PRELIMINARY

TABLE 7-1. MCM3320 SYSTEM STATUS INDICATORS


LAMP TITLE COLOR DESCRIPTION
Utility This lamp lights when the utility bus is available.
DS1 Green
Available
Utility This lamp lights when the utility main circuit breaker is closed.
DS2 Green
Connected
This lamp flashes at a 1/2 Hz rate if the board is awake (running
DS3 Heartbeat Green
normally).
Genset This lamp lights when the generator bus is available.
DS4 Yellow
Connected
Genset This lamp lights when the genset main circuit breaker is closed. It also
DS5 Yellow
Available lights when there isn’t a Genset Main but any 52GN is closed.
Common This lamp lights whenever there is a system fault.
DS6 Yellow
Alarm
This lamp lights when the MCM3320 is not in Automatic Mode. When
DS7 Not In Auto Red lit, the MCM3320 is in Manual Mode, Test Mode, or Extended Parallel
Mode.
When this lamp is flashing green, it is an indication that the MCM3320
Blinking Green is sending a correction signal for voltage or frequency to the generator
sets.
DS8 Synchronizer When this lamp is solid green, it is indicating that it is ok to manually or
Solid Green
automatically close the open breaker.
When this lamp is solid red, it is an indication of an active fail-to-sync
Red
fault.
ModBus This lamp flashes to indicate that there is communication activity on
DS9 Yellow
Activity one of the two ModBus channels (RS-232 or RS-485).

TABLE 7-2. U51 LED ACTIVITY CODES Some diagnostics are mapped to low side driver
outputs.
CODE DESCRIPTION
1 TD Start Warnings are latched until the user does a fault re-
set using the customer-supplied fault reset switch.
2 TD Stop
3 TDTP When in Diagnostic mode, the control flashes each
digit of the fault/event code, with a pause between
4 TDEN
digits and a longer pause between repetitions.
5 TDNE
6 Synchronizing
To switch from Diagnostic mode back to System
mode, press the fault reset switch for at least five
7 Sync Check OK seconds.
8 Inhibit
9 Unassigned
A Ramp Unload
b Ramp Load
C Manual Mode
d Utility Failure
E Test Mode
J Standby Mode
H Extended Parallel
− Not Available

7-2
PRELIMINARY

TEST AND ADJUSTMENT WARNING Do not allow connection of an op-


erating generator bus to a utility service with-
Basic Configuration out explicit written permission of the utility ser-
vice provider. Improper settings and practices
Before any testing of the MCM3320 can be done,
can result in personal injury, death, or serious
the basic configuration of the board must be set up
equipment damage.
and verified (see Section 6). To allow a user to set
up the board for specific application requirements, The commissioning process can result in power
a PC-based configuration tool is provided on a CD outages of varying duration and/or voltage and
for loading on to a local PC. The board can also be frequency disturbances to loads connected to the
set up by a Cummins service technician using generator set or utility buses.
InPowert. The actual commissioning process for any system
The PC may be connected to the circuit board from is dependent on the specific characteristics of that
its serial connection point using Cummins part system. The follow points provide only guidelines
number 338−4683 cable. This cable is available for proper system commissioning. A qualified sys-
from your local Cummins distributor. tem designer should provide specific commission-
ing instructions to validate proper system operation
CAUTION The MCM3320 is factory-config- and settings.
ured for gains that are most appropriate for typ-
ical applications. Adjustment of the gains by 1. Generator sets that are used in conjunction
non-qualified persons can result in misopera- with a MCM3320 must be fully commissioned
tion of the system when the synchronizer is en- as described in the Cummins generator set
abled. Defer settings to a qualified Cummins installation manual prior to commissioning of
service technician. the MCM3320 functions in the system.

Bench Tests 2. Verify that all wiring is installed as required by


the system control drawings and the Cummins
Connect a 12 or 24VDC control power source to interconnecting drawings for the MCM3320.
one of the control power inputs (TB2-7 and TB2-8,
9, 11 or 12). Verify that the control is operating by 3. Set the system up for manual operation so that
viewing DS3 blinking green. the system does not attempt to switch power
to loads. Check the source availability set
If an AC power source of an acceptable magnitude
points in the MCM3320 for proper settings.
and number of phases is available, the board can
verify that proper voltage is sensed at each voltage 4. Verify that DC control power is available at the
reference point, again by verifying that the master synchronizer. DS3 should be flashing
appropriate LED (DS1−green for utility side and green to indicate that the control is ready to op-
DS5−amber for generator bus side) operates when erate.
the source is connected. Note that in the default
configuration, the utility available and generator 5. Verify that the sources are connected properly
bus available relay drivers should also operate to the master synchronizer. Energize each
during this test (TB2-17 and 18). source individually, and verify that the voltage
If both sources are connected simultaneously and of a calibrated meter, the MCM3320 metering,
the sources are synchronized the board should and the switchboard metering (if provided) is
consistently operating. Make calibration ad-
display a ”synchronized” indication by lighting DS8
justments on the MCM3320 as necessary.
continuously. If the synchronizer is enabled
(TB1-10 to 11) and DS8 is flashing both sources 6. Verify proper connections to the generator
are available and the device is attempting to sets from the master synchronizer. With sys-
synchronize them. tem loads connected to the utility, the synchro-
Commissioning nizer not enabled, and a generator set run-
ning, adjust the generator set frequency and
Commissioning of Cummins PowerCommand voltage to a value that is different from utility
generator sets and MCM3320 should be super- frequency by 1 hertz, and utility voltage by
vised by a qualified Cummins service technician. approximately 3%. Enable the synchronizer

7-3
PRELIMINARY

and observe that the generator set correctly one second after receiving a signal to close. When
matches the utility frequency and voltage with- this occurs, the Breaker Fail to Close message is
out connecting the generator set to the utility displayed at the PowerCommand control and the
source. If desired, the settings can be done in amber warning lamp lights.
each direction to verify the capabilities of the
device to drive adjustments in both directions. When this condition occurs, consider the following
Reset generator set frequency and voltage to possible causes of failure and review the circuit
levels to those prior to running test. Repeat breaker manual.
this test for each generator set in the system. • The springs are not charged, possibly due to
a faulty charging motor or circuit.
7. Verify that the generator sets synchronize
• The mechanism is physically jammed and is
properly as a group. With the utility source
unable to move.
available, the generator sets operating with
system loads connected and load properly • A breaker fault lockout is activated because of
balanced between all machines, enable the an overcurrent condition.
master synchronizer and verify that the gener- WARNING Troubleshooting procedures pres-
ator sets synchronize as a group without dis- ent hazards that may result in severe personal
rupting load sharing, and to within the sync injury or death. Only trained and experienced
check parameters set into the MCM3320. The personnel are to perform the following proce-
“SYNC OK” output of the MCM3320 can be dures.
used to signal that the control considers the
generator bus to be synchronized. An external WARNING Do not release the circuit breaker
device should be used to validate the synchro- charging handle until after completing the en-
nizing accuracy of the system. The Cummins tire charging operation. Releasing the handle
service technician may make adjustments before the charging operation is complete
necessary to optimize synchronizing speed. causes the handle to move upward with
enough velocity and force to cause personal
8. Complete the balance of system operation injury.
tests in manual state, then repeat system test- CAUTION The springs are fully charged when
ing in all automatic modes, to totally verify sys- a metallic click is heard and the spring charge
tem operation. indicator reads charged. To avoid damaging
the circuit breaker, do not force the handle be-
TROUBLESHOOTING yond this point.
WARNING Incorrect installation, service, or To troubleshoot this condition,
replacement of parts can result in severe per-
1. Locate the paralleling breaker for the genset
sonal injury or death and/or equipment dam-
with the Breaker Fail-to-close alarm. If the
age. Only trained and experienced personnel
breaker status window displays Spring Dis-
are to perform the following procedures.
charged, continue with step 2. If not, go to step
4.
Malfunctioning Lamps, Meters, Gauges,
and/or Starter Solenoid 2. At the genset displaying the Breaker Fail-to-
Close alarm,
Meters and other control device may malfunction if
any DC fuse is blown. If you are experiencing prob- a. Place the system mode select switch in the
lems with these devices, check the DC fuses and Off position to stop genset operation.
replace as necessary. All fuses are in fuse holders b. Locate the paralleling circuit breaker. Use
that include an integral fuse blown indicator that the emergency charging handle to charge
functions only in AC circuits. the springs. the ratchet requires 10 to 12
pumping operations to charge the springs
Paralleling Breaker Fail-to-Close Alarm completely.
A Paralleling Breaker Fail-to-Close condition exists c. At the genset’s control panel, place the sys-
when the genset circuit breaker fails to close within tem mode select function to Auto. If the

7-4
PRELIMINARY

genset starts and the Circuit breaker turn the 0/Manual/auto switch to the 0 position.
Closed lamp lights, continue with step 3. If Reset the genset alarms. this resets the con-
not, repeat steps 2a and 2b a second time trols for normal operation.
before going to step 3.
8. If the problem is not resolved with these proce-
3. After the operation is complete, verify proper dures, contact a Cummins service representa-
operation of the breaker charge circuit. If the tive.
breaker charge circuit is operating correctly,
go to step 4. If not, go to step 8. Troubleshooting Using Fault / Event
4. If manual paralleling is desired, refer to the Codes
Manual Operation information in Section and Table 7-3 lists the possible fault/event codes that
continue with step 5. If not, go to step 7. are available with the MCM3320. This table also
5. If the breaker was tripped by a fault condition lists the possible cause(s) and provides corrective
AND is the circuit breaker provided with a actions.
manual rest fault indicator, then continue with To reset faults,
step 6. If not, go to step 7.
1. Correct the fault condition.
6. Reset the fault indicator and determine the
cause of the fault before attempting to operate 2. Make sure the control is not in Diagnostic
this breaker. If the cause was found and the State Mode (decimal point is not lit). If in Diag-
problem corrected, continue with step 7. If not, nostic State Mode, press the reset switch for
go to step 8. at least five seconds.

7. If in Manual Mode, use the genset control 3. Activate a Reset input momentarily (less than
screen to turn the genset off. If in auto Mode, 5 seconds).

7-5
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
343 Hardware Failure 1. At least one of the following 1. Identify which of the faults is active
Warning faults is active. by observing the fault displayed on
• Calibration Checksum Warn- the control panel, by observing the
ing (Fault Code 2416) lamps on the MCM3320 control
board, or by using InPower.
• EEPROM Write Failure
Warning (Fault Code 353) 2. Take corrective steps for the active
specific fault(s), as described in this
• Utility Main AC Metering Fail- section.
ure (Fault Code 1335)
3. Cycle power to the MCM3320.
• Generator Bus AC Metering
Failure (Fault Code 1335) 4. If the problem continues, replace the
control board.
2. The hardware version is not
compatible with the software
version.
353 EEPROM Write The current value in RAM memory Clear the fault either by cycling power
Failure Warning (to-be-written value) does not to the MCM3320 or by resetting the
match its post-written value in processor via an InPower initial
EEPROM. This problem occurs calibration.
when you attempt to save a trim
by using either InPower or the
LCD display and it is not
successful. This problem may also
occur when the MCM3320 tries to
automatically save data on a
periodic basis.
1121 Failure to The Genset Main (GM) Circuit Follow the corrective steps, as
Disconnect Breaker or the Utility Main (UM) described in this section, for the
Warning Circuit Breaker has an active appropriate fault.
Fail-To-Open fault. • Genset Main Breaker Fail to Open
Warning (Fault Code 1453)
• Utility Main Breaker Fail to Open
Warning (Fault Code 2397)

7-6
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1219 Utility Main There is an overcurrent / short 1. Check for these problems down-
Breaker Tripped circuit condition at the circuit stream from the Utility Main Breaker.
Warning breaker. 2. Make sure the Utility Main Breaker
tripping adjustments are properly
set.
3. Make sure there are no synchroniz-
ing problems that could trip the UM
circuit breaker just at closing time.
Check for the correct phase se-
quence connections at the circuit
breaker,
4. Make sure all analog reading meters
are calibrated in order to have real
readings of the Utility Main, Genset
Main, and each genset.
5. Make sure there are no breaker
protection coordination problems in
the electrical installation.
1222 Not in Auto The Synchronizing System is not 1. Make sure you want to work in this
Event in Auto mode. mode. If you do not, check relevant
terminal blocks (TB10-6) on the
MCM3320 and related switches for
misoperation.
2. Check cabling from the switches to
the terminal blocks.
3. Make sure the control switch opera-
tion is OK.
4. Use InPower to verify that the
MCM3320 is properly processing
contact data.
1223 Utility Frequency The Utility frequency is greater 1. Check the lower and upper utility
Warning than the upper drop-out threshold frequency drop-out settings on the
or it is less than the lower drop-out MCM3320. To determine if you are
threshold and it stays there for a trying to synchronize to a depend-
time period that is greater than the able source, create a sensible band-
drop-out time delay. width that tells you how good the
Utility is. InPower can be used to ac-
complish this.
2. To avoid lengthy synchronizing op-
eration, make sure the Utility fre-
quency is not varying a lot all of the
time.
3. Make sure the MCM3320 is measur-
ing frequency correctly.

7-7
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1224 Genset Main The GM voltage is greater than 1. Make sure the Genset overvoltage
Overvoltage the Genset overvoltage drop-out threshold is safe for the connected
Warning threshold and it stays there for a load and make that this value is not
time period that is greater than the too close to the rated voltage.
drop-out time delay. 2. Make sure that the drop-out time
delay for this fault is not set too low.
3. Check the AVR system operation of
each individual genset.
4. Make sure all AC voltage sensors
are properly calibrated at the
MCM3320 and the gensets.
5. Use InPower to monitor and make
any necessary adjustments.
6. If used, check external transformer
connections.
1225 Genset Main The generator bus voltage is less 1. Make sure the genset undervoltage
Undervoltage than the Genset undervoltage threshold is safe for the connected
Warning drop-out threshold and it stays load and make that this value is not
there for a time period that is too close to the rated voltage.
greater than the drop-out time 2. Make sure that the drop-out time
delay. delay for this fault is not set too low.
3. Check the AVR system operation of
each individual genset.
4. Make sure all AC voltage sensors
are properly calibrated at the
MCM3320 and the gensets.
5. Use InPower to monitor and make
any necessary adjustments.
6. Make sure the wire size and dis-
tance is correct and check for loose
connections.

7-8
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1226 Genset The GM frequency is greater than 1. Verify that the lower and upper GM
Frequency the upper drop-out threshold or it frequency drop-out settings on the
Warning is less than the lower drop-out MCM3320 create a sensible band-
threshold and it stays there for a width that makes load-feeding a
time period that is greater than the safe activity. InPower can be used to
drop-out time delay. accomplish this. Be aware that the
GM settings harmonize with the
genset settings.
2. To avoid lengthy synchronizing op-
eration, make sure the Utility fre-
quency is not varying a lot all of the
time.
3. Verify that the MCM3320 is measur-
ing frequency correctly.
4. Verify that the genset control is cor-
rectly calibrated.
1328 Genset Main The trip indication contact on the 1. Check to see if there is an overcur-
Breaker Tripped GM breaker is closed. rent/short circuit condition at the cir-
Warning cuit breaker.
2. Check for the following problems
downstream for the GM breaker.
• Verify that the GM breaker tripping
adjustments are properly set.
• Verify that there are no synchroniz-
ing problems that could trip the
GM breaker just at closing time.
Check for correct phase sequence
connections at the terminal block.
• Verify that all analog reading me-
ters are calibrated so that there
are real readings of Utility Main,
Genset Main, and each genset.
• Make sure that there are no break-
er protection coordination prob-
lems in the electrical installation.

7-9
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1335 AC Metering Out At least one of the following 1. Use InPower to determine if the
of Range variables are out of range in utility generator bus or the utility bus is the
Warning bus and/or generator bus analog source of the problem.
measurements. 2. Verify that the meter calibration is
• Voltage okay.
• Current 3. Verify that the MCM3320 VT and CT
• kW ratios are correctly set.
• kVAR 4. Verify that the VT and CT rated val-
ues match the ones set in the
• kVA MCM3320.
• Power Factor 5. Check the number of turns on each
of the built-in CTs to verify that they
comply with requirements regarding
5A-secondary and 1A-secondary.
6. Verify that the CT and VT polarities
and connections are okay.
1444 Genset Bus The total Kw delivered by the 1. Verify that the genset’s kW power is
Overload genset bus is equal to or greater greater than the power demanded
Warning than the genset bus kW overload by the connected load. Check for
threshold continuously for the faulted gensets. Use different me-
genset bus kW overload time ters than the built-in ones included
delay AND/OR the in the MCM3320.
underfrequency delta (system 2. Make sure meter calibration is OK.
frequency − current genbus
3. Make sure the PT and CT ratios are
frequency) is equal to or greater
well set in the MCM3320. Make sure
than the genset bus
the PTs and CTs are operating.
underfrequency overload
threshold continuously for the 4. Verify that the PT and CT rated val-
genset bus underfrequency ues matches those set in the
overload time delay. MCM3320 and your system actual
rated values.
5. Make sure there are no low-frequen-
cy conditions on the generator bus
due to poor quality fuel.
6. Check your fuel supply for inap-
propriate conditions. Check all com-
ponents (dirty filters, pipe size, etc.).

7-10
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1452 Genset Main A close command is sent to the 1. Verify that there is an output close
Breaker Fail to GM breaker but it does not close signal from the MCM3320 to the GM
Close Warning and an incoming close signal does breaker.
not show up on the MCM3320 2. Check the wiring between the
before the time delay expires. MCM3320 and the GM breaker.
3. While making sure to avoid contact
with Utility power, check the GM
breaker operation by simulating a
signal at its close terminal.
4. While making sure to avoid contact
with Utility power, check operation of
GM position contacts “A” and “B.”
5. Use the InPower Monitor menu to
monitor relevant discrete signals.
6. Make sure the GM breaker spring-
charging mechanism is operative.

1453 Genset Main Although an Open command is 1. Verify that there is an output open
Breaker Fail to sent to the GM breaker, it does not signal from the MCM3320 to the GM
Open Warning open and an Open signal does not breaker.
show up on the MCM3320 before 2. Check the wiring between the
the time delay expires. MCM3320 and the GM breaker.
3. Check the GM breaker operation by
simulating a signal at the shunt trip.
The Utility breaker must be open.
4. Check operation of GM position con-
tacts “A” and “B.” The Utility breaker
must be open. Check wiring to the
MCM3320.
5. Use the InPower Monitor menu to
monitor relevant discrete signals.
6. Make sure the GM breaker spring-
charging mechanism is operative.

1454 Genset Main Signals from position contacts “A” 1. Verify that the wiring of contacts “A”
Breaker Position and “B” are contradictory: one and “B” is according to proper wir-
Contact Warning indicates the breaker is open and ing: each one must be wired to spe-
the other indicates the breaker is cific block terminals. Do not inter-
closed. In order for this fault to be change positions.
displayed, the contradictory 2. Verify that the signals coming to the
message must be active for two MCM3320 from these contacts are
seconds. transmitted in a proper way to the
block terminals by the whole wiring.
3. While making sure to avoid contact
with Utility power, make sure the
contacts have a good mechanical
operation by manually opening and
closing the GM.

7-11
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1455 Utility Main Signals from position contacts “A” 1. Verify that the wiring of contacts “A”
Breaker Position and “B” are contradictory: one and “B” is according to proper wir-
Contact Failure indicates the breaker is open and ing: each one must be wired to spe-
Warning the other indicates the breaker is cific block terminals. Do not inter-
closed. In order for this fault to be change positions.
displayed, the contradictory 2. Verify that the signals coming to the
message must be active for two MCM3320 from these contacts are
seconds. transmitted in a proper way to the
block terminals by the whole wiring.
3. While making sure to avoid contact
with Utility power, make sure the
contacts have a good mechanical
operation by manually opening and
closing the UM.
1456 Synchronizer The synchronizer fails to achieve 1. Verify that the Failure to Synchro-
Output Limit a match point when it puts the nize time is not too low.
Warning voltage and/or frequency at their 2. Verify that the Permissive Phase
extreme values (lowest, highest) Window is not too low.
of the allowed bandwidth for a
3. Verify that the Permissive Voltage
time period that is greater than the
Window is not too low.
fail-to-synchronize time period.
This diagnostic logic is shown 4. Check to see that the Permissive
below. Window time is not too high.

If:
Frequency match is at the high or low limit, or
Voltage match is at the high or low limit, or
Voltage match has failed,
Then a synchronizer output warning is initiated.
1457 Fail to This warning is displayed when 1. Verify that the voltage bias and fre-
Synchronize the synchronizer is ON AND quency bias signals to the gensets
Warning Permissive Close is allowed. are arriving at the correct terminals.
Permissive Close Not Allowed is 2. Verify that the MCM3320 is sending
continuously for a Failure to bias signals to the gensets.
Synchronize time period. 3. Check the speed-governing system
of each genset.
4. Check the fuel quality.
5. Make sure that all MCM3320 and
genset meters are properly cali-
brated.

7-12
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1458 Synchronizer This warning is displayed when 1. Use InPower to observe data proc-
Phase Rotation the synchronizer is ON AND the essing on the MCM3320.
Mismatch the Utility Phase Rotation is 2. Verify that Genset and Utility input
Warning different from the Genset Phase voltage lines to the MCM3320 match
Rotation and this status is true the ones shown on the terminal
continuously for a Fail-to- block as to Phase Rotation and line-
Synchronize time period. to-line match.
3. Make sure the Genset and Utility
power lines are properly connected
to relevant breakers. Improper con-
nections can result in a catastrophic
breaker closure.
4. Check the Genset and Utility VT
connections and polarities, if used.
1483 Common This warning is active whenever Search for the active warning and fol-
Warning Event any other warning fault state is low the appropriate relevant trouble-
active. shooting procedures elsewhere in this
document.
1534 Load Control This message is displayed when This message is for information
Output Event there is an active load control purposes only.
output event. This message can be mapped to an
output.
1541 Genset Failed to This warning only applies to 1. Although only one faulted genset
Come Online installations with four or fewer can trigger this fault, check to see in
Warning gensets. more gensets are in the same condi-
This warning is displayed when tion.
the MCM3320 sends a start signal 2. Check each genset control to see
to a genset for coming online but it what fault has occurred and follow
does not do it within the genset fail the genset troubleshooting instruc-
time setting period. When the tions. If there is no active fault and
related paralleling breaker closes, the genset appears to be operating
the time stops. normally, check breaker operation
When the MCM3320’s menu and check breaker position signaling
system is used to set the genset’s to the MCM3320.
kW value to zero, then the control 3. Check to see that the genset’s fail-
does not acknowledge the ure-to-start time delay is not set too
existence of the genset. low.
4. Check for any other active faults and
correct them, as described else-
where in this manual.

7-13
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1689 Real Time Clock This warning is displayed to Use the control’s menu system to set
Power Interrupt remind you to set the real-time the real-time clock properly.
Warning clock properly (date and time)
when the control is powered up.
The clock will retain the time for at
least 24 hours without DC power
being supplied to the control.
1912 Utility Loss of The phase difference in electrical 1. Check to see that there is no incom-
Phase Warning degrees between adjacent phase ing missing line at the MCM3320
UM voltage phasors is greater relevant Utility voltage inputs.
than 150 degrees OR less than 90 2. Make sure there are no loose con-
degrees and this is true nections.
continuously for a Utility Loss of
3. Since there is little chance that there
Phase Drop-Out Delay.
is a real phase difference in Utility
voltage phasors, focus on bad con-
nections.
1913 Genset Loss of This warning is active if the phase 1. Verify that there is no missing in-
Phase Warning difference in electrical degrees coming line at the MCM3320 rele-
between adjacent phase GM vant to the GM voltage inputs.
voltage phasors is greater than 2. Make sure there are no loose con-
150 degrees OR less than 90 nections.
degrees and this remains true
3. Since there is little chance that there
continuously for the Utility
is a real phase difference in Utility
Loss-of-Phase Drop-Out Delay.
voltage phasors, focus on bad con-
nections.
1914 Utility Phase This warning is active whenever 1. Use InPower to verify data process-
Rotation Warning the Utility Phase Rotation ing on the MCM3320.
mismatches the System Phase 2. Use InPower to check the System
Rotation for at least one second. Phase Rotation setting.
3. Verify that he Utility input voltage
lines to the MCM3320 match the
ones shown on the terminal block as
to phase rotation and line-to-line
voltage.
4. To avoid the possibility of a cata-
strophic breaker closure, make sure
your genset and utility power lines
are properly connected to relevant
breakers.
5. Check the genset and utility VT con-
nections and polarities, if used.

7-14
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1915 Genset Phase This warning is active whenever 1. Use InPower to verify data process-
Rotation Warning the Genset Phase Rotation ing on the MCM3320.
mismatches the System Phase 2. Use InPower to check the System
Rotation for at least one second. Phase Rotation setting.
3. Verify that he Genset input voltage
lines to the MCM3320 match the
ones shown on the terminal block as
to phase rotation and line-to-line
voltage.
4. To avoid the possibility of a cata-
strophic breaker closure, make sure
your genset and utility power lines
are properly connected to relevant
breakers.
5. Check the genset and utility VT con-
nections and polarities, if used.
1916 Sync Check OK This event is for information This event can be mapped to a pro-
Event purposes only. It is active grammable output.
whenever a Sync Check Close
Allowed event is active.
1989 kW Load Control This warning is active whenever a 1. Check the wiring from the MCM3320
Output Warning genset has not been able to reach to the Genset load setpoint input to
its load setpoint and the kW load verify that there are no problems
control output on the MCM3320 with allowing signal arrival.
has been at its highest limit OR its 2. Verify that the load kW setpoints at
lowest limit for at least 60 the genset’s control is not too low.
seconds.
3. Make sure that all on-line gensets
are able to deliver demanded power
and applying derating factors.
4. Verify that all meters on the
MCM3320 are well calibrated.
5. Make sure that all GM CTs and VTs
are properly set on the MCM3320.
6. Check the speed governing systems
on all gensets, and check the ramp
times.

7-15
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
1991 kVAR Load This warning is active whenever a 1. Verify that the wiring from the
Control Output genset has not been able to reach MCM3320 to the Genset load set-
Warning the load setpoint and the kVAR point input is allowing signal arrival
Load Control Output on the with no problem.
MCM3320 has been at the highest 2. Verify that the load kVAR setpoints
limit OR the lowest limit for at least at the genset’s control is not too low.
60 seconds.
3. Make sure that all installed gensets
are able to deliver demanded power
after applying derating factors.
4. Verify that all meters on the
MCM3320 are well calibrated.
5. Make sure that all CTs and VTs are
properly set on the MCM3320.
6. Check the speed governing systems
on all gensets, and check the ramp
times.

1999 Maximum This warning is active whenever 1. Verify that the Maximum Parallel
Parallel Time the unit is NOT in extended Time setting is not too low for your
Reached parallel node AND the Maximum purposes. The maximum available
Warning Parallel Time Delay has expired. time is 30 minutes.
2. Make sure the test-start switch is in
good mechanical and electrical con-
dition.
3. Check the timer at your external
control unit that drives this switch
input.

2328 Utility Bus This event is for information This event can be mapped to a pro-
Available Event purposes only. grammable output.
This event is active if the
faults/events listed below are
inactive simultaneously. If a
sensor is disabled, the fault is
considered inactive.
• Fault 2331 − Utility Undervol-
tage Warning
• Fault 2358 − Utility Overvol-
tage Warning
• Fault 1223 − Utility Frequen-
cy Warning
• Fault 1912 − Utility Loss of
Phase Warning
• Fault 1915 − Genset Phase
Rotation Warning
• Fault 1914 − Utility Phase
Rotation Warning

7-16
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
2331 Utility The utility bus voltage is less than 1. Make sure the Utility Undervoltage
Undervoltage the Undervoltage Drop-Out Threshold is safe for the connected
Warning Threshold and it stays there for a load.
time period greater than the 2. Verify that this value is not too close
Undervoltage Drop-Out Delay. to the rated voltage.
3. Make sure that the time delay for
this fault is not set too low.
4. Check the AVR system operation at
each individual genset.
5. Make sure that all AC voltage sen-
sors are properly calibrated at the
MCM3320 and the Utility.
6. Use InPower to monitor and make
any necessary adjustment.
7. Check the wire size, distance, and
loose connections.
2332 Utility Bus This message is displayed when This message is for information
Connected Event the utility main breaker position purposes only.
auxiliary contacts send a message This message can be mapped to an
stating that the utility main breaker output.
is closed.
2333 Genset Bus This message is displayed when This message is for information
Connected Event the genset main breaker position purposes only.
auxiliary contacts send a message This message can be mapped to an
stating that the genset main output.
breaker is closed.
2358 Utility The utility bus voltage is greater 1. Make sure the Utility Undervoltage
Overvoltage than the Utility Overvoltage Threshold is safe for the connected
Warning Drop-Out Threshold and it stays load.
there for a time period greater 2. Make sure the Utility Overvoltage
than the Drop-Out Delay. Threshold is safe for the connected
load.
3. Verify that this value is not too close
to the rated voltage.
4. Make sure that the time delay for
this fault is not set too low.
5. Make sure that all AC voltage sen-
sors are properly calibrated in the
MCM3320.
6. Use InPower to monitor and make
any necessary adjustment.
7. Check VT connections, if used.

7-17
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
2396 Utility Main This fault indicates that a close 1. Verify that there is an output close
Circuit Breaker command was sent to the UM signal from the MCM3320 to the UM
Fail-to-Close breaker but it did not close and the breaker.
Warning incoming close signal did not 2. Check the cabling between the
show up on the MCM3320 before MCM3320 and the UM breaker.
the time delay expired.
3. Check UM-breaker operation by
simulating a signal at its close termi-
nal.
4. Check operation of the UM “A” and
“B” position contacts. Check the wir-
ing to the MCM3320.
5. Use InPower to monitor relevant dis-
crete signals at the Monitor menu.
6. Make sure the UM-breaker spring-
charging mechanism is operative.
7. Verify that the sequence of your
specific topology application is cor-
rect.
2397 Utility Main This fault indicates that an open 1. Verify that here is an output open
Circuit Breaker command was sent to the UM signal from the MCM3320 to the UM
Fail-to-Open breaker but it did not open and the breaker.
Warning incoming open signal did not show 2. Check the cabling between the
up on the MCM3320 before the MCM3320 and the UM breaker.
time delay expired.
3. Check UM-breaker operation by
simulating a signal at the shunt trip.
4. Check operation of the UM “A” and
“B” position contacts. Check the wir-
ing to the MCM3320.
5. Use InPower to monitor relevant dis-
crete signals at the Monitor menu.
6. Make sure the UM-breaker spring-
charging mechanism is operative.
7. Verify that the sequence of your
specific topology application is cor-
rect.
2416 Calibration This warning is displayed 1. Cycle power to the MCM3320.
Checksum Error whenever there is a specific 2. If the fault persists, use InPower to
Warning mismatch regarding comparison of make an Initial Calibration.
some internal data on the
3. If the problem continues, replace the
microprocessor.
control board.

7-18
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
2647 Load Demand This warning is displayed when 1. Make sure that up to four gensets
Setup Warning incorrect data was entered on the are set with a non-zero Kw rating. If
control’s Load Demand Setup your installation includes more gen-
menu. The Load Demand feature sets, the additional gensets must
is only available when there are have their Kw rating set to zero.
two, three, or four gensets. 2. To avoid nuisance starting a stop-
ping, make sure that the difference
between the pickup and dropout is
at least 5%. Although some applica-
tions may want a tighter trim, it is
recommended that default differ-
ence be set to 20%.
3. Verify that the Genset Fail time
delay be set to a number that is less
than the Load Demand Initial time
delay and the Load Demand Shut-
down time delay.
2648 Remote I/O This warning is displayed when 1. Check for loose connections and
Communications the MCM3320 loses communica- broken wiring.
Failure Warning tion with the optional AUX101 I/O 2. If present, verify that the AUX102
module expansion board is attached to the
AUX101.
3. Check to see that the AUX101 com-
munications LED is green.

7-19
PRELIMINARY

TABLE 7-3. CONTROL TROUBLESHOOTING (CONT.)


WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service procedures. Review the safety precautions
on pages xvii and xviii.
FAULT/
DESCRIPTION POSSIBLE CAUSE CORRECTIVE ACTION
EVENT CODE
2965 Genset Bus This event is for information This event can be mapped to a pro-
Available Event purposes only. grammable output.
This event is active if the
faults/events listed below are
inactive simultaneously. If a
sensor is disabled, the fault is
considered inactive.
• Fault 1328 Generator Bus
Breaker Tripped Warning
• Fault 1452 − Generator Bus
Breaker Fail-To-Close Warn-
ing
• Genset Stop Command must
be inactive and Gen CB can
be open or closed
• Fault 1225 − Generator Bus
Undervoltage Warning
• Fault 1224 − Generator Bus
Overvoltage Warning
• Fault 1226 − Generator Bus
Frequency Warning
• Fault 1913 − Generator Bus
Loss of Phase Warning
• Fault 1915 − Generator Bus
Phase Rotation Warning
2971 Test / Extended This message is displayed when a This message is for information
Parallel Event test or extended parallel session is purposes only.
active. This message can be mapped to an
output.
None Lost Settings Scheduler Program and Exception After a download, manually re-establish
settings are lost if the controller the settings.
firmware is downloaded.
Transition Type and Extended After an Update Calibration or Capture
Parallel Enable settings are not File Overlay, check the System Setup
properly restored when using settings and correct them, if necessary.
InPower Update Calibration or
Capture File Overlay features.

7-20
PRELIMINARY

ABNORMAL SCENARIOS / FAULT actions from there. If the tripped input goes inac-
REACTION tive, the utility source can be considered available
again. (This is not a latched operational state, even
In general, the rules for abnormal situations are to though a user reset is required to clear the fault.)
try to connect to an available source (utility pre-
ferred) and to avoid taking any breaker actions Utility Main Breaker Disconnected
which could unintentionally parallel two sources.
If the utility main breaker is racked out for service,
Utility Main Fail to Open the MCM3320 sees this as a utility breaker contact
failure and starts the gensets and transfers to the
If a utility main fail to open occurs during an open genset bus. If this operation is not desired, the indi-
transition transfer to the genset bus, the vidual genset controls must be put in the Off mode.
MCM3320 flags the fault and continues trying to The MCM3320 does NOT have a cell switch input.
open the utility breaker.
Genset Main Fail to Open
If a utility main fail to open occurs during a closed
transition transfer or extended paralleling, the If a genset main fail to open occurs during an open
MCM3320 flags the fault, stops trying to open the transition transfer to the utility bus, the MCM3320
utility breaker, and opens the genset main breaker. flags the fault and continues trying to open the gen-
It will not reattempt to open the utility breaker until set breaker.
the user resets the fault. If a genset main fail to open occurs during a closed
transition transfer or extended paralleling, the
Utility Main Fail to Close
MCM3320 flags the fault, stops trying to open the
If a utility main fail to close occurs, the MCM3320 genset breaker, and opens the utility main breaker.
treats this as a utility source failure. It takes the nor- It will not reattempt to open the genset breaker until
mal actions for a utility source failure and will stay in the user resets the fault.
this state until the user resets the fault.
Genset Main Fail to Close
Utility Main Breaker Contacts If a genset main fail to close occurs, the MCM3320
Normally the control expects the breaker ‘a’ and ‘b’ treats the genset source as not available and takes
contacts to be in opposite states. If they are not, the normal actions from there. This state is latched un-
MCM3320 flags the fault and considers the utility til the user resets the fault.
breaker to be closed. If the current of all three Genset Main Breaker Contacts
phases are above an adjustable threshold (5% de-
fault), the control has confirmed that the breaker is Operation is analogous to Utility Main Breaker
closed. If this is not the case the control considers Contacts.
the utility source as failed and takes normal actions
from there. Genset Main Breaker Tripped

If the control attempts to open the utility breaker, Operation is analogous to Utility Main Breaker
the breaker contacts may or may not read correctly. Tripped.
If they read correctly (breaker is open), the transfer
Genset Main Breaker Disconnected
to the genset can proceed. If the contacts are still
indicating conflicting information, then a transfer to If the genset main breaker is racked out, the
the genset is not possible. In this case, it is possible MCM3320 sees this as a genset main breaker con-
that the load could be unpowered, depending on tact failure which results in the genset source being
the actual state of the utility breaker. This contact unavailable.
failure state is latched until the user resets the fault.
Fail to Disconnect
Utility Main Breaker Tripped
A failure to disconnect can occur when the genset
If the utility breaker tripped input on the MCM3320 and utility sources are paralleled. If one of the
is active, the MCM3320 flags a fault and considers breakers fails to to open when commanded to do
the utility source as failed and then takes normal so, the fail to disconnect logic then tries to open the

7-21
PRELIMINARY

other breaker. If it succeeds, the action is complete transfer to the utility, overriding the retransfer time
and this state is latched until the user resets the fail delay and any active retransfer inhibit.
to open fault. However, if upon attempting to open
the second breaker, it too fails to open, then the If the genset bus fails while paralleled, the
MCM3320 flags the fail to disconnect fault and acti- MCM3320 immediately opens the genset main
vates the breaker inhibit line to the individual gen- breaker.
set controls in a last attempt to disconnect. In addi- Utility Source Failure
tion, the fail to disconnect fault can be mapped to
one of the eight configurable outputs which can in Aside from the normal utility source failure opera-
turn be used to externally trip a breaker. This entire tion, if the utility source fails while paralleled, the
logic function can be optionally disabled. MCM3320 immediately opens the utility main
breaker.
Maximum Parallel Time
Lockout
If extended paralleling is not enabled, then the
maximum paralleled time is enforced by the A number of the faults can cause the control opera-
MCM3320. If the maximum parallel time is exceed- tion to be restricted until the user resets the fault (as
ed, the MCM3320 disconnects from the genset bus described in some of the above abnormal scenar-
and flags a maximum parallel time fault. This state ios). Collectively this is called control “lockout”.
is latched until the user resets the fault. (For exam- The control panel has an LED on it which indicates
ple, paralleling cannot occur again until the fault is this situation. The faults which cause control “lock-
rest.) out” are:
Fail to Synchronize 1. Utility Breaker Fail to Close Fault State = Ac-
tive
If the synchronizer is unable to bring the genset bus
into sync with the utility bus within the fail-to-sync 2. Utility Breaker Fail to Open Fault State = Ac-
time delay, the MCM3320 flags the fault. A fail to tive
synchronize can occur for a number of reasons: the
utility is unstable, the utility frequency or voltage is 3. Utility Breaker Position Contact Fault State =
out of range of the synchronizer, the genset bus is Active
unstable, etc.
4. Genset Breaker Fail to Close Fault State = Ac-
If a fail to synchronize occurs, the MCM3320 can tive
take one of three actions:
5. Genset Breaker Fail to Open Fault State = Ac-
• The default action is to continue trying to syn- tive
chronize.
6. Genset Breaker Position Contact Fault State
• The MCM3320 can be configured to stop syn- = Active
chronizing until the user resets the fault.
• The MCM3320 can be configured on a retran- 7. Fail to Synchronize Fault State = Active AND
sfer to utility to go back to the utility on an open Fail to Sync Lockout Enable = Enabled
transition.
8. Maximum Parallel Time Fault State = Active
Genset Bus Failure
9. Genset Bus Overload Fault State = Active
If the genset bus fails during a test with load, the AND (Load Demand Enable = Enabled OR
MCM3320 does an immediate open transition re- Load Add Shed Enable = Enabled)

7-22
PRELIMINARY

8. Wiring Diagrams
This section includes the following: Page
MCM3320 Wiring Diagram − Switchgear Interconnect (Transfer Pair) . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
MCM3320 Wiring Diagram − Genset Interconnect (Transfer Pair) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
MCM3320 Wiring Diagram − Customer I/O Interconnect (Transfer Pair) . . . . . . . . . . . . . . . . . . . . . . . . 8-5
MCM3320 Wiring Diagram − Switchgear Interconnect (Common Bus) . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
MCM3320 Wiring Diagram − Genset Interconnect (Common Bus − 4 Gensets or Less) . . . . . . . . . . . 8-7
MCM3320 Wiring Diagram − Genset Interconnect (Common Bus − 5 Gensets or More) . . . . . . . . . . 8-8
MCM3320 Wiring Diagram − Customer I/O Interconnect (Common Bus) . . . . . . . . . . . . . . . . . . . . . . . . 8-9
MCM3320 Wiring Diagram − Switchgear Interconnect (Isolated Bus with GM) . . . . . . . . . . . . . . . . . . 8-10
MCM3320 Wiring Diagram − Genset Interconnect (Isolated Bus with GM) . . . . . . . . . . . . . . . . . . . . . 8-11
MCM3320 Wiring Diagram − Customer I/O Interconnect (Isolated Bus with GM) . . . . . . . . . . . . . . . . 8-12
MCM3320 Wiring Diagram − Switchgear Interconnect (Isolated Bus with No GM) . . . . . . . . . . . . . . . 8-13
MCM3320 Wiring Diagram − Genset Interconnect (Isolated Bus with No GMs − 4 Gensets or Less)8-14
MCM3320 Wiring Diagram − Genset Interconnect (Isolated Bus with No GMs − 5 Gensets or More)8-15
MCM3320 Wiring Diagram − Customer I/O Interconnect (Isolated Bus with No GM) . . . . . . . . . . . . . 8-16
MCM3320 Wiring Diagram − Switchgear Interconnect (Master Synchronizer Only) . . . . . . . . . . . . . . 8-17
MCM3320 Wiring Diagram − Genset Interconnect (Master Synchronizer Only) . . . . . . . . . . . . . . . . . 8-18
MCM3320 Wiring Diagram − Customer I/O Interconnect (Master Synchronizer Only) . . . . . . . . . . . . 8-19
MCM3320 Wiring Diagram − Connectors and Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . 8-20
MCM3320 Wiring Diagram − Optional Load Add / Load Shed Interconnect (AUX101) . . . . . . . . . . . 8-21
MCM3320 Wiring Diagram − Optional Load Add / Load Shed Interconnect (AUX102) . . . . . . . . . . . 8-22
MCM3320 Board Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23

8-1
PRELIMINARY

THIS PAGE LEFT INTENTIONALLY BLANK

8-2
PRELIMINARY

No. 630-3133 Sh 1 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 1 OF 20)

8-3
PRELIMINARY

No. 630-3133 Sh 2 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 2 OF 20)

8-4
PRELIMINARY

No. 630-3133 Sh 3 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 3 OF 20)

8-5
PRELIMINARY

No. 630-3133 Sh 4 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 4 OF 20)

8-6
PRELIMINARY

No. 630-3133 Sh 5 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 5 OF 20)

8-7
PRELIMINARY

No. 630-3133 Sh 6 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 6 OF 20)

8-8
PRELIMINARY

No. 630-3133 Sh 7 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 7 OF 20)

8-9
PRELIMINARY

No. 630-3133 Sh 8 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 8 OF 20)

8-10
PRELIMINARY

No. 630-3133 Sh 9 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 9 OF 20)

8-11
PRELIMINARY

No. 630-3133 Sh 10 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 10 OF 20)

8-12
PRELIMINARY

No. 630-3133 Sh 11 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 11 OF 20)

8-13
PRELIMINARY

No. 630-3133 Sh 12 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 12 OF 20)

8-14
PRELIMINARY

No. 630-3133 Sh 13 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 13 OF 20)

8-15
PRELIMINARY

No. 630-3133 Sh 14 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 14 OF 20)

8-16
PRELIMINARY

No. 630-3133 Sh 15 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 15 OF 20)

8-17
PRELIMINARY

No. 630-3133 Sh 16 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 16 OF 20)

8-18
PRELIMINARY

No. 630-3133 Sh 17 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 17 OF 20)

8-19
PRELIMINARY

No. 630-3133 Sh 18 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 18 OF 20)

8-20
PRELIMINARY

No. 630-3133 Sh 19 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 19 OF 20)

8-21
PRELIMINARY

No. 630-3133 Sh 20 of 20
Rev. D Sys: HP
Modified 2/2006

MCM3320 WIRING DIAGRAM (SHEET 20 OF 20)

8-22
TABLE 8-1. MCM3320 BOARD CONNECTIONS
Connection
System
Connector Connector Schematic Optional for
MCM3320 Connection Name Connects To Topology Signal Type Description
Assignment Type Signal Name Applicable
Applicability
Topologies?
Switch I/O / PCCNet (TB1)
PCCNet B+ TB1-1 Fused B+ PCCNet Device ALL Yes B+ Power Output B+ output fused at 1/2 Amp with self-resetting PTC device; use to supply operator panel;
supplied from Battery 1 and Battery 2
PCCNet RS-485 A TB1-2 Mon 485 A PCCNet Device ALL Yes RS-485 Port PCCNet RS-485 A; Port for auxiliary devices such as the control panel, bargraph, and I/O
modules
PCCNet RS-485 B TB1-3 Mon 485 B PCCNet Device ALL Yes RS-485 Port PCCNet RS-485 B; Port for auxiliary devices such as the control panel, bargraph, and I/O
modules
PCCNet RS-485 Gnd/Shield TB1-4 Return8 PCCNet Device ALL Yes Return PCCNet RS-485 Ground/shield reference; Port for auxiliary devices such as control panel,
bargraphs, I/O modules
SPARE Lside8 TB1-5 Lside 8 Low-Side Output This signal is not used. Do not connect.
SPARE CTACT_7A TB1-6 CTACT_7A Relay Output (Dry N.O.) This signal is not used. Do not connect.
SPARE CTACT_7B TB1-7 CTACT_7B Relay Output (Dry N.O.) This signal is not used. Do not connect.
Plug
SPARE CTACT_6A TB1-8 Terminal CTACT_6A Relay Output (Dry N.O.) This signal is not used. Do not connect.
SPARE CTACT_6B TB1-9 Block CTACT_6B Relay Output (Dry N.O.) This signal is not used. Do not connect.
Discrete Input Return TB1-10 Return9 Customer I/O ALL Return Use as signal return for switch inputs.
synchronizer Enable TB1-11 Switch 20 Customer I/O ALL Yes Switch Input Use to enable synchronizing when in Manual mode or when the module is used only as a
synchronizer (otherwise, sync enabling is automatically done by the control)
SPARE Switch21 TB1-12 Switch 21 Customer I/O ALL Switch Input This signal is not used. Do not connect.
Discrete Input Return TB1-13 Return10 Customer I/O ALL Return Use as signal return for switch inputs.
Override TB1-14 Switch 22 Customer I/O ALL Except MSO Yes Switch Input Use to force a transfer or retransfer to occur as quickly as possible; overrides transfer in-
hibit, retransfer inhibit, transfer time delay and retransfer time delay.
Discrete Input Return TB1-15 Return11 Customer I/O ALL Return Use as signal return for switch inputs.
Utility Source Failure TB1-16 Switch 23 Customer I/O ALL Yes Switch Input Use to indicate to the control that the utility has failed; for applications which desire to move
an external device, determine utility source availability in addition to internal sensors.
Switch I/O / DC Power In (TB2)
Test Start TB2-1 Switch 3 Customer I/O ALL Except MSO Yes Switch Input Starts/stops a test of the system; can be configured for with or without load
Battery − TB2-2 B-1 Genset Controls ALL Depends Battery Ground Ground return for either Battery1 or battery2 DC power source
Battery + TB2-3 B-2 Genset Controls ALL Depends Battery Ground Ground return for either Battery1 or battery2 DC power source
Extended Parallel Start TB2-4 Switch 13 Customer I/O UMGM, UMGX Yes Switch Input Starts/Stops and extended parallel mode; used for base load or peak shave operation
Battery − TB2-5 B-4 Station Battery ALL Depends Battery Ground Ground return for either Battery1 or Battery2 DC power source
Discrete Input Return TB2-6 Sw Rtn 5 Customer I/O ALL Return Use as signal return for switch inputs
Battery − TB2-7 B-3 Station Battery ALL Depends Battery Ground Ground return for either Battery1 or Battery2 DC power source
Battery 1+ TB2-8 B+4 Genset Controls ALL Depends B+ Power Input Battery DC power input; diode or’d with Battery2 input to allow redundant supply voltage
Battery 1+ TB2-9 B+3 Genset Controls ALL Depends B+ Power Input Battery DC power input; diode or’d with Battery2 input to allow redundant supply voltage
Relay Coil B+ Supply (Fused 2A) TB2-10 Relay Customer I/O ALL Yes B+ Power Output B+ output fused at 1Amp with self-resisting PTC device; use to supply high side of relay
Plug Supply coils which are returned output; supplied from Battery 1 and Battery 2
Terminal
Battery 2+ TB2-11 Block B+2 Station Battery ALL Depends B+ Power Input Battery DC power input; diode or’d with Battery1 input to allow redundant supply voltage
Battery 2+ TB2-12 B+1 Station Battery ALL Depends B+ Power Input Battery DC power input; diode or’d with Battery1 input to allow redundant supply voltage
SPARE Switch12 TB2-13 Switch 12 Switch Input (Wakeup) This signal is not used. Do not connect.
Fault Reset TB2-14 Switch 14 Customer I/O ALL Yes Switch Input Acknowledges and resets faults; also used to activate the fault flashout on the seven-seg-
ment display on the board (hold active for >5 seconds to activate this mode)
Configurable Output1 (Common Warning) TB2-15 Lside 7 Customer I/O ALL Yes Low-Side Output Configurable Output #1; intended to drive a relay coil; default as Common Warning
Configurable Output2 (Fail to Sync) TB2-16 Lside 5 Customer I/O ALL Yes Low-Side Output Configurable Output #2; intended to drive a relay coil; default as Fail to Sync
Configurable Output3 (Genset Available) TB2-17 Lside 6 Customer I/O ALL Yes Low-Side Output Configurable Output #3; intended to drive a relay coil; default as Gen Available
Configurable Output4 (Utility Available) TB2-18 Lside 4 Customer I/O ALL Yes Low-Side Output Configurable Output #4; intended to drive a relay coil; default as Utility Available
Connect to Grounded Chassis TB2-19 Chassis ALL No Chassis Ground Provides the I/O signal filter ground patch; it must be connected via a short wire/strap to the
earth grounded equipment chassis.

8-23
TABLE 8-1. MCM3320 BOARD CONNECTIONS (CONT.)
Connection
System Optional for
Connector Connector Schematic
MCM3320 Connection Name Connects To Topology Signal Type Description
Assignment Type Signal Name Applicable
Applicability Topologies?
Switch I/O / CAN (TB3)
Load Govern Enable TB3-1 Lside2 Genset Controls UMGM UMGX No Low-Side Output Connect to the utility cb position inputs on the individual genset controls; tells the genset
controls when they are parallel to the utility
Load Demand Gen1 TB3-2 Lside1 Genset Controls ALL except MSO Yes Low-Side Output Connect to the load demand input on Genset#1
Master CAN Shield TB3-3 CAN0SHLD Shield This signal is not used. Do not connect.
Master CAN L TB3-4 CAN0L CAN Data This signal is not used. Do not connect.
Master CAN H TB3-5 CAN0H CAN Data This signal is not used. Do not connect.
Transfer Inhibit TB3-6 Switch 16 Customer I/O UMGM, UMGX Yes Switch Input Normally inhibit retransfer to genset; under some conditions, it is ignored; not the same as
gen cb inhibit
Retransfer Inhibit TB3-7 Switch 17 Customer I/O UMGM, UMGX Yes Switch Input Normally inhibit retransfer to utility; under some conditions, it is ignored; not the same as
util cb inhibit
Discrete Input Return TB3-8 Plug Sw Rtn 6 Customer I/O ALL Return Use as signal return for switch inputs
Load Demand Gen2 TB3-9 Terminal Lside 9 Genset Controls ALL except MSO Yes Low-Side Output Connect to the load demand input on Genset #2
Bl k
Block
Load Demand Gen3 TB3-10 Lside 10 Genset Controls ALL except MSO Yes Low-Side Output Connect to the load demand input on Genset #3
Load Demand Gen4 TB3-11 Lside 11 Genset Controls ALL except MSO Yes Low-Side Output Connect to the load demand input on Genset #4
Configurable Output5 (Fail to Disconnect) TB3-12 Lside 12 Customer I/O ALL Yes Low-Side Output Configurable Output#5; intended to drive a relay coil; default as Fail to Disconnect
Configurable Output6 (Synchronized) TB3-13 Lside 16 Customer I/O ALL Yes Low-Side Output Configurable Output#6; intended to drive a relay coil; default as Synchronized
Configurable Output7 (Sync Output Limit) TB3-14 Lside 15 Customer I/O ALL Yes Low-Side Output Configurable Output#7; intended to drive a relay coil; default as TBD
Configurable Output8 (Hardware Failure) TB3-15 Lside 14 Customer I/O ALL Yes Low-Side Output Configurable Output#8; intended to drive a relay coil; default as TBD
Paralleling Gensets Breaker Inhibit Output TB3-16 Lside 13 Genset Controls ALL except MSO Yes Low-Side Output Connect to all of the individual genset circuit breaker inhibit inputs; allows control to treat
individual genset breakers in concert as a genset main breaker
Master Inhibit TB3-17 1st Start Customer I/O ALL Yes Bidirectional Arbitration Phase 1 − Manual inhibit only; ground/return this signal to activate inhibit; Phase 2 − Inter-
connect between multiple 3320s in a multiple transfer pair situation to provide controlled
return to utility
Genset PT Inputs (TB6)
Gen Bus Voltage L1 TB6-1 Gen V1 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Gen Bus Voltage L2 TB6-2 Plug Gen V2 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Terminal
Gen Bus Voltage L3 TB6-3 Block Gen V3 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Gen Bus Voltage N TB6-4 Gen N UMGM Switchgear ALL Depends AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Genset CT Inputs
Genset Bus Current L1+ Wire 1 CT4+ UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
through hole for 5A
Genset Bus Current L2+ Wire 2 CT4− UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
through hole for 5A
Genset Bus Current L3+ Wire 3 CT5+ UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
Wire Passed through hole for 5A
Through CT
Genset Bus Current L1− Wire 4 Hole CT5− UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
through hole for 5A
Genset Bus Current L2− Wire 5 CT6+ UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
through hole for 5A
Genset Bus Current L3− Wire 6 CT6− UMGM Switchgear ALL Depends AC Current Input CT input connection; 1A or 5A secondary; two passes through hole for 1A, one pass
through hole for 5A
Utility PT Inputs (TB7)
Util Bus Voltage L1 TB7-1 Util V1 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Util Bus Voltage L2 TB7-2 Plug Util V2 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Terminal
Util Bus Voltage L3 TB7-3 Block Util V3 UMGM Switchgear ALL No AC Voltage Input PT input connection; up to 480VLL nominal direct connection
Util Bus Voltage N TB7-4 Util N UMGM Switchgear ALL Depends AC Voltage Input PT input connection; up to 480VLL nominal direct connection

8-24
TABLE 8-1. MCM3320 BOARD CONNECTIONS (CONT.)
Connection
System Optional for
Connector Connector Schematic
MCM3320 Connection Name Connects To Topology Signal Type Description
Assignment Type Signal Name Applicable
Applicability Topologies?
Utility CT Inputs
Util Bus Current L1+ Wire 7 CT1+ UMGM Switchgear ALL Depends AC Current Input CT input
p connections;; 1A or 5A secondary;
y; two passes
p through
g the hole for 1A,, one pass
p
Util Bus Current L1− Wire 8 CT1− UMGM Switchgear ALL Depends AC Current Input through
h h the
h hole
h l for
f 5AA

Util Bus Current L2+ Wire 9 Wire Passed CT2+ UMGM Switchgear ALL Depends AC Current Input
Through CT
Util Bus Current L2− Wire 10 Hole CT2− UMGM Switchgear ALL Depends AC Current Input
Util Bus Current L3+ Wire 11 CT3+ UMGM Switchgear ALL Depends AC Current Input
Util Bus Current L3− Wire 12 CT3− UMGM Switchgear ALL Depends AC Current Input
Breaker Control (TB8)
(Do not connect) TB8-1 CTACT_1NC (Do not connect) This signal is not used. Do not connect.
Gen Main CB Close Relay 1 TB8-2 CTACT_1COM UMGM Switchgear UMGM, GM No Relay Output (Dry N.O.) Contact for closing genset main breaker; ratings 8A 30VDC/250VAC resistive, 3.5A
30VDC/250VAC inductive L/R=7msec or 0.4PF
Gen Main CB Close Relay 2 TB8-3 CTACT_1NO UMGM Switchgear UMGM, GM No Relay Output (Dry N.O.) Contact for closing genset main breaker; ratings 8A 30VDC/250VAC resistive, 3.5A
30VDC/250VAC inductive L/R=7msec or 0.4PF
(Do not connect) TB8-4 CTACT_2NC (Do not connect) This signal is not used. Do not connect.
Gen Main CB Open Relay 1 TB8-5 CTACT_2COM UMGM Switchgear UMGM, GM No Relay Output (Dry N.O.) Contact for opening gen main breaker; ratings 8A 30VDC resistive, 3.5A 30VDC inductive
L/R=7msec NOT rated for AC voltage
Gen Main CB Open Relay 2 TB8-6 CTACT_2NO UMGM Switchgear UMGM, GM No Relay Output (Dry N.O.) Contact for opening gen main breaker; ratings 8A 30VDC resistive, 3.5A 30VDC inductive
L/R=7msec NOT rated for AC voltage
Plug
Starts Gensets Relay.NC TB8-7 Terminal
e a CTACT_2NC Genset controls ALL except MSO Depends Relay Output (Dry N.C.) NC contact for starting gensets
Starts Gensets Relay.COM TB8-8 Block CTACT_3COM Genset Controls ALL except MSO No Relay Output (Dry COM) COM for starting gensets
Starts Gensets Relay.NO TB8-9 CTACT_3NO Genset Controls ALL except MSO Depends Relay Output (Dry N.O.) NO contact for starting gensets; connect in parallel to all genset remote start inputs
Utility Main CB Close Relay.1 TB8-10 CTACT_4A UMGM Switchgear UMGM, UMGX No Relay Output (Dry N.O.) Contact for closing utility main breaker; ratings 8A 30VDC/250VAC resistive, 3.5A
30VDC/250VAC inductive L/R = 7msec; for 0.4PF
Utility Main CB Close Relay.2 TB8-11 CTACT_4B UMGM Switchgear UMGM, UMGX No Relay Output (Dry N.O.) Contact for closing utility main breaker; ratings 8A 30VDC/250VAC resistive, 3.5A
30VDC/250VAC inductive L/R = 7msec; for 0.4PF
Utility Main CB Open Relay.1 TB8-12 CTACT_5A UMGM Switchgear UMGM, UMGX No Relay Output (Dry N.O.) Contact for opening utility main breaker; ratings 8A 30VDC resistive, 3.5A 30VDC inductive
L/R=7msec NOT rated for AC voltage
Utility Main CB Open Relay.2 TB8-13 CTACT_5B UMGM Switchgear UMGM, UMGX No Relay Output (Dry N.O.) Contact for opening utility main breaker; ratings 8A 30VDC resistive, 3.5A 30VDC inductive
L/R=7msec NOT rated for AC voltage
Analog I/O (TB9)
kW Load Setpoint TB9-1 kW Load Customer I/O UMGM, UMGX Yes Analog Input Analog input for setting the base load or peak shave kW setpoint; alternatively can be done
by trim
Analog Return TB9-2 Analog Rtn Customer I/O UMGM, UMGX Yes Analog Return Use a signal return for analog input/output
kVAR Load Setpoint TB9-3 kVAR Load Customer I/O UMGM, UMGX Yes Analog Input Analog input for setting the base load or peak share kVAR setpoint;alternatively can be
done by trim
kW Master Load Control TB9-4 Mstr Load Genset Controls UMGM, UMGX No Analog Output Analog output which sets the genset kW load govern level; connect in parallel to all genset
kW load set inputs; use shielded twisted pair cable
kVAR Master Load Control TB9-5 Speed Bias Genset Controls UMGM, UMGX Depends Analog Output Analog output which sets the genset kW load govern level; connect in parallel to all genset
Plug
g kVAR load set inputs; use shielded twisted pair cable
T
Terminal
i l
Analog Return TB9-6 Analog Rtn Genset Controls UMGM, UMGX No Analog Return Use as signal return for analog input / output
Block
(Do not connect) TB9-7 kW Share − (Do not connect) This signal is not used. Do not connect.
Master Frequency Bias + TB9-8 kW Share + Genset Controls ALL No Bidirectional Analog Connect to genset kW+ load share line; used for master synchronizing freq/phase match.
NOTE: PCC3100 wiring diagrams have the + and − designations reversed.
Analog Return TB9-9 Analog Rtn Genset Controls ALL No Analog Return Connect to genset kW− and kVAR− load share; used for master synchronizing.
NOTE: PCC3100 wiring diagrams have the + and − designations reversed.
Master Voltage Bias + TB9-10 kVAR Share + Genset Controls ALL No Bidirectional Analog Connect to genset kVAR+ load share line; used for master synchronizing voltage match.
NOTE: PCC3100 wiring diagrams have the + and − designations reversed.
(Do not connect) TB9-11 kVAR Share − (Do not connect) This signal is not used. Do not connect.

8-25
TABLE 8-1. MCM3320 BOARD CONNECTIONS (CONT.)
Connection
System Optional for
Connector Connector Schematic
MCM3320 Connection Name Connects To Topology Signal Type Description
Assignment Type Signal Name Applicable
Applicability Topologies?
Breaker Status Inputs (TB10)

Genset Main CB Position A Contact TB10-1 Switch 8 UMGM Switchgear ALL Depends Switch Input The ‘a’ contact from genset main breaker; control uses this to determine breaker position
Genset Main CB Position B Contact TB10-2 Switch 2 UMGM Switchgear ALL Depends Switch Input The ‘b’ contact from genset main breaker; control used this only to determine breaker cir-
cuit failure by comparing it to the ‘a’ contact; this feature can be enabled/disabled
Genset Main CB Tripped TB10-3 Switch 9 UMGM Switchgear ALL Yes Switch Input Use to indicate to control that genset main is tripped. Control will consider source unavail-
able.
Discrete Input Return TB10-4 Sw Rtn 1 UMGM Switchgear ALL Depends Return Use as signal return for switch inputs
Genset Main CB Inhibit TB10-5 Switch 7 Customer I/O ALL except MSO Yes Switch Input Opens genset main if closed; inhibits closure if genset main is open.
Auto/Manual TB10-6 Switch 15 UMGM Switchgear ALL Yes Switch Input Puts the breaker and synchronizer control in manual mode; control relinquishes breaker
control unless fundamental rules are violated
Utility Main CB Position A Contact TB10-7 Switch 1 UMGM Switchgear ALL Depends Switch Input The ‘a’ contact from utility main breaker; control uses this to determine breaker position
Discrete Input Return TB10-8 Sw Rtn 2 UMGM Switchgear ALL Depends Return Use to signal return for switch inputs
Utility Main CB Position B Contact TB10-9 Switch 10 UMGM Switchgear ALL Depends Switch Input The ‘b’ contact from utility main breaker; control uses this only to determine breaker circuit
Plug failure by comparing it to the ‘a’ contact; this feature can be enabled / disabled
Utility Main CB Tripped TB10-10 Terminal Switch 11 UMGM Switchgear ALL Yes Switch Input Use to indicate to control that the utility main is tripped. Control will consider source un-
Block available.
Utility Main CB Inhibit TB10-11 Switch 4 Customer I/O ALL except MSO Yes Switch Input Opens utility main if closed; inhibits closure if utility main is open
Gen1 CB Position A Contact TB10-12 Switch 5 Genset Switchgear ALL except MSO Depends Switch Input The ‘a’ contact from genset#1 breaker; (required for load demand and some other configu-
rations)
Discrete Input Return TB10-13 Sw Rtn 3 Genset Switchgear ALL except MSO Return Use as signal return for switch inputs
Gen2 CB Position A Contact TB10-14 Switch 19 Genset Switchgear ALL except MSO Depends Switch Input The ‘a’ contact from genset#2 breaker; (required for load demand and some other configu-
rations)
Gen3 CB Position A Contact TB10-15 Switch 8 Genset Switchgear ALL except MSO Depends Switch Input The ‘a’ contact from genset#3 breaker; (required for load demand and some other configu-
rations)
Gen4 CB Position A Contact TB10-16 Switch 6 Genset Switchgear ALL except MSO Depends Switch Input The ‘a’ contact from genset#4 breaker; (required for load demand and some other configu-
rations)
Discrete Input Return TB10-17 Sw Rtn 4 Customer I/O ALL Return Use as signal return for switch inputs
Discrete Input Return TB10-18 Sw Rtn 7 Customer I/O ALL Return Use as signal return for switch inputs

RS-232 DTE ModBus RTU Port (J14)

Not Used J14-1 Customer I/O ALL This pin is not used; this pin is not connected to anything on the MCM3320 board
ModBus RS-232 Rx J14-2 232 Rx1 Customer I/O ALL Yes RS-232 Port (DTE) ModBus RS-232 RX input; NOTE: Port is shared with TB15.
ModBus RS-232 Tx J14-3 232 Tx1 Customer I/O ALL Yes RS-232 Port (DTE) ModBus RS-232 TX input; NOTE: Port is shared with TB15.
Not Used J14-4 Customer I/O ALL This pin is not used; this pin is not connected to anything on the MCM3320 board
ModBus RS-232 GND J14-5 232 Gnd1 Customer I/O ALL Yes RS-232 Port (DTE) ModBus RS-232 GND reference; NOTE: Port is shared with TB15.
DB-9 (Pins)
Not Used J14-6 Customer I/O ALL This pin is not used; this pin is not connected to anything on the MCM3320 board
RTS J14-7 232 RTS Customer I/O ALL Yes RS-232 Port (DTE) ModBus RS-232 RTS output; NOTE: Connected device must loop this back to the CTS
input
CTS J14-8 232 CTS Customer I/O ALL Yes RS-232 Port (DTE) ModBus RS-232 CTS input
Not Used J14-9 Customer I/O ALL This pin is not used; this pin is not connected to anything on the MCM3320 board

RS-485 InPower or ModBus RTU Port (TB15)

Tool/ModBus RS-485 Gnd/Shield TB15-1 485 Gnd1 Customer I/O ALL Yes RS-485 Port ModBus OR Tool RS-485 shield connection port
B+ Output (Fused −.25A) TB15-2 Bat+ Out Customer I/O ALL Yes B+ Power Output Auxiliary B+ output to power RS-232 to RS-485 converter, or low cost display
Plug
Pl
Tool/ModBus RS-485 A TB15-3 485 A Customer I/O ALL Yes RS-485 Port ModBus OR Tool RS-485 port
Terminal
Tool/ModBus RS-485 B TB15-4 Block 485 B Customer I/O ALL Yes RS-485 Port ModBus OR Tool RS-485 port
Bidirectional Wakeup TB15-5 Bidirectional Bidirectional Discrete This signal is not used. Do not connect.
Wakeup− (Wakeup)

8-26
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
1-800-888-6626
763-574-5000 International Use
Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.

You might also like