DC traction networks require safe power distribution and reliable control systems.
The DC switchgear serves as the control and protection equipment for the DC
power distribution.
The DC breaker panel type MBS is a modular concept cubicle which integrates
different functions and equipment in three compartments:
• Rear high voltage busbar compartment
• Protection and control system
• High speed circuit breaker
Proven Sécheron components are applied for all major functions in the MBS
MBS Feeder Trolley cubicle.
2
HSCB D.C. Switchgear: Characteristics
Symbol Unit
Cubicle type MBS 08
MBS 05
Rated service current INe [A] 2600 4000 4000 6000 8000
Rated voltage UNe [VDC] 900/1800 900/1800 3600 900/1800 900
Circuit breaker type UR26 UR36/40 UR40 UR45/60 UR80
Power frequency withstand voltage
Active part to earth (50 Hz, 1min) [kV] 5.5/9.2 5.5/9.2 18.5 5.5/9.2 5.5
Main busbar Ie <- up to 11 kA ->
Busbar rating: connection [A] 2500 4000 4000 6000 8000
Rated short-circuit current INss/ÎNss [kA]
TNc 100 ms (900V) 125/178 125/178 125/178 134/190
TNc 31.5 ms (1800V) 63/90 80/113 80/113
TNc 31.5 ms (3600V) 40/57
Protection degree (general/roof) <- IP30 / IP20 or IP42* ->
Ambient temperature range T [°C] <- -5 ... +40 ->
Typical weight [kg] 500 550 700 650 700
Dimensions (WxDxH) [mm] <- 500 or 800x1400x2200 ->
**IP42: option.
For further characteristic: refer to the data sheet for the individual circuit-breaker type.
Designed according to standard specifications EN50123 and IEC61992.
Unique feature:
Key components of the switchgear are designed and manufactured by Sécheron and are fully compatible.
The withdrawable high speed circuit breaker trolley has four positions:
• Service position
• Test position
• Disconnected position
• Removed position
When the trolley is in service position, the front high voltage door is locked
and it is not possible to access the trolley. When high voltage is applied to the
breaker, it must be open before the trolley can be moved from service to test
position. The trolley is moved from one position to another either manually by
an external handle or electrically via the SEPCOS touch screen display. In this
way, user’s security is ensured. Trolleys can be encoded to ensure that they
cannot be exchanged for a trolley of another type.
Advantages:
• Very compact with minimum depth.
• Possibility to install cubicles directly against a wall.
• Front access to all equipment.
Motorized trolley:
This new feature is an available option that allows the trolley to be disconnected
in remote mode, thus replacing the line isolating disconnecting switch.
Service and test positions
Main dimensions
breaker trolley
3. Low-voltage
compartment 3
(protection and
control circuits)
8
4. Main plugs (power
circuit)
10
5. Shunt (current)
1400
6. Current measuring 7
amplifier
7. Voltage measuring 11
amplifier
2200
8. High voltage
12
compartment 1 4
1430 (1605*)
9. Output cable
10. Bypass busbar
2
(option) 5
13
11. Disconnector
(option) 9
12. Main busbar 6
13. Motor (option)
Disconnector cubicles are applied for incoming DS, negative DS or coupling DS.
The system contains two compartments:
• High voltage compartment
• Low-voltage compartment
Each compartment has a separate front door and can be mounted against the wall.
Cable connection is possible from the bottom or top.
Disconnectors are rated 2000A, 4000A, 6300A and 8000A.
Incoming DS Cubicle:
Incoming DS cubicles isolate the positive high voltage output transformer/rectifier
group from the feeder DC distribution bus.
Disconnectors may have single or double poles. Double poles are used to
disconnect the positive and the negative pole simultaneously. Operation may be
motorized or manual. There are four different sizes: 500mm, 800mm, 1200mm or
1600mm. Incoming DS cubicles may contain up to 4 disconnectors.
Negative DS Cubicle:
Negative DS cubicles isolate the negative pole of the rectifier groups from the return
current of the network (rail). Operation may be motorized or manual. There are four
different sizes: 500mm, 800mm, 1200mm or 1600mm. Negative DS cubicles may
contain up to 4 disconnectors.
Coupling DS Cubicle:
Coupling DS cubicles subdivide the DC switchboard into separate busbar sections.
Disconnecting Switch cubicle
Operation may be motorized or manual, size is 500mm.
Below are the different configurations according to the cubicle dimensions and types:
40
20
40
60
20
40
60
20
40
60
00
00
00
00
00
00
00
00
00
00
00
A
A
A
A
-2
-2
-1
-1
-1
-1
-1
-1
-1
-1
-1
po
po
po
po
po
po
po
po
po
po
po
le
le
le
le
le
le
le
le
le
le
le
s
500
2200
50
0
00
14
2 2 2 1 1 2 2 2 1 1 1
80
0
00
14
1200/1600
2200
4 4 4 1 1 4 4 4 1 1 1
12 00
00 14
Protection Relay
SEPCOS is a protection and control unit that is applied to the outgoing feeder
or the incoming HSCB cubicles in the DC traction substation.
Main features:
• Modular PLC concept, PLC programming, IEC61131 normalized
programming.
• Fully approved in railway substation environment EN50255-22.
• High noise immunity thanks to sampling rate at 40 microseconds and 16
bits A-D converter.
Protection functions:
• All typical protection functions (e.g. Function DDL +/-, Imax +/-, etc.).
Control functions:
• HSCB ON / OFF control with electric or magnetic holding.
• Intertripping, automatic reclosing, anti-pumping, line test function.
• External synchronization of the PLC, measurement supervisor control.
Sécheron also provides services in order to support customers in network design and installation of our systems:
• DC System Engineering
• Dynamic simulation of complete networks
• Short-circuit, earthing circuit and harmonic calculation
• Supervision of installation and commissioning
• In line and field testing
6
MBS line up
Complete DC switchgear can be provided in line with MBS cubicles as shown below.
Line Test
Line Test
I I I
Line Test
I I I
M M
U U
VM10 VM10
M
4 5 6
According to standards:
• IEC61992-2:2006
• EN50123-2:2003
• IEC60980 (Seismic tests)
Approved type test reports available.
Main features related to MBS05 breaker panel Main features related to MBS08 breaker panel
Rated voltage (UNe) 900 VDC Rated voltage (UNe) 900 VDC
Rated service current (INe) 4000 A Rated service current (INe) 8000 A
Rated making & breaking capacity (ÎNss/INss) 177/125 kA Rated making & breaking capacity (ÎNss/INss) 190/134 kA
Rated track time constant (TNc) 100 ms Rated track time constant (TNc) 100 ms
Duty classes f, e, d Duty classes f, e, d
Rated voltage (UNe) 1800 VDC Rated voltage (UNe) 3600 VDC
Rated service current (INe) 4000 A Rated service current (INe) 4000 A
Rated making & breaking capacity (ÎNss/INss) 113/80 kA Rated making & breaking capacity (ÎNss/INss) 57/40 kA
Rated track time constant (TNc) 31.5 ms Rated track time constant (TNc) 31.5 ms
Duty classes f, e, d Duty classes f, e, d