You are on page 1of 17

IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO.

2, JUNE 2020 837

Effect of Reactive Power Characteristic of Offshore


Wind Power Plant on Low-Frequency Stability
Weihua Zhou , Student Member, IEEE, Yanbo Wang , Senior Member, IEEE,
Raymundo E. Torres-Olguin, and Zhe Chen , Fellow, IEEE

Abstract—Oscillation phenomena of offshore wind power plant to dynamic interactions between control loops of GCIs and time-
(OWPP) in a wide frequency range can be caused due to impedance varying grid impedance have been frequently reported [3]–[8].
interactions between grid-connected inverters (GCIs) and trans- Control loops of the GCI mainly include outer power control
mission cables. In this article, impedance model of GCI with outer
power control loop, inner current control loop and phase-locked loop, inner current control loop and phase-locked loop (PLL),
loop is first established in dq reference frame. The correctness which are used to perform power regulation, current regulation
is validated by frequency scanning method. Then, the effects of and grid synchronization, respectively [7]. Impedance-based
active and reactive power/current references on dq impedance stability criterion (IBSC) for three-phase GCI has been proposed
characteristics of GCI with/without consideration of power control to investigate these oscillation phenomena, where impacts of the
loop are investigated using complex space vectors and complex
transfer functions. Furthermore, RLC circuit model of trans- control loops on terminal impedance have been investigated by
mission cable considering frequency-dependent characteristics is various impedance models [3]–[7], [9]–[14]. The mechanism of
also established for dq-domain IBSC. On the basis of them, it’s high-frequency instability phenomena induced by the interac-
found that low-frequency oscillation phenomena of OWPP under tion between inner current control loop and transmission cable
power control mode may occur if active power reference exceeds is investigated in [6], [10], [11]. The analysis results indicate that
a certain threshold value, which can be mitigated by injecting a
certain amount of negative reactive power. Impacts of PLL param- the impedance formula of a GCI with only consideration of inner
eters, length of transmission cable and number of paralleled GCIs current control loop does not consist of active power reference.
on required negative reactive power for low-frequency stabilization Therefore, the high-frequency stability dominated by the inner
are further investigated. Both Matlab/Simulink-based simulation current control loop is not affected by active power level [11],
and OPAL-RT-based real-time verification are implemented in an [15]. Output impedance of the GCI further considering PLL can
OWPP with four permanent magnet synchronous generators to
validate the correctness of the reactive power characteristic analy- be represented as a two-dimensional matrix, which is diago-
sis results and the feasibility of mitigating low-frequency oscillation nally dominant if the GCI is operated under high power factor
phenomena by negative reactive power injection. condition [7]. However, the high power factor condition is not
Index Terms—Frequency scanning, grid-connected inverter
commonly satisfied in practical application, since the GCIs are
(GCI), low-frequency stability, offshore wind power plant (OWPP), sometimes controlled to inject reactive power [12], [16], [17].
reactive power, transmission cable. The recent study in [7], [18] shows that magnitude of cross-
coupling term of the two-dimensional impedance matrix can be
increased once reactive current reference is increased, whereas
I. INTRODUCTION the quadrature-axis impedance which reflects the negative re-
FFSHORE wind power plants (OWPPs) are increasingly sistor feature of PLL in low-frequency range is not affected. In
O explored in recent years, which are commonly connected
into utility grid by transmission cables [1]. Grid-connected
addition, stability analysis of the GCI considering outer power
control loop is implemented in [19], where eigenvalue analysis
inverter (GCI), as an important power electronic interface, is indicates that controller parameters of the outer power control
frequently used to deliver electricity to utility grid [2]. Recently, loop have an important effect on stability in low-frequency
oscillation phenomena of OWPPs in a wide frequency range due range. However, the effect of power operation point, i.e., active
and reactive power references, on stability has not been studied.
Manuscript received July 19, 2019; revised October 19, 2019 and December Impedance model of the GCI with both inner current control loop
10, 2019; accepted December 31, 2019. Date of publication January 10, 2020; and outer power control loop is established in [13], [14], which is
date of current version May 20, 2020. This work was supported by the ForskEL related with active and reactive power references. Furthermore,
and EUDP project “Voltage Control and Protection for a Grid towards 100%
Power Electronics and Cable Network” under Project 880063. Paper no. TEC- instability phenomena in a two-terminal VSC-HVDC system
00757-2019. (Corresponding author: Yanbo Wang.) can be caused by high active power reference [13], [20]. Also,
W. Zhou, Y. Wang, and Z. Chen are with the Department of Energy Tech- flow direction of active power of two-terminal and three-terminal
nology, Aalborg University, 9220 Aalborg, Denmark (e-mail: wez@et.aau.dk;
ywa@et.aau.dk; zch@et.aau.dk). VSC-HVDC systems can influence system stability [14]. How-
R. E. Torres-Olguin is with the SINTEF Energy Research Institute, 7034 ever, impacts of power level and flow direction of reactive power
Trondheim, Norway (e-mail: raymundo.torres-olguin@sintef.no). on system stability have slightly been analyzed.
Color versions of one or more of the figures in this article are available online
at https://ieeexplore.ieee.org. In addition to the aforementioned works about stability anal-
Digital Object Identifier 10.1109/TEC.2020.2965017 ysis of offshore wind generators connected to long transmission

0885-8969 © 2020 EU

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
838 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

cables, extensive researches about stability analysis of solar cables in [10], [11], [34]–[36] are used for phasor-domain
PV generators which work under weak grid condition have IBSC. In [34], the transmission cable is modelled as a Π section
been reported in [21]–[24]. The stability issues of PV inverters which consists of a series inductor and two parallel capacitors,
connected with weak grid considering effects of inner current which fails to reveal practical frequency characteristics and may
control loop on both low-frequency and high-frequency stability perform inaccurate stability assessment. Furthermore, circuit
are initially investigated in [21]. Furthermore, it is found in [22] models of transmission cables with consideration of distributed
that increase of grid impedance can suppress the low-frequency parasitic capacitance are established in [10], [11], [35], in
instability, whereas the increase of grid impedance can degrade which multiple-cascaded Π-section circuit model is used.
the high-frequency stability. In [23], a probabilistic method is However, per-unit-length (p.u.l.) resistance and inductance
presented to analyze the small-signal stability of power systems of transmission cable are still regarded as constant, which
with PV integration considering variation and uncertainty of cannot reveal practical frequency-dependent characteristics and
solar irradiation. In [24], a nonlinear describing function method corresponding damping characteristics. To simulate practical
is presented to perform the accurate stability analysis of PV frequency characteristics of transmission cables, extra RL
generators with consideration of the nonlinear and discontinuous branches are inserted into each Π section in parallel connection
perturbation and observation-based power control. However, in [37]–[39]. However, the established frequency-dependent
only stability analysis methods of PV generators connected circuit models are used for state space model-based eigenvalues
with weak grid are developed in [21]–[24], whereas no further analysis. Whether the RLC circuit model of transmission cable
stability enhancement strategies are explored. In [18], [25]–[30], considering frequency-dependent characteristics is applicable
dq impedance model of the GCI is reshaped to mitigate the for dq-domain IBSC should further be investigated.
negative effect of PLL on low-frequency stability. In [18], the In this paper, dq impedance models of GCIs with only inner
stability margin under weak grid condition is improved by opti- current control loop and PLL, and with outer power control
mizing current controller parameters. In [25], [26], the stability loop, inner current control loop and PLL are first established,
margin under weak grid condition is improved by decreasing respectively. A frequency scanning scheme is also developed to
PLL bandwidth. However, system dynamic performances will verify the correctness of the established dq impedance models.
be degraded, if a lower PLL bandwidth is adopted. In [27]–[30], The effects of active and reactive current/power references on
grid voltage feed-forward control strategies are used to reshape dq impedance feature, especially on quadrature-axis impedance
the quadrature-axis impedance to mitigate the negative effect feature, are then theoretically derived using complex space vec-
of PLL on low-frequency stability. However, too large or too tors and complex transfer functions. On its basis, a quadrature-
small grid voltage feed-forward coefficient can degrade system axis impedance reshaping method through negative reactive
stability, which makes it difficult to select optimal value [30]. power injection for low-frequency stability improvement is pre-
In addition, only inner current control loop and PLL, instead of sented. In addition, circuit model of transmission cable consider-
outer power control loop, are considered in [18], [21]–[30]. ing frequency-dependent characteristics of p.u.l. resistance and
Similar with OWPP case, reactive power injection has been inductance is established for dq-domain IBSC. The correctness
a well-developed solution of PV applications for voltage sup- of the effects of active and reactive current/power references on
port [31], for power transfer capability improvement [32], and quadrature-axis impedance feature and corresponding system
for power losses minimization [33]. However, few researches stability is validated in an OWPP. In addition, the effectiveness
have been reported to reshape the quadrature-axis impedance of the proposed low-frequency stabilization method based on
through adjusting power operation point. Case studies in [7] negative reactive power injection is verified with variation of
show that reactive power injection affects all the four compo- PLL bandwidth, grid strength and number of operating inverters.
nents of the dq impedance model when further considering outer Main contributions of this paper are summarized as follows.
power control loop. However, quantitative and general analysis 1) The dq impedance models of the GCI without and with
of the impacts of reactive power injection on quadrature-axis consideration of outer power control loop are reformu-
impedance and corresponding system stability has not been lated using complex space vectors and complex transfer
performed yet. To the best of the authors’ knowledge, there is no functions, which facilitates the observation of effects of
report about the application of the reactive power injection in ei- different control loops on dq impedance model.
ther OWPP case or PV case to mitigate low-frequency instability 2) The impact of reactive current/power injection on dq
phenomena through reshaping quadrature-axis impedance. The impedance model under current/power control mode, es-
low-frequency stabilization approach presented in this paper pecially on quadrature-axis impedance, is theoretically
may explore the inherent capability of the GCI to mitigate derived, which shows that the quadrature-axis impedance
low-frequency instability phenomena under weak grid condition without outer power control loop remains unchanged
by injecting negative reactive power. with variation of reactive power injection, whereas the
Besides the aforementioned dq impedance models of GCIs, quadrature-axis impedance will be affected by outer power
it’s also important to establish accurate circuit models of control loop.
transmission cables to reproduce practical terminal impedance 3) Circuit model of transmission cable considering
feature for dq-domain IBSC. Previous works about circuit frequency-dependent feature is established for dq-domain
modelling of transmission cable have been presented in [10], IBSC, which is able to obtain an accurate impedance-
[11], [34]–[39]. The established circuit models of transmission based stability analysis result.

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 839

4) A quadrature-axis impedance reshaping method through


negative reactive power injection to improve low-
frequency stability is presented, where the amount of re-
quired reactive power under a specific weak grid condition
can be obtained.
The rest of this paper is organized as follows. In Section II,
system configuration of the studied OWPP is introduced, fol-
lowed by impedance modelling of GCIs and transmission ca-
bles. In Section III, the effects of reactive power injection on
quadrature-axis impedance feature of current-controlled and
power-controlled GCIs are theoretically analyzed, based on
which the quadrature-axis impedance reshaping method through
negative reactive power injection is presented. The correctness
of the analysis results is validated in Section IV. On its basis, in
Section V, impacts of PLL parameters, grid strength and num-
ber of operating GCIs on required negative reactive power for
low-frequency stabilization are analyzed and validated. Finally,
conclusions are drawn in Section VI.

II. SYSTEM CONFIGURATION AND IMPEDANCE MODELING


Fig. 1. Typical configuration of an HVAC-connected OWPP. (a) Four PMSGs
In this section, system configuration of an exemplified OWPP connected with PCC via transmission cables in parallel. (b) Control structure of
the four GCIs.
is first depicted, followed by establishing dq impedance matrix
of GCI with consideration of outer power control loop, inner cur-
rent control loop and PLL. Also, circuit model of transmission
cable considering frequency-dependent feature is established. they share the same phase-locking principle and differ mainly
in the area of phase-angle measurement [40]. Its impact on the
converter output impedance is negative, which is not changed
A. System Configuration by advanced PLL, current, and power control strategies [7].
Fig. 1(a) shows the circuit configuration of an exemplified Therefore, the synchronous reference frame-PLL (SRF-PLL)
OWPP, where four permanent magnet synchronous generators which is currently the most common phase-locked method is
(PMSGs) are connected with point of common coupling (PCC) used in this paper.
through 575 V/ 33 kV transformers T1, T2, T3, T4 and trans- Instability phenomena may occur under weak grid condi-
mission cables TC1, TC2, TC3, TC4. And the 33 kV bus is tion. Specifically, the grid is regarded as weak if it has a high
connected into 150 kV main AC grid through 33 kV/150 kV impedance seen from PCC, which can be depicted by the short-
transformer T5 and transmission cable TC5. circuit ratio (SCR), shown as follows [32].
For each PMSG, controls of generator side converter and
GCI are decoupled, and dc-link voltage Vdc is regarded as PSC Vg2 / |Zg |
SCR = = (1)
constant [10]. Therefore, output impedances of the four PMSGs POW P P _rated POW P P _rated
are only dependent on the four GCIs. The control structure of
the GCIs is shown in Fig. 1(b), where outer power control loop, where PSC and POW P P _rated are the short-circuited capacity of
inner current control loop and PLL are marked as blue, black the grid at the PCC and the rated generation power of the OWPP,
and red, respectively. Although many PLL structures different respectively. Generally, the grid is weak when 2 ≤ SCR ≤ 3
from each other by the phase detectors have been proposed, and very weak when SCR < 2 [18].

 P LL P LL
 
Zdd Zdq −1 
CL = = −ΔI (ΔV )
m s s
ZLCL_no_P P LL P LL g,dq P CC,dq  ref
Zqd Zqq ΔIg,dq =0
 −1  
1 1
= YLCL,c − Vdc YLCL,g Gdel (Gci GP LL_i + GP LL_d )
m m m m m m
· I + Vdc YLCL,g Gdel Gci
m m m m
(2)
2 2
 P CL P CL
 
Zdd Zdq −1 
m
ZLCL_with_P CL = P CL P CL = = −ΔIg,dq (ΔVP CC,dq ) 
s s
Zqd Zqq ΔPPref
Q =0

 −1
1
= YLCL,c − Vdc YLCL,g Gdel ((Gci + Gci GcP Q GP Q_i )GP LL_i + GP LL_d − Gci GcP Q GP Q_v GP LL_v )
m m m m m m m m m m m m m
2
 
1
· I + Vdc YLCL,g Gdel (Gci + Gci GcP Q GP Q_i )
m m m m m m m
(3)
2

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
840 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Fig. 4. Multi-segment lumped-parameter RLC circuit model of transmission


cable.

Fig. 2. Block diagram of the GCIs in Fig. 1 using transfer matrices [7]. where ZS and YP are series impedance and shunt admittance;
z(ω) = r(ω) + jωl(ω) and y(ω) =  g(ω) + jωc(ω) the p.u.l.
impedance and admittance; γ(ω) = (z(ω)y(ω) propagation
constant, and L the length of transmission cable; r(ω), l(ω),
g(ω) and c(ω) p.u.l. resistance, inductance, conductance and
capacitance, respectively. For transmission cable, r(ω) and l(ω)
change as frequency varies. g(ω) can be ignored, and c(ω) is
regarded as constant [41].
2) Generate Cascaded Π-Section Circuit Model of Trans-
Fig. 3. Circuit model of transmission cable. (a) Two-port network model. mission Cable: In the proposed circuit modelling method,
(b) RL circuit model of p.u.l. series impedance. r(ω), l(ω) and c(ω) are first calculated by Matlab toolbox
power_cableparam based on the material and size of the trans-
B. DQ Impedance Modeling of GCI mission cable [42]. On its basis, vector fitting (VF) algorithm
is then employed to fit frequency characteristics of p.u.l. series
Output impedances of L-filtered GCI without and with outer impedance z(ω). The mathematical representation can be ob-
power control loop have been derived in [7]. On its basis, dq tained as follows [43].
impedance models of LCL-filtered GCIs without and with power
control loop can be established based on the control block 
N

diagram in Fig. 2, shown as (2) and (3) on the bottom of the f (s) = Bn /(s − An ) + D + sE (6)
m m n=1
previous page, where YLCL,c and YLCL,g are defined as follows.
 where f (s) is the fitted transfer function, N is the order of f (s),

m
YLCL,c = −ΔIg,dq
s
(ΔVPsCC,dq )−1  s Bn and An are the nth residue and pole pair. D is nonzero if the
ΔVm,dq =0
order of the numerator polynomial is not lower than the order
= (((ZLmf 1 )−1 + m −1 −1
(ZC f
) ) + ZLmf 2 )−1 of denominator polynomial. Nonzero E indicates the transfer
 (4) function is improper [43].

m
YLCL,g = ΔIg,dq
s
(ΔVm,dq
s
)−1  Equation (6) is then represented by an RL network, as shown
ΔVPsCC,dq =0
in Fig. 3(b), where parameters of the RL circuit are calculated
= (ZLmf 2 (I m + ((ZLmf 2 )−1 + (ZC
m −1
f
) )ZLmf 1 ))−1 as follows.
where the superscript m denotes matrix. Detailed expressions 
n

of the symbols in (2) and (3) are shown in Appendix A. It R0 = D − Bn /An L0 = E


i=1
can be seen that the two PLL-related transfer matrices (Gm P LL_i
and GmP LL_d ) and the three power control loop-related transfer Rk = Bk /Ak Lk = −Rk /Ak (k = 1, 2. . .N ) (7)
matrices (Gm m m
P LL_v , GP Q_i and GP Q_v ) are highly sensitive to
s s
operating point VP CC,dq , Ig,dq and Ddq s
. The effects of the Finally, cascaded Π-section circuit model of the transmission
operation point on dq impedance model will be investigated in cable is established, as shown in Fig. 4, where the parameters of
Section III. each Π section are calculated as follows.

R0 = R0 L/m L0 = L0 L/m Rk = Rk L/m


C. Circuit Modeling of Transmission Cable With
 
Consideration of Frequency-Dependent Characteristics Lk = Lk L/m C = cL/m (k = 1, 2. . .N ) (8)
1) Practical Electrical Characteristics of Transmission where L is cable length, m number of Π sections, c p.u.l.
Cable: Transmission cable can be modelled as a two-port net- capacitance. Basically, m increases as L increases. In addition,
work, as shown in Fig. 3(a). The parameters are given as fol- N increases as frequency range of interest widens.
lows [41]. Note that the impedance models of GCIs (2) and (3) are
sinh(γ(ω)L) established in dq-domain, whereas the impedance model of
ZS = z(ω)L transmission cable in Fig. 4 is established in phasor-domain. The
γ(ω)L
impedance models of GCIs and transmission cable should also
tanh(γ(ω)L/2) be represented in phasor-domain and dq-domain, respectively,
YP = y(ω)L (5)
γ(ω)L/2 to investigate the impedance interaction. The phasor-domain

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 841

TABLE I
CIRCUIT AND CONTROLLER PARAMETERS OF THE GCIS

impedance model of the GCI can be obtained as follows [44].


Zinv_pp Zinv_pn m −1
Zinv_pn =
m
= Am Z Zinv_dq (AZ )
m
(9)
Zinv_np Zinv_nn
m m
where Zinv_dq and Zinv_pn are dq-domain and modified Fig. 5. Comparison of different circuit models of transmission cable for
sequence-domain impedance models of the GCI, respectively. stability analysis. (a) Bode diagrams of output impedances of WideBand Line
√1
AmZ = 2 [1, j; 1, −j], Zinv_pp = Zinv (s + jω1 ), Zinv_nn =
model and RLC circuit models for 11 km transmission cable. (b) Bode diagrams
of output impedances of GCI 1 and 11 km transmission cable using different
Zinv (s − jω1 ). Zinv is the phasor-domain impedance model. circuit models.
On the other hand, the dq-domain impedance model of the
transmission cable can be obtained as follows.
−1 m
ZTmC_dq = (Am
Z ) ZT C_pn AZ
m
in form of Fig. 4 is established based on (7) and (8). Specifi-

cally, Bode diagrams of the frequency-dependent RLC circuit
m −1 ZT C_pp ZT C_pn models with different number of Π sections (1, 5, 10 and 20)
= (AZ ) Am
Z (10)
ZT C_np ZT C_nn ZF D_1_P i , ZF D_5_P i , ZF D_10_P i , ZF D_20_P i for the 11 km
transmission cable are plotted in Fig. 5(a). It can be seen that
where ZTmC_dq and ZTmC_pn are dq-domain and modified fitting accuracy becomes higher as the number of cascaded Π
sequence-domain impedance models of the transmission cable, sections increases. On the other hand, Bode diagram of termi-
respectively. ZT C_pn = ZT C_np = 0, ZT C_pp = Zcable (s + nal impedance of RLC circuit model which consists of 20 Π
jω1 ), ZT C_nn = Zcable (s − jω1 ). Zcable is the phasor-domain sections without consideration of frequency-dependent charac-
impedance model in Fig. 4. teristics Znon_F D_cable is plotted in Fig. 5(b). It can be seen that
3) Comparison of Different Circuit Models of Transmission the non-frequency-dependent RLC circuit model cannot reveal
Cable for Stability Analysis: Circuit and controller parameters practical damping characteristics, especially in high-frequency
of the GCIs are shown in Table I, where the bandwidths of range.
inner current control loop, outer power control loop and PLL Three-phase voltages and currents when GCI 1 is connected
are 278 Hz, 13 Hz and 111 Hz, respectively. In addition, the with the 11 km transmission cable using the non-frequency-
material and physical parameters of the transmission cables can dependent circuit model with 20 Π sections, WideBand Line
be found in [42]. Based on the material and physical parameters, model and frequency-dependent circuit model with 20 Π sec-
the OPAL-RT ARTEMiS-SSN library is able to generate the tions are shown in Figs. 6(a), 7(a) and 7(b), respectively. It
WideBand Line model which can accurately reproduce terminal can be seen that the system is unstable in Fig. 6(a) and stable
impedance characteristics [45]. Therefore, the WideBand Line in Figs. 7(a),(b). In addition, frequency spectrum of Fig. 6(a)
model will be regarded as a benchmark to assess the accuracy is shown in Fig. 6(b), where oscillation phenomena occur at
of the fitted RLC circuit models. The Bode diagram of the 427 Hz and 714 Hz. To reveal the high-frequency oscillation
WideBand Line model for a 11 km transmission line, i.e., SCR phenomena, phasor-domain impedance model of GCI 1 Zinv
= 3.27, is plotted as Zwideband in Fig. 5(a). is calculated from (2) using matrix transformation (9), and
Furthermore, Matlab toolbox power_cableparam is used to Bode diagram of Zinv is plotted in Fig. 5(b). It can be seen
calculate r(ω) and l(ω). On its basis, z(ω) is fitted as (6) using that magnitudes of Zinv and Znon_F D_cable interact at both
VF algorithm, and frequency-dependent RLC circuit models 424 Hz and 699 Hz, where phase angle differences are higher

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
842 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Fig. 8. Block diagram of the GCIs in Fig. 1 using complex space vectors and
complex transfer functions.

III. IMPACTS OF ACTIVE AND REACTIVE POWER ON DQ


IMPEDANCE FEATURE OF THE GCI
In this section, impacts of active and reactive current/power
references on low-frequency dq impedance characteristics of the
GCI are first theoretically derived using complex space vectors
and complex transfer functions. On its basis, a quadrature-axis
Fig. 6. Simulation results using non-frequency dependent circuit model with impedance reshaping method through reactive power injection
20 Π sections. (a) Time-domain simulation results. (b) Frequency spectrum of is presented.
three-phase voltages and currents.

A. Theoretical Derivation of Impacts of Active and Reactive


Current/Power References on DQ Impedance Characteristics
The dq impedance models in (2) and (3) will be reformulated
using complex space vectors and complex transfer functions
to clearly observe the effects of different control loops on dq
impedance characteristics. The complex transfer function rep-
resentations of the transfer matrices in (2) and (3) are listed in
Appendix A, based on which the complex transfer functions-
based control block diagram of the GCIs is derived in Fig. 8.
1) Without Outer Power Control Loop: The closed-loop re-
sponse of ΔIsg,dq can be derived from Fig. 8, shown as follows.

−ΔIsg,dq ΔIref = Ycl,dq
CCL
ΔVsPCC,dq −Ycl,dq
PLL
ΔVsPCC,dq
g,dq=0

+ Ycl,dq
PLL
ΔVs∗
PCC,dq (11)

where Ycl,dq
CCL
and Ycl,dq
PLL
are the complex transfer function
representations of current control loop-related and PLL-related
Fig. 7. Time-domain simulation results using WideBand Line model and output admittance, respectively, shown as follows.
frequency-dependent circuit model with 20 Π sections. (a) Simulation results us-
ing the WideBand Line model. (b) Simulation results using frequency-dependent
circuit model with 20 Π sections.
Ycl,dq
CCL
= YLCL,c /(1 + Tcl,dq )
 
G+,PLL_d
Ycl,dq
PLL
= + G+,PLL_i GCCL (12)
Gci cl,dq

than 180◦ . It indicates that the system is unstable at the two


1
frequency points. In addition, magnitudes of Zwideband and where GCCL cl,dq = Tcl,dq /(1 + Tcl,dq ) and Tcl,dq = 2 Vdc
ZF D_20_P i do not interact with Zinv in non-passive region of YLCL,g Gdel Gci are the closed-loop and open-loop gains of
GCI 1, which indicates that the system is stable. The analysis the current control loop, respectively.
results agree with the simulation results in Figs. 6 and 7. Since When ΔIref g,dq = 0, the following equation can be obtained
low-frequency stability is focused in this paper, and the low- based on (11).
frequency impedance characteristic of transmission cable can   CCL

be reproduced by one Π section, the proposed one-Π-section- ΔIsg,dq Ycl,dq − Ycl,dq


PLL
Ycl,dq
PLL
− = ...
based frequency-dependent RLC circuit modelling method of ΔIs∗
g,dq Ycl,dq
PLL∗
Ycl,dq
CCL∗
− Ycl,dq
PLL∗

transmission cable will be used in Sections IV and V for the    


ΔVsPCC,dq PLL,m ΔVPCC,dq
s
dq impedance-based stability analysis of the OWPP shown in = Y±,dq (13)
Fig. 1(a). ΔVs∗PCC,dq ΔVs∗PCC,dq

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 843

PLL,m
Y±,dq is actually the modified sequence-domain admit- where Ycl,dq
CCL1
and Ycl,dq
PLL1
are the complex transfer function
tance model [46]. The four components of the dq-domain admit- representations of current control loop-related and PLL-related
tance model (2) can thus be derived using (9), shown as follows. output admittance when considering power control loop, respec-
tively. In addition, Ycl,dq
PCL1
and Ycl,dq
PCL2
are the power control
Ycl,dq
CCL
+ Ycl,dq
CCL∗
loop-related output admittance. The detailed expressions are
P LL
Ydd =
2 shown as follows.

Ycl,dq − Ycl,dq
CCL CCL∗
1 + Tcl,dq CCL
P LL
Ydq =j −Ycl,dq + Ycl,dq
PLL PLL∗
Ycl,dq
CCL1
= Ycl,dq
2 1 + TPCL
cl,dq

Ycl,dq
CCL∗
− Ycl,dq
CCL
1 + Tcl,dq PLL
P LL
Yqd =j Ycl,dq
PLL1
= Ycl,dq
2 1 + TPCL
cl,dq

Ycl,dq
CCL
+ Ycl,dq
CCL∗ 2Tcl,dq
P LL
Yqq = −Ycl,dq
PLL
− Ycl,dq
PLL∗
(14) Ycl,dq
PCL1
= G+,PLL_i VPCC,dq
s∗
GcPQ
2 1 + TPCL
cl,dq

It can be seen from (2) and (14) that the effects of current Tcl,dq
control loop and PLL on the four components of the dq admit- Ycl,dq
PCL2
= (Isg,dq − 2G+,PLL_i VPCC,dq
s∗
)GcPQ
1 + TPCL
cl,dq
tance model can be clearly observed with the help of complex
P LL (17)
transfer functions. Specifically, PLL dynamics only affect Ydq
P LL
and Yqq . By substituting (12), (37) and (40) into (14), it can
P LL P LL
where TPCL
cl,dq
= (1 + GcPQ VPCC,dq
s∗
)Tcl,dq .
be found that Yqq and Ydq are affected by active power Similar with (13), the complex transfer function represen-
s s
injection Ig,d and reactive power injection Ig,q , respectively. In tation of the dq admittance model when further considering
addition, the four components of the dq impedance model are power control loop can be derived based on (16), shown as
shown in (15) (L-type filter Lf is used here for simplicity.). follows.
1

P LL
Zdd = Zinv + j ω1 Lf (Vc,q
s
+ Ig,q
s
Gci )GP LL Gdel Vdc /. . . Y±,dd
PCL
Y±,dq
PCL
2 PCL,m
Y±,dq = (18)
  Y±,dq
PCL∗
Y±,dd
PCL∗
1 s
1 − (Vc,d + Ig,d
s
Gci )GP LL Gdel Vdc
2
where
1 s
P LL
Zdq = −ω1 Lf + j (Vc,q + Ig,q
s
Gci )
2 Y±,dd
PCL
= Ycl,dq
CCL1
− Ycl,dq
PLL1
− Ycl,dq
PCL1
 
1 Y±,dq
PCL
= Ycl,dq
PLL1
− Ycl,dq
PCL2
(19)
× Lf s + Gci Gdel Vdc . . .GP LL Gdel Vdc /
2
  By substituting (14) and (17) into (19), and applying the in-
1 s
1 − (Vc,d + Ig,d
s
Gci )GP LL Gdel Vdc verse transformation of (9), the dq admittance model considering
2
  power control loop is shown as follows.
1 s
P LL
Zqd = (ω1 Lf )/ 1 − (Vc,d + Ig,d Gci )GP LL Gdel Vdc
s
1 + Tcl,dq P LL Tcl,dq GcPQ P ref
2 P CL
Ydd = Ydd −
  1 + TPCL 1 + TPCL s
1 s cl,dq cl,dq VP CC,d
P LL
Zqq = Zinv / 1 − (Vc,d + Ig,d Gci )GP LL Gdel Vdc
s
2 1 + Tcl,dq P LL Tcl,dq GcPQ Qref
(15)
P CL
Ydq = Ydq + ...
1 + TPCL
cl,dq 1 + TPCL s
cl,dq VP CC,d

where Zinv = Lf s + 12 Vdc Gci Gdel . It can be seen from (15) (2GP LL VPsCC,d − 1)
s P LL P LL
that reactive current injection Ig,q affects both Zdd and Zdq .
P LL
Note that the case study in [7] shows that only Zdq is affected 1 + Tcl,dq P LL Tcl,dq GcPQ Qref
P CL
Yqd = Yqd −
s
by Ig,q , which may be not accurate based on the aforementioned 1 + TPCL
cl,dq 1 + TPCL s
cl,dq VP CC,d
analysis.
1 + Tcl,dq P LL Tcl,dq GcPQ P ref
2) With Outer Power Control Loop: Similar with (11), the P CL
Yqq = Yqq + ...
closed-loop response of ΔIsg,dq when further considering power 1 + TPCL
cl,dq 1 + TPCL s
cl,dq VP CC,d
control loop can be derived from Fig. 8, shown as follows. (1 − 2GP LL VPsCC,d ) (20)

−ΔIsg,dq ΔPref =0 = Ycl,dqCCL1
ΔVsPCC,dq − Ycl,dq PLL1
...
PQ It can be seen from (14) and (20) that, under power control
P CL P CL
ΔVsPCC,dq + Ycl,dq
PLL1
ΔVs∗ − Ycl,dq
PCL1
ΔVsPCC,dq . . . mode, Ydd and Yqq are affected by active power injection
PCC,dq
ref P CL P CL
P . In addition, Ydq and Yqd are affected by reactive
−Ycl,dq
PCL2
ΔVs∗
PCC,dq (16) power injection Q .ref

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
844 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Similar with (15), the four components of the dq impedance negative flow direction of reactive power is required for passivity
model (3) can be derived as follows. enforcement. Therefore,
 
P CL
Zdd =
BD + CE ∠Zqq
P CL
∈ (−90◦ , −0◦ ) ↔ Γ1_2 + Γ2_2 P ref − Γ3 Qref  < 0
A
(25)
BE − CD
P CL
Zdq =
A Based on (25), for a given P ref , passivity of Zqq P CL
can be
ref
ref
GcP Q Gci Gdel Ig,q B − CF enforced if Q satisfies the following inequation.
P CL
Zqd =  ref   ref  Γ1_2 + Γ2_2 Pref    
A  Q  > Q  =  ref   ref 
min =  Q min 1  +  Q min 2 
ref
GcP Q Gci Gdel Ig,q C + BF Γ3
P CL
Zqq =− (21)
A (26)
where the detailed expressions of A, B. . ., F are shown in
where |Qref ref
min 1 | and |Qmin 2 | are independent and dependent on
Appendix B. It can be seen from (21) and (43) that, when further
active power injection, respectively.
considering power control loop, all of the four elements of the
On the other hand, for a given negative Qref , passivity of
dq impedance model are affected by both active and reactive
Zqq can be enforced if P ref satisfies the following inequation.
P CL
power injection P ref and Qref .
−Γ1_2 + Γ3 |Qref | ref ref
P ref < Pmax
ref
= = Pmax 1 + Pmax 2
B. Impacts of Active and Reactive Power References on Γ2_2
Low-Frequency Stability (27)
P CL
Since low-frequency stability is mainly determined by Zqq , where Pmaxref ref
ref ref P CL 1 and Pmax 2 are independent and dependent on
investigation of impacts of P and Q on Zqq is focused reactive power injection, respectively. When the grid impedance
P CL
here [18], [27]–[29]. Zqq is reformulated as follows. is not purely inductive, e.g., the phase angle of grid impedance
is lower than 90◦ , the allowed maximum delivered active power
Γ1 + Γ2 P ref + Γ3 Qref
P CL
Zqq =− (22) ref
not to trigger the low-frequency instability is higher than Pmax ,
A and the required minimum reactive power to mitigate the low-
where Γ1 , Γ2 and Γ3 are shown as follows. frequency instability is lower than |Qref
min |.
Gdel Vdc Gci (1 + GcP Q VPsCC,d )
Γ1 = L f s + = Γ1_1 s + Γ1_2 IV. SIMULATION VERIFICATION OF IMPACTS OF ACTIVE AND
2
REACTIVE POWER ON LOW-FREQUENCY STABILITY
Gci GcP Q Gdel Lf s
Γ2 = + ··· In this section, the impacts of power control loop, ac-
VPsCC,d
tive and reactive power on low-frequency stability derived in
G2ci GcP Q G2del Vdc (1 + GcP Q VPsCC,d ) Section III are verified by time-domain simulation results in
= Γ2_1 s + Γ2_2
2VPsCC,d Matlab/Simulink.

Gci GcP Q Gdel ω1 Lf A. Impact of Power Control Loop on Low-Frequency Stability


Γ3 = (23)
VPsCC,d
Fig. 9(a) shows Bode diagrams of measured impedance
P CL frequency responses of GCI 1 without power control loop
Then, phase angle of Zqq
at specific angular frequency ω0
m,mea ref
CL when Ig,d = 1.5 kA and Ig,q = 0, and with
ref
can be derived as follows. ZLCL_no_P
m,mea
 (Γ1_1 + Γ2_1 P ref )ω0 power control loop ZLCL_with_P CL when P ref = 1.3 MW
P CL 
∠Zqq = −180◦ +arctan and Qref = 0 obtained by frequency scanning method. Zdq
s=jω0 Γ1_2 + Γ2_2 P ref +Γ3 Qref
and Zqd are omitted, since instability phenomena can be re-
(24) vealed using diagonal elements Zdd and Zqq [7], [18]. Bode
It can be seen from (24) that ∠Zqq
P CL
may be below −90◦ diagram of the theoretically-derived dq impedance model with-
m
out power control loop ZLCL_no_P CL using (2) is also plotted
for certain combination of P ref and Qref , which may lead to m,mea
in Fig. 9(a). It can be seen that ZLCL_no_P CL highly agrees
instability phenomena under weak grid condition. m
with ZLCL_no_P CL , which verifies the correctness of the mea-
sured impedance data. In addition, Bode diagram of the dq
C. Requirement of Flow Direction and Power Level of
impedance model of frequency-dependent circuit model with
Reactive Power Injection for Stability Enhancement
one Π section of a 19 km transmission cable, i.e., SCR = 1.90,
The parameters in (24) except Qref are guaranteed to be pos- m
derived by the method presented in Section II is shown as ZLdq
itive. Therefore, if Qref ≥ 0, then ∠Zqq P CL
∈ (−180◦ , −90◦ ), m,mea
in Fig. 9(a). Magnitude of ZLCL_with_P CL interacts with that
P CL m
which means that the passivity of Zqq cannot be guaranteed of ZLdq at point A (20 Hz), where phase angle difference is
under positive flow direction of reactive power. In other words, 84 − (−98) = 182◦ , which indicates that the system is unstable.

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 845

Fig. 9. Impedance-based stability analysis of GCI 1 connected with 19 km transmission cable and simulation results considering effect of power control loop.
(a) Bode diagrams. (b) Three-phase voltages and currents. (c) Active and reactive power.

Fig. 10. Impedance-based stability analysis of GCI 1 connected with 19 km transmission cable and simulation results considering effect of different P ref with
Qref = 0. (a) Bode diagrams. (b) Three-phase voltages and currents. (c) Active and reactive power.

m,mea
On the other hand, magnitude of ZLCL_no_P CL interacts with
range, which agrees with the theoretical analysis results in
m Section III.A.
that of ZLdq at point B (22 Hz), where phase angle difference
is 74.4 − (−91.1) = 165.5◦ , which indicates that the system is
stable.
B. Impact of Active Power on Low-Frequency Stability
Figs. 9(b), (c) show corresponding simulation results with
power control loop before 3 s and without power control loop Fig. 10(a) shows Bode diagrams of Zdd and Zqq of dq
after 3 s. It can be seen that low-frequency oscillation phenom- impedance matrices of GCI 1 as P ref increases from 0.1 MW
ena occur before 3 s. Frequency spectrum of phase A voltage to 2.0 MW and Qref = 0. It can be seen that magnitude of Zqq
and current before 3 s is shown in Fig. 9(a). It can be seen decreases in low-frequency range as P ref increases, making
that oscillation phenomenon occurs at 26.75 Hz (50−23.25 = magnitude interaction point move leftward and phase angle dif-
26.75 Hz) and 73.25 Hz (50 + 23.25 = 73.25 Hz), which ference increase. For example, if P ref is increased from 0.5 MW
verifies correctness of the impedance-based stability analy- to 2.0 MW, magnitude interaction point of Zqq moves from point
sis. Therefore, the presence of power control loop increases C to point D, where phase angle difference is increased from
the possibility of instability phenomena in low-frequency 74 − (−95) = 169◦ to 84 − (−98) = 182◦ . It indicates that the

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
846 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Fig. 11. Impedance-based stability analysis of GCI 1 connected with 19 km transmission cable and simulation results considering effect of different Qref with
P ref = 2.0 MW. (a) Bode diagrams. (b) Three-phase voltages and currents. (c) Active and reactive power.

system is stable when P ref = 0.5 MW, and unstable when Bode diagrams in Fig. 11(a). It can be seen that negative reactive
P ref = 2.0 MW. Similarly, it can be seen that the system is stable power of GCI 1 can be adjusted to stabilize the low-frequency
when P ref = 0.1 MW and unstable when P ref = 1.3 MW. oscillation, which agrees with the theoretical analysis results in
Figs. 10(b), (c) show corresponding simulation results of GCI Section III.C.
1 when P ref changes from 1.3 MW to 0.5 MW at 3 s and
from 0.5 MW to 2.0 MW at 6 s. It can be seen that GCI 1 is V. IMPACTS OF DIFFERENT FACTORS ON REQUIRED REACTIVE
stable when P ref is 0.5 MW, and is unstable when P ref are POWER FOR LOW-FREQUENCY STABILIZATION
1.3 MW and 2.0 MW, respectively. The simulation results agree In this section, impacts of different factors, e.g., PLL parame-
with the theoretical analysis result in Fig. 10(a). In addition, ters, length of transmission cable and number of paralleled GCIs,
frequency spectrum of three-phase voltages and currents from on required reactive power for low-frequency stabilization are
6 s to 9 s is also shown in Fig. 10(a). It can be seen from Figs. 9(a) investigated. Real-time verification based on OPAL-RT digital
and 10(a) that total harmonic distortion (THD) of three-phase simulator platform is also performed. In addition, comparisons
voltages increases from 319.92% to 401.98%, and THD of three- among the presented low-frequency stabilization method and
phase currents increases from 100.77% to 131.84% once P ref existing commonly-used methods are also performed.
is increased from 1.3 MW to 2.0 MW. In conclusion, higher
P ref tends to cause low-frequency instability when the GCI is
A. Impact of PLL Parameters on Required Reactive Power for
connected into weak grid, and brings severer distortion of three-
Low-Frequency Stabilization
phase voltages and currents, which agrees with the theoretical
analysis results in Section III.C. Fig. 12(a) shows Bode diagrams of output impedances of GCI
1 with different PLL controller parameters and Qref . It can be
seen that, when PLL bandwidth fpll = 56 Hz (kppll = 10 and
C. Impact of Reactive Power on Low-Frequency Stability kipll = 50) and Qref = −0.1 MVar, phase angle difference at
Fig. 11(a) shows Bode diagrams of output impedances of magnitude interaction point A (20 Hz) is 83.57 − (−96.22) =
GCI 1 with P ref = 2.0 MW and Qref changing from 0 MVar 179.79◦ , which indicates that the system is stable. In addition,
to −1.2 MVar. When Qref is 0 MVar or −0.1 MVar, phase when fpll = 133 Hz (kppll = 24 and kipll = 288) and Qref =
angle difference at magnitude interaction point E of Zqq is −0.1 MVar, phase angle difference at magnitude interaction
84 − (−99) = 183◦ or 84 − (−98) = 182◦ , which indicates point A (20 Hz) is 83.57 − (−99.05) = 182.62◦ , which indi-
that the system is unstable. When Qref is changed to −0.8 MVar cates that the system is unstable. Furthermore, when fpll = 133
and −1.2 MVar, phase angles of Zqq of GCI 1 impedance matrix Hz and Qref = −0.6 MVar, phase angle difference at magnitude
at magnitude interaction points E and F are within −90◦ , which interaction point A (20 Hz) is 83.57 − (−87.57) = 171.14◦ ,
indicates that the system is stable. which indicates that the system is stable. Figs. 12(b), (c) show
Figs. 11(b), (c) show corresponding simulation results of GCI corresponding simulation results when PLL controller parame-
1 with P ref = 2.0 MW and Qref changing from 0 MVar to −0.8 ters and reactive power reference change from fpll = 56 Hz and
MVar at 1 s and from −0.8 MVar to −0.1 MVar at 4 s. It can be Qref = −0.1 MVar to fpll = 133 Hz and Qref = −0.1 MVar
seen that the system is unstable from 0 s to 1 s, stable from 1 s at 3 s, to fpll = 133 Hz and Qref = −0.6 MVar at 7 s. It can
to 4 s and unstable again from 4 s to 8 s, which agree with the be seen that the system is stable from 0 s to 3 s, unstable from

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 847

Fig. 12. Impedance-based stability analysis and simulation results of GCI 1 with different PLL controller parameters and Qref . (a) Bode diagrams. (b) Three-phase
voltages and currents. (c) Active and reactive power.

Fig. 13. Impedance-based stability analysis and simulation results of GCI 1 connected with length-scalable transmission cable. (a) Bode diagrams. (b) Three-phase
voltages and currents. (c) Active and reactive power.

3 s to 7 s, stable again from 7 s, respectively. Simulation results when LT C = 20 km, i.e., SCR = 1.80, and Qref = −0.1 MVar,
agree with the impedance-based stability analysis in Fig. 12(a). phase angle difference at magnitude interaction point B (17 Hz)
It can be seen that the GCI with lower PLL bandwidth can be is 82.71 − (−99.17) = 181.88◦ , which indicates that the system
stabilized by less negative reactive power. is unstable. Furthermore, when LT C = 20 km and Qref = −0.7
MVar, phase angle difference at magnitude interaction point C
(16 Hz) is 84.59 − (−94.50) = 179.09◦ , which indicates that
B. Impact of Length of Transmission Cable on Required the system is stable again. Figs. 13(b), (c) show correspond-
Reactive Power for Low-Frequency Stabilization ing simulation results with length of transmission cable and
Fig. 13(a) shows Bode diagrams of grid impedance and output reactive power reference changing from LT C = 19 km and
impedance of GCI 1 with different Qref when P ref = 2.0 Qref = −0.1 MVar to LT C = 20 km and Qref = −0.1 MVar
MW and fpll = 89 Hz (kppll = 16 and kipll = 128). When at 4 s, to LT C = 20 km and Qref = −0.7 MVar at 6 s. It can be
LT C = 19 km and Qref = −0.1 MVar, phase angle difference seen that the system is stable from 0 s to 4 s, unstable from 4 s
at magnitude interaction point A (20 Hz) is 83.57 − (−95.86) = to 6 s, stable again from 6 s, respectively. Frequency spectrum
179.43◦ , which indicates that the system is stable. In addition, of three-phase voltages and currents when LT C = 20 km and

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
848 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Fig. 14. Impedance-based stability analysis and simulation results of the OWPP shown in Fig. 1(a). (a) Bode diagrams. (b) Three-phase voltages and currents.
(c) Active and reactive power.

TABLE II Qref = −0.7 MVar is shown in Fig. 14(a). It can be seen that
IMPACT OF NUMBER OF PARALLELED GCIS ON REQUIRED REACTIVE
POWER FOR LOW-FREQUENCY STABILIZATION the simulation results agree with the impedance-based stability
analysis. In conclusion, integration of more GCIs tends to make
OWPP unstable, which can be stabilized by injecting more
negative reactive power.

D. Real-Time Simulation Verification Based on OPAL-RT


Platform
Real-time simulation verification based on OPAL-RT digital
simulator platform is performed to further validate the correct-
Qref = −0.1 MVar is shown in Fig. 13(a). It can be seen that
ness of the theoretical analysis results in Section III and the
the simulation results agree with the impedance-based stability
time-domain simulation results obtained by Matlab/Simulink.
analysis results. Therefore, weaker grid tends to make system
Fig. 15 shows the picture of the adopted OP5600 real-time digital
unstable, which can be stabilized by more negative reactive
simulator. The OP5600 combines the power and reliability of
power injection.
Intel Xeon E5 processing cores with the high-performance latest
generation Xilinx Virtex-6 FPGA to address a wide range of
C. Impact of Number of Paralleled GCIs on Required Reactive rapid control prototyping applications with OPAL-RT s RT-
Power for Low-Frequency Stabilization
LAB or HYPERSIM software platforms. The Simulink-based
Fig. 14(a) shows Bode diagrams of the OWPP in Fig. 1(a) model is established in the RT-LAB software, based on which
with P ref = 2.0 MW, fpll = 89 Hz, different number of par- code is generated and downloaded into the OP5600 hardware.
alleled GCIs NGCI and different Qref . When NGCI = 2, Both software and hardware platforms allow high-speed and
Qref = −0.1 MVar and NGCI = 2, Qref = −0.7 MVar, phase real-time simulation. The real-time simulation results obtained
angle differences at magnitude interaction points A (19 Hz) by OPAL-RT platform are then processed in Matlab. The circuit
and B (17 Hz) are 84.99 − (−97.81) = 182.8◦ and 86.45 − and controller parameters of the GCI used in the real-time
(−90.02) = 176.47◦ , respectively, which indicate that the sys- simulation verification are shown in Table I.
tem is unstable and stable in the two cases, respectively. In Fig. 16 shows the real-time verification of the effect of outer
addition, when NGCI = 4, Qref = −0.7 MVar, phase angle power control loop on low-frequency stability. It can be seen
difference at magnitude interaction point C (11 Hz) is 87.71 − that the system is unstable with power control loop before 3 s,
(−104.80) = 192.51◦ , which indicates that the system is un- and stable without power control loop after 3 s, which agrees
stable. Finally, when NGCI = 4, Qref = −2.0 MVar, the Bode with the simulation results based on Matlab/Simulink in Fig. 9.
diagrams indicate that the system is stable. The corresponding Fig. 17 shows the real-time verification of the effect of active
simulation results are shown in Figs. 14(b), (c), and collected in power delivery on low-frequency stability. It can be seen that
the fifth and sixth columns in Table II. In addition, frequency the system is unstable with Pref = 1.3 MW before 3 s, stable
spectrum of three-phase voltages and currents when NGCI = 2, with Pref = 0.5 MW between 3 s and 6 s, and unstable again

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 849

Fig. 18. OPAL-RT platform-based real-time verification of the simulation


results in Fig. 11. (a) Three-phase voltages and currents. (b) Active and reactive
power. (c) FFT of three-phase voltages and currents between 4 s and 6 s.

Fig. 15. Picture of the OP5600 real-time digital simulator platform in


laboratory.

Fig. 19. OPAL-RT platform-based real-time verification of the simulation


results in Fig. 12. (a) Three-phase voltages and currents. (b) Active and reactive
power. (c) FFT of three-phase voltages and currents between 3 s and 7 s.

Fig. 16. OPAL-RT platform-based real-time verification of the simulation


results in Fig. 9. (a) Three-phase voltages and currents. (b) Active and reactive
power. (c) FFT of three-phase voltages and currents with power control loop.

Fig. 20. Simulation results of q-axis output voltage VP CC,q of PLL when
P ref is changed from 2.0 MW to 1.0 MW at 2.0 s based on two low-frequency
stabilization schemes. (a) Scheme 1: By decreasing PLL controller parame-
ters from kpll = 20, 200 to kpll = 10, 50, kpll = 6, 18 and kpll = 2, 2 with
Qref = −0.1 MVar. (b) Scheme 2: By increasing negative reactive power
injection from Qref = −0.1 MVar to Qref = −0.8 MVar, Qref = −1.2
MVar and Qref = −1.5 MVar with kpll = 20, 200.

with Pref = 2.0 MW after 6 s, which agrees with the simulation


results based on Matlab/Simulink in Fig. 10.
Fig. 18 shows the real-time verification of the effect of reactive
power injection on low-frequency stability. It can be seen that
the system is unstable with Qref = 0 before 1 s, stable with
Qref = −0.8 MVar between 1 s and 4 s, and unstable with
Fig. 17. OPAL-RT platform-based real-time verification of the simulation
results in Fig. 10. (a) Three-phase voltages and currents. (b) Active and reactive Qref = −0.1 MVar after 4 s, which agrees with the simulation
power. (c) FFT of three-phase voltages and currents between 6 s and 9 s. results based on Matlab/Simulink in Fig. 11.

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
850 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

Fig. 21. Impedance-based stability analysis of GCI 1 connected with 19 km transmission cable and simulation results considering effect of different grid voltage
feed-forward coefficient Gf f v . (a) Bode diagrams of q-q component of dq impedance model. (b) Zoomed Bode diagrams of (a). (c) Three-phase voltages and
currents when Gf f v is increased from 1.0435e-3 to 1.4783e-3 at 20 s. (d) Active and reactive power when Gf f v is increased from 1.0435e-3 to 1.4783e-3 at 20 s.
(e) Three-phase voltages and currents when Gf f v is decreased from 1.3043e-3 to 8.6957e-5 at 10 s. (d) Active and reactive power when Gf f v is decreased from
1.3043e-3 to 8.6957e-5 at 10 s.

Fig. 19 shows the real-time verification of the effect of PLL In addition, the low-frequency instability phenomena can also
bandwidth on require negative reactive power for low-frequency be mitigated based on grid voltage feed-forward control which is
stabilization. It can be seen that the system is stable with kppll = able to reshape the output impedance of the GCI [27]–[30]. High
10, kipll = 50 and Qref = −0.1 MVar before 3 s, unstable with proportional feed-forward coefficient Gf f v increases |Zqq |,
kppll = 24, kipll = 288 and Qref = −0.1 MVar between 3 s and which tends to increase stability margin. However, high Gf f v
7 s, and stable again with kppll = 24, kipll = 288 and Qref = also decreases ∠Zqq , which tends to decrease stability margin.
−0.6 MVar after 7 s, which agrees with the simulation results To further illustrate the two opposite impacts of the usage of grid
based on Matlab/Simulink in Fig. 12. voltage feed-forward control loop on the low-frequency stability,
Figs. 21(a) and (b) show the Bode diagrams of Zqq with different
Gf f v . It can be seen that when Gf f v is 8.6957e-5 or 1.4783e-3,
E. Discussions of the Presented Low-Frequency Stability phase angle difference at magnitude interaction points A (20 Hz)
Improvement Method Based on Negative Reactive and B (21 Hz) are 83.56 − (−98.56) = 182.12◦ or 78.98 −
Power Injection (−101.11) = 180.09◦ , respectively, which indicates that the
It can be seen from Figs. 11 and 12 that the low-frequency system is unstable under the two cases. In addition, when Gf f v
instability phenomenon which occurs when P ref = 2.0 MW, is 1.0435e-3 or 1.3043e-3, phase angle difference at magnitude
Qref = −0.1 MVar, kppll = 20 and kipll = 200 can be mit- interaction point B (21 Hz) is 78.98 − (−100.32) = 179.30◦
igated by either increasing negative reactive power injection or 78.98 − (−100.79) = 179.77◦ , respectively, which indicates
Qref from −0.1 MVar to −0.8 MVar or reducing PLL controller that the system is stable under the two cases. Figs. 21(c) and
parameters from kppll = 20 and kipll = 200 to kppll = 10 and (d) show the simulation results when Gf f v is increased from
kipll = 50. The low-frequency stabilization method based on 1.0435e-3 to 1.4783e-3 at 20 s, which indicates that the stable
PLL controller parameters re-tuning has actually been investi- system becomes unstable again if larger Gf f v is selected. In
gated in [18], [25], [26]. However, phase tracking performance addition, Figs. 21(e) and (f) show the simulation results when
may be weakened, if the PLL bandwidth is decreased. Fig. 20(a) Gf f v is decreased from 1.3043e-3 to 8.6957e-5 at 10 s, which
shows the simulation results of q-axis output voltage VP CC,q indicates that the system becomes unstable again if smaller Gf f v
of PLL when P ref is changed from 2.0 MW to 1.0 MW at is selected. The simulation results in Figs. 21(c)-(f) agree with
2.0 s with different PLL controller parameters and Qref = −0.1 the impedance-based stability analysis in Figs. 21(a) and (b).
MVar. It can be seen that the system with lower PLL bandwidth Both the impedance-based stability analysis and the simulation
experiences a larger deviation and slower dynamics. Therefore, results indicate that the system can be unstable if too large or
decreasing PLL bandwidth is actually a trade-off between sys- too small Gf f v is adopted. On the other hand, as derived in
tem stability and PLL dynamics. On the other hand, Fig. 20(b) Section III.C, the system can be stabilized only if amount of the
shows the simulation results of q-axis output voltage VP CC,q of negative reactive power injection |Qref | is larger than |Qref min |
PLL when P ref is changed from 2.0 MW to 1.0 MW at 2.0 s which is calculated based on (26).
with different amount of negative reactive power injection and
kppll = 20, kipll = 200. It can be seen that the system dynamic
VI. CONCLUSION
is slightly affected by reactive power injection, i.e., the presented
method is able to improve system low-frequency stability while This paper investigates the impacts of power control
maintaining fast system dynamics. loop and reactive power injection on dq impedance model

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 851

and low-frequency stability of OWPPs, and presents a where zdq = [zd , zq ]T and zdq = zd + jzq . x∗dq = xd − jxq is
low-frequency stability improvement strategy based on the complex conjugate of xdq . Specifically, if ydq
m
is symmet-
reshaping the quadrature-axis impedance through injecting rical, i.e., ydd = yqq = yd and yqd = −ydq = yq , (30) can be
negative reactive power. The circuit model of transmission simplified as follows.
cable considering frequency-dependent characteristics is also
established for dq-domain IBSC. Simulation results show zdq = ydq xdq (31)
that the established circuit model is able to obtain accurate where ydq = yd + jyq .
impedance-based stability analysis results. In addition, dq According to (29), the transfer matrices in (2) and (3) can be
impedance model of GCI is established using transfer matrices represented as complex transfer functions, shown as follows.
and reformulated using complex transfer functions to investigate  
sLf i −ω1 Lf i
the effects of different control loops on dq impedance feature, ZLmf i = → ZLfi = sLf i + jω1 Lf i (32)
based on which this paper shows that reactive power injection ω 1 Lf i sLf i
under power control mode is able to affect the quadrature-axis where ω1 = 2πf1 is the fundamental angular frequency and i =
impedance, whereas the quadrature-axis impedance remains 1, 2.
unchanged under current control mode. Theoretical analysis also  
1 s ω1 1
indicates that negative reactive power injection tends to mitigate Z Cf = 2
m
→ Z Cf =
2
(s + ω1 )Cf −ω 1 s (s + jω1 )Cf
the low-frequency instability. Specifically, the amount of the
required negative reactive power is highly related with length (33)
of transmission cable, PLL bandwidth and number of paralleled  −1.5T s 
e s
0
Gm del = → Gdel = e−1.5Ts s (34)
GCIs. The presented low-frequency stabilization method based 0 e−1.5Ts s
on negative reactive power injection is superior to the PLL
bandwidth retuning-based method in terms of system dynamic where Ts is the sampling period.
performances, and is superior to the grid voltage feed-forward  
kpi + ksii 0 kii
control-based method in terms of simple structure and Gci =
m
→ Gci = kpi + (35)
0 kpi + ksii s
robustness. In addition, the maximum bandwidth of the PLL not
to violate the low-frequency stability under weak grid condition where kpi and kii are proportional and integrator coefficients of
can be extended with the help of negative reactive power injec- inner current controller, respectively.
tion. A four PMSGs-based OWPP has been developed in Mat-

kiP Q
k pP Q + 0
lab/Simulink and OPAL-RT real-time digital simulator platform GmcP Q = →
s
k
to demonstrate the correctness of the theoretical analysis results. 0 kpP Q + iPs Q
kiP Q
APPENDIX A GcPQ = kpP Q + (36)
s
COMPLEX TRANSFER FUNCTIONS REPRESENTATIONS OF
where kpP Q and kiP Q are proportional and integrator coeffi-
TRANSFER MATRICES IN (2) AND (3)
cients of outer power controller, respectively.
A three-phase symmetrical and balanced electrical parameter GmP LL_i models the small-signal perturbation path from PCC
xabc can be represented in dq reference frame in form of either voltage in system dq frame to grid current in controller dq frame.
real space vector xdq (italic letter) or complex space vector xdq  
0 −Ig,q s
GP LL
(bold letter), shown as follows [47]. Gm = →
P LL_i 0 Ig,ds
GP LL
xdq = [xd , xq ]T ↔ xdq = xd + jxq (28) s
Ig,dq GP LL
G+,PLL_i = −G−,PLL_i = (37)
m
In addition, a two-dimensional matrix ydq can be represented 2
by two complex transfer functions, shown as follows. s
where Ig,d s
and Ig,q are d-axis and q-axis components of three-
  phase currents in system dq frame. In addition, GP LL is defined
y y
m
ydq = dd dq ↔ as follows.
yqd yqq
kppll + kipll /s
ydd + yqq yqd − ydq GP LL = (38)
y+,dq = +j s + VPsCC,d (kppll + kipll /s)
2 2
ydd − yqq yqd + ydq where kppll and kipll are proportional and integrator coefficients
y−,dq = +j (29) of PLL controller, respectively.
2 2
GmP LL_v models the small-signal perturbation path from PCC
where the superscript m indicates that the parameter is a matrix.
voltage in system dq frame to voltage in controller dq frame.
Based on (28) and (29), the equation using real space vectors  
and transfer matrices can be reformulated using complex space 1 VPsCC,q GP LL
Gm = →
vectors and complex transfer functions, shown as follows. P LL_v 0 1 − VPsCC,d GP LL
zdq = ydq
m
xdq ↔ G+,PLL_v = 1 − VPCC,dq
s
GP LL /2
zdq = y+,dq xdq + y−,dq x∗dq (30) G−,PLL_v = VPCC,dq
s
GP LL /2 (39)

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
852 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 2, JUNE 2020

where VPsCC,d and VPsCC,q are d-axis and q-axis components of [3] S. Shah and L. Parsa, “Impedance modeling of three-phase voltage source
three-phase voltages in system dq frame. converters in DQ, sequence, and phasor domains,” IEEE Trans. Energy
Convers., vol. 32, no. 3, pp. 1139–1150, Sep. 2017.
GmP LL_d models the small-signal perturbation path from PCC [4] I. Vieto and J. Sun, “Sequence impedance modeling and analysis of type-III
voltage in system dq frame to duty cycle in controller dq frame, wind turbines,” IEEE Trans. Energy Convers., vol. 33, no. 2, pp. 537–545,
shown as follows. Jun. 2018.
  [5] H. Liu, X. Xie, and Z. Liu, “Comparative studies on the impedance
0 −Dqs GP LL models of VSC-based renewable generators for SSI stability analysis,”
Gm = → IEEE Trans. Energy Convers., vol. 34, no. 3, pp. 1442–1453, Sep. 2019.
P LL_d
0 Dds GP LL [6] W. Zhou, Y. Wang, and Z. Chen, “Impedance-decoupled modelling method
Dsdq GP LL of multi-port transmission network in inverter-fed power plant,” IEEE
G+,PLL_d = −G−,PLL_d = (40) Trans. Ind. Appl., vol. 56, no. 1, pp. 611–621, Jan./Feb. 2020.
2 [7] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen, “Analysis
of DQ small-signal impedance of grid-tied inverters,” IEEE Trans. Power
where Dds and Dqs are d-axis and q-axis components of three- Electron., vol. 31, no. 1, pp. 675–687, Jan. 2016.
phase duty cycles in system dq frame. [8] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Harmonic instability assess-
In addition, Gm m ment using state-space modeling and participation analysis in inverter-fed
P Q_i and GP Q_v model the small-signal dy- power systems,” IEEE Trans. Ind. Electron., vol. 64, no. 1, pp. 806–816,
namics of power control loop, shown as follows. Jan. 2017.
 s  [9] J. Sun, “Impedance-based stability criterion for grid-connected inverters,”
VP CC,d VPsCC,q IEEE Trans. Power Electron., vol. 26, no. 11, p. 3075, Nov. 2011.
GP Q_i =
m
→ GPQ_i = VPCC,dq
s∗
−VPsCC,q VPsCC,d [10] S. Zhang, S. Jiang, X. Lu, B. Ge, and F. Z. Peng, “Resonance issues
and damping techniques for grid-connected inverters with long transmis-
(41) sion cable,” IEEE Trans. Power Electron., vol. 29, no. 1, pp. 110–120,
 s  Jan. 2014.
−Ig,d −Ig,q s
[11] Y. Song, E. Ebrahimzadeh, and F. Blaabjerg, “Analysis of high-frequency
P Q_v = −I s
Gm s
Ig,d
→ resonance in DFIG-based offshore wind farm via long transmission
g,q
cable,” IEEE Trans. Energy Convers., vol. 33, no. 3, pp. 1036–1046,
G+,PQ_v = 0 G−,PQ_v = −Isg,dq (42) Sep. 2018.
[12] I. Erlich, M. Wilch, and C. Feltes, “Reactive power generation by DFIG
based wind farms with AC grid connection,” in Proc. IEEE Eur. Conf.
Power Electron. Appl., 2007, pp. 1–10.
APPENDIX B [13] L. Xu and L. Fan, “Impedance-based resonance analysis in a VSC-HVDC
DETAILED EXPRESSIONS OF PARAMETERS IN (21) system,” IEEE Trans. Power Del., vol. 28, no. 4, pp. 2209–2216, Oct. 2013.
[14] M. Amin, M. Molinas, J. Lyu, and X. Cai, “Impact of power flow di-
rection on the stability of VSC-HVDC seen from the impedance nyquist
2 2 plot,” IEEE Trans. Power Electron., vol. 32, no. 10, pp. 8204–8217, Oct.
GcP Q G2ci G2del (GcP Q + GP LL )[(P ref ) + (Qref ) ] 2017.
A= [15] K. M. Alawasa, Y. A.-R. I. Mohamed, and W. Xu, “Active mitigation of
(VPsCC,d )2 subsynchronous interactions between PWM voltage-source converters and

power networks,” IEEE Trans. Power Electron., vol. 29, no. 1, pp. 121–134,
0.5Vdc Gci P ref +(VPsCC,d )2 −ω1 Lf Qref Jan. 2014.
+ · · · GP LL Gdel [16] H. Zhao, Q. Wu, J. Wang, Z. Liu, M. Shahidehpour, and Y. Xue, “Combined
0.5Vdc VPsCC,d
active and reactive power control of wind farms based on model predictive
control,” IEEE Trans. Energy Convers., vol. 32, no. 3, pp. 1177–1187,
GP LL GcP Q Gci G2del P ref
+ ··· −1 Sep. 2017.
0.5Vdc [17] W. Zhou, Y. Wang, D. Liu, and Z. Chen, “Optimization of active and
reactive power dispatch among multi-paralleled grid-connected inverters
Gdel Vdc Gci (1 + GcP Q VPsCC,d ) considering low-frequency stability,” in Proc. IEEE 45th Annu. Conf. IEEE
B = Lf s +
2 Ind. Electron. Soc., Oct. 2019, pp. 6024–6031.
[18] S. Zhou, X. Zou, D. Zhu, L. Tong, Y. Zhao, Y. Kang, and X. Yuan,
C = ω 1 Lf “An improved design of current controller for LCL-type grid-connected
converter to reduce negative effect of PLL in weak grid,” IEEE J. Emerg.
Gdel GP LL VPsCC,d Gci Gdel (GcP Q + GP LL )P ref Sel. Topics Power Electron., vol. 6, no. 2, pp. 648–663, Jun. 2018.
D= +
0.5Vdc VPsCC,d [19] N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and
testing of autonomous operation of an inverter-based microgrid,” IEEE
ω1 Lf Gdel GP LL Qref Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007.
− ··· −1 [20] J. Lyu, X. Cai, and M. Molinas, “Frequency domain stability analysis of
0.5Vdc VPsCC,d MMC-based HVDC for wind farm integration,” IEEE J. Emerg. Sel. Topics
Power Electron., vol. 4, no. 1, pp. 141–151, Mar. 2016.
ω1 Lf Gdel GP LL P ref Gci Gdel (GcP Q + GP LL )Qref
E= + [21] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and
0.5Vdc VPsCC,d VPsCC,d wind turbine grid-connected inverters for a large set of grid impedance val-
ues,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 263–272, Jan. 2006.
Gci GcP Q Gdel P ref [22] Y. Xia, Y. Peng, P. Yang, Y. Li, and W. Wei, “Different influence of grid
F =1+ (43) impedance on low-and high-frequency stability of PV generators,” IEEE
VPsCC,d Trans. Ind. Electron., vol. 66, no. 11, pp. 8498–8508, Nov. 2019.
[23] S. Liu, P. X. Liu, and X. Wang, “Stochastic small-signal stability analysis of
grid-connected photovoltaic systems,” IEEE Trans. Ind. Electron., vol. 63,
REFERENCES no. 2, pp. 1027–1038, Feb. 2016.
[1] P. Bresesti, W. L. Kling, R. L. Hendriks, and R. Vailati, “HVDC connection [24] W. Wei, Y. Xia, and F. Blaabjerg, “Nonlinear stability analysis for three-
of offshore wind farms to the transmission system,” IEEE Trans, Energy phase grid-connected PV generators,” IEEE J. Emerg. Sel. Topics Power
Convers., vol. 22, no. 1, pp. 37–43, Mar. 2007. Electron., to be published, doi: 10.1109/JESTPE.2019.2939379.
[2] F. Blaabjerg, Z. Chen, and S. B. Kjaer, “Power electronics as efficient [25] M. Cespedes and J. Sun, “Adaptive control of grid-connected inverters
interface in dispersed power generation systems,” IEEE Trans. Power based on online grid impedance measurements,” IEEE Trans. Sustain.
Electron., vol. 19, no. 5, pp. 1184–1194, Sep. 2004. Energy, vol. 5, no. 2, pp. 516–523, Apr. 2014.

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.
ZHOU et al.: EFFECT OF REACTIVE POWER CHARACTERISTIC OF OWPP ON LOW-FREQUENCY STABILITY 853

[26] M. Amin and M. Molinas, “A gray-box method for stability and con- Weihua Zhou (Student Member, IEEE) was born
troller parameter estimation in HVDC-connected wind farms based on in Anhui, China, in 1993. He received the B.Eng.
nonparametric impedance,” IEEE Trans. Ind. Electron., vol. 66, no. 3, and M.Sc. degrees in electrical engineering from the
pp. 1872–1882, Mar. 2019. School of Automation, Northwestern Polytechnical
[27] J. Fang, X. Li, H. Li, and Y. Tang, “Stability improvement for three-phase University, Xi’an, China, in 2014 and 2017, respec-
grid-connected converters through impedance reshaping in quadrature- tively. He is currently working toward the Ph.D. de-
axis,” IEEE Trans. Power Electron., vol. 33, no. 10, pp. 8365–8375, gree in electrical engineering with the Department
Oct. 2017. of Energy Technology, Aalborg University, Aalborg,
[28] X. Zhang, D. Xia, Z. Fu, G. Wang, and D. Xu, “An improved feedforward Denmark.
control method considering PLL dynamics to improve weak grid stability From November 2015 to May 2016, he was a Junior
of grid-connected inverters,” IEEE Trans. Ind. Appl., vol. 54, no. 5, Research Assistant with the Department of Mechani-
pp. 5143–5151, Sep./Oct. 2018. cal and Automation Engineering, The Chinese University of Hong Kong, Hong
[29] D. Yang, X. Wang, F. Liu, K. Xin, Y. Liu, and F. Blaabjerg, “Sym- Kong. His research interests include modeling and control of grid-connected
metrical PLL for SISO impedance modeling and enhanced stability in converters and small-signal stability analysis of power-electronic-dominated
weak grids,” IEEE Trans. Power Electron., vol. 35, no. 2, pp. 1473–1483, power systems.
Feb. 2020. Mr. Zhou was the recipient of the Best Paper Award in the 6th International
[30] T. Messo, R. Luhtala, A. Aapro, and T. Roinila, “Accurate impedance Conference on Smart Grids (icSmartGrid) cosponsored by IEEE Industry Ap-
model of a grid-connected inverter for small-signal stability assessment in plication Society in 2018.
high-impedance grids,” in Proc. IEEE Int. Power Electron. Conf.-ECCE
ASIA, 2018, pp. 3156–3163.
[31] Á. Molina-García, R. A. Mastromauro, T. García-Sánchez, S. Pugliese, Yanbo Wang (Senior Member, IEEE) received the
M. Liserre, and S. Stasi, “Reactive power flow control for PV inverters Ph.D. degree in electrical engineering with the De-
voltage support in LV distribution networks,” IEEE Trans. Smart Grid, partment of Energy Technology, Aalborg University,
vol. 8, no. 1, pp. 447–456, Jan. 2017. Aalborg, Denmark, in 2017.
[32] D. Yang, X. Wang, F. Liu, K. Xin, Y. Liu, and F. Blaabjerg, “Adaptive He is currently an Assistant Professor with the De-
reactive power control of PV power plants for improved power transfer partment of Energy Technology, Aalborg University.
capability under ultra-weak grid conditions,” IEEE Trans. Smart Grid, From June to October 2016, he was a Visiting Scholar
vol. 10, no. 2, pp. 1269–1279, Mar. 2019. with Power System Research Group, Department of
[33] R. A. Jabr, “Linear decision rules for control of reactive power by dis- Electrical and Computer Engineering, University of
tributed photovoltaic generators,” IEEE Trans. Power Syst., vol. 33, no. 2, Manitoba, Winnipeg, MB, Canada. His research in-
pp. 2165–2174, Mar. 2018. terests include distributed power generation system,
[34] X. Wang, F. Blaabjerg, and P. C. Loh, “Passivity-based stability analysis wind power system, microgrid, as well as operation and control technologies of
and damping injection for multiparalleled VSCs with LCL filters,” IEEE power electronic-dominated power system.
Trans. Power Electron., vol. 32, no. 11, pp. 8922–8935, Nov. 2017. Dr. Wang’s paper on Distributed Power System received the First Prize Paper
[35] H.-C. Chen, P.-T. Cheng, and X. Wang, “A passivity-based stability analy- Award in the 6th International Conference of Smart Grid cosponsored by IEEE
sis of the active damping technique in the offshore wind farm applications,” Industry Application Society in 2018. He was the recipient of the Best Session
IEEE Trans. Ind. Appl., vol. 54, no. 5, pp. 5074–5082, Sep./Oct. 2018. Paper Award at the Annual Conference of the IEEE Industrial Electronics Society
[36] W. Zhou, Y. Wang, and Z. Chen, “Frequency and temperature-dependent in 2015 in Japan.
power cable modelling for small-signal stability analysis of grid-connected
inverter system,” in Proc. IEEE 4th Southern Power Electron. Conf., 2018,
pp. 1–8. Raymundo E. Torres-Olguin received the B.Sc. de-
[37] J. Beerten, S. D’Arco, and J. A. Suul, “Frequency-dependent cable mod- gree in electromechanical engineering from the Uni-
elling for small-signal stability analysis of VSC-HVDC systems,” IET versity of San Luis Potosí, San Luis Potosí, Mexico,
Gen., Transm. Distrib., vol. 10, no. 6, pp. 1370–1381, May 2016. in 2004, the M.Sc. degree in control and dynamical
[38] J. Beerten, S. D’Arco, and J. A. Suul, “Identification and small-signal systems from the Applied Mathematics Department,
analysis of interaction modes in VSC MTDC systems,” IEEE Trans. Power Research Institute of Science and Technology of San
Del., vol. 31, no. 2, pp. 888–897, Apr. 2016. Luis Potosí—(IPICYT), San Luis Potosí, Mexico, in
[39] Q. Hao, Z. Li, F. Gao, and J. Zhang, “Reduced-order small-signal models 2006, and the Ph.D. degree in electric power engi-
of modular multilevel converter and MMC-based HVdc grid,” IEEE Trans. neering from the Norwegian University of Science
Ind. Electron., vol. 66, no. 3, pp. 2257–2268, Mar. 2019. and Technology (NTNU), Trondheim, Norway, in
[40] S. Golestan, J. M. Guerrero, and J. C. Vasquez, “Three-phase PLLs: 2013.
A review of recent advances,” IEEE Trans. Power Electron., vol. 32, no. 3, From 2012, he was a Research Scientist with SINTEF Energy Research,
pp. 1894–1907, Mar. 2017. Trondheim, Norway. His main research interest includes control of power
[41] C. R. Paul, Analysis of Multiconductor Transmission Lines. Hoboken, NJ, electronics for the integration of renewable resources, dc transmission, and
USA: Wiley, 2008. microgrids.
[42] W. Zhou, Y. Wang, and Z. Chen, “Vector fitting-based reduced order
modelling method for power cables,” in Proc. IET 15th Int. Conf. AC
and DC Power Transmission, Feb. 2019, pp. 1–6. Zhe Chen (Fellow, IEEE) received the B.Eng. and
[43] B. Gustavsen and A. Semlyen, “Rational approximation of frequency M.Sc. degrees in electrical engineering from the
domain responses by vector fitting,” IEEE Trans. Power Del., vol. 14, Northeast China Institute of Electric Power Engineer-
no. 3, pp. 1052–1061, Jul. 1999. ing, Jilin City, China, the M.Phil. degree in power
[44] A. Rygg, M. Molinas, C. Zhang, and X. Cai, “On the equivalence and electronic from Staffordshire University, Stoke-on-
impact on stability of impedance modeling of power electronic converters Trent, U.K., and the Ph.D. degree in electrical en-
in different domains,” IEEE J. Emerg. Sel. Topics Power Electron., vol. 5, gineering from the University of Durham, Durham,
no. 4, pp. 1444–1454, Dec. 2017. U.K.
[45] C. Dufour, H. Saad, J. Mahseredjian, and J. Bélanger, “Custom-coded He is a Full Professor with the Department of En-
models in the state space nodal solver of ARTEMiS,” in Proc. Int. Conf. ergy Technology, Aalborg University, Aalborg, Den-
Power Syst. Transients. Jul. 2013, pp. 1–6. mark. He is a Leader of Wind Power System Research
[46] X. Wang, L. Harnefors, and F. Blaabjerg, “Unified impedance model of program with the Department of Energy Technology, Aalborg University and the
grid-connected voltage-source converters,” IEEE Trans. Power Electron., Danish Principle Investigator for Wind Energy of Sino-Danish Centre for Edu-
vol. 33, no. 2, pp. 1775–1787, Feb. 2018. cation and Research. His research areas are power systems, power electronics
[47] L. Harnefors, “Modeling of three-phase dynamic systems using complex and electric machines, and his main current research interests are wind energy
transfer functions and transfer matrices,” IEEE Trans. Ind. Electron., and modern power systems. He has led many research projects and has more
vol. 54, no. 4, pp. 2239–2248, Aug. 2007. than 500 publications in his technical fields.

Authorized licensed use limited to: University of Exeter. Downloaded on June 09,2020 at 21:49:03 UTC from IEEE Xplore. Restrictions apply.

You might also like