Application and Installation Guide EP Applications, Engine & Generator Sizing
This is considered to be 90% of Any variation in these conditions
rated frequency. Figure 20 will affect the start time. graphically shows a packaged Natural Gas Engines genset’s typical starting Special engine conditioning is performance. required for a natural gas engine to start in 10 seconds. Ten-second starting is only possible on specific gas engines. Consult the factory for specific engine model starting requirements. Starting condition requirements for natural gas engines are the same as diesel engine starting requirements, except for one detail: The solenoid gas valve must be located as closely as possible to the carburetor or “A” regulator, depending on the fuel train consists. Figure 19 A maximum distance of 0.61 m (2 ft) is desired. Ten-Second Start A customer’s starting time Ten-second start refers to the requirements should be determined ability of a non-paralleled generator before sizing the genset. A quick set to start, accelerate to rated starting application requires speed and be ready to accept load consider-ation of altitude, within 10 seconds after receiving temperature and other factors that a signal to start. affect the engine starting to find the For 10-second starting, the best solution. following conditions must exist: Refer to Emergency & Fast 1. Cranking batteries must be Starting in the Starting Systems adequately sized and fully Application and Installation Guide charged. for more information. Note: there is a difference Health Care Facilities & NFPA 99 for battery versus ambient The standard NFPA 99 is written temperature sizing. Also, in specifically for health care facilities. cases where air starting is used, the air system must supply the 3-4.1.1.8 states the following: required air volume and “The generator set(s) shall have maintain a 100 psi (689.5 kPa) sufficient capacity to pick up the minimum pressure. load and meet the minimum frequency and voltage stability 2. Combustion air must be a requirements of the emergency minimum of 21°C (70°F). system within 10 seconds after 3. A jacket water heater to loss of normal power.” maintain a minimum of Customers requiring this 32°C (90°F) jacket water capability can achieve it by using temperature. the correct generator system. Select 4. A readily available supply of an appropriate genset according to clean fuel. this standard for all health care 5. The generator rotating inertia facilities in the United States. must not exceed that of the Sizing a genset requires standard Cat Generator. knowledge of the customer’s loads