You are on page 1of 72

Operating

instructions

Belt-driven
screw compressors
S 40-2 ... S 341
SF 40-2 ... SF 220 series

Before installation or starting the


compressor for the first time, this
manual should be studied carefully to
obtain a clear knowledge of the unit
and of the duties to be performed while
operating and maintaining the unit.

RETAIN THIS MANUAL WITH UNIT.


This Technical manual contains
IMPORTANT SAFETY DATA and should
be kept with the air compressor at all
times.

separate manuals:
compressor control /
frequency converter
Index

Operating instructions
for the belt-driven screw compressors
– S 40-2 / SF 40-2 ( 40 Hp)
– S 50-2 ( 50 Hp)
– S 60-2 / SF 60-2 ( 60 Hp)
– S 61-2 ( 60 Hp)
– S 75-2 ( 75 Hp)
– S 100-2 / SF 100-2 (100 Hp)
– S 101 (100 Hp)
– S 125 (125 Hp)
– S 150-2 / SF 150 (150 Hp)
– S 151 (150 Hp)
– S 180 (180 Hp)
– S 220-2 / SF 220 (200 Hp)
– S 271 (270 Hp)
– S 341 (340 Hp)

BOGE KOMPRESSOREN
P.O. Box 10 07 13
D-33507 Bielefeld
Germany
Otto-Boge-Straße 1–7
D-33739 Bielefeld
Phone: ++49 / 52 06-6 01-0
Fax: ++49 / 52 06-6 01-2 00
Mail: info@boge.com
Net: www.boge.com

As of 04 / 2010
No. 596.0935.18
Nominal price: US $ 5.00

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page I
Inhalt.pm6.5 - USA
Index

Page II BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Inhalt.pm6.5 - USA
Index

Index

Part 1: 1.1 General safety instructions ......................................................... 1.1


General Safety instructions for compressor operation ................................. 1.1
Safety instructions for maintenance and repair of the compressor . 1.2
Accident prevention regulations ..................................................... 1.2

1.2 Introduction .................................................................................. 1.4


Symbols used ................................................................................. 1.4
Symbols on the compressor ........................................................... 1.5
Intended use .................................................................................. 1.7
Inadmissible use ............................................................................ 1.7
Transportation damage .................................................................. 1.8
Data on the type plate .................................................................... 1.8
Service ........................................................................................... 1.8

Part 2: 2.1 Technical data .............................................................................. 2.1


Product description Technical data S 40-2 to S 100-2, part 1 ........................................ 2.1
Technical data S 101 to S 341, part 1 ............................................. 2.2
Technical data S 40-2 to S 100-2, part 2 ........................................ 2.3
Technical data S 101 to S 341, part 2 ............................................. 2.4
Technical data SF 40-2 to SF 220, part 1 ....................................... 2.5
Technical data SF 40-2 to SF 220, part 2 ....................................... 2.6

2.2 Function description .................................................................... 2.7


Function principle of the air end ..................................................... 2.7
Air circuit ........................................................................................ 2.7
Oil circuit ........................................................................................ 2.8

2.3 Compressor control ..................................................................... 2.9


Supply pressure ............................................................................. 2.9
Operating states ............................................................................. 2.9
Operating modes ............................................................................ 2.9
Short operating times ..................................................................... 2.9

2.4 Control devices .......................................................................... 2.10


Operating pressure transmitter ..................................................... 2.10
Proportional controller (option for S-series) .................................. 2.10

2.5 Safety and monitoring devices ................................................. 2.11


General ........................................................................................ 2.11
Safety temperature limiting device ............................................... 2.11
Safety valve .................................................................................. 2.11
Monitoring the drive and fan motor ............................................... 2.11
Rotational direction monitoring ..................................................... 2.11
Safety pressure switch (option) .................................................... 2.11
System pressure build-up (option) ............................................... 2.11

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page III
Inhalt.pm6.5 - USA
Index

2.6 Water cooling .............................................................................. 2.12


Serial connection .......................................................................... 2.12
Parallel connection ....................................................................... 2.12

2.7 Cooling water ............................................................................. 2.13


Water connection (for water cooling) ............................................ 2.13
Cooling water quality .................................................................... 2.13

Part 3: 3.1 Transport ....................................................................................... 3.1


Installation General .......................................................................................... 3.1
Transport possibilities ..................................................................... 3.1

3.2 Compressor room ........................................................................ 3.2


Installation surface ......................................................................... 3.2
Fire protection ................................................................................ 3.2
Admissible environmental influences ............................................. 3.2
Frost protection .............................................................................. 3.2
Ventilation ....................................................................................... 3.2
Cooling air requirement .................................................................. 3.3
Ventilation possibilities ................................................................... 3.4
Condensate disposal ...................................................................... 3.4

3.3 Installation .................................................................................... 3.5


General .......................................................................................... 3.5
Checking the delivery scope .......................................................... 3.5
Installing the compressor ............................................................... 3.5
Connecting the compressor to the compressed air network .......... 3.5
Connecting the cooling water (option) ............................................ 3.6
Removing the transport securing bolts ........................................... 3.6
Activating the belt tensioning device .............................................. 3.7
Checking the oil level ...................................................................... 3.7

3.4 Electrical connection ................................................................... 3.8

3.5 Commissioning .......................................................................... 3.10


Checking the rotational direction .................................................. 3.10
Opening the stop valves ............................................................... 3.10
Checking for leaks ........................................................................ 3.10
Conduct trail run ........................................................................... 3.10
Commissioning following extended stoppages ............................. 3.11

Part 4: 4.1 General .......................................................................................... 4.1


Faults
4.2 General faults ............................................................................... 4.2

Part 5: 5.1 Safety instructions ....................................................................... 5.1


Maintenance 5.2 General .......................................................................................... 5.2
Maintenance through BOGE service .............................................. 5.2
Review of regular maintenance work ............................................. 5.2

Page IV BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Inhalt.pm6.5 - USA
Index

Maintenance intervals .................................................................... 5.3


General information concerning the lubricants used ...................... 5.4
Disposal of used operating material ............................................... 5.5
Spare and wearing parts ................................................................ 5.5

5.3 Regular maintenance work .......................................................... 5.6


Clean or change intake filter ........................................................... 5.6
Cleaning the filter cartridge ............................................................ 5.6
Changing the supply air filter mats (option) .................................... 5.7
Lubricating the drive motor bearings .............................................. 5.7
Drive motors with permanent lubrication ........................................ 5.7
Drive motors with lubrication device ............................................... 5.8
Servicing drive motor ..................................................................... 5.9
Changing the V-belt ...................................................................... 5.10
Setting GM – Belt tensioning device S 40-2 – S 341 /
SF 40-2 – SF 220 ......................................................................... 5.11
Checking the oil level, topping up oil ............................................ 5.11
Changing the oil filter ................................................................... 5.13
Changing the oil separator ........................................................... 5.14
Oil change .................................................................................... 5.16
Flushing the oil circuit ................................................................... 5.18
Cleaning the compressed air / oil cooling unit (air cooling) ........... 5.18
Proportional controller (option for S-series) .................................. 5.19
Checking the safety valve ............................................................. 5.20

5.4 Spare parts and optional equipment ........................................ 5.21


List of spare and wearing parts (for maintenance) ....................... 5.21

Part 6: 6.1 Flow chart ..................................................................................... 6.1


Appendix Air cooled version, standard ........................................................... 6.1
Water cooled version, serial connection ......................................... 6.2
Water cooled version, parallel connection ...................................... 6.2
Air cooled version, frequency-controlled ........................................ 6.3

6.2 List of maintenance and service work ........................................ 6.4

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page V
Inhalt.pm6.5 - USA
Index

Page VI BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Inhalt.pm6.5 - USA
General 1.1 General safety instructions

WARNING!
Nonobservance of the following safety instructions may lead to injuries
and damage to the compressor.
Also observe the generally valid safety and accident prevention regu-
lations in addition to the information in these operating instructions!

Safety instructions for 1. Ensure that no commissioning or maintenance work on the compressor
compressor operation be undertaken until these operating instructions are understood.
2. Only use the compressor for its intended use, as described in these op-
erating instructions.
3. The owner must ensure:
– That only appropriately trained and authorized personnel work on this
compressor.
– That the operating, maintenance and repair personnel has been made
fully familiar with all safety instructions, and that they are being observed
– That the compressor is only operated in a safe operating condition.
4. Avoid any operating method which may impair the safety of the com-
pressor.
5. Do not exceed the limit value for the final compression pressure specified
on the type plate.
6. Do not operate the compressor without the attendant protection and
safety devices.
Do not dismantle any built-in safety devices or put them out of operation.
Ensure that all cladding and doors are closed prior to commissioning/
starting up the compressor and are not opened during operation.
7. Place the compressor out of operation as described in these operating
instructions, when dismantling the cladding or safety devices for repair
or maintenance work. Reattach all cladding and safety devices immedi-
ately upon completion of the repair or maintenance work.
8 Only operate the compressor using the additional equipment (options)
recommended or authorized by the manufacturer.
9. Undertake conversions and modifications of the compressor only in
agreement with BOGE, taking all relevant safety regulations into consid-
eration.
The manufacturer is not liable for damages resulting from independent
modifications on the compressor.
10. Never start compressor when one or serveral parts (e.g. cable, plug) are
damaged, when not in perfect working order or when damage is detected
or suspected.
11. Observe all safety and danger signs directly attached on the compressor!
12. The compressed air-oil pressure receiver has to be inspected in pre-
determined intervals according to the local authorities responsible for
pressure receivers.
13. To avoid damages, special precautions have to be taken during (re-)
operation of compressors with frequency control, if the frequency con-
verter was cut off from the power supply for a longer period of time
(> 12 months). In this case please contact the BOGE-Service.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 1.1
Allgemeines.pm6.5 - USA
General 1.1 General safety instructions

Safety instructions for 1. Ensure that maintenance work is only carried out by appropriately trained
maintenance and repair persons.
of the compressor 2. Ensure that setting work, malfunction rectification and repair are only
carried out by specialists or appropriately trained persons.
3. Prior to maintenance or repair work:
– Switch off main switch.
– Secure main switch against unintentional switch-on.
– Check to ensure that all parts have been isolated.
– Disconnect compressor from compressed air network (relieve or block
pressurized lines).
4. Exercise extreme caution during repair or maintenance work requiring
compressor to be operational.
Ensure that no persons are located in the hazardous area.
5. Ensure that work on the electrical equipment is only undertaken by quali-
fied electricians.
6. Work on voltage carrying parts and devices are not permitted. Exceptions
are governed by the appropriate regulations.
CAUTION
7. Only use original spare parts, compressor oils and operating
materials released by BOGE during repair or maintenance.
8. The operator is required to check the compressor daily for externally vis-
ible damage and defects, and to immediately report any changes (includ-
ing operational behavior).
9. When the automatic restart (Auto-Restart) is activated, the compressor
restarts automatically following a voltage loss.
Prerequisite: The net pressure is lower than the switch-on pressure.

Accident prevention The owner of a compressor plant is required to ensure that it is properly in-
regulations stalled, operated and maintained.

For operation of the compressor plant, the accident prevention regulations


of the owner country must be observed in addition to the data contained in
these operating instructions.
In the event that measures are required above and beyond the legal regu-
lations or the data contained in these operating instructions, then it is of
utmost importance that these be carried out prior to commissioning the
compressor plant.

Page 1.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General 1.1 General safety instructions

WARNING!
Failure to adhere to these recommendations can result in mechanical failure,
property damange and serious injury or death.
All air and water inlet, and air and water discharge pipework to and from the
inlet and discharge port connections must take into account vibration, pul-
sations, temperature, maximum pressure applied, corrosion and chemical
resistance. In addition, it should be noted that lubricated compressors will
discharge some oil into the air stream; therefore, compatibilty between dis-
charge piping, system accessories and software must be assured.
For the foregoing reasons, the use of plastic piping, and soldered copper
fittings as discharge piping is not recommended. In addition, flexible joints
and/or flex lines can only be considered for such purposes if their specifi-
cations fit the operating parameters of the system.
It is the responsibility of the installer and owner to provide the appropriate
service pipework to and from the machine.

WARNING!
Statement concerning the inadvertent breathing of compressed air
exhaust.
The purchaser/user shall ensure that adequate ventilation and make up air
are provided if a non-BAP designated compressor supplies air in a confined
area to air consuming devices such as air motors, air tools, solenoids, air
cylinders, air guns, nozzles, etc. The compressed air discharge stream may
contain residual coolants/lubricants/carbon monoxide and condensable
hydrocarbons or other materials which may be hazardous to health with pro-
longed inhalation.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 1.3
Allgemeines.pm6.5 - USA
General 1.2 Introduction

The purpose of these operating instructions is to familiarize the user with the
function and all application possibilities of the compressor.
These operating instructions contain important information on how to operate
the compressor safely, economically and according to its intended use. Ob-
serving these operating instructions will assist in avoiding danger, to reduce
repair costs and downtimes and to increase the reliability and service life of
the compressor. It contains important information concerning the required
maintenance and repair measures, assists in case of malfunctions and con-
tains data concerning spare and wearing parts.
The operating instructions must at all times be made available to the com-
pressor operating personnel at the place of operation.
The operating instructions must be carefully read and applied by all persons
engaged to undertake the following work on the compressor:
– Operation, including fault rectification and daily care
– Maintenance (service, inspection, repair)
– Commissioning
– Transportation
The compressor and its additional equipment must not be installed and
commissioned until the operating instructions are understood.
These operating instructions can be supplemented with instructions on the
basis of existing national regulations concerning accident prevention and
environmental protection.
In the illustrations, the compressor is shown in part without cladding or safety
devices for better visualization. However, operation without these compo-
nents is prohibited!

Symbols used DANGER!


Risk of injury! Danger is used to indicate the presence of a hazard which
will cause severe personal injury, death, or substatial property damage if the
warning is ignored.

WARNING!
Warning is used to indicate the presence of a hazard which can cause se-
vere personal injury, death, or substantial property damage if the warning is
ignored.

CAUTION!
Caution is used to indicate the presence of a hazard which will or can cause
minor personal injury or property damage if the warning is ignored.

DANGER: Voltage! This symbol indicates information warning of life threat-


ening electrical voltage levels.
It indicates work which must be exclusively performed by skilled electricians.

NOTICE!
Notice is used to notify people of installation, operation, or maintenance in-
formation which is important but not hazard-related.

Page 1.4 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General 1.2 Introduction

DANGER Before working at the compressor:


– disconnect all current-cyarrying parts!
– check if all parts actually voltage-free!
– secure the compressor against switching-on!
– reduce the pressure in all areas!
If you neglect these rules, your health will be endangered!

Before putting into service: Regular maintenance:


Discharge air. – read the instructions Observe the operating instructions!
Can contain carbon monoxide – check electric connections – check suction filter weekly, if necessary clean
or other contaminants. Will – check oil-level (not for oil-free) or replace it
cause severe injury or death.
– if applicable, remove the transport safety device – check cooler for dirt, if necessary clean it
Do not breathe this air. – check the direction of rotation of compressor – check oil-level weekly (not for oil-free)
– operate only with a belt protective grating – drain condensation water from pressure tank
or a sound protection bonnet. at least once a week
– do not close the cooling air inlets and outlets air – check operativeness of automatic steam trap
during operation!

NOTICE NOTICE
Electrical power inlet. Air discharge.

Prohibited:
Warning: Never open the valve before
The unit is operated by remote control, the air hose (connection to
and might start without warning. the compressed air network)
is connected.

NOTICE
Reler to the
Instruction/Operators Manual
before performing any
maintenance.

NOTICE

Do not operate without


enclosure panels & forklift
covers in place.
Refer to the
Instruction/Operators Manual
before performing any
maintenance.
WARNING
NOTICE

Hazardous voltage. Can cause


severe injury or death.
Motors must be greased
periodically. See Operators Disconnect power before
Manual for procedure. servicing.
Lockout/Tagout machine.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 1.5
Allgemeines.pm6.5 - USA
General 1.2 Introduction

Motor lubrication CAUTION


See motor rating plate for Improper coolant filter replace-
relubrication interval, kind and ment will cause compressor
quantity of grease. Always damage.
lubricate with motor running. Replace filter element after first
500 hours of operation and every
3000 hours thereafter or when
coolant is changed.

WARNING

Exposed fan blade. Can cause


severe injury.

Do not operate with covers


removed.
Disconnect power. Lock and tag.

WARNING

Hot surface.
NOTICE Can cause severe injury.

Do not touch. Allow to cool bevore


servicing.
Lift here.

NOTICE

Rotation.

WARNING
WARNING
CAUTION
Use of incorrect coolant can
cause system contamination.
Moving parts.
Can cause severe injury. Use only BOGE Syprem 8000 S. High pressure air.
Can cause severe injury or death.
Do not operate with covers removed.
Service only with machine blocked to Relieve pressure before removing
prevent turn over. filter plugs / caps. fittings or covers.

Page 1.6 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General 1.2 Introduction

Intended use BOGE S series screw compressor, including its additional equipment, is
exclusively intended for the compression of air.
The air taken in must not contain any explosive or chemically instable gases
or vapors.
Do not exceed specified final compression temperature.

BOGE screw compressors are designed for stationary operation.


Ensure that they are only installed and operated in dry and clean rooms.

Operation, control and maintenance are designed to be executed by trained


and authorized operators.

Inadmissible use Never direct the produced compressed air towards persons. Danger to life!

WARNING!
Statement concerning the use of this equipment for breathing air and/
or aqua lung service. If the model number on this air compressor contains
the letters "BAP", the compressor is suitable for use in breathing air services.
In the absence of such a designation, the compressor is NOT considered as
capable of producing air of breathing quality. For a compressor to be capable
of use in breathing air services it must be fitted with additional specialized
equipment to properly filter and/or purify the air to meet all applicable federal,
state and local laws, rules, regulations and codes, such as, but not limited
to, OSHA 29 CFR 1910.134, Compressed Gas Association Commodity
Specification G-7, 1-1966, Grade D Breathing Air and/or Canadian Standards
Association. Should the Purchaser and/or User fail to add such specialized
equipment and proceeds to use the compressor for breathing air service,
the Purchaser/User assumes all liability resulting therefrom without any re-
sponsibility or liability being assumed by BOGE COMPRESSORS.
The Purchaser is urged to include the above provision in any agreement for
any resale of this compressor.

This BOGE screw compressor is not explosion protected. Do not operate in


explosive areas!

Do not operate compressor in rooms in which extreme dust, toxic or flam-


mable vapors and gases may occur.

The following is not permitted:


– Exceeding the final compression pressure indicated on the type plate.
– Altering the safety devices and cladding or placing them out of operation.
– Removing or painting over signs and symbols on the compressor.
– Operation of the compressor by unauthorized or untrained persons.
– Operation of the compressor with removed cladding or safety devices.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 1.7
Allgemeines.pm6.5 - USA
General 1.2 Introduction

Transportation BOGE does not accept any liability for breakage or transportation damage.
damage Please inspect the compressor immediately after delivery and direct dam-
age claims to the last carrier – even when the packing is not damaged!
To safeguard claims against the carrier we recommend leaving the machine,
devices and packing material in the same condition as they were in when
the damage was detected.

In the event of any other complaints, please inform us within six days after
arrival of the delivery.

Data Enter the data of your compressor from the type plate or enclosed data
on the type plate sheet in the illustration below. This will ensure that in the event of enquiries,
you will always have the most important data at hand.

Fig. 1.1: Data on the type plate

Service Please do not hesitate to contact BOGE service if you have any questions.
Please call:
 770 - 8 74 -1570

In the event of inquiries, always specify the following data of your compressor
to prevent any delays:
– Type
– Year of manufacture
– Machine number

NOTICE!
Only BOGE service technicians or persons authorized by BOGE in writing
may repair or alter the compressor during the warranty period. Otherwise all
warranty claims will expire!

Page 1.8 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Product description 2.1 Technical data

Technical data for S 40-2 to S 100-2, part 1

Type S 40-2 S 50-2 S 60-2 S 61-2 S 75-2 S 100-2


Dimensions
– Height (silenced) [inch] 57 57 57 57 57 57
– Height (super silenced) [inch] 77 77 77 77 77 77
– Depth [inch] 64 64 64 79 79 79
– Width (silenced / super silenced) [inch] 38 38 38 42 42 42
Weight
– silenced [lbs.] 1790 1830 1855 2570 2680 3135
– super silenced [lbs.] 1860 1900 1915 2670 2790 3245
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 76/71 78/72 78/73 79/73 79/73 80/73
Air cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension
15/16 15/16 15/16 16/17 16/17 16/17
– silenced / super silenced [dB(A)]
Sound capacity level
91/87 93/88 93/98 95/90 95/90 96/90
– silenced / super silenced [dB(A)]
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 75/70 77/71 77/72 78/72 78/72 79/72
Water cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension
15/16 15/16 15/16 16/17 16/17 16/17
– silenced / super silenced [dB(A)]
Sound pressure capacity
90/86 92/87 92/88 94/89 94/89 95/89
– silenced / super silenced [dB(A)]
Compressor
max. final compression temperature [°F] + 230 + 230 + 230 + 230 + 230 + 230
Volume flow according to ISO 1217 Part C
– pmax = 100 psig [cfm] 195.3 234.8 257.6 285.5 345.9 448.6
– pmax = 115 psig [cfm] 182.6 224.2 247.2 271.9 329.4 427.3
– pmax = 125 psig [cfm] 182.6 224.2 247.2 271.9 329.4 427.3
– pmax = 150 psig [cfm] 163.5 204.1 223.9 244.4 293.1 370.8
– pmax = 190 psig [cfm] 134.9 174.8 189.3 207.3 251.1 324.9
Drive motor
Rated power [hp] 40 50 60 60 75 100
Rated speed
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600
Protection type TEFC TEFC TEFC TEFC TEFC TEFC
ISO class F F F F F F
Electrical connection
200/208/230 230 230 230 230 230
Mains voltage 1) [V]
460/575 460/575 460/575 460/575 460/575 460/575
Frequency 1) [Hz] 60 60 60 60 60 60
150/150/125 175/70 175/90 175/90 225/125 300/150
Recommended fuse protection 2) [A]
60/50 60 70 70 90 125
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.1
Produkt.pm6.5 - USA
Product description 2.1 Technical data

Technical data for S 101 to S 341, part 1

Type S 101 S 125 S 150 S 151 S 180 S 220 S 271 S 341


Dimensions
– Height (silenced) [inch] 69 69 69 79 79 79 84.4 84.4
– Height (super silenced) [inch] 89 89 89 99 99 99 104.1 104.1
– Width (silenced / super silenced) [inch] 93 93 93 89/101 89/101 89/101 122 122
– Depth [inch] 53 53 53 63 63 63 75.2 75.2
Weight
– silenced [lbs.] 4080 4190 4565 5090 5400 5735 9921 11023
– super silenced [lbs.] 4210 4315 4700 5315 5620 5955 10141 11244
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 76/72 79/74 79/74 85/77 85/77 83/74 84/77 87/80
Air cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension
17/18 17/18 17/18 18/19 18/19 18/19 18/19 19/20
– silenced / super silenced [dB(A)]
Sound capacity level
93/90 96/92 96/92 101/93 101/93 101/93 105/99 105/99
– silenced / super silenced [dB(A)]
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 72/70 73/71 73/71 79/71 79/71 79/71 86/79 86/79
Water cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension
17/18 17/18 17/18 18/19 18/19 18/19 18/19 18/19
– silenced / ssuper silenced [dB(A)
Sound pressure capacity
89/88 90/89 90/89 79/90 79/90 97/90 104/98 104/98
– silenced / super silenced [dB(A)]
Compressor
max. final compression temperature [°F] + 230 + 230 + 230 + 230 + 230 + 230 + 230 + 230
Volume flow according to ISO 1217 part C
– pmax = 100 psig [cfm] 480 580 685 706 861 1024 1208 1498
– pmax = 115 psig [cfm] 463 555 650 685 823 985 1080 1439
– pmax = 125 psig [cfm] 463 – – 685 823 950 1080 1439
– pmax = 150 psig [cfm] 403 484 576 600 735 886 – 1310
– pmax = 190 psig [cfm] 346 424 501 508 629 766 – 1119
Drive motor
Rated power [Hp] 100 125 150 150 180 200 250 350
Rated speed
– 60 Hz [min-1] 3600 3600 3600 3600 3600 1800 1800 1800
Protection type TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC
ISO class F F F F F F F F
Electrical connection
230/460 460/575 460/575 460/575 460/575 460/575 460/575 460/575
Mains voltage 1) [V]
575
Frequency 1) [Hz] 60 60 60 60 60 60 60 60
300/150 175/150 200/175 200/175 300/225 300/250 400 500
Recommended fuse protection 2) [A]
125
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.

Page 2.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.1 Technical data

Technical data for S 40-2 to S 100-2, part 2

Type S 40-2 S 50-2 S 60-2 S 61-2 S 75-2 S 100-2


Oil filling quantity
Oil receiver volume [gallon] 11 11 11 17 17 17
Total oil filling quantity [gallon] 6 6 6 10 10 10
Oil topping up quantity
between min. + max. [gallon] 1.5 1.5 1.5 2 2 2
Intake air temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41 + 41
– max. [°F] + 113 + 113 + 113 + 113 + 113 + 104
Cooling air requirement
Air cooling

– free-standing installation [cfm] 6600 7700 7700 7700 9400 10800


– with supply and exhaust [cfm] 3300 3800 3800 3800 4700 5400
– (air duct)
– free ventilator pressure [inch/H2O] 0.24 0.24 0.24 0.24 0.24 0.24
Cooling air requirement
– free-standing installation [cfm] 1200 1200 1200 1200 1200 1200
– with supply and exhaust [cfm] 600 600 600 600 600 600
Required cooling water quantity
– delta t = 15 K [cfm] 0.958 1.182 1.440 1.440 1.764 2.404
Water cooling

– delta t = 30 K [cfm] 0.479 0.591 0.720 0.720 0.882 1.202


Max. cooling water quantity [cfm] 2.05 2.1 2.05 2.05 2.5 2.5
Cooling water inlet temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41 + 41
– max. [°F] + 86 + 86 + 86 + 86 + 86 + 86
Cooling water outlet temperature
– max. [°F] + 113 + 113 + 113 + 113 + 113 + 113
Cooling water pressure
– min. [psig] 30 30 30 30 30 30
– max. [psig] 146 146 146 146 146 146
Operating pressure switch 1)
(factory settings)
– pmax = 100 psig: Switch-off press. pmax [psig] 100 100 100 100 100 100
Switch-on press. pmin [psig] 87 87 87 87 87 87
– pmax = 115 psig: Switch-off press. pmax [psig] 115 115 115 115 115 115
Switch-on press. pmin [psig] 100 100 100 100 100 100
– pmax = 125 psig: Switch-off press. pmax [psig] 125 125 125 125 125 125
Switch-on press. pmin [psig] 110 110 110 110 110 110
– pmax = 150 psig: Switch-off press. pmax [psig] 150 150 150 150 150 150
Switch-on press. pmin [psig] 130 130 130 130 130 130
– pmax = 190 psig: Switch-off press. pmax [psig] 190 190 190 190 190 190
Switch-on press. pmin [psig] 174 174 174 174 174 174
Safety valve
Activation pressure at:
– pmax = 100 psig [psig] 160 160 160 160 160 160
– pmax = 115 psig [psig] 160 160 160 160 160 160
– pmax = 150 psig [psig] 160 160 160 160 160 160
– pmax = 190 psig [psig] 203 203 203 203 203 203
1
) Compressors for other operating pressures Pmin = Pmax minus (– ) 14.5 psig.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.3
Produkt.pm6.5 - USA
Product description 2.1 Technical data

Technical data for S 101 to S 341, part 2

Type S 101 S 125 S 150 S 151 S 180 S 220 S 271 S 341


Oil filling quantity
Oil receiver volume [gallon] 29 29 29 46 46 46 61 61
Total oil filling quantity [gallon] 16 16 16 24 24 24 34 34
Oil topping up quantity
between min. + max. [gallon] 2.4 2.4 2.4 4.0 4.0 4 4.8 4.8
Intake air temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 + 41 + 41
– max. [°F] + 113 + 113 + 113 + 113 + 113 + 113 + 113 + 113
Cooling air requirement
Air cooling

– free-standing installation [cfm] 11800 18900 18900 18900 28700 28700 32960 38846
– with supply and exhaust [cfm] 5900 9400 9400 9400 14350 14350 16480 19423
– (air duct)
– free ventilator pressure [inch/H2O] 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24
Cooling air requirement
– free-standing installation [cfm] 2000 2000 2000 2000 5880 5880 5880 5880
– with supply and exhaust [cfm] 1000 1000 1000 1000 2940 2940 2940 2940
Required cooling water quantity
– delta t = 15 K [cfm] 2.41 2.881 3.528 7.997 4.23 5.127 6.409 7.997
Water cooling

– delta t = 30 K [cfm] 1.20 1.440 1.764 3.998 2.11 2.564 3.205 3.998
Max. cooling water quantity [cfm] 5.30 5.3 5.3 8.0 7.1 7.1 8.0 8.0
Cooling water inlet temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 + 41 + 41
– max. [°F] + 86 + 86 + 86 + 86 + 86 + 86 + 86 + 86
Cooling water outlet temperature
– max. [°F] + 113 + 113 + 113 + 113 + 113 + 113 + 113 + 113
Cooling water pressure
– min. [psig] 30 30 30 30 30 30 30 30
– max. [psig] 146 146 146 146 146 146 146 146
Operating pressure switch 1)
(factory settings)
– pmax = 100 psig: Switch-off press. pmax [psig] 100 100 100 100 100 100 100 100
Switch-on press. pmin [psig] 87 87 87 87 87 87 87 87
– pmax = 115 psig: Switch-off press. pmax [psig] 115 115 115 115 115 115 115 115
Switch-on press. pmin [psig] 100 100 100 100 100 100 100 100
– pmax = 125 psig: Switch-off press. pmax [psig] 125 125 125 125 125 125 125 125
Switch-on press. pmin [psig] 110 110 110 110 110 110 110 110
– pmax = 150 psig: Switch-off press. pmax [psig] 150 150 150 150 150 150 – 150
Switch-on press. pmin [psig] 130 130 130 130 130 130 – 130
– pmax = 190 psig: Switch-off press. pmax [psig] 190 190 190 190 190 190 – 190
Switch-on press. pmin [psig] 174 174 174 174 174 174 – 174
Safety valve
Activation pressure at:
– pmax = 100 psig [psig] 160 160 160 160 160 160 160 160
– pmax = 115 psig [psig] 160 160 160 160 160 160 160 160
– pmax = 150 psig [psig] 160 160 160 160 160 160 160 160
– pmax = 190 psig [psig] 203 203 203 203 203 203 203 203
1
) Compressors for other operating pressures Pmin = Pmax minus (– ) 14.5 psig.

Page 2.4 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.1 Technical data

Technical data for SF 40-2 – SF 220, part 1

Type SF 40-2 SF 60-2 SF100-2 SF150 SF 220


Dimensions
– Height (silenced) [inch] 57 57 57 69 79
– Height (super silenced) [inch] 77 77 77 89 99
– Width (silenced / super silenced) [inch] 64 64 79 93 89/101
– Depth [inch] 38 38 42 53 63
Weight
– silenced [lbs] 1470 1850 3377 4720 5735
– super silenced [lbs] 1540 1920 3487 4850 5955
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 76/71 78/73 80/73 79/74 83/74
Air cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension 18/19
15/16 15/16 16/17 17/18
– silenced / super silenced [dB(A)]
Sound capacity level
91/87 93/89 96/90 96/92 101/93
– silenced / super silenced [dB(A)]
Max. sound pressure level [± 3 dB(A)]
accord. to DIN 45635, part 13 75/70 77/72 79/72 73/71 79/71
Water cooling

– silenced / super silenced [dB(A)]


Measuring surface dimension
15/16 15/16 16/17 17/18 18/19
– silenced / super silenced [dB(A)]
Sound pressure capacity
90/86 92/88 95/89 90/89 97/90
– silenced / super silenced [dB(A)]
Compressor
max. final compression temperature [°F] 230 230 230 230 230
Volume flow according to ISO 1217 Part C
– pmax = 100 psig [cfm] 48,7 – 195,3 64,4 – 257,6 114,1 – 448,6 171,3 – 685 256 – 1024
– pmax = 115 psig [cfm] 45,6 – 182,6 61,8 – 247,2 106,6 – 427,3 162,4 – 650 246 – 985
– pmax = 125 psig [cfm] 45,6 – 182,6 61,8 – 247,2 106,6 – 427,3 162,4 – 650 246 – 985
– pmax = 150 psig [cfm] 41,0 – 163,5 55,8 – 223,9 92,7 – 370,8 144,1 – 576 222 – 886
– pmax = 190 psig [cfm] 33,9 – 134,9 47,3 – 189,3 81,2 – 324,9 125,3 – 501 192 – 766
Drive motor
Rated power [hp] 40 60 100 150 200
Rated speed
– 60 Hz [min-1] 3600 3600 3600 3600 3600
Protection type TEFC TEFC TEFC TEFC TEFC
ISO class F F F F F
Electrical connection
Mains voltage 1) 3) [V] 460/575 460/575 460/575 460/575 460/575
Frequency 1) [Hz] 60 60 60 60 60
Recommended fuse protection 2) [A] 60/50 90/70 150/125 200/175 300/250
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.
3
) For the refrigeration compressed air dryer 230 V / 60 Hz are required.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.5
Produkt.pm6.5 - USA
Product description 2.1 Technical data

Technical data for SF 40-2 – SF 220, part 2

Type SF 40-2 SF 60-2 SF100-2 SF150 SF 220


Oil filling quantity
Oil receiver volume [gallon] 11 11 17 29 46
Total oil filling quantity [gallon] 6 6 10 16 24
Oil topping up quantity
between min. + max. [gallon] 1.5 1.5 2 2.4 4
Intake air temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41
– max. [°F] + 104 + 119 + 104 + 119 + 113
Cooling air requirement
Air cooling

– free-standing installation [cfm] 6600 7600 10800 18900 28700


– with supply and exhaust [cfm] 3300 3800 5400 9400 14350
(air duct)
– free ventilator pressure [psig/H2O] 0.24 0.24 0.24 0.24 0.24
Cooling air requirement
– free-standing installation [cfm] 1200 1200 1200 2000 5880
– with supply and exhaust [cfm] 600 600 600 1000 2940
Required cooling water quantity
– delta t = 15 K [cfm] 0.959 1.440 1.764 3.528 5.127
Water cooling

– delta t = 30 K [cfm] 0.479 0.720 0.882 1.764 2.564


Max. cooling water quantity [cfm] 2.4 2.1 2.5 5.3 7.1
Cooling water inlet temperature
– min. [°F] + 41 + 41 + 41 + 41 + 41
– max. [°F] + 86 + 86 + 86 + 86 + 86
Cooling water outlet temperature
– max. [°F] + 113 + 113 + 113 + 113 + 113
Cooling water pressure
– min. [psig] 30 30 30 30 30
– max. [psig] 146 146 146 146 146
Operating pressure switch 1)
(factory settings)
– pmax = 100 psig: Switch-off press. pmax [psig] 100 100 100 100 100
Switch-on press. pmin [psig] 87 87 87 87 87
– pmax = 115 psig: Switch-off press. pmax [psig] 115 115 115 115 115
Switch-on press. pmin [psig] 100 100 100 100 100
– pmax = 125 psig: Switch-off press. pmax [psig] 125 125 125 125 125
Switch-on press. pmin [psig] 110 110 110 110 110
– pmax = 150 psig: Switch-off press. pmax [psig] 150 150 150 150 150
Switch-on press. pmin [psig] 130 130 130 130 130
– pmax = 190 psig: Switch-off press. pmax [psig] 190 190 190 190 190
Switch-on press. pmin [psig] 174 174 174 174 174
Safety valve
Activation pressure at:
– pmax = 100 psig [psig] 160 160 160 160 160
– pmax = 115 psig [psig] 160 160 160 160 160
– pmax = 150 psig [psig] 160 160 160 160 160
– pmax = 190 psig [psig] 203 203 203 203 203
1
) Compressors for other operating pressures Pmin = Pmax minus (– ) 14.5 psig.

Page 2.6 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.2 Function description

Function principle The air end operates according to the displacement principle. In the housing,
of the air end the main and secondary screws are driven by means of an electric motor
and V-belt.
Both screws have screw-shaped profiles, intermeshing without contact.
Together with the housing wall, these screws form chambers which gradually
reduce in size, seen in air flow direction.
Rotation of the rotors causes the air taken in to be compressed to the final
pressure in the chambers.
During compression oil is continuously injected into the air end. This having
a cooling, sealing and lubricating function.

Air circuit
1

3 4 5
2

Fig. 2.1:
Components of
8 7 6
the air circuit

1 = Intake filter
The intake filter cleans the air suctioned by the air end.
2 = Intake regulator
The intake regulator opens (load operation) or closes (idling operation or
standstill) the intake line depending on the operating condition of the com-
pressor.
3 = Air end
The air end compresses the intake air.
4 = Compressed air/oil receiver
The compressed air separates from the oil under the force of gravity in the
compressed air/oil receiver.
5 = Oil separator
The oil separator separates the residual oil contained in the compressed air.
6 = Minimum pressure check valve
The minimum pressure check valve does not open until the system pressure
has increased to 3.5 bar (51 psig). This causes a rapid build-up of the system
pressure and ensures lubrication in the starting phase. Once the compressor
has been switched off, the check valve prevents the compressed air from
flowing back out of the mains line.
7 = Compressed air after-cooler (air and water cooled)
The compressed air is cooled in the compressed air after-cooler, causing the
water contained in the air to condensate.
8 = Stop valve
The screw compressor may be isolated from the mains by means of the stop
valve.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.7
Produkt.pm6.5 - USA
Product description 2.2 Function description

Oil circuit The oil injected into the air end has the following function:
– It dissipates the compression heat (cooling).
– It seals the gaps between the screws and between the screws and housing.
– It lubricates the bearings.

5 6

2
4

Fig. 2.2:
Components of the oil circuit

1 = Compressed air/oil receiver


The oil separated from the compressed air through the force of gravity collects
in the compressed air/oil receiver.
The system pressure forces it out of the receiver into the air end.
2 = Thermostatic oil control valve
Depending on the oil temperature, the thermostatic oil control valve either
allows the oil to pass through the oil cooler or through a bypass (e.g. in the
starting phase).
Thus the oil constantly maintains its optimum operating temperature.
3 = Oil cooler (air or water cooled)
The oil cooler cools down the hot oil to operating temperature.
4 = Oil filter
The oil filter traps impurities in the oil.
5 = Air end
The injected oil returns to the compressed air/oil receiver together with the
compressed air. There, it is separated through the force of gravity.
6 = Drainage line
The collectet oil from the oil-separator is drained back to the air end into the
oil circuit via the drainage line.

Page 2.8 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.3 Compressor control

Supply pressure For the compressor, the pressure downstream of the check valve is termed
the supply pressure. The control system switches the compressor on and off
during operation depending on the supply pressure.

Operating states All screw compressor controls are based on three basic operating states:
1. Load operation
– The compressor delivers its maximum amount of compressed air.
– It consumes its maximum energy.
2. Idling operation
– The compressor runs but does not deliver any compressed air.
– It consumes approx. 75% less energy than in load operation.
– When compressed air is required, it switches to load operation with-
out delay.
– Idling operation reduces switching frequencies which can damage the
drive motor, and reduces wear of the system.
3. Standstill ready for operation
– The compressor is standing still but ready for operation.
– When compressed air is required, it switches automatically to load
operation.

Operating modes The two most important operating modes are achieved by combining the
three operating states:
1. Intermittent operation
In intermittent operation the energy balance is perfect.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to standstill. It does not consume any energy.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches back to load operation.
2. Continuous operation
Continuous operation limits the drive motor switching cycles and reduces
wear to the system.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to idling operation.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches from idling operation back to load operation.

Short operating CAUTION!


times During short operating times, the compressor does not reach its operating
temperature. It operates below the dew point. The generated condensate
mixes with the oil. The lubricating ability of the oil is reduced. This leads to
damage on the air end.
It is of utmost importance to consult BOGE, if you operate your system with
short operating times.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.9
Produkt.pm6.5 - USA
Product description 2.4 Control devices

Operating pressure The operating pressure transmitter  controls the operation of the compres-
transmitter sor within the set switching limits.

Switch-on pressure pmin


If the network pressure drops to the set switch-on pressure pmin, the compres-
sor switches on.
1
Switch-off pressure pmax
If the network pressure increases to the switch-off pressure pmax, the compres-
sor either switches off (intermittent operation) or switches to idling operation
(continuous operation).

Proportional controller The proportional controller is an additional control device intervening in the
(option for S-series) sequences of the intake regulator.
The intake regulator only opens as far as necessary to supply the current
compressed air requirement. Thus the compressor saves compression
energy.
A compressor with proportional controller is able to supply its ’delivered
quantity variable between 0% and 100%. However, the energy consumption
does not reduce accordingly. Therefore, a control is only practical between
50% and 100% of the delivered quantity.
The proportional controller is factory set to a delivered quantity between
50% and 100% of the compressor capacity.
The proportional controller closes when the desired delivered quantity has
dropped below 50% of the compressor capacity. The compressor then oper-
ates in idling operation (continuous operation) or switches off (intermittent
operation).

Page 2.10 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.5 Safety and monitoring devices

General The safety devices guarantee a high degree of operational safety, in connec-
tion with the BOGE monitoring system.
When one of the safety devices responds, the control system reacts as follows:
– The compressor is immediately switched off.
– A flashing fault number in the left field of the display indicates the cause
of the fault.

DANGER!
Do not operate the compressor without built-in safety devices.
Do not dismantle the safety devices or put them out of operation.

Safety temperature Safety temperature limiting device switches off the compressor once the
limiting device maximum admissible final compression temperature has been reached.
The compressor does not switch on when dropping below the minimum
temperature.
– Switch off the compressor (OFF button). Fault is acknowledged.
– Rectify the fault.
– Switch on the compressor (ON button).

Safety valve Safety valve  on the compressed air/oil receiver prevents the maximum
admissible pressure being exceeded. When the maximum pressure is ex-
ceeded (e.g. incorrect setting of the operating pressure switch), the entire
delivery volume of the compressor is ejected.

Monitoring the drive The following monitoring devices are standard for BOGE control systems:
and fan motor The drive motor is monitored by PTC resistors.
The fan motor is monitored by overcurrent/overload release units.

Rotational direction The pressure switch checks the rotational direction of the drive motor each
monitoring time the system starts up.
The pressure switch for the rotational direction is placed next to the operat-
ing pressure switch.

Safety pressure switch The safety pressure switch prevents the maximum admissible system pres-
(option) sure being exceeded. The switch-off pressure is below the response pres-
sure of the safety valve.

System pressure The system pressure build-up unit monitors the system pressure build-up
build-up (option) when the compressor starts up.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.11
Produkt.pm6.5 - USA
Product description 2.6 Water cooling

Water cooling BOGE screw compressors are available in water or air-cooled design.
In the standard version, the oil and compressed air after-coolers are con-
nected in series on the water side. A parallel connection is possible as an
option.

4 5
Serial connection

Fig. 2.3: Serial connection

2 3 1

4 5
Parallel connection

Fig. 2.4: Parallel connection

2 3 1

1 = Cooling water solenoid valve


The cooling water solenoid valve closed the cooling water supply when the
compressor switches off.
2 = Cooling water stop valve
The compressor may be separated from the cooling water supply by means
of the stop valve (e.g. for maintenance or repair work).
3 = Dirt trap (provided by customer)
The dirt trap protects the cooling unit against sedimenting.
Pore size: max. 0.6 mm
4 = Oil cooling unit
5 = Compressed air after-cooler
The water cooling units are designed for specific standard cooling water
quantities, temperatures and pressures (see "Technical data").
For individually fluctuating values, they are designed according to the speci-
fied order data.

Page 2.12 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description 2.7 Cooling water

Water connection The cooling water must have the following properties:
(for water cooling)
Electrical conductivity: >50 µS/cm at pH value 7– 9:
Carbonatehardness CaCo3 <16°dH
Cooling water pressure – max. [psig] 146
– min. [psig] 30
Cooling water inlet temperature – min. [°F] 41
– max. [°F] 86
Max. cooling water quantity – refer to technical data.

Cooling water quality The cooling units are fitted with nonferrous heat exchangers, as standard.
To avoid damage to these components and to guarantee a long term function,
ensure that the substances contained in the cooling water used do not exceed
the following values:

Substances Symbol max. admissible concentration [mg/l]


Ammonia NH3 2
Chloride <70°C Ci 100
Sulphite, free chlorides Ci 5
Iron Fe 2
Free carbon dioxide Co2 20
Manganese Mn 1
Nitrate NO3 100
Oxygen O2 2
Silicon oxide SiO2 8
Sulphate SO4 60
Total dissolved substances TD-S 600
Table: Maximum admissible concentration of the substances

If the specified limit values are exceeded, use cooling units made of other
materials.
Please consult BOGE service.

ATTENTION!
If the cooling water data changes, the cooling units may have to be
redesigned. Incorrectly designed cooling units may cause malfunctions
and the compressor to switch off!
Please consult BOGE.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 2.13
Produkt.pm6.5 - USA
Product description

Page 2.14 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Produkt.pm6.5 - USA
Installation 3.1 Transport

General Please observe the generally accepted safety and accident prevention regu-
lations when transporting the compressor. BOGE accepts no liability for
damage caused by improper transport!!

CAUTION!
The compressor is delivered filled with oil.
Do not tilt during transport!

Transport possibilities Forklift truck or lifting


carriage transport
Ensure that the forks grip
underneath the base frame
of the compressor.

Crane transport
Only use suitable transport slings having a
minimum length of approx. 315 in.
Position the slings at the ends underneath the
base frame of the compressor.

CAUTION!
Do not subject the safety cladding to force during transport.
Protect the compressor using wooden spacers (see arrows).
Remove the transport timbers.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.1
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room

Installation surface A level industrial floor without foundation is adequate for the installation of the
compressor. No special fastening elements are required.

Fire protection WARNING!


Requirements of fire protected compressor rooms:
– Flammable liquids must never be stored in the compressor room.
– The floor around the compressor must be made of non-flammable material.
– Leaking oil must not spread out over the floor.
– No inflammable materials must be located within a radius of at least
3 metres around the compressor.
– No inflammable machine parts, such as cable ducts, may run overhead
of the compressor.

Admissible The compressor room must be clean, dry, cool and free of dust.
environmental
influences Admissible ambient temperatures (see "Technical data")
Maximum ambient temperature (for air cooling): + 104 / 113°F
Minimum ambient temperature: + 141°F

CAUTION!
Nonobservance of the admissible ambient temperature may lead to the
following problems:
– The compressor will switch off when the admissible final compres-
sion temperature is exceeded or gone below.
– Pipe lines and valves will freeze up at low temperatures.
– Damage due to reduced lubricating ability of the compressor oil.

Measures to be taken to ensure that admissible ambient temperatures


are observed:
– Avoid any pipe lines or units radiating heat in the vicinity of the compres-
sor, or insulate them well.
– Never install the compressor in the cooling air flow of other machines.
– Provide the supply air openings with adjustable louvres to ensure that
the minimum temperature is not gone below in winter.
– Use the BOGE frost protection device.

Frost protection The compressor must be installed frost-protected.

Ventilation If the following instructions are not observed, the admissible final
compression temperature may be exceeded.
In this case, the compressor will switch off automatically.

CAUTION!
Arrange the compressor intake openings or ducts such, that dangerous
admixtures (e.g. explosive or chemically unstable materials) cannot be
drawn in.

Page 3.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room

Ventilation openings (free-standing installation)


– Arrange supply air openings close to the floor.
– Arrange exhaust air openings in the ceiling or at the top of the wall.
– The required cross sections for the supply openings (as well as for the
flaps and weather protection grids) are indicated in the table.
Supply and exhaust air ducts
– Ensure that the flow rates in the ducts do not exceed 9 mph.
– Never position cooling air ducts directly on the compressor.
Always use a compensator to avoid distortion and the transfer of vibrations.
Fans
Ensure that the heated exhaust air is not taken in again.
If necessary, the heated air must be extracted by exhaust fans.
To ensure perfect cooling even at higher temperatures in the summer, the
fans must be designed as follows:
– The fan capacity must be rated approx. 10 – 15% higher than the sum of the
cooling air quantity required for all machines operated in the room.
– For free-standing installation, the cooling air requirement specified in the
table corresponds to the required fan capacity.
Supply air filter
– Equip the compressor with supply air filter mats if the compressor room
is contaminated with dust (option).

Cooling air requirement Please refer to the following table for the cooling air requirement and size of
the supply air openings for your compressor. Ensure that flaps and weather
protection grids have the necessary free cross section. We generally recom-
mend contacting a specialist company for performing the duct construction
work and planning.

Type Drive Air cooling Water cooling*


rating Cooling air Necessary Cooling air Necessary Cooling air Necessary
requirement inlet opening requirement free duct requirement inlet opening
for free for free for installation cross section for free for free
standing unit standing unit with ducting standing unit standing unit
[Hp] [cfm] [sq. ft.] [cfm] [sq. ft.] [cfm] [sq. ft.]
S 40-2 40 6600 17.0 3300 4.5 1200 2.7
S 50-2 50 7700 17.0 3800 5.2 1200 2.7
S 60-2 60 7700 15.0 3800 5.2 1200 2.7
S 61-2 60 7700 15.0 3800 5.2 1200 2.7
S 75-2 75 9400 22.0 4700 6.3 1200 2.7
S 100-2 100 10800 24.0 5400 7.3 1200 2.7
S 101 100 11800 27.0 5900 8.0 2000 4.8
S 125 125 18900 43.0 9400 13.1 2000 4.8
S 150/S 151 150 18900 43.0 9400 16.2 2000 4.8
S 180 180 28700 66.0 11800 18.7 5880 13.5
S 220/SF 220 200 28700 66.0 14350 22.7 5880 13.5
S 271 270 32960 75.0 16430 26.9 5880 13.5
S 341 340 38846 89.0 19423 26.9 5880 13.5
SF 40-2 40 6600 18.5 3300 4.5 1200 2.7
SF 60-2 60 7700 17.0 3800 5.2 1200 2.7
SF 100-2 100 10800 24.0 5400 7.3 1200 2.7
SF 150 150 18900 43.0 9400 16.2 2000 4.8
SF 220 200 28700 66.0 14350 22.7 5880 13.5
Table 1: cooling air requirement, necessary cross sections for openings and ducts.
* For the cooling air requirements the basis is a 7°F temperature difference between room and outside temperature.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.3
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room

Ventilation possibilities

A B

C D

A: Supply and exhaust air openings in the outside walls (free-standing


installation)
B: Supported by exhaust air fan
C: Exhaust air duct into the open
D: Exhaust air duct with recirculation flap
Hot exhaust air is mixed with the cold ambient air, as required, preventing
the plant from freezing up at temperatures below freezing.
E: Using the hot exhaust air for heating
In the winter, the hot exhaust air is used for room heating. In summer it is
directed into the open.

Condensate disposal The air taken in contains water in form of vapour, which turns into condensat
during compression.

WARNING!
The condensate contains oil. Never lead it into the public sewage system
without prior treatment.
Strictly observe the effluent disposal laws of your local authorities.

Page 3.4 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation 3.3 Installation

General BOGE screw compressor units are supplied ready for connection. Only the
work described in the following paragraphs needs to be carried out during
the installation.

CAUTION!
Only have the installation work carried out by appropriately trained persons
or specialists.

Prior to delivery, each compressor is subjected to a trail run at the factory.


It is carefully tested and set. However, possible transport damage cannot be
excluded.
– Please inspect the compressor immediately after delivery and direct dam-
age claims to the last haulier – even when the packing is not damaged!
To safeguard claims against the haulier we recommend leaving the
machine, devices and packing material in the same condition as they
were in when the damage was detected.
– Prior to commissioning, check the compressor for external damage.
– Observe the compressor very closely during commissioning and the
following trial run.
– If malfunctions occur, switch off the compressor immediately and inform
the BOGE-Service.

Checking the delivery The delivery scope depends on your order.


scope Prior to commissioning, please check whether all required parts have been
provided. Please check the order confirmation for any possible accessory
equipment.

The delivery scope includes the following component parts:


– Operating instructions
– Keys
– Electric circuit diagram (in the compartment of the switch cabinet)
– List of electrical equipment (in the compartment of the switch cabinet)

Installing – Remove the packing material on and in the compressor.


the compressor – Install compressor and align horizontally.
The compressor must stand firmly on the ground on all feet.

Connecting the – Connect the compressor to the compressed air network or a compressed
compressor to the air receiver.
compressed air network For this, use a BOGE high pressure hose.

NOTICE!
Do not install a check valve in the pressure line.
The compressor is already equipped with a check valve.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.5
Aufstellung.pm6.5 - USA
Installation 3.3 Installation

Connecting the The pipework for the cooling water circuit in the compressor is completely
cooling water (option) installed at the factory.
Only the following work must be performed during installation:
– Check, whether the water supply has the required data and whether the
cooling water quality is adequate (see page 2.10).
– Connect the cooling water supply and discharge line to the water supply.

The following component parts must be provided by the customer for cooling
water installation:
– Dirt traps
The dirt trap at the cooling water inlet protects the cooling units against
sediment collecting. Pore width: max. 0.6 mm
– Expansion vessel and safety valve

ATTENTION!
If the stop valves in the supply and discharge lines are simultaneously closed
in a closed cooling system, an enclosed room will result. If the water heats
up in this room, it will expand and the pressure will increase.
Install an expansion vessel and a safety valve to prevent damage to the
cooling units.

Removing the transport The frame of the drive unit is bolted to the base frame for transport.
securing bolts Remove the four red marked screws  and  (each two on the longitudinal
side) together with the space collars.

1
2

Fig. 3.1: Removing the transport securing bolts Note:

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

Page 3.6 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation 3.3 Installation

Activating the belt The V-belts are slackened for transport.


tensioning device Activate the GM belt tensioning device prior to commissioning by lowering
the motor plate.
– Secure bolt head  against turning by means of a spanner (NW 27).
– Turn locknut  upwards by turning counterclockwise until it locks against
the bolt head.
The belt tensioning device is activated. It automatically sets the correct V-belt
tension in every operating mode.

Fig. 3.2: Activating the belt tensioning device Note

Checking the oil level BOGE compressors are supplied with a complete oil filling.
Prior to commissioning/start up, check the oil level as described in chapter
"Maintenance".

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.7
Aufstellung.pm6.5 - USA
Installation 3.4 Electrical connection

Electrical connection DANGER: Voltage!


Ensure that work on the electrical equipment of the compressor is only carried
out by authorized electricians.
When connecting to the power supply, observe the valid regulations or the
local safety regulations.
Also observe the regulations of your local power supply company regarding
the load rating of your power supply.

Main switch
The customer is responsible to provide the following safety measures:
Compressor plants having a drive motor larger than 3 kW and current inten-
sities larger than 16 amperes must be equipped with a lockable main switch
and series fuses.
Please refer to the technical data for the design and fuse rating.

Rated voltage
The data of your mains (operating voltage, control voltage, type of current,
frequency, ...) must coincide with the data on the type plate on the switch
cabinet.
In the event of deviations, please contact the BOGE service or your supplier.

Connecting the leads


– Check to ensure that all terminals in the switch cabinet are firmly tightened.
If necessary, retighten the screw connections.
– Guide the lead cable through the PG screw connection.
– Connect the leads L1, L2, L3, N, Pe (PEN) firmly to the power supply
terminal.
A clockwise rotational field must be created.
– Tighten the electrical connections after the first operating hours.

Drive with frequency converter


According to operational conditions electrical drive systems with frequency
converter may have an earth leakage current above 10 mA.
Therefore the required precautions according to EN 60204-1:2006 and
EN 50178:1997 have to be applied as soon as the compressor is electrically
connected.
A permanently installed connection is required.
One or several of the following qualifications for the protective-conductor
system have to be fulfilled:
1. The protective conductor must have a minimum cross section of 10 mm2 Cu
along its total length.
2. If the protective conductor has a minimum cross section of less than
10 mm2 Cu, a second conductor with at least the same cross section has
to be provided up to the point from where the protective conductor has a
minimum cross section of more than 10 mm2.
3. Automatic interruption of the supply if the continuity of the protective con-
ductor is lost.
Please observe any additional national rules and regulations.

Page 3.8 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation 3.4 Electrical connection

DANGER: Risk of injury!


Prior to any work on the compressor:
– Switch off the main switch and secure against unintentional switching-on.
– Check to ensure that all machine parts are voltage free.
– Depressurize all areas under pressure.

Never omit a single safety step! Otherwise, you will risk injuries due to
restarting, electric shock or self-releasing parts.

DANGER!
When the automatic restart (Auto-Restart) is activated, the compressor will
automatically restart following a power failure.
Prerequisite: The net pressure is lower than the switch-on pressure.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.9
Aufstellung.pm6.5 - USA
Installation 3.5 Commissioning

Checking the rotational CAUTION!


direction Always check the rotational direction of the drive motor prior to commission-
ing/initial start up.
Even brief operation in the wrong direction of rotation (more than approx.
5 seconds) may cause total destruction of the air end!

Ensure that the rotational direction coincides with the rotational direction
arrow on the air end.

– Switch on the main switch.


– Switch the compressor on and immediately off again to check the rota-
tional direction.

Changing the rotational direction:

DANGER: Risk of injury!


Switch off the main switch and secure against unintentional switching-on.
– Interchange two phases (L1, L2 or L3) in the power cable.

Opening the stop valves Open ball valve on the compressor outlet.

Checking for leaks Undertake the following to prevent leaks:


– Check screw connection of the lines and retighten, if necessary.
– Check to ensure that the oil filter and oil separator are hand tight seated.

Conduct trail run Switch on the main switch.


– Switch on the compressor using the ON key. The compressor starts.
– The compressor switches off automatically once the switch-off pressure,
factory set on the operating pressure switch, has been reached.
– Check the supply pressure on the supply pressure gauge.
If necessary, reset operating pressure switch.
– The compressor is ready for operation.

Page 3.10 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation 3.5 Commissioning

Commissioning If an extended stoppage is scheduled, you should contact BOGE-Service


following extended beforehand.
stoppages Following an extended stoppage of more than 2 months, fill a small amount
of oil in the suction controller prior to starting the compressor.

CAUTION!
Only fill the suction controller with the grade of oil used to operate the com-
pressor.
Never mix different oil grades and brands.

DANGER: Risk of injury!


Switch off main switch and secure against unintentional switching-on.
– Unscrew the plug on the suction controller .
– The following quantities of compressor oil have to be filled into the intake
regulator:
approx. 0.13 gallon for models S 31-2 – S 60-2
approx. 0.65 gallon for models S 61-2 – S 100-2
approx. 1.30 gallon for models S 101 – S 150
approx. 2.10 gallon for models S 151 – S 220 / SF 220
approx. 2.65 gallon for models S 271 – S 341
approx. 0.13 gallon for models SF 40-2 – SF 60-2
approx. 0.65 gallon for models SF 100-2
approx. 1.30 gallon for models SF 150
– Reclose the controller using the plug.
– Turn the air end by hand 5 to 10 times to distribute the oil evenly.

Fig. 3.3: Suction controller

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 3.11
Aufstellung.pm6.5 - USA
Installation

Page 3.12 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Faults 4.1 General

General The tables on the following pages give information on the possible causes
of operating faults and measures for their rectification (please also refer to
operating instructions of the compressor control).

ATTENTION!
Ensure that any work required to rectify faults is only carried out by trained
personnel or specialists.
Ensure that components which have a safety function are only set, repaired
or exchanged by BOGE Service!

Please contact BOGE-Service at the following telephone number, if you have


any questions.
 770 - 874 -1570

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 4.1
Stoerung.pm6.5 - USA
Faults 4.2 General faults

Fault Possible cause Rectification


No quantity delivered, System components in the Check oil and compressed air lines inside the com-
no pressure build-up, compressor are leaking pressor; tighten and/or reseal screw connections,
max. pressure 0.5 bar if necessary
Minimum pressure valve is Close ball valve and check whether pressure builds
defective up; if so, open ball valve again immediately; replace
minimum pressure valve
Electromagnetic venting Check solenoid valve and replace, if necessary
valve does not close
Suction controller does not Suction controller or solenoid valve is defective;
open check and replace, if necessary
V-belts are torn Fit new V-belts

Compressor No electric power to com- Check electrical connection


does not start up pressor
Fuses are defective Check the mains and control fuses, replace if
necessary
Machine has not vented Check venting valve and replace, if necessary
perfectly
Voltage fluctuations in the Ensure constant voltage in accordance with IEC 38
electrical mains power
Compressor oil is very Heat up the compressor
viscous due to low ambient (additional heater available as as option)
temperature

Oil in suction filter Minimum pressure non- Check the minimum pressure check valve and
return valve is leaking replace, if necessary
Suction controller is leaking Check the suction controller and replace,
if necessary
Cut-out performed by Cut-out normally via O key
emergency-off switch

Excessive oil Drain line is blocked Dismantle and clean drain line
consumption Defective oil separator Check oil separator and replace, if necessary
element
Excessive oil filling Drain off oil

Safety valve blows Operating pressure switch Set operating pressure to the maximum
has been misadjusted permissible pressure of the screw compressor
Defective safety valve Replace safety valve

System pressure Venting valve does not open Check venting valve and replace, if necessary
does not decrease
when switch- Check valve is leaking Check the check valve and replace, if necessary
ing off

Page 4.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Stoerung.pm6.5 - USA
Maintenance 5.1 Safety instructions

DANGER!
Ensure that maintenance work is only carried out by specialists or appro-
priately trained person.
– Prior to starting any maintenance work, always stop the compressor as
described in these operating instructions prior to removing any cladding
or safety devices. Refit the cladding or safety devices immediately upon
completion of the maintenance work.
– Only use original spare parts, compressor oils and operating materials
released by BOGE for the maintenance work.
– When the automatic restart (Auto-Restart) is activated, the compressor
restart automatically following a voltage loss.
Prerequisite: The net pressure is lower than the switch-on pressure.

Safety precautions

DANGER: Risk of injury!


Always adhere to the specified operating method described below for all
maintenance work. Never omit a single safety step!
Otherwise you will risk injury from restarting, electric shock or parts which
may fly off.

Prior to all maintenance work:


1. Switch off the compressor using the OFF button.
2. Switch off the main switch and secure it against unintentional switch-
on.
3. Check to ensure that all machine elements are definitely isolated.
4. Separate the compressor from the compressed air network by closing
the ball valve at the compressed air outlet.
5. Vent the compressor.
To this effect open the safety valve on the combined compressed air-
oil receiver as follows:
– Turn the knurled nut counterclockwise until you can feel a resilient
resistance.
– Tun the knurled nut a little further.
Any possibly existing air will escape.
The system pressure gauge will indicate a pressure of 0 bar.
– Once the residual air has completely escaped from the system,
firmly retighten the knurled nut.
6. Remove all safety cladding necessary to perform the maintenance
work.

Once the maintenance work has been concluded:


7. Reattach all removed safety cladding.
8. Open the ball valve at the compressed air outlet.
9. Prior to switching on again, check whether anyone else is working on
the compressor!

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.1
Wartung.pm6.5 - USA
Maintenance 5.2 General

Maintenance through Have BOGE service check your compressor every 3000 operating hours or
BOGE service annually.

NOTICE:
Maintenance agreement
Enter into a maintenance agreement with BOGE.
BOGE service will carry out the proper maintenance on your compres-
sor at regular intervals.This guarantees maximum safety and realiability
of your compressed air supply.

Review of regular maintenance work

Check intake filter


with S 100-2 on the back sid
of the compressors
Check / set – Clean filter and cartridge Change Clean compressed air /
pressure switch – Change filter cartridge oil filter oil cooler externally

Top up oil in the suction


controller after an
extended down time

Change oil separator

Change supply air filter – Check oil level


(option) – Top up oil

Change oil
(Lubricate Check
motor bearings) V-belts (S 60-2 air-cooled)

Fig. 5.1: Review of regular maintenance work Note:

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

Page 5.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.2 General

Maintenance intervals The maintenance intervals specified in the table are based on average oper-
ating and ambient conditions.
Extreme conditions may require shorter maintenance intervals.
NOTICE: Note down any maintenance work in the table on the last page.
This will facilitate trouble shooting for BOGE service.

CAUTION! Oil change


Please change oil and replace oil filter and nozzle with dirt catch after the
first 500 operating hours!

Maintenance work Maintenance intervals in operating hours 1) Page


weekly / 1000 1500 3000 8000
monthly annually annually annually annually
General maintenance work
Check final compression temperature
w Control
(set point value: 160 – 212° F)
Check compressor for leaks X –
Check system relief on system pressure gauge
w Control
(set point value 0 – 21 psig)
Check function of EMERGENCY STOP button m Control
Check and if necessary change supply air filter (option) w 5.7
Clean oil cooler X 5.18
Check if electr. connections are firmly tightened X –
Air circuit
Check and if necessary change intake filter m 5.6
Change intake filter cartridge X 5.6
Replace suction controller (wearing parts set) X –
Check / reset operating pressure X Control
Replace minimum pressure valve (wearing parts set) X –
Replace solenoid valve X –
Check safety valve X 5.20
Oil circuit
Check oil level and top up as required 2) X 5.11
Replace oil regulator (wearing parts set) X –
Replace nozzle with dirt catch X –
Change oil separator 2) X 5.14
Change oil filter 2) X 5.13
Change oil 2) X 5.16
Drive
Check / change V-belt X X 5.10
Lubricate drive motor bearings for details please see nameplate or enclosed operating instructions
for drive motor from 45 kW and up
Replace grease in motor bearings Depending on mains frequency: 50 Hz 10.000 operating hours
60 Hz 8.000 operating hours
1)
If the compressor is not often used, undertake the maintenance according to the specified intervals (weekly/monthly/annually) depending
on the number of operating hours.
2)
The specified intervals only apply when BOGE compressor oil Syprem 8000 S is used! The service life may differ depending on the
ambient temperature. In this case have the oil analyzed by your BOGE service!

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.3
Wartung.pm6.5 - USA
Maintenance 5.2 General

General information
DANGER: Risk of injury!
concerning the Oil presents a potential danger to health and environment due to their
lubricants used additives.
– Avoid contact with skin and eyes.
Wear protective gloves made of resistant synthetic material.
Wash yourself thoroughly after contact with oils.
– Do not inhale the fumes or mist.
– Protect your environment.
Ensure that no oil is spilt.
– Fire, naked flames and smoking is stricltly prohibited when handling
oil.

We recommend using only oil according to following specification:


– Viscosity range of 55 mm2/s at 40°C.
– Minimum viscosity at 100°C of 8 mm2/s.
– Maximum viscosity at 0°C of 1.000 mm²/s.
– Failure load stage 10, FZG-Test, DIN 51 354-02/ ISO DIS 14 635-1.
– Test Method A/8,3/90 10.
– Excellent oxidation stability: Meets requirements of Pneurop oxidation test.
– Antifoam – additives.
– Additives to prevent residue formation.
– Compatibility with all materials which are resistant to mineral hydrocar-
bons, e.g. Neoprene, NBR, FPM, PTFE, acrylic and epoxy resin pains,
nylon (polyamide) and PVC.
– Flash point (DIN ISO 2592) > 230°C.
– Excellent demulsifying properties.
– Additives for corrosion protection of metallic surfaces.
– Excellent oxidation stability: Rotating bomb oxidation Test (ASTM D 2272)
higher than 2,400 minutes.
– Meets VDL requirements DIN 51 506 (including Pneurop test).
– Or you use BOGE compressor oil Syprem 8000 S.
The stated maintenance intervals refer to the use of Syprem 8000 S only.
– Syprem 8000 S can be purchased from BOGE retailers.
– Never mix different oil types and brands. The additives may be incompat-
ible. It may lead to foam formation, premature aging or loss of lubricating
ability.

Page 5.4 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.2 General

Disposal of WARNING!
used The handling and disposal of mineral oils is subject to legal regulations.
operating It is an offense not to ensure correct and safe disposal of old oil!
material Please instruct one of the known service companies to dispose of used
operating materials or deliver them to an authorized disposal point.

Observe the following points when disposing of old oil:


– Never mix the oil with other material or liquids.
– Used oil filters and oil separator cartridges require special waste treat-
ment and must be kept separate from normal waste!

Spare and wearing parts CAUTION!


Only use original spare parts, compressor oils and operating materials
released by BOGE for repair and maintenance work.
BOGE is not liable for any damage resulting from the use of other spare
parts or operating materials.

ATTENTION!
If the nozzle with dirt catch is soiled the oil consumption may increase sig-
nificantly!

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.5
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Clean or change Cleaning: – 1x monthly,


intake filter however, at least every 500 operating hours.
– Correspondingly earlier if the air taken in is heavily soiled.
Change: – In the event of damage.
– After the second cleaning.

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.

Removing the filter cartridge


– Remove cladding on the maintenance side.
– Remove lid  of the filter housing.
– Loosen nut  and remove filter cartridge .

Cleaning the CAUTION! Do not clean filter cartridges in liquids.


filter cartridge Do not use any hard objects when cleaning to avoid damaging the filter
paper.
Refit a new filter cartridge in the event of damage or once it has been
cleaned twice.
– Hit on the filter cartridge using the palm of your hand to knock out coarse
dust.
– Blow out fine dust from the inside to the outside using dry compressed
air (maximum pressure 70 psig).
– Clean the sealing surface of the filter cartridge.

Fitting a filter cartridge


– Insert filter cartridge into the filter housing.
– Tighten nut.
– Attach lid of the filter housing.
– Attach cladding on the maintenance side.

Note: Demonstration example. Com-


pressor may only be operated
with the switch cabinet closed Fig. 5.2: Changing the intake filter Note:
and all panels fitted.

Page 5.6 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Changing the supply Check: – 1x weekly,


air filter mats (option) however, at least every 500 operating hours.
– Correspondingly earlier if the air taken in is heavily soiled.
Change: – When a crust of dirt has accumulated on the filter mat.
– When the final compression temperature has exceeded
its set point value by 7 to 9°F. The crust of dirt on the filter
mat prevents an adequate cooling air supply.

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.

CAUTION!
– Pull filter mat  out of its holder from above.
– Insert new filter mat into the holder.

Fig. 5.3: Changing the supply


air filter Note:

Lubricating the drive As a rule, the bearings of the drive motors are provided with a maintenance
motor bearings free permanent lubrication. The drive motor of some series are equipped
with a post-lubricating unit. These motors can be easily recognised by the
two grease nipples on the upper side of the housing. In addition, plates
on the compressor indicate the type of motor lubrication.

Drive motors with Under normal operating conditions (coolant temperature max. 105°F,
permanent lubrication continous operation) the bearings are maintenance free for the service life.

Bearing service life: Mains frequency Operating hours


60 8,000

The service life decreases or increases as thermal stress increases or


decreases (due to increased or reduced coolant temperature).

NOTICE: ATTENTION!
Have BOGE service dismantle the bearings and install new bearings once the
specified service life has expired!

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.7
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Drive motors with Motors with lubrication devices are easily recognised by the two grease nip-
lubrication device ples on the top of the cover. Please check which motor is installed in your
compressor and service it according to the respective instructions.
Lubricate the bearings of the drive motor at the prescribed intervals so as
not to sustain damage due to lack of lubricant.
The motors with lubrication device can be recognised by the two grease nip-
ples on the top of the cover. Adhesive plates on the compressor also indicate
the motor lubrication. On motors with lubrication devices, regular greasing
belongs to the scope of maintenance.
The lubrication intervals, quantity and type of grease are given on the
type plate or a separate plate. For lubrication, the required quantity is
pressed through the nipple into the bearing with a grease gun while
the compressor is running.

DANGER: Risk of injury!


Always exercise great caution when lubricating the bearings with the com-
pressor running and observe all safety precautions! Never put your hand in
the area of the V-belt and the fan wheel. Fitted safety devices and cladding
may not be removed.

CAUTION!
Always use the same type of grease for lubrication.The lubricating ability can
be sharply reduced if different types of greases are mixed.
If you intend to use a different type of grease:
– have the bearings removed and thoroughly cleaned prior to filling with
new grease.
Please always observe the specified lubrication intervals and quantities of
grease.
Even over-greasing and an excess of lubricant can the bearings to be de-
stroyed.

Lubricating nipple

Fig. 5.4: Grease nipples of the lubricating device on the cabinet corner post
for external greasing

Page 5.8 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Servicing drive motor The drive motors have an automatic lubricating device (see figure).
There is a lubricating nipple on the A bearing and B bearing side of the motor.
The lubricating nipple is connected with the automatic lubricating device via
a tube.
The tubes are already filled with grease. When the tubes are replaced, they
must be filled with grease.
The type of grease is indicated on the lubrication unit of the compressor
(see Fig. 5.5 below).

Voltage is supplied from the switch cabinet.

Both LC units (LC = lubrication canister) are designed for 1 year in three-
shift operation. After one year, the canisters must be replaced because
of lubricant ageing, no matter how much lubricant they have.

So as to comply with the necessary lubricating deadlines, the coding switches


"VOL" and "TIME" of the drives are preset in the factory according to table
7.2 of the Operating Instructions for CONTROL TIME.

Set values:
– LC unit S250 for A bearing: 2.89 cm³/ per 100 operating hours

For information regarding operating and maintenance to CONTROL TIME,


please read enclosed operating instructions.

Fig. 5.5: Automatic lubricating device CONTROL TIME

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.9
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Changing the V-belt Check: – 1x per year for damage.


Change: – At visible damage.

The BOGE GM drive system automatically adjusts the V-belt to the correct
V-belt tension in any operating mode.
Maintenance of the V-belt drive is limited to the above mentioned work.

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.

Slacken the V-belts:


– Remove cladding on the maintenance side as well as the belt protection.
– Secure screw head  of the tensioning device with NW 27 spanner to
prevent it from turning.
– Turn locknut  clockwise. Raise the motor in arrow direction  until the
V-belts are fully slackened.

Change the V-belts:


– Remove the slackened belts from the belt pulleys.
– Fit new V-belts on the belt pulleys on the motor and compressor.

CAUTION!
The new V-belts must be of precisely the same length.
Only change the V-belts as a complete set!

Tensioning the V-belts:


– Lower the motor again. For this purpose, secure screw head  against
turning, then turn locknut  counterclockwise and lock by means of the
screw head. The V-belts are automatically correctly tensioned by the
BOGE GM drive system.
– Fit belt protection.
– Reattach cladding on the maintenance side.

Fig. 5.6: The BOGE GM


drive system
Note:
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

Page 5.10 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Setting GM – Model Pressure Setting


Belt tensioning device + 0 / – 0.04
S 40-2 – S 341 psig inch
SF 40-2 – SF 220 S 40-2 / SF 40-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
S 50-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
blue
S 60-2 / SF 60-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
S 61-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
S 75-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
Setting inch

S 100-2 / SF 100-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
S 101 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4
S 125 100 / 115 / 125 / 150 / 190 3.6 / 3.8 / 3.8 / 3.7 / 3.9
S 150 / SF 150 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.0
sealed
S 151 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.0
S 180 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.5
S 220 / SF 220 100 / 115 / 125 / 150 / 190 3.5 / 3.3 / 3.3 / 3.4 / 3.5
S 271 100 / 115 / 125 / 150 / 190 4.0 / 4.0 / 3.8 / 3.8 / 4.8
S 341 100 / 115 / 125 / 150 / 190 3.5 / 3.5 / 3.2 / 3.2 / 4.6

The settings shown in the table are fixed by the manufacturer and may not
be changed. Slight deviations are allowed and compensated by the GM
drive system.
The current settings are also shown on the GM drive system. With special
versions the settings on the sticker may deviate from the standard values.
If the spring is not pre-tensioned at the set measure, the measure must be
reduced until the spring is slightly pretensioned (to prevent the spring clap-
ping).

Checking the oil level, Check: – Prior to commissioning/start-up of the compressor.


topping up oil – Then every 1000 operating hours,
however at least once a year.
Topping up: – When the oil level has dropped below the "min" mark
(see sketch).

CAUTION!
Always use the same oil type when topping up.
Never mix different oil types and brands.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.11
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Close ball valve at the compressed air outlet.
– Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
– Wait approx. 3 minutes to permit the oil to settle.
– Remove cladding on the maintenance side.

DANGER: Risk of injury!


Danger of burning due to hot oil!
– Remove plug  of oil filling socket .
– Check oil level.
The oil level must not drop below the "min" mark (see sketch).
– If necessary, top up with oil to the lower edge of the thread ("max." mark)
on the oil filling socket.
– Screw plug with viton seal  back in.
– Reattach clading on the maintenance side.
– Open ball valve at the compressed air outlet.

Fig. 5.7: Checking the oil level, topping up with oil Note:

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

Page 5.12 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Changing the oil filter Change: – After 3000 operating hours,


however, no later than after one year.
– With each oil change!

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Close ball valve at the compressed air outlet.
– Take off safety warm air hood and open safety sound insulation hood.
– Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
– Wait approx. 3 minutes to permit the oil to settle.
– Remove cladding on the maintenance side.

DANGER: Risk of injury!


Danger of burning due to hot oil!
– Unscrew soiled oil filter  by hand or use a strap wrench, turning counter-
clockwise.
Catch the draining oil and dispose of properly according to environmental
regulations.
– Fill the new oil filter with compressor oil.
– Lightly oil the sealing ring of the new oil filter.
– Screw in new oil filter  by hand, turning clockwise.
– Close safety sound insulation hood.

CAUTION!
Do not use tools to screw in the new oil filter!
You might damage the oil filter or its sealing ring.
A hand tight seating of the oil filter is sufficient.
– Close safety sound insulation hood and reattach cladding on the mainte-
nance side.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by hand,
if necessary (Procedure as described above).

DANGER: Risk of injury!


Switch off the main switch and secure against unintentional switch-on.
– Check the oil filter for leaks and tighten by hand, if necessary.
– Check oil level.
Top up oil losses, if any.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.13
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Fig. 5.8: Changing the oil filter Note:

Changing Change: – When the difference between supply and system pressure
the oil separator exceeds 12 psig.
– When warning message "8" appears on the control system
display (if option is installed).
– After 3000 operating hours,
however, no later than after one year.

NOTICE:
If the specified maintenance intervals are not observed, the oil separa-
tors might become blocked. In this case, the differential pressure will
increase until the safety valve blows.

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Close ball valve at the compressed air outlet.
– Open safety sound insulation hood.
– Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
– Wait approx. 3 minutes to permit the oil to settle.

Note: Demonstration example. Com-


pressor may only be operated
with the switch cabinet closed
and all panels fitted.

Page 5.14 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

DANGER: Risk of injury!


Danger of burning due to hot oil!
– Remove cladding on the maintenance side.
– Unscrew soiled oil separators  by hand or use a strap wrench, turning
counterclockwise.
– Catch the draining oil and dispose of properly according to environmental
regulations.
– Lightly oil the sealing rings of the new oil separator.
– Screw in new oil separators  by hand, turning clockwise.

CAUTION!
Do not use tools to screw in the new oil separators!
You might damage the oil separators or their sealing rings.
A hand tight seating of the oil separators is sufficient.
– Close safety sound insulation hood.
– Reattach cladding on the maintenance side.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Check the oil filter for leaks once again (Procedure as described above).

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Check the oil separators for leaks and tighten by hand, if necessary.

Fig. 5.9: Changing the oil separators Note:

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.15
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Oil change Change: – After 9000 operating hours,


however, at the latest after two years.
– For other types of oil the appropriate oil change intervals
must be complied with.

NOTICE:
The service life of the oil, the oil filter and oil separators is reduced under the
following conditions:
– When the compressor is operated at extreme ambient temperatures.
– When the intake air is extremely soiled.

Building up a pressure cushion


The combined compressed air / oil receiver is located at the lowest point of
the system. Therefore, a light pressure cushion (approx. 30 psig system
pressure) must be applied to drain the oil. This pressure cushion forces the
oil through the drain hose into a suitable collecting basin.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Screw cap nut  onto the vent hole of the solenoid valve on the suction
controller by hand.
The cap nut (M8) is located in the storage compartment of the switch
cabinet.

CAUTION!
Never use any tools to screw on the cap nut!
Damage af the solenoid valve might result.
– Switch on the compressor again and allow it to start up.
If necessary, let out some air from the compressed air receiver until the
switch-on pressure of the compressor is reached.
– Switch off the compressor at approx. 30 – 44 psig system pressure using
the EMERGENCY-OFF-button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Slowly loosen cap nut  until compressed air escapes.
– Let off compressed air until the system pressure gauge shows a residual
pressure of approx. 30 psig.
– Tighten cap nut  by hand.

DANGER: Risk of injury!


Danger of burning due to hot oil!

Draining old oil


– Place the oil drain hose into a suitable container .
– Slowly open the stop valve.
The pressure cushion forces the oil into the container.
– Once the compressed air/oil receiver has been completely drained, close
the stop valve.
– Remove the cap nut from the solenoid valve.

Page 5.16 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

– Remove oil filler screw  on the compressed air/oil cooler and drain the
residual oil (max. 5 litres) into a suitable container.
– Reinsert the oil filler screw together with a new copper sealing ring.
– Change oil filter (Procedure as described above).
– Change oil separators (Procedure as described above).

Filling with new oil:


– Fill up to the edge of the thread of the filling socket (max.).
(Procedure as described above).

CAUTION!
After each oil change you have to fill a small quantity of oil into the suction
controller before starting the compressor.
For oil quantity and procedure see chapter "Commissioning following extended
stoppages".

CAUTION!
Always fill with the same oil type as previously used.
Never mix different oil types and brands.
The oil circuit must be flushed prior to changing the oil type.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Reattach cladding on the maintenance side.
– Conduct trial run.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Check the oil filters and oil separators for leaks and tighten by hand,
if necessary (procedure as described above).
– Check oil level (procedure as described above).
Top up oil losses, if any.

7
5

6
Fig. 5.10: Solenoid valve Note: Fig. 5.11: Note: Fig. 5.12: Note:
on the intake controller with Drain off old oil from Drain off residual oil from
the cap nut screwed on air/oil separator vessel oil cooler

Note: Demonstration example. Compressor may only be operated with the switch cabinet closed and all panels fitted.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.17
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Flushing the oil circuit Flushing the oil circuit with clean oil becomes necessary:
– When the oil is excessively soiled.
– Prior to changing the oil type.

CAUTION!
Detailed information as to the flushing with BOGE oils you can obtain from
the following service number.
 770 - 874 -1570

Cleaning the Cleaning: – After 1500 operating hours,


compressed air / oil however, at the latest after one year.
cooling unit
The service life of the compressed air/oil cooling unit depends on the
(air cooling) degree of soiling (dust, oil vapour) of the suctioned cooling air. Extreme
external soiling of the cooling unit leads to an increased temperature
in the oil circuit.

– Switch off the compressor using the OFF button.

DANGER: Risk of injury!


Switch off the main switch and secure it against unintentional switch-on.
– Remove cladding on the maintenance side.
– Unscrew the maintenance flap on the air guidance box.
– Remove accumulated soiling with a fibre brush.

CAUTION!
Do not use any sharp objects for cleaning!
These could damage the cooling unit!
– Blow down the dirt with compressed air  in the opposite direction to the
normal cooling air flow. Clean out the dirt using an industrial vacuum
cleaner  (see Fig.).

If the cooling unit is excessively soiled (cleaning is no longer possible with


compressed air), have it disassembled and cleaned by BOGE service.

Page 5.18 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

2
For water-cooled versions
a cleaning is not necessary

Fig. 5.13: Cleaning the compressed air/oil cooling unit Note:

Proportional controller Check: – After approx. 3000 operating hours,


(option for S-series) however, at least once a year.

1. Setting the operating pressure sensor


Switch-on pressure: Pmin = Final compression pressure – 14 psig.
Switch-off pressure: Pmax = Final compression pressure.

2. Setting the proportional controller


1 Displace the control range of the proportional controller by turning cap .
– Increase pressure level:
Turn cap  clockwise.
– Reduce pressure level:
Turn cap  counterclockwise.

Always set the proportional controller higher than the bottom operat-
ing pressure value (Pmin)!

3. Pressure switch for infinitely variable capacity control


The low pressure switch for the infinitely variable capacity control limits the
reduction of the delivered quantity and switches the compressor in the event
of less than 50 % delivered quantity into idling operation or off.

Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.19
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work

Checking DANGER: Risk of injury!


the safety valve Because a hot air-oil mixture will escape when checking the safety valve
with running compressor only trained personnel or specialists should carry
out this work!

Check: – After approx. 3000 operating hours,


however, at least once a year.

Check safety valve by opening the screw plug .

DANGER: Risk of injury!


Danger of burning due to hot oil!
Take extreme care when checking the safety valve with the compressor
running taking all safety measures into consideration. Wear eye protection.
A hot air-oil mixture escapes when opening!
– Open the threaded plug  counterclockwise.
The compressed air escapes.
– Tighten the threaded plug by turning clockwise.

Fig. 5.14: check safety valve

Page 5.20 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance 5.4 Spare parts and optional equipment

List of spare and Designation


wearing parts
(for maintenance) Filter mat for supply air filter
Compressor oil Syprem 8000 S
Set of V-belts
Lubrication for drive motor bearings
Maintenance kit consisting of:
oil filter, oil separator, suction filter cartridge, gaskets, nozzle with dirt catch
Wearing part kit consisting of:
oil regulator, intake regulator, minimum pressure valve
Solenoid valve

NOTICE:
When ordering, please specify the data on the type plate:
– Type
– Year of manufacture
– Machine number

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 5.21
Wartung.pm6.5 - USA
Maintenance

Page 5.22 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Wartung.pm6.5 - USA
Appendix 6.1 Flow chart

Air cooled version, standard

Air IN

Compressed air
OUT

1 = Suction filter 23 = Pressure sensor system pressure


2 = Maintenance display (from 30 kW) 24 = Pressure sensor network pressure
3 = Vacuum switch 25 = Stop valve, compressed air outlet
(for suction filter monitoring) * 27 = Stop valve, oil drainage
4 = Suction controller 28 = Check valve drainage line (up to 75 kW)
5 = Ventilation and regulation control valve 29 = Proportional controller *
7 = Drive motor 30 = Diff. pressure switch for prop. controller *
8 = Compressor air end 31 = 3/2-way solenoid valve for prop. contr. *
9 = Sensor for final compression temperature (with standard control passage here)
10 = Combined compressed air/oil receiver 37 = Display of F.a.d. for prop. controller *
11 = Oil separator 42 = 3/2-way solenoid valve for suction control
12 = Safety valve regulation *
16 = Thermostatic oil control valve 43 = Double check valve*
17 = Oil cooler (Pos. 42 + 43 = rapid-start valve)
18 = Oil filter 44 = Double check valve *
19 = Differential pressure switch (Monitoring of rotational direction)
(for oil filter monitoring) *
20 = Oil throttle
21 = Minimum pressure check valve
22 = Compressed air after-cooler * = Option

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 6.1
Fliess.pm6.5 - USA
Appendix 6.1 Flow chart

Water cooled version, serial connection – parallel connection

Air IN

Water OUT Water OUT

Water IN Compressed Water IN Compressed


air OUT air OUT

* Parallel connection Serial connection

1 = Suction filter 27 = Stop valve, oil drainage


2 = Maintenance display (from 30 kW) 28 = Check valve drainage line (up to 75 kW)
3 = Vacuum switch 29 = Proportional controller*
(for suction filter monitoring) * 30 = Diff. pressure switch for prop. controller *
4 = Suction controller 31 = 3/2-way solenoid valve for prop. contr. *
5 = Air relief and regulation control valve (with standard control passage here)
7 = Drive motor 32 = 2/2-way solenoid valve
8 = Compressor air end 33 = Control valve water supply (preadjusted)
9 = Sensor for final compression temperature 34 = Control valve water supply (preadjusted)
10 = Combined compressed air/oil receiver 37 = Display of F.a.d. for prop. controller *
11 = Oil separator 42 = 3/2-way solenoid valve for suction control
12 = Safety valve regulation *
16 = Thermostatic oil control valve 43 = Double check valve*
17 = Oil cooler (Pos. 42 + 43 = rapid-start valve)
18 = Oil filter 44 = Double check valve *
19 = Differential pressure switch (Monitoring of rotational direction)
(for oil filter monitoring) *
20 = Oil throttle To be provided by customer:
21 = Minimum pressure check valve 35 = Dirt trap
22 = Compressed air after-cooler 36 = Stop valve
23 = Pressure sensor system pressure
24 = Pressure sensor network pressure
25 = Stop valve, compressed air outlet * = Option

Page 6.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Fliess.pm6.5 - USA
Appendix 6.1 Flow chart

Air cooled version, frequency-controlled

Air IN

Compressed
air OUT

1 = Suction filter 17 = Oil cooler


2 = Maintenance display 18 = Oil filter
3 = Vacuum switch (for suction filter monitoring) * 19 = Differential pressure switch
4 = Suction controller (for oil filter monitoring) *
5 = Air relief and regulation control valve 20 = Oil throttle
6 = Pressure switch (for rotational direction, 21 = Minimum pressure check valve
system relief and V-belt monitoring) 22 = Compressed air after-cooler
7 = Drive motor 23 = Operating pressure switch
8 = Air end 24 = Pressure gauge (line pressue)
9 = Final compression temperature display and switch 24.1= Pressure gauge (system pressure)
10 = Combined compressed air/oil receiver 25 = Stop valve, compressed air outlet
11 = Oil separator 27 = Stop valve, oil drainage
12 = Safety valve 27.1= Stop valve, oil drainage
13 = Differential pressure switch (oil cooler, 75 – 250 kW)
(for oil separator monitoring) * 28 = Check valve drainage line
14 = System pressure switch (to 75 kW)
(for system pressure build-up and monitoring) *
15 = Safety pressure switch (for pressure limitation) *
16 = Thermostatic oil control valve * = Option

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors Page 6.3
Fliess.pm6.5 - USA
Please note the completed maintenance work in the respective columns

Page 6.4
Date Operating Line System Tempera- Intake Oil- Oil- Oil Cooling Motor Remarks
hours pressure pressure ture filter filter level separator unit mainte-
Appendix

* ** cleaning nance
6.2
List of maintenance and service work

* Cl = Cleaning ** C = Check

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Fliess.pm6.5 - USA
Ch = Change Ch = Change
Please note the completed maintenance work in the respective columns

Date Operating Line System Tempera- Intake Oil- Oil- Oil Cooling Motor Remarks

Fliess.pm6.5 - USA
hours pressure pressure ture filter filter level separator unit mainte-
Appendix

* ** cleaning nance
6.2

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
List of maintenance and service work

* Cl = Cleaning ** C = Check

Page 6.5
Ch = Change Ch = Change
Please note the completed maintenance work in the respective columns

Page 6.6
Date Operating Line System Tempera- Intake Oil- Oil- Oil Cooling Motor Remarks
hours pressure pressure ture filter filter level separator unit mainte-
Appendix

* ** cleaning nance
6.2
List of maintenance and service work

* Cl = Cleaning ** C = Check

BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Fliess.pm6.5 - USA
Ch = Change Ch = Change

You might also like