+ Correction of the synchronizing filter phase shifting
Fault messages (F03, F11) can occur for supply networks having significant harmonics.
Parameter 134: - 199... + 199% 10 ps additional phase shifting
Setting instructions: P89 = 3 (current-controlled operation)
P76 = 0 (field current setpointis zero)
input current setpoint >2% at terminal X1.4
Read-out contents of parameter PO7 (EMF)
‘Adjust 134 until the contents of PO7 = 0
Parameter 133 is mainly set, as the harmonic contents of the supply network are generally
not constant.
8.14 — Switching-out monitoring functions
WARNING
‘The monitoring functions incorporated in the unit serve to protect the
equipment and the safety of the installation. If monitoring functions are to be
switched-out, this can cause the unit to either not respond, or respond
incorrectly to fault conditions. This can lead to loss of life, severe injuries or
property damage.
The resulting damage to the equipmentis not part of the warranty conditions.
Only qualified personnel, who have detailed knowledge of all the safety
instructions contained in these operating instructions, as well as installation,
‘operating and maintenance instructions, should work on this unit
Each individual monitoring function which can be switched-out, is assigned one bit in a control
register (parameter 91). The required bit pattern must be input in hexadecimal form. The
conversion tables below can be used to determine the hexadecimal number.
Bit No. 11} 10} 9} 8] 7] 6} 5} 4] 3) 2) 1) 0
Fault No. F26|F19|F17| Fi6| F14]F07|F11/Fo5|| Foa) Fo3| Fo2| F23|
” 2 2
Example 1) 1/0}0}/0;/0}1}0}/ 0; 1} 0J}0
So
Hundred'sdigit ——Ten’sdigit One's digit from 91
c | 2 4
100