temperatures determined in the sections were obtained by the
seudy of Chen etal
‘Through the thermal analysis, final temperatures of the
struetural members were acquired under the inluence of fire,
and material properties of the stel were determined according
to these temperature values. In the structural analysis, physical
behavior of the loaded joint was investigated using modified
material properties. Thus, the fire effect was reflected on the
joint and the members through the alteration of mechanical
characteristics.
2.2. Material Properties. 2.2.1. Thermal Properties of
‘Steel. Type of the steel material is $355 for this study with
yield steength of 355 MPa and tensile strength of 500 MPa.
Furocode 3 Part 12. was used to determine the thermal
conductivity, specific heat, and density of structural steel.”
‘The structural steel ulized in the model has a density of 7850
igim’.
‘2.22. Thermal Properties of Intumescent Coating. The
indluence of density and specific heat on the protected steel
temperature in the validation investigation is minimal because
the thickness isso modest. As a result, the constant values from
Annex E of EN 13381-8:2013 were used. The specific heat
‘value is 1000 J/(kgK), while the density value is 100 kg/m’.
‘The viscosity of the fire-retardant coating is taken as 11000
mPas at 25.°C. However, the effective thermal conductivity
has been obtained by Wang et al.” based on their fre test,
and the furnace temperature followed the 150-834. Fire has
‘been applied to the protected surfaces in their model, which is
also applicable in the mentioned study. Cipici et al?
proposed that if the fire condition is less severe than the
Standard fre condition, the effective thermal conductivity of
the coating retrieved from the Standaed fire test can be utilized
to estimate steel temperatures for ather heating circumstances.
In the model the convective heat transfer coeficient is set to
25 W/(m?K), and the emissivity ofthe coating for radiation is
taken as 0.92." The intumescent coating expansion mecha-
nism that leads to the ultimate char has not been studied in
this study
3. RESULTS AND DISCUSSION
3.1. Comparison of Steel Temperatures (Eurocode-
ANSYS Results). To demonstrate the numerical method's
confidence, a validation study comparing Eurocode solution
and ANSYS results of structural members’ steel temperatures
in terms of beam, upright, and connector was conducted. The
beam temperature was determined using dey film thicknesses
(DFT) of 0.5 mm, 10 mm, and 1.4 mm for the intumescent
coating. For all coating thicknesses, a very satisfactory
agreement war found, as illustrated in Pigure 1. The resulte
‘of LO mm DFT thickness difer from those of 14 mm DFT.
thickness by a litle margin, As a result, the 0.6 mm and 1.0
mm have been chosen for confirming upright and connection
temperatures. Figures 2 and 5 show the results of the upright
and connection comparisons, respectively. As can be seen, the
‘numerical model's validity is confirmed by the close findings.
3.2. Mechanical Properties of Steel at Elevated
‘Temperature, Beam, column, and connectors are manufac:
tured from cold-formed steel. Mechanical properties of these
materials were determined by tensile coupon tests according to
[ASTM ES standards." The tensile test was carried out on a
tensile testing machine with a capacity of 250 KN at a tensile
speed of 25 mm/min. Dimensional properties of the tensile
coupon test and mechanical properties are given in Figuce 4
hitp//pubsaesorgjournalacsodt
“Temperature )
Tine)
Figure 1. Comparison of beatn temperatures with va
Jntumescent coating thickness.
“Temperature 1)
8
= = recta son (0FT=06 rn)
‘Soense couton(Oe7=1 9m
‘mere son BFF)
Tine )
Figure 2. Compaticon of upright temperatures with various
intumescent coating thicknes.
Temperate)
Time (6)
FFigore 3. Comparison. of connector temperatures with various
Jntumescent coating thickness.
and Table 1, respectively. For coupon tests of cold-formed
steel, samples with the cross-section properties of 1.5 mm, 2S
mm, and 3 mm were prepared and kept at the target
temperature of 700 °C for 20 min.” After the samples were