L2 V4 08 C264 LBUS Configuration E 01
L2 V4 08 C264 LBUS Configuration E 01
Configuration
PACiS Technical Training Level 2
CS&P Support Team
PCL
• Content
Synchronization cycle :
periodic synchro. frames
Inter frame Downgraded cycle :
when IED not responding, periodic retry
Schneider Electric - CS&P – C264 LBUS Configuration – E01 4
• Add / Configure a LBUS (2)
3) Connect LBUS to communication port
Communication parameters
Note that COM3 and COM4 should have same
transmission speed
For COM3 and COM4 => Tx carrier management
set to Switched
IED @ on LBUS
4) Acq Profile attributes (example given with T103, cf. C264 AP chapter)
4.1) General Tab
MV reduction coefficient :
- 1.2 or 2.4 (cf. IED documentation)
- MV = red_coeff x transmitted val x nominal val.
IED Mapping :
set of SPS, DPS, MPS, MV, SPC, DPC, …
managed by IED (cf. IED documentation)
To add a DP address :
1) select kind of DP Mapping
2) Through Objects Entry Window, add an address
SPS address :
as per IED documentation, here ASDU, FTYP
and INF (as per IEC-60870-5-103 standard
public or IED private)
DPS address :
as per IED documentation, here ASDU, FTYP
and INF (as per IED private)
SPC address :
as per IED documentation, here ASDU, FTYP
and INF (as per IEC-60870-5-103 standard
public or IED private)
2.4) MV address
MV address :
as per IED documentation, here ASDU, FTYP,
INF and index=rank in ASDU (as per IEC-60870-
5-103 standard public or IED private)
Under datapoint :
DP link with relevant address on the IED
Standard attributes :
same as T103 (nb of retries, response timeout,
…)
Synchronization :
None/AREVA (for AREVA Modbus)
Limits
up to 4 communication links (LBUS+TBUS serial or ethernet)
up to 4 LBUS
up to 2 TBUS
Connections
BIU port 1 => RS232/RS485
Jumpers on BIU board
BIU port 2 => RS232/RS485/RS422
2) Template instantiations :
=> DP and links already done
=> only configure IED name and @
=> repeatable
=> all DP already tested OK => IED integration