2 NRX breakers
2.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Selection criteria. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Breaker technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Catalog selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Accessories
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Selection criteria. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5 Appendix
5.1 Reference documents and information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2 Excerpt from PXR user manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3 NRX Breaker cover details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.4 Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 1
1 Series NRX air circuit breakers with Power Xpert release trip units
Introduction
1
1
1
1
1
1
2 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Introduction
1
Space-saving circuit breakers with useful accessories 1
1
1
1
1
1
1
Breaker rear side 1
(withdrawable breaker)
1
1
Value propositions Options/accessories/components
• Increased worker safety with faster response • Variety of continuous amperages and interruption ratings 1
• Seamless integration to enable faster installation Configurations with 3- and 4-pole designs
and commissioning
•
• Fixed and drawout options
1
• Smarter solution enabling connectivity, reliability
and diagnostics
• Rear, front and hybrid connect configurations (NF Frame,
UL 489 only)
1
Features and benefits Additional options include: automatic and non-automatic
•
configurations, shunt trips, under-voltages releases, remote 1
• Eaton’s software simplifies testing, serviceability and motor operation, latch check switches, auxiliary switches,
customization—yielding significant time and labor savings trip indication, padlock and keylock provisions, cassettes 1
• An enhanced user interface enables engineers to view and configurations
adjust the trip unit settings
Why Eaton?
1
• The compact size of Series NRX frames reduces non-revenue
generating floor space Finding safe, seamless, and smart protection for your electrical 1
• Modular design and common accessories allow for easy system and personnel is your number one priority. With a
panel and switchboard integration complete portfolio of circuit protection products, including 1
molded case, low and medium voltage circuit breakers, you
Certifications and standards can feel confident that whatever the application, Eaton has the
solution.
1
• Underwriters Laboratories (UL) 489
• International Electrotechnical Commission (IEC) 60947-2 For more information, visit www.eaton.com/SeriesNRX 1
• Canadian Standards Association 22.2
1
1
1
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 3
2 Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
1
1
1
4 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
2
Fixed circuit breaker Table 1. Front Connect Primary Terminal Configurations
1
Name Top connection Bottom connection
A fixed circuit breaker is rigidly mounted in its structure
with no drawout feature, making for a simple and economic Bus connect Bus bar Bus bar 2
construction. It is available in both front and rear-connected
configurations. Full visual and physical access to the circuit 1
breaker trip unit, controls, and indicators is available through the
compartment front panel. Door escutcheon kits are available Cable connect Cable adapter Cable adapter 1
as an option to provide a finished trim to the front panel cutout.
Extensive accessorization capability of the breaker is retained,
including trip units, internal and communication accessories,
1
lock-off devices, and mechanical interlocks. Metal mounting Hybrid Bus bar Cable adapter
brackets are provided as a standard feature for use in securely 1
bolting the breaker to the enclosure.
Front connect
1
Hybrid Cable adapter Bus bar
Front-connected breakers are for UL 489 applications and can 1
accommodate a number of primary terminal configurations, see
Table 1. Front connect is exclusive to the NF-frame and uses 1
mounting brackets for breaker mounting and installation
Rear connect
Rear view of fixed NF and RF breakers 1
A standard fixed rear-connected circuit breaker is supplied with
flat primary terminal pads on the rear of the breaker that will
1
accommodate a variety of primary connection configurations
including both horizontal and vertical primary adapters as well 1
as long and short lengths (length option for NF only). The
breaker bolts directly to the enclosure main bus, which allows 1
for efficient current transfer under loaded conditions. This
improves thermal management and provides for the design of 1
compact enclosures with shallow depth.
1
Drawout breaker and cassette
Front view of drawout NF and RF breakers 1
A drawout circuit breaker is used in combination with a drawout
cassette. Mounted on the drawout breaker are the primary 1
disconnect finger clusters and levering mechanism.
These components are located on the breaker to allow 1
users easy access when performing product inspection or
maintenance. The cassette provides all the necessary drawout
circuit breaker interfaces, including primary and secondary
1
connections.
1
Standard flat terminal pads on the rear of the cassette provide
for a variety of primary connection configurations. Optional
primary adapters are available for front and rear bus or cable
1
connections. Refer to “Minimum Clearances” section for
mounting and installation dimensional information. 1
Sample RF cassette with full complement of secondary terminal blocks 1
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 5
2 Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
6 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
2
Temperature and altitude derating factors 1
Table 2. Temperature derating 2
NF- frame 1
Rated current 630A 800A 1200A
1
40ºC [A] 630 800 1200
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 7
2 Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
and painted flat black. For other bus bar configurations, larger
1 bus bar sizes may be required or the breaker may have to be Legend
de-rated. Refer to the tables presented earlier in this section for T = thickness of bus bar
1 de-rating information at higher ambient temperatures W = width of bus bar
1
Table 4. UL bus bar sizes and quantities
1 Frame rating at
40˚C ambient Recommended bus bar
(A) NF-frame RF-frame quantities and sizes (0.25 in)
1 (in) (mm)
1
1 Table 5. IEC bus bar sizes and quantities m
)
0 m
Frame rating at (6
1 40˚C ambient
(A) NF-frame RF-frame
Recommended bus bar
quantities and sizes
(in) (mm)
1 Example (millimeters)
(2) 5 mm by 50 mm bus bars stacked to carry 800 amperes
1 800 (2) 5 x 50 (1) .25 x 3.0
8 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
2
2.3 Breaker technical data 1
2
1
1
Table 6. UL 489 ratings 1
NRX NF (Front
Connect)
NRX NF (Rear
Connect) NRX RF (Rear Connect) 1
General
Standard UL 489
1
Ambient temperature Storage °C -20 – 70 1
Operating (open) °C -20 – 70
Mounting position 1
1
1
Protection type IP20, IP55 device with protective cover, IP41 with door sealing frame
1
Direction of incoming supply as required
Switching capacity 1
Rated Current (In , A) 200, 250, 300, 400, 500, 600, 800, 1200 800, 1200, 1600, 2000, 2500, 3000
Rated voltage (V) 480, 600 480 1
Interrupting rating (rms, ka) 240 Vac (50/60Hz) 42, 50, 65, 85 65, 85, 100
480 Vac (50/60Hz) 42, 50, 65 65, 85, 100
1
600 Vac (50/60Hz) 42 —
1
Instantaneous override (equivalent 8 @ 800A In , 12 @ 1200A In 8 @ 800A In , 12 @ 1200A In , 16 @
symmetrical rms, kA) 1600A ln , 20 @ 2000A ln , 25 @ 2500A
ln , 30 @ 3000A ln
1
Short-time withstand current
(rms, kA)
30 cycle withstand option 42 65
1
Operating delays (ms) Closing delay 25 30
1
Closing delay electrical (via SR) 30 35
Opening delay electrical (via ST) 25 22 1
Opening delay electrical (via UVR) 50 37
Maximum operating frequency Operations/hr 60 60 1
Durability and installation characteristics
Lifespan (operations) Mechanical, w/o maintenance 20,000 10,000
1
Dimensions (H × W × D, in (mm)) Fixed 3P 16.00 × 8.27 × 7.15
(406 × 210 × 182)
13.31 × 8.27 × 7.24
(338 × 210 × 184)
15.67 × 14.80 × 11.73 (398 × 376 × 298) 1
Fixed 4P 16.00 × 10.98 × 7.15
(406 × 279 × 182)
13.31 × 10.98 × 7.24
(338 × 279 × 184)
15.67 × 19.37 × 11.73 (398 × 492 × 298)
1
Withdrawable 3P — 14.17 × 10.00 × 11.38 17.95 × 16.77 × 15.47 (456 × 426 × 393)
(360 × 254 × 289) 1
Withdrawable 4P — 14.17 × 12.76 × 11.38 17.95 × 21.30 × 15.47 (456 × 541 × 393)
(360 × 324 × 289) 1
Weight (lb (kg)) Fixed 3P/4P 40/53 (18/24) 33/44 (15/20) 99/123 (45/56)
Withdrawable 3P/4P — 86/104 (39/47) 216/267 (98/121)
1
a For IEC ratings and specifications, please refer to: www.eaton.com/seriesNRX
1
b UL489 doesn’t require a short-time withstand rating for breakers. The UL489 NRX breakers have instantaneous over-ride fixed at 22.5 x I (asymmetrical peak value). An equivalent symmetrical RMS
n
value would roughly equate to 10 x In.
c A 30 cycle withstand option is available for NRX breakers to provide better selectivity. These breakers will have higher instantaneous override to provide short-time withstand capabilities.
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 9
2 Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
1 N G S6 08 3 W 2A 8 A B A N 4 X N D X
1
Breaker frame size Spring release,
1 N = NF-frame for UL 489 Motor operator latch check switch
or IEC, (2.75 inches or M = Manually operated N = No spring release, no LCS
1 70 mm pole spacing) B = 110–125 Vac
W = 110–125 Vdc
A = 110–127 Vac/Vdc, no LCS
B = 110–127 Vac/Vdc, spring release LCS
T = 208–250 Vac C = 110–127 Vac/Vdc, LCS wired external
1 Standard, mechanism, device
G = IEC 60947-2, stored
P = 220–250 Vdc R = 208–250 Vac/Vdc, no LCS
Continuous L = 24 Vdc S = 208–250 Vac/Vdc, spring release LCS
energy, air breaker
1 Y = UL 489, stored energy,
rating (In in
amperes)
H = 48 Vdc T = 208–250 Vac/Vdc, LCS wired external
L = 24 Vdc, no LCS
S = 60 Vdc
insulated case breaker
P = 24 Vdc, spring release LCS
1 1
2
= 200
= 250 Shunt trip Q = 24 Vdc, LCS wired external
Fault current rating 3 = 300 H = 48 Vdc, no LCS
N = No shunt trip
1 R4 = 42 kA at 480 Vac (UL 489 only) 4 = 400 A = 110–127 Vac/Vdc
J = 48 Vdc, spring release LCS
R5 = 50 kA at 480 Vac (UL 489 only) 5 = 500 K = 48 Vdc, LCS wired external
R = 208–240 Vac/Vdc
1 R6 =
S4 =
65 kA at 480 Vac (UL 489 only)
42 kA at 480 Vac
6
7
= 600
= 630
L = 24 Vdc
1 = 60 Vdc, no LCS
2 = 60 Vdc, spring release LCS
H = 48 Vdc
(30 cycle, UL 489) or 415 Vac IEC (IEC only) 3 = 60 Vdc, LCS wired external
1 S5 = 50 kA at 480 Vac 8 = 800
S = 60 Vdc
(30 cycle, UL 489) or 415 Vac IEC A = 1000
1 S6 = 65 kA at 480 Vac (30 cycle,
UL 489 only), 66 kA at 415 Vac IEC
(IEC only)
B = 1200
(UL only)
1 Frame rating (amperes) C = 1250
(IEC only)
1 07 = 630 (IEC only)
08 = 800
D = 1600
(IEC only)
10 = 1000 (IEC only)
1 12 = 1200 (UL only)
13 = 1250 (IEC only) Trip unit, power supply
1 16 = 1600 (IEC only)
SW = Non-automatic switch, 42 kA for IEC and UL 489
2A = PXR20 LSI
1 Poles, phasing
3 = Three-pole, ABC
2B =
2H =
PXR20 LSI with Modbus
PXR20 LSI with Modbus and Arcflash Reduction Maintenance System
4 = Four-pole, NABC 2K = PXR20 LSI with Arcflash Reduction Maintenance System
1 2C = PXR20 LSIG
Mounting configuration 2D = PXR20 LSIG with Modbus
1 W = Drawout
2E = PXR20 LSIG with Arcflash Reduction Maintenance System
2F = PXR20 LSIG with Modbus and Arcflash Reduction Maintenance System
B = Fixed mount rear connected with side
1 mounting brackets
2P =
2Q =
PXR25 LSI with Modbus
PXR25 LSI with Modbus and Arcflash Reduction Maintenance System
F = Front connected, fixed mount, for bus or cable
2R = PXR25 LSIG with Modbus
1 connections with side mounting brackets
H = Fixed hybrid breaker, top rear connect and
2S = PXR25 LSIG with Modbus and Arcflash Reduction Maintenance System
bottom front connect
1 J = Fixed hybrid breaker, top front connect and
bottom rear connect
1
UL 489 three-pole only.
1
1
1
1
1
1
10 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
2
Table 7. Series NRX with Power Xpert Release NF-frame circuit breaker (exclusionary rules apply) (continued) 1
N G S6 08 3 W 2A 8 A B A N 4 X N D X 2
UVR, second shunt trip
1
N = None
A = 110–125 Vac/Vdc UVR Trip indicator OTS Secondary Remote 1
R = 220–250 Vac/Vdc UVR and bell alarm terminal blocks reset Drawout breaker shipping,
L = 24 Vdc UVR N None None Per breaker options None fixed breaker terminals (door frame kit 1
H = 48 Vdc UVR X Trip indicator None Per breaker options None ships as standard unless noted otherwise)
S = 60 Vdc UVR
1 = 110–127 Vac/Vdc
Z
M
Trip indicator
Interlock trip indicator
2 Form C
None
Per breaker options
Per breaker options
None
None
D = Drawout breaker shipping
alone, without door frame kit
1
second shunt trip Y Interlock trip indicator 2 Form C Per breaker options None C = Drawout breaker shipping in cassette,
2 = 208–240 Vac/Vdc 1 None None Full complement None no shutters, no terminals 1
second shunt trip 2 Trip indicator None Full complement None 1 = Drawout breaker shipping in cassette,
4 = 24 Vdc second shunt trip
8 = 48 Vdc second shunt trip
3
4
Trip indicator
Interlock trip indicator
2 Form C
None
Full complement
Full complement
None
None
no shutters, short vertical/horizontal
2 = Drawout breaker shipping in cassette,
1
9 = 60 Vdc second shunt trip 5 Interlock trip indicator 2 Form C Full complement None no shutters, long vertical/horizontal
4 = Drawout breaker shipping in cassette, 1
Auxiliary switches, Pushbutton Key Lock Operations with shutters, short vertical/horizontal
label language padlock cover Provisions counter 5 = Drawout breaker shipping in cassette,
with shutters, long vertical/horizontal
1
E = No auxiliary switches, N No None No
9 = Drawout breaker shipping in cassette,
English A No — Provided with shutters, no terminals 1
2 = 2 Form C, English B Yes (plastic/plastic) — No K = Rear connect, fixed breaker,
4 = 4 Form C, English J
K
Yes (plastic/plastic)
Yes (metal/metal)
—
—
Provided
No
no terminal adapters 1
F = Fixed breaker, rear connect, with
L Yes (metal/metal) — Provided mounting feet and short terminal
adapters 1
H = Fixed breaker, rear connect, with
mounting feet and long terminal 1
adapters
J = Front connect, fixed breaker, with no
terminal adapters 1
Q = Fixed Hybrid, no rear terminals,
TA1200NB1M front cable terminals 1
T = Fixed hybrid, no rear terminals,
TA1201NB1M front cable terminals
1
Two Form C contacts except on NF with Power Xpert Release and OTS and RRTI, where only one Form C OTS contact will be provided.
1
Table 8. Series NRX with Power Xpert Release NF-frame cassette
1
NY 12 3 F A B N S N N N C 1
Cassette family and Cassette shipping 1
breaker frame C = Cassette only
NY = UL 489 NF-frame B = Breaker shipped in cassette 1
NG = IEC NF-frame
Future 1
Continuous ampere range N = None
Arc hood
12 = 800–1200 (UL 489)
16 = 630–1600 (IEC)
A = Arc hood installed (default) 1
Future
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 11
2 Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
1
R G S6 08 3 W 2A 8 A B A N 4 X N D X
1
Breaker frame size Spring release,
1 R = RF frame for UL 489 Motor operator latch check switch
or IEC (4.5 inches or M = Manually operated N = No spring release, no LCS
1 115 mm pole spacing) B = 110–125 Vac A = 110–127 Vac/Vdc, no LCS
T = 208–250 Vac B = 110–127 Vac/Vdc, spring release LCS
1 Standard, mechanism, device L = 24 Vdc
H = 48 Vdc
C = 110–127 Vac/Vdc, LCS wired external
R = 208–250 Vac/Vdc, no LCS
G = IEC 60947-2, stored Continuous S = 60 Vdc S = 208–250 Vac/Vdc, spring release LCS
1 energy, air breaker
Y = UL 489, stored energy,
rating (In in
amperes)
T = 208–250 Vac/Vdc, LCS wired external
Shunt trip L = 24 Vdc, no LCS
insulated case breaker
1 8 = 800
A = 1000
N = No shunt trip
P = 24 Vdc, spring release LCS
Q = 24 Vdc, LCS wired external
Fault current rating A = 110–127 Vac/Vdc
(IEC only) H = 48 Vdc, no LCS
1 R6 = 65 kA at 480 Vac (UL 489 only) B = 1200
R = 208–240 Vac/Vdc
L = 24 Vdc
J = 48 Vdc, spring release LCS
R8 = 85 kA at 480 Vac (UL 489 only) (UL only) K = 48 Vdc, LCS wired external
H = 48 Vdc
1 RC = 100 kA at 480 Vac (UL 489 only) C = 1250
S = 60 Vdc
1 = 60 Vdc, no LCS
2 = 60 Vdc, spring release LCS
S5 = 55 kA at 415 Vac (IEC only) (IEC only)
3 = 60 Vdc, LCS wired external
1 S6 = 65 kA at 480 Vac (30 cycle,
UL 489 only), 66 kA at 415 Vac IEC
D = 1600
M = 2000
S8 = 85 kA at 480 Vac (30 cycle, N = 2500
1 UL 489 only) P = 3000
SC = 100 kA at 480 Vac (30 cycle, (UL only)
1 UL 489 only), 105 kA at 415 Vac IEC Q = 3200
(IEC only)
R = 4000
1 Frame rating (amperes) (IEC only)
08 = 800 20 = 2000
1 10 = 1000 (IEC only) 25 = 2500 Trip unit, power supply
12 = 1200 (UL only) 30 = 3000 (UL only) SW = Non-automatic switch, 42 kA for IEC and UL 489
1 13 = 1250 (IEC only) 32 = 3200 (IEC only) 2A = PXR20 LSI
16 = 1600 40 = 4000 (IEC only) 2B = PXR20 LSI with Modbus
1 Poles, phasing
2H = PXR20 LSI with Modbus and Arcflash Reduction Maintenance System
2K = PXR20 LSI with Arcflash Reduction Maintenance System
1 3 = Three-pole, ABC
4 = Four-pole, NABC
2C =
2D =
PXR20 LSIG
PXR20 LSIG with Modbus
2E = PXR20 LSIG with Arcflash Reduction Maintenance System
1 Mounting configuration 2F = PXR20 LSIG with Modbus and Arcflash Reduction Maintenance System
2P = PXR25 LSI with Modbus
W = Drawout with universal pads
1 U = Drawout, integral horizontal terminals
2Q =
2R =
PXR25 LSI with Modbus and Arcflash Reduction Maintenance System
PXR25 LSIG with Modbus
B = Fixed mount rear connected with side 2S = PXR25 LSIG with Modbus and Arcflash Reduction Maintenance System
1 mounting brackets
C = Fixed mount rear connected with integral
1 horizontal terminals
1
1
1
1
1
1
1
12 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
NRX breakers
2
Table 9. Series NRX with Power Xpert Release RF-frame circuit breaker (exclusionary rules apply) (continued) 1
R G S6 08 3 W 2A 8 A B A N 4 X N D X
Options
2
UVR, second shunt trip X = No on-board metering
taps (default)
1
N = None
W = Low temperature
A = 110–125 Vac/Vdc UVR
R = 220–250 Vac/Vdc UVR
Trip indicator
and bell alarm
OTS Secondary
terminal blocks
Remote
reset applications (–57 °C) 1
L = 24 Vdc UVR N None None Per breaker options None
H = 48 Vdc UVR X Trip indicator None Per breaker options None Drawout breaker shipping, 1
S = 60 Vdc UVR Z Trip indicator 2 Form C Per breaker options None fixed breaker terminals (door frame kit
1 = 110–127 Vac/Vdc
second shunt trip
M
A
Interlock trip indicator
Interlock trip indicator
None
None
Per breaker options
Per breaker options
None
24 Vdc RR
ships as standard unless noted otherwise)
D = Drawout breaker shipping
1
2 = 208–240 Vac/Vdc 6 Interlock trip indicator None Per breaker options 48 Vdc RR alone, without door frame kit
second shunt trip
4 = 24 Vdc second
7 Interlock trip indicator None Per breaker options 60 Vdc RR C = Drawout breaker shipping in cassette, 1
B Interlock trip indicator None Per breaker options 120 Vdc RR no shutters, no terminals
shunt trip
8 = 48 Vdc second
C
Y
Interlock trip indicator
Interlock trip indicator
None
2 Form C
Per breaker options
Per breaker options
240 Vdc RR
None
1 = Drawout breaker shipping in cassette,
no shutters, vertical adapters
1
shunt trip D Interlock trip indicator 1 or 2 Form C Per breaker options 24 Vdc RR
2 = Drawout breaker shipping in cassette,
9 = 60 Vdc second
shunt trip
8
9
Interlock trip indicator
Interlock trip indicator
1 or 2 Form C
1 or 2 Form C
Per breaker options
Per breaker options
48 Vdc RR
60 Vdc RR no shutters, horizontal adapters 1
E Interlock trip indicator 1 or 2 Form C Per breaker options 120 Vdc RR 4 = Drawout breaker shipping in cassette,
F Interlock trip indicator 1 or 2 Form C Per breaker options 240 Vdc RR with shutters, vertical adapters 1
1 None None Full complement None 5 = Drawout breaker shipping in cassette,
Auxiliary switches,
label language
2
3
Trip indicator
Trip indicator
None
2 Form C
Full complement
Full complement
None
None
with shutters, horizontal mounting
9 = Drawout breaker shipping in cassette, 1
E = No auxiliary switches, 4 Interlock trip indicator None Full complement None with shutters, no terminals
English
2 = 2 Form C, English
J
G
Interlock trip indicator
Interlock trip indicator
None
None
Full complement
Full complement
24 Vdc RR
48 Vdc RR
K = Rear connect, fixed breaker, 1
no terminal adapters
4 = 4 Form C, English H Interlock trip indicator None Full complement 60 Vdc RR
6 = 6 Form C, English K Interlock trip indicator None Full complement 120 Vdc RR
F = Fixed breaker, rear connect with
vertical adapters 1
8 = 8 Form C, English L Interlock trip indicator None Full complement 240 Vdc RR H = Fixed breaker, rear connect with
A = 10 Form C, English
W = 12 Form C, English
5
R
Interlock trip indicator
Interlock trip indicator
2 Form C
1 or 2 Form C
Full complement
Full complement
None
24 Vdc RR
horizontal adapters 1
U Interlock trip indicator 1 or 2 Form C Full complement 48 Vdc RR
V Interlock trip indicator 1 or 2 Form C Full complement 60 Vdc RR Pushbutton
padlock cover
Key Lock Operations
Provisions counter
1
S Interlock trip indicator 1 or 2 Form C Full complement 120 Vdc RR
T Interlock trip indicator 1 or 2 Form C Full complemen 240 Vdc RR N
A
No
No
None
—
No
Provided
1
B Yes (plastic/plastic) — No
J Yes (plastic/plastic) — Provided 1
K Yes (metal/metal) — No
L Yes (metal/metal) — Provided
Two Form C contacts except on NF with Power Xpert Release and OTS and RRTI, where only one Form C OTS contact will be provided.
1 Yes (metal/metal) Yes No 1
NF with PXR, 2-point (W) secondaries, OTS and no RRTI: Trip Unit ALM3 contact will not be wired out. 2 Yes (metal/metal) Yes Provided
1
Table 10. Series NRX with Power Xpert Release RF-frame cassette
RY 12 3 F A B N S N N N C
1
1
Cassette family and Cassette shipping
breaker frame C = Cassette only 1
RY = UL 489 NF-frame B = Breaker shipped in cassette
RG = IEC NF-frame 1
Future
Continuous ampere range
Arc hood N = None 1
30 = 3000 A (UL only)
A = Arc hood installed (default)
40 = 3200–4000 A (IEC only) Future 1
Door frame gasket N = None
Poles and phasing and rejection kits 1
(facing front of breaker) B = Door kit included (default), Secondary contact terminals installed
3 = Three-pole ABC
4 = Four-pole NABC
with rejection kit N = None
B = Breaker defined, when breaker ships in cassette
1
Load terminal connections
Cell switch options
(available on breaker +
F = Full complement
1
cassette or cassette only) Shutters
F = With flat tapped pads only (no terminals)
G = With vertical/horizontal bus adapter kit N = Not included N = Not included (default)
1
(short style) 3 = Cell switch assembly S = Included
A = With vertical/horizontal bus adapter kit with 3 Form C Contacts 1
(long style)
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 13
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
14 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
3
Arcflash Reduction ARMS uses a separate
analog trip circuit providing
Major benefits • Enabled only for the time
required to perform the 1
Maintenance faster signal processing of ARMS: desired maintenance work
System™ and interruption times • Increased personnel safety • Preserves overcurrent 2
than the standard (digital) – by limiting the available coordination under normal
“instantaneous” protection. arc flash energy conditions 3
Eaton’s patented Arcflash The ARMS function is • Simple to operate • Reduction in incident
Reduction Maintenance activated either directly on • Potential to be enabled energy levels may permit 1
System (ARMS) technology the trip unit, through a local with the circuit breaker reduced levels of Personal
provides maintenance
staff improved safety of
switch/contact or remotely
through communications.
door closed by a remote Protective Equipment (PPE),
therefore improving worker
1
mounted switch which can
downstream maintenance be locked out and tagged comfort and mobility
locations using a simple and
Arcflash Reduction
Maintenance System is out
1
reliable method to reduce optional on both PXR20 and Meets the NEC® 2014
fault clearing times and PXR25 trip units.
•
section 240.87 method 1
incident energy in an arc flash to reduce clearing time
event. by providing an energy- 1
reducing maintenance
switch with local status 1
indicator
1
1
Power Xpert Software requirements Make sure that your PXR
20/25 trip unit is disconnected
range of capabilities varying
from configuring trip unit
Protection Manager • Microsoft® Windows 7 (32- from the PC/Laptop. Allow settings to performing remote 1
bit or 64-bit) the PXPM installation wizard control and test functions.
Eaton’s Power Xpert • Adobe® Acrobat Reader to complete installation on A summary of which 1
Protection Manager (PXPM) is (version 5 or higher). the desired machine before capabilities are contained in
a Microsoft ® Windows-based
software that configures, Screen resolution
continuing. each path of PXPM’s main
dashboard.
1
controls and tests Eaton Using the PXPM
PXR 20/25 trip units. The
• 1280 x 1024 pixels or higher
resolutions software: 1
PXPM software and PXR
trip unit, in conjunction, are To download the software, Upon starting PXPM, the 1
designed to make it easier go to the link http://www. user will be presented with
for OEMs and end customers eaton.com/SeriesNRX. Click
on product “Series NRX NF
the main dashboard. This
dashboard provides which
1
to access breaker load and
and RF frame Low-Voltage allows users to navigate a
usage information, conduct
diagnosis and troubleshooting Power Circuit Breakers with 1
activities, configure settings, PXR electronic trip units”. The
as well as validate and PXPM link will be found to PXPM main dashboard 1
perform testing. download on the Features tab.
1
Installation: Installing Power Xpert
System requirements
Protection Manager 1
Run “Power Xpert Protection
Hardware requirements Manager x32.exe” file for 1
Windows 7 32-bit Operating
Eaton PXR 20/25 trip unit
•
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 15
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
16 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Introduction
1
ModBus PROFIBUS-DP Ethernet 1
configuration configuration configuration
Native ModBus is an option Communications module Communications module 1
on all PXR trip units therefore, PCAM has a 9-pin D-Sub ECAM has a standard RJ45
depending on your application, socket for connection socket for connection to 1
eliminating the need to to PROFIBUS. The Ethernet. This module has
purchase an MCAM.
However, if the system
module works as a slave
on PROFIBUS-DP; the
a configured web server on
board and supports Simple
1
requires redundant data is defined through a Network Mail Protocol
communication or the ability standardized device master (SNMP) for alarm or event 1
to remotely open/close the data file, which permits notifications.
breaker, an external MCAM is smooth integration of a DP 1
required. line. • IP address and related
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 17
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
The zone interlock function provides for hard-wired selective circuit breaker coordination in the power distribution system. In the
1 event that a fault on the system exceeds the trip unit Short Time or Ground Fault pick-up settings, the breaker nearest to the fault
trips instantaneously. At the same time the trip unit sends a logic signal to the connected upstream trip unit to restrain it from
1 tripping immediately and follow its protective delay settings. Coordination is maintained, the breaker closest to the fault trips first
and power is only selectively disrupted.
1
Zone selective interlocking example
1
Example A – Short- CB4 gets no input from any and do not send a ZSI Example C – Short-
lower zone circuit breaker. output.
1 circuit at position 3
This breaker will then trip • Circuit breaker CB3 sends
circuit at position 1
• Circuit breakers CB1, CB3, immediately without any a ZSI output blocking signal • Only Circuit breaker CB1
1 CB4 all see the short-circuit time delay. CB4 interrupts to CB1 ZSI input. CB1 sees the short circuit
current and register a short the fault and CB1 and CB3 sends a ZSI output signal. current and registers a
1 delay pick-up. stop short delay timing In this example that signal short delay pick-up. CB2,
• Circuit breaker CB4 sends because the fault current is not wired. CB3, CB4 and CB5 do not
1 a ZSI output blocking signal
to CB3 ZSI input. CB3
is gone. • CB1 registers the ZSI input
see the fault current and do
not send ZSI outputs.
• If for some reason CB4 signal and starts a timer
sends a ZSI output blocking CB1 sends a ZSI output
1 signal to CB1 ZSI input.
does not open and interrupt
the fault then at the end
for 300ms. CB3 gets no •
signal. In this example that
input from any lower zone
CB1 sends a ZSI output of the its short delay time signal is not wired.
1 signal that is not wired. This CB3 will open and interrupt
circuit breaker. This breaker
will then trip immediately • CB1 gets no input from any
signal could be wired to a the fault. without any time delay. lower zone circuit breaker.
1 MV relay on the other side CB3 interrupts the fault This breaker will then trip
of the transformer with a Example B – Short- and CB1 stops short immediately without any
1 compatible ZSI circuitry. circuit at position 2 delay timing because the time delay. CB1 interrupts
• CB1 registers the ZSI input fault current is gone. The the fault and the clearing
• Circuit breakers CB1, CB3,
1 signal and starts its timer
for 300ms. CB3 registers
see the short circuit current clearance time is reduced
by approximately 150ms.
time is reduced by
approximately 250ms.
and register a short delay
the ZSI input signal and
1 starts its timer for 200ms.
pick-up. CB4 and CB5 do
not see the fault current
1
1
1
CB 1
1 tsd = 300 ms
ZSI
1 Zone 1
1
1
CB 2 CB 3
1 tsd = 200 ms ZSI tsd = 200 ms ZSI
1
Zone 2 2
1 M
CB 4 CB 5
tsd = 100 ms ZSI tsd = 100 ms ZSI
1
Zone 3
1 3
1 CB = Circuit Breaker
ZSI = Zone Selective Interlocking
18 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
3
3.2 Selection criteria for PXR trip units 1
Table 11. Trip unit functions
2
Trip unit type Catalog number Protection style High load alarm Ground fault Maintenance mode ModBus RTU 3
PXR20V000L00C LSI
1
PXR20V000L00M LSI
PXR20V000LG0C LSIG
1
PXR20V000LG0M LSIG 1
PXR 20
PXR20V000LGAC LSIG 1
PXR20V000LGAM LSIG
1
PXR20V000L0AC LSI
1
PXR20V000L0AM LSI
PXR25V000L00M LSI 1
PXR25V000LG0M LSI 1
PXR 25
PXR25V000L0AM LSI
1
PXR25V000LGAM LSIG
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 19
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
1 Over-temperature trip
Thermal memory
1 Zone selectivity ZSI
Making current release (MCR)
1 Maintenance Mode ARMS
(Arcflash Reduction Maintenance SystemTM )
1 System diagnostic
Status/Overload LED
1 Cause of trip LEDs
1 Current at trip point (display indication)
High load or ground fault alarm contact
1 System monitor
LCD display 2 2
1 Current metering accuracy ±1% of Reading ±1% of Reading
Voltage (%) L to L – ±1% of Reading 3
1 Power and energy (%) – ±2% of Reading 3
1 Apparent power kVA and demand – 3
Reactive power kVAR – 3
1 Power factor – 3
Communications
1 Onboard (ModBus RTU)
External (CAM Module)
1 Power supply requirement +24 V DC, optional +24 V DC, optional
1 Additional functions
Test Capability Integral Integral
1 Trip log
Electronic operations counter
1 Event initiated waveform capture
(via communication)
1 Breaker health monitor
1 a 0s: nominal clear time is 60ms with auxiliary power and 120ms without.
b Requires external 24 VDC control voltage supply when continuous current is below 20% of I
Standard Optional – not available
n
c Requires external PT module for voltage sensing input to trip unit
20 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
3
1
2
3
Table 13. Protection features
1
Protection PXR 20 PXR 25
Slope I2t, I4t, I0.5t, It I2t, I4t, I0.5t, It
1
Long delay pickup (Ir) x(In) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95,
0.98, 1.0
0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95,
0.98, 1.0
1
Long delay protection (L) Long delay time @ 6 x (Ir) Seconds 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24 1
Thermal memory Enable/disable Enable/disable
1
High load alarm % x (Ir) Fixed level 85% Fixed level 85%
Ground fault delay at 0.625 Seconds 0.1, 0.2, 0.3, 0.4, 0.5 0.1, 0.2, 0.3, 0.4, 0.5
1
Ground (earth) fault protection x (In) I2t
(option G)
Ground fault delay flat Seconds 0.1, 0.2, 0.3, 0.4, 0.5 0.1, 0.2, 0.3, 0.4, 0.5
1
Zone interlock Enable/disable Enable/disable 1
Thermal memory Enable/disable Enable/disable
1
Setting Enable or disable/remote Enable or disable/remote
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 21
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
3 Minimum IA, IB, IC, IN, IG Amperes ±1% of reading Group values held until reset
1 Maximum IA, IB, IC, IN, IG Amperes ±1% of Reading Group values held until reset
1
Voltage metering Units Accuracy Notes
1 VAB, VBC, VCA Volts ±1% of reading Line to line voltage
1 Minimum VAB, VBC, VCA Volts ±1% of reading Group values held until reset
1 Maximum VAB, VBC, VCA Volts ±1% of Reading Group values held until reset
1
1
1
1
1
1
1
1
1
1
1
1
22 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
3
Table 15. Power and energy metering data
1
Power metering Units Accuracy Notes
2
Real kW ±2% of Reading Approximately 1 second update
Apparent demand (peak) kVA ±2% of Reading Value held until reset 1
Reactive demand (peak) kVA ±2% of Reading Value held until reset 1
Power factor _ Approximately 1 second update 1
Energy metering Units Accuracy Notes 1
Real total kWh ±2% of Reading Forward + reverse
1
Real net kWh ±2% of Reading Forward + reverse
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 23
3 Series NRX air circuit breakers with Power Xpert release trip units
PXR 20/25 trip units
1
2
3
1
1
Table 16. Technical data
1 PCAM MCAM ECAM
General
1
Dimensions (W x H x D) mm 24 x 105 x 80 24 x 105 x 80 24 x 105 x 80
1
Mounting DIN rail Din rail DIN rail
1 Protection type IP20 IP20 IP20
24 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Accessories
4
4.1 Overview Shunt trip (ST) Spring release (SR) • Off key lock;
1
• Pushbutton cover;
The shunt trip opens The spring release (closing
Accessory devices the circuit breaker coil) remotely closes the • Prevent close cover;
2
instantaneously when its circuit breaker when the coil • Lockout cover;
A variety of accessory devices
coil is energized by a voltage is energized by a voltage
are available for use with
input. input. When the spring
• Cassette safety shutters;
Door escutcheon;
3
Series NRX circuit breakers. •
release is used in conjunction
Unless otherwise stated, they
are all considered optional Undervoltage release with a latch check switch,
• IP55 waterproof cover; and 4
(UVR) the closing spring must be • Mechanical interlock.
devices in the sense that they
are not provided as standard The under-voltage release
fully charged and the trip
Non-interlocked pop- 1
on a manually operated circuit latch reset (not held in the
opens the circuit breaker out mechanical trip
breaker. Available accessories when its supply voltage falls
tripped position) for the SR to
operate. If these conditions indicator 1
are discussed in general into the range of 35–60% of are not met, the close signal
terms. For more detailed
information and/or installation
rated voltage. If the release will be ignored until it is
A non-interlocking red, pop-
out mechanical trip indicator,
1
is not energized to 85% of its removed and re-applied.
instructions, refer to individual located to the right of the
instruction leaflets dedicated
supply voltage, the breaker
trip unit on the breaker’s
1
cannot be closed electrically Latch check switch
to individual items. or manually. front faceplate, operates
(LCS) by releasing and popping 1
Series NRX circuit breaker out any time the breaker
Overcurrent trip switch A latch check switch
accessories are designed
to be plug-and-play and (OTS) indicates when the circuit trips due to an overcurrent 1
breaker is “ready to close.” condition. It will not prevent
can be field installed. The
accessories fall into one of
An overcurrent trip switch
(bell alarm) provides an
Two versions of the LCS are the breaker from being
reclosed. The indicator is
1
available.
three categories: electrical indication when reset manually by pushing it
a circuit breaker trips as a 1. The LCS wired to the back in. 1
• Accessory tray devices
result of the trip unit reacting spring release will not
• Other internal electrical to an overcurrent condition. permit activation of the An optional overcurrent trip 1
devices Opening as a result of a spring release until the switch (bell alarm) can be
• Mechanical devices circuit breaker’s manual circuit breaker is fully- used in conjunction with the
mechanical trip indicator.
1
open button, shunt trip, or charged and the trip latch
Accessory tray devices The overcurrent trip switch
under-voltage release does
not cause the overcurrent
is reset.
operates off the position of 1
Certain accessory devices 2. The LCS used for remote the mechanical trip indicator,
trip switch to operate.
are mounted in a mounting
tray. The tray is then installed Overcurrent trip switches
indication consists of one and is reset when the 1
Form C contact wired indicator is reset.
in a left- or right-hand slot are available in two switch
located in the upper left- and combinations only.
to the circuit breaker
secondary contacts for
1
Interlocked pop-
right-hand sides of the circuit integration into external
breaker Auxiliary switch control schemes.
out mechanical trip 1
indicator
An auxiliary switch provides
Left accessory tray remote electrical indication if NNote: Wiring the LCS for remote
indication directly in series with
An interlocked, red, pop-out 1
The left accessory tray will the circuit breaker is open or the SR accessory is not recom- mechanical trip indicator is an
accommodate a maximum of closed. Each switch has one mended as this will override the optional feature. It is located 1
four devices as follows: normally open (“a”) and one “anti-pump” feature. in the front of the breaker
• Zero, one, or two shunt
normally closed (“b”) type
contact. Auxiliary switches Motor operator
near the top and to the right
of the trip unit. It operates
1
trips (ST); are available in two switch by releasing and popping out
• Zero or one undervoltage combinations only. A motor operator is an any time the circuit breaker 1
release (UVR); electric motor assembly trips due to an overcurrent
• Combination (one ST and Other internal internally mounted in the condition. 1
one UVR); or circuit breaker. It charges the
electrical devices NNote: The interlocked mechani-
• Zero or two overcurrent trip
closing springs electrically
for remote or local operation.
cal trip indicator will prevent the 1
switches (OTS). There are three types of breaker from being reclosed until
The motor operator can be
Right accessory tray
internally mounted electrical
devices: factory or field installed.
the red, pop-out indicator is reset
or pushed back in.
1
The right accessory tray will • Spring release; Mechanical devices The indicator is reset 1
accommodate up to two and • Latch check switch; and manually by pushing it back
six 2a/2b auxiliary switch • Motor operator. The following are optional
mechanical type accessories:
in. If the interlocked indicator
is not reset, the circuit
1
combinations for the NF and
RF, respectively. breaker will not close until
• Pop-out trip indicator, non-
interlocked and interlocked; the indicator is pushed back 1
in.
• Operations counter; 1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 25
4 Series NRX air circuit breakers with Power Xpert release trip units
Accessories
An overcurrent trip switch Pushbutton cover circuit breaker is not in the Mechanical interlock
1 (bell alarm), discussed later in CONNECT position.
this section, that operates off Padlockable covers are Mechanical interlocks are
2 the position of the mechanical available to limit access to the
ON and OFF pushbuttons.
Door escutcheon available to interlock the
closing of two or three Series
trip indicator is also available.
The door escutcheon is a NRX circuit breakers. The
3 Operations counter Safe-off pushbutton molded frame used to seal mechanical interlock holds
cover the space between the circuit one or more circuit breakers
4 The operations counter is breaker and the compartment tripped (prevents closure)
a mechanical device used When padlocked, it maintains door cutout. It is supplied when others are closed.
1 to provide a record of the
number of circuit operations.
the OFF button in the
actuated position, which
with a mounting gasket.
Refer to IL01301012E for
Consult Eaton for details.
26 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Accessories
4
4.2 Selection criteria 1
Table 17. Shunt trip 2
Control Operational voltage Inrush/continuous power Opening time
voltages Frequency range 70-110% consumption (VA) (ms) 3
24 DC 17-26 400/2 25
48 DC 34-53 500/3 25
4
60 DC 42-66 500/4 25 1
110-127 50-60 Hz 77-140 800/8 25
110-125 DC 77-138 800/8 25 1
208-240 50-60 Hz 146-264 850/8 25
1
220-250 DC 154-275 850/8 25
1
Table 18. UVR
1
Control Operational voltage Drawout volts Inrush/continuous power Opening time
voltages Frequency range 70-110% 35-60% consumption (VA) (ms)
1
24 DC 20-26 8-14 425/2 50
48 DC 41-53 17-29 750/3 50 1
60 DC 51-66 21-36 825/4 50
110-127 50-60 Hz 94-140 44-66 1150/8 50
1
110-125 DC 94-138 44-66 1150/8 50 1
208-240 50-60 Hz 177-264 84-125 1200/8 50
220-250 DC 187-275 88-132 1200/8 50
1
1
1
Table 19. Spring release
Control Operational voltage Inrush/power Opening time 1
voltages Frequency range 70-110% consumption (VA) (ms)
24 DC 20-26 400 25 1
48 DC 41-53 500 25
60 DC 51-66 500 25
1
110-127 50-60 Hz 94-140 750 25 1
110-125 DC 94-138 750 25
208-240 50-60 Hz 177-264 800 25 1
220-250 DC 187-275 800 25 1
1
Table 20. OCT/OTS Table 21. Auxiliary switch
1
Control Compact rating Control Compact rating
voltages Frequency (amperes) voltages Frequency (amperes)
1
250 50-60 Hz 10 250 50-60 Hz 10
125 DC 0.5 125 DC 0.5 1
250 DC 0.25 250 DC 0.25
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 27
4 Series NRX air circuit breakers with Power Xpert release trip units
Accessories
1
Table 23. Motor operator ratings — RF
1 Control
voltages Frequency
Operational voltage
range 85-110%
Running current
(A)
Typical inrush
current
Power consumption
(VA)
Maximum charging
time (sec)
1 Control voltages 24 Vdc 48 Vdc 110-125 Vdc 110-127 Vac 220-250 Vdc 208-240 Vac
Current
1
1
1
1
1
1
1
1
1
1
28 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Accessories
4
Table 25. Testing procedures NF frame Table 26. Testing procedures RF frame 1
Breaker Continuity between red Continuity between blue Breaker Continuity between red Continuity between blue
position and black lead pairs and black lead pairs position and black lead pairs and black lead pairs
Open No 47 and 45 Open No 55 and 57
2
48 and 49 60 and 61 3
53 and 51 65 and 63
54 and 55 66 and 67
4
Closed 46 and 45 No 71 and 69 1
50 and 49 72 and 73
52 and 51 77 and 75 1
56 and 55 78 and 79
1
83 and 81
84 and 85 1
89 and 87
1
90 and 91
Closed 58 and 57 1
62 and 61
64 and 63
1
68 and 67 1
70 and 69
74 and 73
1
76 and 75 1
80 and 79
82 and 81
1
86 and 85 1
88 and 87
92 and 91 1
1
1
1
1
1
1
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 29
4 Series NRX air circuit breakers with Power Xpert release trip units
Accessories
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55
2 + +
MODBA
MODBG
ACCY2
CMM1
CMM3
ACCY5
ACCY7
ZCOM
ALMC
ALM2
OT1C
OT1B
PTVA
PTVC
+24V
UV1
EO1
SR1
ST1
ZIN
N1
G1
C1
B1
C2
C3
B3
C4
4
ARMSIN
-
-
MODBB
ACCY1
ACCY3
CMM2
CMM4
ACCY4
ACCY6
AGND
OT1M
ALM1
ALM3
ZOUT
PTVN
PTVB
UV2
EO2
SR2
ST2
N2
G2
SC
A1
A2
A3
A4
B2
B4
1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56
1
RF control circuit terminal assignment
1 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
1 + +
ARCON2
MODBA
MODBG
2CMM3
2CMM1
CMM1
CMM3
ZCOM
ALMC
ALM2
OT1C
OT1B
OT2C
PTVA
PTVC
+24V
UV1
RR1
ST1
ZIN
N1
G1
1
ARMSIN
ARCON1
ARCON3
-
-
2CMM2
2CMM4
MODBB
CMM2
CMM4
AGND
OT1M
OT2M
ALM1
ALM3
ZOUT
PTVN
OT2B
PTVB
1
UV2
RR2
ST2
N2
G2
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
1
1, 2 - Shunt trip 20,22 - ARMs
1 3, 4 - UVR/2nd shunt trip 25-28 - External CAM module
5~7 - Overload trip switch 1 (OTS) (5-COM, 6-N.O, 7-N.C.) 29~32 - PT module
1
8~10 - Overload trip switch 2 (OTS) (8-N.C., 9-COM, 10-N.O.) 33~35 - Onboard ModBus
1 11,12 - External neutral sensor 36~39 - External CAM module (future)
13~16 - Alarm 40~42 - ARCON
1 17,18 - Ground fault source sensor 43,44 - Remote reset
19, 20 - Control voltage supply 24VDC 45~48 - Reserved
1 21,23,24 - Zone selectivity ZSI
1
49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95
1 +
SR1
LCC
LCB
C10
C11
B11
C12
E01
1
C1
B1
C2
C3
B3
C4
C5
B5
C6
C7
B7
C8
C9
B9
-
1
LCM
SR2
A10
A11
A12
B10
B12
E02
SC
A1
A2
A3
A4
A5
A6
A7
A8
A9
B2
B4
B6
B8
1 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
30 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
5.1 Reference documents and information PXR trip unit user manual 1
Visit www.eaton.com/SeriesNRX and select the option for
Time current curves Series NRX with PXR then review the “Documents” tab 2
Visit www.eaton.com/tcc and select ‘Low Voltage and Medium Power Xpert protection manager 3
Voltage Power Breakers’ followed by “Series NRX” from the
drop-down. Available for download at www.eaton.com/SeriesNRX and
select the option for Series NRX with PXR 4
2D & 3D drawings Wiring diagrams 5
Authorized original equipment manufacturers (OEMs) should
Visit www.eaton.com/SeriesNRX and select the option for
contact their local sales representative in order to gain access
Series NRX with PXR then review the “Documents” tab 1
to the latest customer drawings.
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 31
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
1 PXR trip unit front face
1 Status
indicator
1 Status
indicator
1
1
The status indicator blinks red if the trip unit detects an internal
1 problem. This indicates a problem with the trip actuator coil, a
firmware error, calibration error, or a mechanism error. To view
1 the NRX with PXR Manual click here MN013003EN
1
Battery tray
1
1
1
1
32 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
When the PXR trip unit is initially powered-up, the display will Rotary switches 1
briefly show a loading screen and then change to the “Main”
menu. During this time, the trip unit is already functioning Depending on the trip unit style, up to 8 switches can be found
and performing protection operations. Depending on the trip on the trip unit’s front panel. The top 7 rotary switches set 2
unit style, there are up to 13 submenu selections from the protection settings using a surrounding legend indicating the
main menu. Each submenu can be accessed by highlighting
the appropriate submenu by pressing the Down or Up Arrow
value. These are the core protection settings. Each switch has
ten positions and is set to achieve the appropriate trip-curve
3
buttons, then the Enter button. A complete map of the response. The “PICKUP” switches set the levels as a function
information and navigation is included in IL0131128EN. of the breaker ratings. The “TIME” switches set the response 4
in seconds. Each switch can be set using a small screwdriver,
Pickup/cause-of-trip indicators the arrow pointing to the selected value. When a change 5
is made to the rotary switches, the display will temporarily
There are four pickup/cause-of-trip indicators on the face of the
trip unit labeled “LONG”, “SHORT”, “INST”, and “GND”.
change to indicate updated value of the setpoints. 1
Maintenance mode switch 1
The PXR trip unit incorporates the Arc Flash Reduction
Pickup/cause-of-trip indicators and reset
Maintenance System™ (ARMS). If equipped, this switch 1
is labeled “MAINT. MODE” and has two positions labeled;
“OFF/Remote” & “ON”. A blue colored ring surrounding
the maintenance mode switch is illuminated when ARMS is
1
enabled.
1
Maintenance mode switch 1
Pickup/
1
cause-of-trip
indicators 1
Maintenance
mode switch 1
1
Reset 1
Reset The button labeled “RESET”, located in the lower right face
of the trip unit, can be depressed to reset the cause of trip
1
indicators.
1
The appropriate cause-of-trip indicator illuminates when a Tamper-resistant cover
current level pickup setting is exceeded. After a trip event, the 1
indicator blinks (one second on, three seconds off) and the A clear, plastic cover is provided which allows the settings to
cause will be shown on the display if auxiliary power is applied. be viewed but not changed. Unauthorized access to change
settings can be prevented by the insertion of a standard sealing
1
The indicators and the display can be cleared by pressing the
wire through the security holes in order to meet applicable
RESET button.
tamper-resistant requirements. 1
Following is a list of conditions detected and displayed by the
cause-of-trip indicators. Door 1
• “LONG” – Solid indicates long delay pickup. Blinking Near the bottom of the PXR trip unit, there is a small door with
“AUX” and the Universal Serial Bus (USB) icon. The door can
1
indicates a long delay trip or overtemperature
be opened downward to expose the temporary auxiliary power
trip has occurred.
port and the USB port. 1
• “SHORT” – Blinking indicates short delay trip or mechanism
•
“INST” –
error.
Blinking indicates instantaneous trip, making
1
current release trip, high instantaneous trip, or
maintenance mode trip has occurred.
1
“GND” – Blinking indicates ground trip or ground alarm
•
condition has occurred. 1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 33
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1 USB
The USB is a micro-B USB connector utilizing USB 2.0 protocol.
1 This USB connection may be used in conjunction with the
Power Xpert Protection Manager software to configure and
Battery tray
1 monitor the trip unit. A USB connection will also typically
provide power from the host side of the USB cable to power
up the trip unit when another source of auxiliary power is not
1 available. This connection is intended for temporary use while In rating
configuring or monitoring the trip unit.
1
In rating
1 Behind the trip unit door
This label shows the In rating of the breaker. The label is part of
1 the frame module and not the trip unit. It is also shown on the
lower left corner of the trip unit display. The trip unit gets this
information from the memory in the frame module.
1
Auxiliary Side labels
1 power USB port
The side of the trip unit has agency certification, model, and
1 manufacturing information printed on a label.
1
1 Temporary auxiliary power
1 The two-pin socket under the left side of the door (see picture
above) accepts the mating connector from a Digitrip auxiliary
power module (Catalog Number: PRTBAPMDV for U.S.
1 power sockets, DTAUXPMEU for European power sockets,
or DTAUXPMUK for U.K. power sockets). This power source
1 may be used to power the trip unit when another source of
auxiliary power is not available. This connection is intended for
1 temporary use while configuring or monitoring the trip unit, or
providing a power source to trip the breaker during testing.
1
1
1
1
1
1
1
1
34 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
PXR protection settings Long delay thermal memory
1
The PXR trip unit protection settings are designed to be In addition to the standard Long Delay protection, a Long
easily customized to any application. Settings for long delay Time Memory (LTM) function is supported. This protects load
circuits from the effects of repeated overload conditions. LTM
2
pickup, long delay time, short delay pickup, short delay time,
is configured using the display and navigation buttons or using
instantaneous pickup, ground fault pickup, and ground fault
time are all independently configurable. These functions are the Power Xpert Protection Manager software. 3
set using rotary switches on the front of the trip unit. Additional
options are chosen using the display and navigation buttons
As an example, if a circuit breaker is closed soon after a Long
Delay trip, and the current again exceeds the Long Delay
4
or by using the Power Xpert Protection Manager configuration setting (Ir), the LTM automatically reduces the time to trip to
software. allow for the fact that the load conductor temperature is already 5
higher than normal because of the prior overload condition.
Long delay pickup and time setting When the load current returns to normal, the LTM begins to 1
reset (after about ten minutes it will have reset fully) so the
The PXR trip unit offers a wide range of settings for Long Delay
Pickup (Ir). This setting ranges from 0.4 to 1.0 and is expressed
next long delay trip time will again correspond to the setting
value.
1
as a multiple of the frame’s current rating (In ). The pickup value
for Long Delay is 105% to 115% of the calculated value to
Short delay pickup and time settings 1
ensure that the circuit breaker can carry the full rating of (Ir),
without tripping. Settings for Short Delay Pickup (Isd ) are expressed as multiples 1
ranging from 1.5 to 10 for the long delay pickup (Ir).
The long delay time settings range from 0.5 to 24 seconds.
They represent the total clearing times when the current value The short delay time (tsd) is selected in conjunction with one
1
equals six times Ir. All times are referenced from the top of of two short delay slopes, flat, or I2t. There are six settings for
the tolerance band, ensuring that the time never exceeds that the flat curve and four settings for I2t, range from 0 seconds 1
maximum setting. When an I4t slope is selected, an overload (minimum time) to 0.5 seconds.
creates a very long time delay which could exceed breaker
ratings. Therefore, when an I4t slop is selected and a time delay
1
The I2t response curve will provide a longer time delay for
above seven seconds is selected, a seven second time delay
will be used instead.
currents below eight times Ir as compared with a flat response
curve. For currents greater than eight times Ir, the I2t response
1
flattens out to a fixed response time.
If a long delay causes the circuit breaker to trip, the “LONG” 1
LED indicator will be illuminated and the “Long Delay” If a short delay causes the circuit breaker to trip, the “SHORT”
message will be displayed if auxiliary power is present. indicator will be illuminated and the “Short Delay Trip” 1
message will be displayed if auxiliary power is present.
Long delay slope selection
The Zone Selective Interlocking (ZSI) feature may affect the 1
The I2t setting is the factory default curve for long delay. The tripping times for the short delay protective function. Please
curve can be changed using the display and navigation buttons refer to the section on ZSI. 1
to several alternative curves to better match the requirements
for protection and coordination. Instantaneous pickup setting 1
The instantaneous (Ii ) setting is expressed as multiples
ranging from 2 to 15 of the In value or can be set to “OFF”. The 1
instantaneous protection trips the breaker with no intentional
Ir slope type Time current curve
time delay. 1
I t Slightly inverse
1
0.5
It Moderately inverse
1
I2 t Standard inverse
1
It
4
Extremely inverse
1
1
1
1
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 35
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1
1
1
1
1
1
1
36 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Maintenance mode High instantaneous 1
The PXR trip units support Eaton’s Arcflash Reduction The PXR trip unit can provide a high instantaneous trip function
Maintenance System™ (ARMS), also referred to as that will trip the circuit breaker at the withstand rating of the 2
Maintenance Mode. When enabled, the trip unit will trip the circuit breaker frame. This function is factory set within the
breaker with no intentional delay whenever the configured
pickup level is exceeded. When enabled, the Maintenance
frame module and reacts to the peak current level. It is always
active regardless of the user’s instantaneous adjustment
3
Mode function operates regardless of the Instantaneous selection, including “OFF”. The instantaneous (“INST”)
settings. If Maintenance Mode causes the circuit breaker to indicator shows this cause of trip. 4
trip, the “INST” indicator will be illuminated and the “ARMS
Trip” message will be displayed on the trip unit if auxiliary All Series NRX NF frame modules have an high instantaneous 5
power is present. trip feature. Selected Series NRX RF frame modules have the
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 37
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
38 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Table 27. Event and log matrix
1
Event code
Event
and
time-stamp
Alarm
snapshot
Trip
snapshot
User
waveform
Alarm
waveform
Trip
waveform Notes 2
200 10 10 1 10 10 Quantity stored
3
User initiated capture USB or network triggered
Power up - clock OK 4
Power up - clock bad 5
Event - setpoints download
1
Event - enter test mode
Event - exit test mode 1
Event - test complete
1
Event - enter maintenance mode Indicator on front also
illuminates 1
Event - exit maintenance mode
Event - opened by communications w/ CAM supported module,
1
spring release and shunt trip
Event - closed by communications 1
Event - time change (if > 60 seconds) Previous time is recorded 1
Alarm - calibration
Alarm - setpoints fault
1
Alarm - battery low voltage 1
Alarm - low control voltage
1
Alarm - RTC error
Alarm - NV memory error
1
Alarm - watchdog timer 1
Alarm - long delay pickup (test mode)
1
Alarm - ground fault (test mode)
Alarm - trip actuator fault 1
Alarm - operations count 1
Alarm - long delay pickup
Alarm - ground fault
1
Alarm - mechanism error 1
Alarm - high load
1
Trip - over temperature
Trip - making current release 1
Trip - test 1
Trip - long delay
1
Trip - short delay
Trip - instantaneous 1
Trip - ground
1
Trip - maintenance mode
Trip - neutral
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 39
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
40 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
PXR communication features Important system components 1
Integrated ModBus-remote terminal unit Potential transformer (PT) module 2
(RTU) port For the PXR 25, a Potential or Voltage Transformer (PT) module
A ModBus communication port is integrated into the PXR trip provides the signals to measure the system voltage and 3
unit for certain styles. The trip unit responds to messages calculate power and energy. The PT module is a wye to wye
from the master using the remote terminal unit (RTU) protocol. configuration, using a three-wire input to generate the four-wire 4
ModBus port configuration can be viewed and set using the output signal for the trip unit. It is mounted externally to the
trip unit display and navigation buttons or using Power Xpert circuit breaker and wired to the secondary terminals.
5
Protection Manager software.
The power and energy metering and the protection functions
are calculated with the convention that power flow is from 1
line to load through the circuit breaker. This assumes the top
Table 29. Factory defaults side conductor to be the line side. If the distribution system is 1
Factory default Options configured such that the bottom side is the incoming side, the
Slave address 001 001 to 247 power values will indicate reverse power. This can be changed
through a setting by using the display and navigation buttons.
1
Baud rate 9600 9600 to 19,200
Parity Event Event, odd, none Auxiliary power 1
Stop bits 1 1 or 2
Providing auxiliary power to the PXR trip unit will provide full 1
The trip unit uses ModBus function codes 02, 03, 04, 06, 08, functionality even when the circuit breaker is open or when
and 16 and supports up to 122 registers (244 bytes) in a single the circuit breaker is under very light load. Auxiliary power is
connected to the circuit breaker’s secondary terminal block.
1
ModBus transaction.
1
USB port IMPORTANT!
The PXR includes a micro-B USB port on the front of the trip 1
unit. This USB connection may be used in conjunction with the Auxiliary power is not required to provide current protection
Power Xpert Protection Manager software to configure, control, features. Protection is active well below any overload. The
trip unit begins to self power-up at very low levels of current
1
and test the trip unit. Alternatively a USB power bank can be
(approximately NF frame = 60 A, RF frame = 100 A)
used to temporarily power the trip unit if auxiliary power is not
available.
1
Power Xpert Protection Manager (PXPM)
External communications adapter modules configuration software 1
(CAMs) Eaton’s PXPM is a Microsoft ® Windows-based software that 1
The NRX circuit breakers with PXR 20/25 trip units are configures, controls, and tests Eaton PXR 20/25 trip units.
equipped to handle a flexible and modular system of This software is used to initiate the built in secondary current
injection testing of the electronic trip unit. The user can create,
1
communication adapter modules (CAMs). These modules
modify, and save setting configurations for PXR 20/25 trip
provide communication from the trip unit to a field bus network.
Various networks are supported by the following modules, units. The software further allows the user to reset trip units, 1
listed with their instruction leaflet: adjust trip unit’s date and time, capture current or voltage
waveforms, and perform trip or no-trip tests. The software is 1
• ICAM - INCOM: IL0131124EN available as a download from the following link: http://www.
• MCAM - ModBus RTU: IL0131091EN eaton.com/SeriesNRX. Click on product “Series NRX NF 1
and RF frame Low-Voltage Power Circuit Breakers with PXR
• PCAM - PROFIBUS: IL0131092EN
• ECAM - ETHERNET: IL0131125EN
electronic trip units.” The PXPM download link will be found on
the Features tab.
1
• PXR-ECAM - ETHERNET: IL0131132EN
These modules are remotely mounted on a DIN rail and wired
1
into the trip unit using the circuit breaker’s secondary terminal
block. The wiring harness as described in the module’s 1
instruction leaflet must be used. The field bus is then wired to a
connection on the CAM Supported module. 1
If so equipped and wired, an added feature of the CAMs is
the option to open (using a shunt-trip) or close (using a spring
1
release) the circuit breaker remotely via communications. On
some styles of CAM modules, there is a jumper on the front - 1
or via a USB programming port - that will enable or disable the
remote communication control capability. It may be desirable 1
to disable remote control when maintenance work or testing is
being done on the circuit breaker. 1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 41
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1
1
1
1
1
1
1
1
1
1
1
1
1
1
42 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Testing the trip unit and circuit breaker Internal simulated test
1
This is a test to verify the trip unit’s firmware integrity. The
Testing prior to startup shall be accomplished with the
circuit breaker either in a de-energized system, or in TEST or
test current values are simulated in the trip unit’s firmware
algorithm to check its integrity and can be used as a trip feature
2
DISCONNECTED cassette position, or WITHDRAWN from the to exercise the complete mechanical trip mechanism of the
cell. breaker. 3
NNotes: Since time-current settings are based on desired system
coordination and protection schemes, the protection settings, if Internal secondary injection test 4
altered during any test sequence, should be reset to their as-found
The trip unit uses an independent built-in circuit to generate
conditions.
a test signal which is injected into the sensor input circuit. 5
This test feature replaces the need for an external secondary
injection test kit. 1
WARNING
Do not attempt to install, test, or perform maintenance Current sensor test (remote) via 1
on equipment while it is energized. Death or severe USB/PXPM
personal injury can result from contact with energized 1
equipment. De-energize the circuit and disconnect the The PXPM software has another mode that can inject current
circuit breaker before performing maintenance or tests. to test for continuity of each sensor. This includes the neutral
sensor which can be tested whether or not there is a sensor
1
installed.
CAUTION 1
Any tripping operation will cause disruption of service 1
and possible personal injury, resulting in the unnecessary
switching of connected equipment. Testing a circuit breaker Sensor input circuit
1
while it is in-service and carrying load current is not rec-
ommended. Testing of a circuit breaker that results in the 1
tripping of the circuit breaker should be done only with the
circuit breaker in the test or disconnected cell positions or
while the circuit breaker is on a test bench.
1
The built-in test system will prevent a test if more than 5% 1
of the rated current (In) is sensed. A password is required
to prevent unauthorized use which could lead to the tripping 1
of the breaker. The default password is 0000.
1
Functional opening test (local) via display
This feature allows a simple functional open test command
1
only from the face of the trip unit. This test is a command sent
to the microprocessor to exercise the components such as the 1
trip actuator and the interface to the breaker mechanism.
1
Functional current testing (remote) via
USB/PXPM 1
The Functional Current Testing uses the PXPM software to
control testing of long delay trip, short delay trip, instantaneous
1
trip, maintenance mode, and ground (earth) fault trip via the
USB communication. The Functional Current Test feature 1
allows for testing on any phase including neutral. The trip unit’s
display is used to observe the current being injected and the 1
elapsed time until trip. On the PXPM software, the test mode
allows the user to enter a current to be injected, initiate the
test, observe operation, and record the results.
1
The PXR 20/25 trip unit has two built-in test modes available 1
for use. One is an internal simulated current test and the other
is an internal secondary injected current test. Either mode can 1
be configured for opening or not opening the breaker.
1
1
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 43
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
3 1. Nameplate
2. Charging handle
4 3. Operations counter (optional)
4. Position Indicator (CONNECT, TEST, DISCONNECT,
5 drawout only)
12
5. Lockable levering access door interlock
1 (drawout only) 19
11
6. Levering access door (drawout only)
1
7. Levering key lock (optional, drawout only, not shown)
1 8. Frame rating module (FRM)
2
1
9. FRM battery cover
1 10. USB and aux. power ports
10
1
8 20
1
1
1
1
1 9
21
1 10
1 NNote: The In rating on the LCD and FRM battery cover should always
agree.
1 NNote: The frame rating module should not be removed.
1
1
1
1
44 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Nameplate identification 1
RF-frame nameplate identification A 2
Nameplates are prominently displayed on the front of the circuit
breaker, and provide important information relative to that B 3
specific circuit breaker. All low voltage circuit breakers must be
applied within their nameplate ratings. It is always advisable 4
to be familiar with the location and information provided on a
breaker’s nameplate.
5
A NRX RF circuit breaker is easily identified by its specific
nameplate designation. Review the nameplate example 1
provided.
Characters 1 2 3 4 5 6 7 8
C 1
Example R Y S 6 2 5 3 B
1
Character 1 Breaker frame size (Character 2) D
R RF-frame for UL 489 or IEC, (4.5 inches (115 mm) pole spacing) 1
Character 2 Standard, mechanism, device (Character 2)
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 45
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1
1 11. Pop-out trip indicator (optional)
12. OFF key lock (optional, not shown)
1 13. Contact status (OPEN - Green, CLOSED - Red)
9
14. Mechanism spring status (charged - Yellow, discharged
1 - White) 3
15 Manual OFF
1 4
16. Manual ON
1 17. Pushbutton cover mounting holes
18. In rating - LCD display on trip unit 15 16 5
1 19. In rating - FRM battery cover
1
1
1 10
1
7 18
1
1
1
1
1 8
19
1 9
1 NNote: The In rating on the LCD and FRM battery cover should always
agree.
1 NNote: The frame rating module should not be removed.
1
1
1
1
46 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
NF-frame nameplate identification 1
Nameplates are prominently displayed on the front of the circuit
breaker, and provide important information relative to that A 2
specific circuit breaker. All low voltage circuit breakers must be
applied within their nameplate ratings. It is always advisable
to be familiar with the location and information provided on a B
3
breaker’s nameplate.
4
A NRX NF circuit breaker is easily identified by its specific
nameplate designation. Review the nameplate example 5
provided. C
1
Characters 1 2 3 4 5 6 7 8
D 1
Example N Y S 6 1 2 3 B
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 47
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1 5.4 Drawings
2 Series NRX NF frame 3P/4P drawout - top, front, side and rear view
3 11.35 (288)
Door/cover
Door/cover
8.6 (218)
Disconnect
4
4 pol
6.53 (168.5)
1
4.45 (115.5)
1
1.26 1.42
(32) (36)
1
3.73 (94.7)
1
0.3 (7)
7.5 (190)
1 8.35 (212)
Contact surface
0.4 (1)
10.67 (271)
1 11.1 (282)
2.87 (73)
1
1 Door/cover
4 pol 7.44 (189)
1
Connect
1
1
1 14.17 (360)
13.43 (341)
11.65 (296)
1
1
1
10 (254) 0.69 (17,5) 9.88 (250) .66 (17)
1 12.7 (323)
1 1 (25.4)
4 pol
1
1 (25.4)
1 M8
1
3 (76)
1
3 (76)
1
6.37 (162)
1
1 2.75 (70) 2.75 (70) 2.75 (70)
48 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame 3P/4P drawout - long horizontal terminal 1
adapters - top and side view
2
2.75 2.75 2.75 3
(70) (70) (70)
1.73 4
φ
0.
(44)
53
5
(1
3.
5)
0.75
(19)
1
(44.5)
1.75
4pol 1
(38.2)
1.50
1
1
Contact surface
1
1
1
1
1
1
1
1
1
(9.5)
0.37
1
1
1
6.00 (152)
1
1
1
3.19
(81)
1
5.24 (133) 1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 49
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
(9.5)
0.37
1
(101.7)
1
4.00
4pol
1
1
Contact surface
1
1
1
1
1
1
1
1
1
1
1.73
(44)
1
(76)
3
1
φ0
1 .5
3
(1
(76)
3.
3
5)
1
6.37 (162)
1
1
1 1.75
(44.5) 5.24 (133)
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
50 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame 3P/4P drawout - short horizontal terminal 1
adapters - top and side view
2
2.75 2.75 2.75 3
(70) (70) (70)
φ0
2 1.06 4
(12.5)
.53
.49
(1 (51) (27)
3.5
) 5
1
(47.4)
1.87
4pol
1
1
Contact surface
1
1
1
1
1
1
1
1
1
1
(15)
.59
1
1
1
6.00 (152)
1
1
1
3.11
(79)
1
5.59 (142) 1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 51
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
2.36
(60)
4pol
1
1 Contact surface
1
1
1
1
1
1
1
1
1
1
1
(51)
1
2
1
(76)
.5)
3
3 (13
1
φ 0.5
1
(76)
3
6.37(162)
1.06
1
(27)
1
1
.49 (12.5) 5.59 (142)
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
52 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame 3P/4P fixed - front, rear and top view 1
11 (279.5)
2
8.25 (209.5)
4pol
3
7.47 (190)
4
5
1
1
1
13.31 (338)
1
(38)
1.5
9.83 (250)
1
9 (228)
.32
(8)
1
(100)
3.96
(12)
.47
1
(25.4) 4pol
1
1.26
(32)
1
9.43 (239.5)
1
.35
(9)
12.18 (309.5) M8
1
10.24 (260)
1
13 (330)
1
(76)
3
(25.4)
1
1
1
4.53 (115)
(76)
3
1
1
2.75 2.75 2.75
(70) (70) (70) 1
Contact surface
1
4pol
1
1
(25)
.98
1
(20)
.79
3.50
3.86
(89)
(98)
1.45
(38)
1
(19)
.75
1
(77) -30
3.03 0
φ8
3.82
(97)
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
Door/cover
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 53
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
0.75
(19)
1
(44.5)
1.75
4pol
4.57 (152)
1
2.86 (73.3)
1
1
1 Contact surface
1
1
1
1
1 4.99 (126.7)
1
1
1
1
(9.5)
0.37
1
1
6.00 (152)
1
1
1
1.38
(35)
1
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
54 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame 3P/4P fixed - long vertical terminal 1
adapters - top and side view
2
1.97
(50)
2.75
(70)
2.75
(70)
2.75
(70) 3
.37
(9.5) 4
5
4pol 1
6.87 (174.5)
1
4.37 (111)
1
(73.3)
2.89
1
1
Contact surface
1
1
1
1
1
1
1
1
1.73
(44)
1
(76)
3. 3
3
(1 0.5
5)
1
φ
1
4.55 (115.5)
(76)
3
1
1
1
1.75
(44.5)
1
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 55
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
4 1.97
(50)
2.75
(70)
2.75
(70)
2.75
(70)
5 2
(12.5)
φ 0 3.5
.49
(51)
(1
.5 )
3
1 4pol
.52 (13.3)
4.74 (120.5)
1 (73.3)
2.89
1
1
1 Contact surface
1
1
1
1
1
(15)
.59
1
1
1
5.98 (152)
1
1
1
1.26
(32)
1
1
1
1
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
56 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame 3P/4P fixed - short vertical terminal 1
adapters - top and side view
2
5.24 (133)
4.74 (120.5)
1
(73.3)
1
2.89
1
Contact surface 1
1
1
1
1
1
1
1
(51)
2
1
(76)
)
3
13.5
1
53 (
φ 0.
1
4.55 (115.5)
(76)
3
1
1.06
(27)
1
.49
(12.5) 1
1
1
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 57
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1 Series NRX NF frame 3P/4P drawout - cassette side and rear view
2 1.34
Door/cover (34) 4pol
3 Disconnect
4
5 M
8
1.34
(34)
1
2.60
(66) 2.60 (66)
1
7.32 (186)
1
.36 (9)
1
.12 (3) 4.53 (115) 4.53 (115) 4.53 (115)
1
2.87
1 (73)
Door/cover
1 Connect
1
1
1
17.96 (456)
17.68 (449)
14.89 (379)
1
1
1
1
1.00 (25.5) 13.62 (346) .86 (22)
1
1
1
1
1
1
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
58 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX RF frame 3P/4P drawout - rear and front view 1
2
19.67 (499.5)
15.14 (384.5) 3
.75
4 pol
Door/cover
4
(19)
5
5.25 (133.5)
1
9.38 (238.5)
φ9
1.77 (45)
3.85 (97.5)
.37
(9.5)
1
8.76 (222.5)
Scale 1:2
1
1.77
(45)
(32.5)
1.23
1
4.15 1.16 4.15
(105.5)
8.67 (220.3)
(29.5)
3.39 (86)
(105.5)
1.16
Contact surface 1
(29.5)
1
4 pol 13.15 (134) 1
1
1
1
1
1
1
1
1
15.76 (426) 1
21.30 (541)
1
1
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 59
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
.48 (12.5)
4.53 (115) 4.53 (115) 4.53 (115)
IEC UL
4 1.95 (50)
1.06
(27)
2.99 (76)
φ 11 “T” .79 (20) 0.75 (9)
5 4pol
1.42
(36)
1
1 Contact surface
1
1
1
1
1
1
1
1
1
1
“T”
1
5.20 (132)
1
1
1
4.33 (110)
1
10.14 (257.5)
1
1
1
1
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
60 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX RF frame 3P/4P drawout - with centered three-hole vertical 1
terminal adapters - top and side view
2
4.53 (115) 4.53 (115) 4.53 (115) 3
IEC UL
“T”
“T” .79 (20) 0.75 (9) 4
4pol 5
1.42
(36)
1
Contact surface
1
1
1
1
1
1
1
1
1
1
1
1
2.99 (76)
1
2.60
(66)
1
φ
11
2.60 (66)
1
1.97 (50)
7.32 (186)
1
1
.48 (12.5) 10.14 (257.5)
1
1.06
1
(27)
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 61
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
(12.5)
.48
1
5
1.06
(27)
1.42
(36)
1 2.26
4pol (57.5)
1 5.91 (150) 5.91 (150)
Contact surface
1 3.94 (100)
1.08
4.63 (117.5)
.98 .98 .98
(27.5) (25)(25)(25) .59 (15)
1 .48 .98 .98 .98
(12.5)
(12.5) (25)(25)(25)
φ1
.48
1
1
1.06
(27)
1.42
(36)
1
1 Contact surface
1
1
1
1
1
1
1
1 IEC UL
1
“T”
1
1
5.20 (132)
1
1
4.33 (110)
1
1
10.14 (257.5)
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
62 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX Type RF 3P/4P drawout - with offset four-hole vertical 1
terminal adapters - top and side view
2
4.53 (115) 4.53 (115) 4.53 (115)
3
“T” IEC UL
1.42
(36)
5
Contact surface
1
1
1
1
1
1
1
1
1
1.06
(27)
1
.48
(12.5) 1
1
4.63 (117.5)
1
3.98 (101)
1
1
φ1
3.98 (101)
1
1
(15) (25) (25) (25)
7.32 (186)
1
1
10.14 (257.5)
1
1
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 63
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
2
1) .53 (13.4)
(5.
3 φ .20
(15.5)
16x
.61
4
5
1
1
1
12.00 (304.8)
15.51 (394)
(101.6)
4.00
1
1
7.83 (198.8)
1
1 Ground
1
1 4.00
(101.6)
1 12.00 (304.8)
1 14.08 (358)
1
Series NRX Type RF - drawout IP55 waterproof cover cutout
1
1 9.76 (248) 8.23 (209)
1
4.41 (112)
(19)
.75
1
1
1
14.15 (395.3)
9.76 (248)
1
1
1 φ.
26
(6
.5)
1
1 .5) (6
.5)
(6
.26 26
φ.
1 φ
64 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX RF frame 3P/4P fixed - front, top and rear view 1
13.22 (334) 2
3
4pol
4
5
15.65 (398)
1
13.83 (351)
11.75 (298)
1
1
.14 (4) 1
1
Contact surface
.69 (7.5)
.67 (17)
1
(106)
4.17
1
(130)(+9) -1.18
(-30)
6.00 (106)
(15.5)
5.12 .35
1
.61
1
16.07 (410)
20.67 (525)
Door/cover
1
16.88 (430)
1
21.46 (545)
1.34 1
(34)
1
4pol 1
M8 1
1
1.34
(34)
1
2.60
(66)
1
2.60 (66)
(124)
4.89
1
4.53 (115) 4.53 (115) 4.53 (115)
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 65
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
.48 (12.5)
1.06
(27)
(53.5)
2.11
1
1
(17.5)
.69
1 Contact surface
1
1
1
1
1
1
1
1
1
1
1 IEC UL
1
1
5.20 (132)
1
1
1
1.89
(48)
1
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
66 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX RF frame 3P/4P fixed - with centered three-hole vertical 1
terminal adapters - top and side view
2
4.53 (115) 4.53 (115) 4.53 (115) 3
IEC UL
“T”
“T” .79 (20) 0.75 (9) 4
4pol
5
1
(53.5)
2.11
1
(17.5)
.69
1
Contact surface
1
1
1
1
1
1
1
1
1
1
1
1
1
2.99
(76)
1
2.60
(66)
1
φ1
1
2.60
(66)
1
4.89 (124)
1.97 (50)
1
1
.48
(12.5)
1
1.06
1
(27)
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 67
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
(12.5)
φ1
4.94 (125.5) .48 (12.5)
.48
(25)(25)(25)
1
5
1.06
(27)
(53.5)
2.11
1
1 2.26
1.42
(36)
4pol (57.5)
Contact surface
1 5.91 (150) 5.91 (150)
(12.5)
(12.5)
(25)(25) (25)
.48
1
1
1.06
(27)
(53.5)
2.11
1
1.42
(36)
1 Contact surface
1
1
1
1
1
1
IEC UL
1
“T”
1
1
5.20 (132)
1
1
1
1.89
(48)
1
1
1
1 2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX
68 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX RF frame 3P/4P fixed - with offset four-hole vertical 1
terminal adapters - top and side view
2
4.53 (115) 4.53 (115) 4.53 (115) 3
IEC UL
“T” “T” .79 (20) 0.75 (9)
4
4pol 5
1
(53.5)
2.11
1
(17.5)
.69
1
Contact surface
1
1
1
1
1
1
1
1.06
1
(27)
1
.48
(12.5)
1
1
1
4.63 (117.5)
1
3.98 (101)
1
1
φ1
1
1
3.98 (101)
4.88 (124)
1
(15) (25) (25) (25)
.59 .98 .98 .98
1
1
1
1
2D drawings and 3D STP drawings are available from www.eaton.com/SeriesNRX 1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 69
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
1 Series NRX NF frame - drawout front door cutout (top drawing) / IP55
waterproof cover cutout (bottom drawing)
2
.1)
3 0
(5
0.53
(13.5)
0.2
(15.5)
0.61
xφ
4 12
5
1
1
1
(310.5)
(266.5)
12.22
(101.5)
10.5
1
4.00
1
6.16 (156.4)
1
1 Ground
1
1 4.00
(101.5)
1 8.39
(213)
1 9.45
(240)
1 5.61 (142.5) 5.50 (139.7)
1
1
0.75
(19)
1
1
1
1
12.28 (312)
9.75 (247.7)
1
1
1
1
φ
1
0.
26
(6
5)
(6.
.5
1
)
6
φ 0.2
70 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Series NRX NF frame - fixed front door cutout (top drawing) / IP55 1
waterproof cover cutout (bottom drawing)
2
)
(5.1 0.53
3
0 (13.5)
.2
(15.5)
φ0
0.61
x
12 4
5
1
1
1
(266.5)
(263.5)
(101.5)
10.38
10.5
4.00
1
1
5.28 (134)
1
Ground 1
1
4.00
1
(101.5)
8.39 1
(213)
9.45 1
(240)
1
1
1
1
12.28 (260)
7.79 (197.9)
1
1
1
1
φ
1
0.
26
(6
5)
(6.
.5
1
)
.26
φ0
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 71
5 Series NRX air circuit breakers with Power Xpert release trip units
Appendix
2 (5.
1)
.53 (13.4)
0
(13.8)
φ .2
.54
3 16x
4
5
1
1
12.00 (304.8)
14.47 (388)
1
(101.6)
4.00
1
7.06 (179.3)
1
1 Ground
1
1
4.00
1 (101.6)
12.00 (304.8)
1
14.08 (357.7)
1
1 Series NRX Type RF - fixed IP55 waterproof cover cutout
1
1
4.80 (122)
(19)
.75
1
1
1
7.80 (198)
15.73 (399.6)
1
1
1
φ
.2
6
(6
1
.5
)
1 (6.
5)
26 .5)
φ. (6
1 φ.
26
72 SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com
Series NRX air circuit breakers with Power Xpert release trip units
Appendix
5
Recommended safety clearances 1
The following information 4.0 (100) 2
about safety distances
is intended to provide a
guideline for the installation
3
a a
of circuit breakers in an
enclosure. 4
5
1
b b
1
1
1
a Cell switch (optional)
Key lock (optional)
1
Ventilation openings (do not block!)
1
Enclosure 1
clearance To insulated surface To ground metal surface With cell switch / key lock
In mm In mm In mm 1
Drawout a 0 0 0 0 0 0
1
b 1.0 25 1.0 25 1.0/2.9 25/75
1
The illustration shows a typical enclosure.
The table below lists the associated minimum distances 1
between enclosures and ventilation openings.
This information is intended as a guideline for constructing 1
H
a suitable circuit-breaker enclosure. Ensure that integration
complies with applicable UL standards. 1
1
1
D
1
V
Rear or bottom
1
vent open area
1
W - Cassette width +3.0 in +75 mm
H - Height 21.7 in 550 mm
1
D - Front compartment depth 17.7 in 450 mm 1
V Ventilation 25 in2 160 cm2
1
SERIES NRX AIR CIRCUIT BREAKERS WITH POWER XPERT RELEASE TRIP UNITS MZ013001E—November 2016 www.eaton.com 73
Eaton is a power management company with 2015 sales of $20.9
billion. Eaton provides energy-efficient solutions that help our
customers effectively manage electrical, hydraulic and mechanical
power more efficiently, safely and sustainably. Eaton has
approximately 97,000 employees and sells products to customers
in more than 175 countries.