This is considered to be 90% of Any variation in these conditions


rated frequency. Figure 20 will affect the start time.
graphically shows a packaged Natural Gas Engines
genset’s typical starting Special engine conditioning is
performance. required for a natural gas engine
to start in 10 seconds. Ten-second
starting is only possible on specific
gas engines. Consult the factory for
specific engine model starting
requirements.
Starting condition requirements
for natural gas engines are the
same as diesel engine starting
requirements, except for one detail:
The solenoid gas valve must be
located as closely as possible to the
carburetor or “A” regulator,
depending on the fuel train consists.
Figure 19 A maximum distance of 0.61 m (2 ft)
is desired.
Ten-Second Start A customer’s starting time
Ten-second start refers to the requirements should be determined
ability of a non-paralleled generator before sizing the genset. A quick
set to start, accelerate to rated starting application requires
speed and be ready to accept load consider-ation of altitude,
within 10 seconds after receiving temperature and other factors that
a signal to start. affect the engine starting to find the
For 10-second starting, the best solution.
following conditions must exist: Refer to Emergency & Fast
1. Cranking batteries must be Starting in the Starting Systems
adequately sized and fully Application and Installation Guide
charged. for more information.
Note: there is a difference Health Care Facilities & NFPA 99
for battery versus ambient The standard NFPA 99 is written
temperature sizing. Also, in specifically for health care facilities.
cases where air starting is used,
the air system must supply the 3-4.1.1.8 states the following:
required air volume and “The generator set(s) shall have
maintain a 100 psi (689.5 kPa) sufficient capacity to pick up the
minimum pressure. load and meet the minimum
frequency and voltage stability
2. Combustion air must be a requirements of the emergency
minimum of 21°C (70°F). system within 10 seconds after
3. A jacket water heater to loss of normal power.”
maintain a minimum of Customers requiring this
32°C (90°F) jacket water capability can achieve it by using
temperature. the correct generator system. Select
4. A readily available supply of an appropriate genset according to
clean fuel. this standard for all health care
5. The generator rotating inertia facilities in the United States.
must not exceed that of the Sizing a genset requires
standard Cat Generator. knowledge of the customer’s loads