INSPECTION — MONTHLY EXAMINATION
To provide reasonable assurance that your Ansul A-101
system is charged and operable:
1, Note general appearance of system components for
‘mechanical damage or corrosion.
2. Check nameplate(s) for readability.
3, Remove fill cap.
4, Make certain tank is fillad with free-flowing Ansul
FORAY dry chemical to a level of not more than 3
inches from the bottom of the fill opening.
5. Secure fill cap, hand tighten.
8, Remove expellant gas cartridge and examine disc —
seal should be unruptured,
7. Return cartridge to pneumatic actuatori/ cartridge
receiver, hand tighten and secure in bracket.
LT-A-t01 SYSTEM
Numbers are keyed to inspection instructions
8
8
10.
1B
INSPECTION
415.79 Paget
Check hose, fittings and nozzles for mechanical
damage and cuts.
‘Check nozzle openings — slot on F-Y nozzle should
be closed (capped) with silicone grease or covered
with plastic blow-off cap (4120),
Remove cartridge from manual actuator(s),
examine disc — seal should be unruptured.
Return cartridge to manual actuator(s) assembly,
hand tighten
Roplace any broken or missing lead and wire seals and
record date of inspection.
and
A101 SYSTEM
FIGURE 27MAINTENANCE — SEMI-ANNUAL EXAMINATION.
To provide maximum assurance that your Ansul A-101
system will operate effectively ang safely:
1, Note the general appearance of the dry chemical
tank for mechanical damage or corrosion.
2, Check nameplate for readability,
looseness,
3, Remove fill cap.
4, Examine fill cap gaskets for elasticity — clean and
coat lightly'with a good grade of high heat resistant
grease.
5. Inspect threads on fit! cap and in fill opening for
nicks. burrs, cross-threading, rough or feathered
edges.
6. Check pressure relief vent in fil opening threads for
obstruction
7. Make certain tank is filled with free-flowing Ansul
FORAY dry chemical to a level of not more than 3
inches from bottom of fill opening,
8. Secure fill cap, hand tighten.
9. Disengage bursting disc union.
10, Examine the bursting disc. if necessary, move the
tank slightly to view disc. The bursting disc should
be properly seated with the washer side facing out
(smooth side in) and should be undamaged (smooth,
ot scored or ruptured).
11. Engage bursting disc union (wrench tighten).
CAUTION: Overtightening can damage bursting
disc.
12, Loosen the bolt(s) which restrain the cartridge or
remove extinguisher cartridge guard assembly.
13. Ingpect the expellant gas cartridge assembly tor
evidence of mechanical damage or corrosion.
14, Unscrew the cartridge from the pneumatic actuator!
cartridge receiver and weigh it. Replace If its weight
is not within 1/2 ounce of the weight stamped on
the cartridge.
15,
16,
17,
18,
19,
20.
a
22,
2.
24.
MAINTENANCE
415-79 Page12
Inspect threads on cartridge and in pneumatic
actuator/cartridge receiver for nicks, burrs, cross
threading, rough or feathered edges.
Check pressure vent in pneumatic actuator! cartridge
receiver for obstruction
Examine cartridge receiver gasket for elasticity.
Clean and coat lightly with a good grade of high heat
resistant grease. Return cartridge pneumatic actu-
atoricartridge receiver, hand tighten.
Tighten the bracket bolts) uniformly or return
cartridge guard asembly.
Be sure the dry chemical tank is flrmly mounted in
its bracket.
Check nose, fittings and nozzles for mechanical
damage,
Check nozzle openings — slot should be closed
(capped) with silicone grease or covered with plastic
blow-off cap.
Check remote actuator — Remove cartridge and
weigh (replace if weight is 1/4 ounce less than
stamped on cartridge). Inspect threads on canridge
and in actuator for nicks, burrs, cross-threading,
fough or feathered edges. Check pressure safety
vent in actuator boay for obstruction. Examine
actuator cartridge gasket for elasticity — clean and
coat lightly with a good grade of high heat resistant
grease. Pull ring pin and operate actuator button
‘Several times to check for free movement.
Seal ring pin to puncture lever with lead and wire
seal. Return cartridge to remote actuator, hand
tighten’
Record date of maintenance.MAINTENANCE
445-73 Page 13
MAINTENANCE — SEMI-ANNUAL EXAMINATION
LT-A-to1 SYSTEM
‘A-101 SYSTEM
FIGURE 28
Numbers are keyed to maintenance instructions.