TECHNICAL BULLETIN

MODEL 100D-B
Deluge Valve- Electronically Actuated
UL Listed

Function
Opens on demand to provide water flow to the fire protection sprinkler system.
Pilot system can be hydraulically, pneumatically, or manually operated.
Opening of valve is by electrical signal to solenoid or by manual opening.

Features
The WATTS ACV 100D-B deluge valve meets all requirements for UL Listed,
fire protection service. The design and features incorporated into the
WATTS ACV valve assure dependable performance and long life.

100D-B Specifications
Body and Cover: Ductile Iron - ASTM A536 Fusion Bonded Epoxy Coated
5 TO
Air/Hydraulic Pressure Line ATMOSPHERE Cast Steel - ASTM A216 WCB Fusion Bonded Epoxy Coated
1
3 2
Seat (trim): Stainless Steel AISI 316 (CF8M) -Xylan Coated
Internals: (stem, seat seal retainer, retainer plate and seat):
2 TO
ATMOSPHERE
Stainless Steel AISI 303 or 316
Diaphragm washers: Ductile Iron- ASTM A536 Fusion Bonded Epoxy Coated (6" & 8")
Steel- ASTM A36 Fusion Bonded Epoxy Coated (4" & 10")
4 Stem: Stainless Steel AISI 303 - Xylan Coated
TO
Spring: Stainless Steel AISI 302
ATMOSPHERE 3 Elastomers: BUNA- N
100M Pneumatic/Hydraulic Control:
Y
FC Body & Cover- Bronze -ASTM B61 or Stainless Steel AISI 316 (CF8M)
FLOW
Seat & Stem-Stainless Steel AISI 316
1 Elastomers- BUNA-N
Solenoid: Brass or Stainless Steel/ Explosion Proof-Nema 4,7,9
Flow Direction Shown: Under the Seat
COMPONENTS
1 - Main Valve - Deluge Control Tubing: Copper or Stainless Steel
2 - 100M (Pneumatic/Hydraulic Control) Fittings: Brass,Stainless Steel
3 - Fixed Orifice Restriction
CLOSES VALVE
4 - Ball Valve 2" NPT drain ports provide test and drainage
OPENS VALVE
5 - 3-Way Solenoid
FC - Flow-Clean Strainer

4” 6” 8” 10”
UL UL UL UL

Operation
Figure 100D-B Deluge Valve is controlled by a 3-way direct-acting solenoid which controls the position of the Fig. 100M
Pnematic/Hydraulic pilot.

When the solenoid is de-enegerized, ports 1 and 3 are connected (port 2 is blocked). Pressure is routed to the cover
of the pneumatic/hydraulic control. The pneumatic/hydraulic control closes, closing the main valve.

When the solenoid is energized, port 1 and 2 are connected (port 3 is blocked). The cover of the pneumatic/hydraulic
control is vented. The control opens, opening the main valve.

An isolation ball valve in the control circuit provides a manual by-pass/ override of the pneumatic/hydraulic control.
Opening the ball valve will open the main valve. This ball valve is to be CLOSED during normal operation.

8550 Hansen Road . Houston, TX 77075 . Telephone 713.943.0688 . Fax 713.944.9445 www.wattsacv.com
ACV 100D-B TECHNICAL BULLETIN
DIMENSIONS

INSTALLATION DETECTION
(TYPICAL) Field Installed CONTROL PANEL
Control Line

NOTE:
Avoid mounting valve in
vertical discharge position
`'`'`'`'`'` `'`'`'`'`'` (valve stem horizontal or-
'`'`'`'`'` '`'`'`'`'`
`'`''`'`'
`'`'`' `'`' `'`''`'`'
`'`'`'
`'`' `'`'`'
`'`''`'`' `'`' cover pointed side ways).
'`'`'`'`'`
`'`'`'`'`'` Valves mounted in this
SUPPLY `'`'`'`'`'` `'`'`'`'`'` position may not perform
'`'`'`'`'` '`'`'`'`'` STEM
ST EM
`'`''`'`'
`'`'`' `'`' `'`''`'`'
`'`'`' as tested and approved.
`'`' `'`'`'
`'`''`'`' `'`'
'`'`'`'`'`
`'`'`'`'`'`
DELUGE VALVE TO FIRE
PROTECTION
SYSTEM

INSTALLATION/ START-UP
STEP 5 Partially open the manual ball valve to vent
Start-up of a deluge valve requires that proper procedures air trapped in the cover chamber. Close
be followed: when fluid begins to vent. Caution: Do not
remove or loosen top cover plug while valve
- Clear the line of slag and other debris. is under pressure.
- Close upstream system isolation valve, if so equipped.
- Install the valve so that the FLOW ARROW marked STEP 6 Energize the solenoid. This will vent the
on the valve body matches the flow through the line. pneumatic/hydraulic control cover chamber,
- Ensure that the manual by-pass isolation ball valve causing the main valve to open.
is closed.
- Connect actuating air/hydraulic pressure source to STEP 7 De-energize the solenoid. This will pressure the
port 3 of the solenoid control. pneumatic/hydraulic control cover chamber,
causing the main valve to close.
STEP 1 Energize the solenoid to check actuation and to
confirm connection to power source. STEP 4 Open manual by-pass ball valve to ensure that
the main valve opens. MANUAL BY-PASS BALL
STEP 2 De-energize the solenoid for initial valve filling. VALVE MUST BE CLOSED DURING NORMAL
OPERATION OF VALVE.
STEP 3 Activate the air/hydraulic pressure source.
*Where difficulty in performance is experienced, WATTS-
STEP 4 Pressure the line, opening the upstream isolation ACV or an authorized representative shall be contacted if any
valve slowly. field adjustment is to be made.

8550 Hansen Road . Houston, TX 77075 . Telephone 713.943.0688 . Fax 713.944.9445 www.wattsacv.com