Professional Documents
Culture Documents
Temperature Controller
WITH REAL TIME CLOCK
PRODUCT DATA
FEATURES
• Models with selectable floating output functions:
— Floating.
— 2, 3, 4, or 6 stage.
• Models with analog outputs 0/2 to 10 Vdc selectable.
• Space/supply limit or cascade control.
• Sequence control of heating, mixed air damper,
economizer, or energy recovery system and cooling.
• Weekly time schedule with up to 6 switching points per
day.
• Automatic daylight saving time change.
• Four different operating modes: Occupied,
Unoccupied, Night, and Off.
• Yearly advance holiday programming.
• Three types of holiday schedules.
• Self-adaptive optimum start program for room control
system.
• Night-cycle program.
APPLICATION • Selectable control: proportional (P) or
proportional plus integral (P+I).
• Pre-programmed control parameters.
R7426A,B,C Temperature Controllers use direct digital control
technology to provide more accurate and efficient operation of • Digital parameter setting.
heating, ventilation and air conditioning (HVAC) systems. • Selectable direct/reverse acting analog output.
Parameters are preset for plug and play operation and provide • 24 Vac power supply.
different control strategies for optimum system performance. • 3 inputs for temperature sensors.
The controller performs proportional or proportional plus • Automatic sensor type identification of Pt 1000
integral (P+I) control and covers all space, supply air or water or NTC 20K ohm.
flow applications within the specified ranges of 32°F to 130°F • 2 digital inputs, occupancy (alternatively summer/
or 32°F to 260°F. Standard Pt 1000 or NTC 20K ohm winter changeover) and freeze protection.
temperature sensors can be used. • Start-up routine.
The modern design with its easy to operate user interface and Contents
LCD allows complete flexibility of control system design,
accurate parameter setting, and display of actual temperature Application ........................................................................ 1
values, setpoints and outputs. Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Introduction ....................................................................... 5
Operation .......................................................................... 5
Keypad Operation ............................................................ 10
Schedules ......................................................................... 12
Troubleshooting ................................................................ 13
Appendix A ....................................................................... 14
Control and Configuration Parameters ........................ 14
Parameter Details ........................................................ 16
Appendix B ....................................................................... 20
Programming Charts ................................................... 20
SPECIFICATIONS
Models: Accuracy: ±0.9°F (±0.5K) (not including sensor inaccuracy).
R7426: Temperature controller with integrated real time clock
(RTC), On/Off output, and other model-specific features. Digital inputs:
R7426A: Includes one three-position floating output. Choice of Occupancy (Summer/Winter Changeover):
selectable output signals to drive solid-state or step relays. Operation Mode: unoccupied (winter), occupied (summer).
R7426B: Three three-position floating outputs. Choice of Potential Free Contact:
selectable output signals to drive solid-state or step relays. open > 40K ohms, closed < 100 ohms.
R7426C: For sequence control of heating, energy recovery or Freeze Protection:
mixed-air damper, and cooling. Operation Mode: freeze protection (normal contact closed).
Three analog 0/2 to 10 Vdc outputs. Potential Free Contact:
open > 40K ohms, closed < 100 ohms.
Dimensions: See Fig. 1.
Output:
Weight: 0.55 lb (250g). Maximum Load:
R7426A,B: 450 mA at 24 Vac.
Mounting: Back panel, wall, DIN rail, or (with panel mounting R7426C (Analog 0/2 to 10 Vdc Outputs): 1.2 mA at 12 Vdc.
accessory frame) front panel. On/Off: 24 Vac On/Off single-pole, single-throw (spst) digital
output to switch pump or fan.
Electronic: TRIAC (selectable):
Microcontroller: 8-bit, 10-bit A/D converter, EEPROM and LCD. Floating: Single-pole, double-throw (spdt) switching.
Power Supply: 24 Vac +10, -15%, 50/60Hz. Multi-Stage: On (24 Vac) / Off (0 Vac).
Power Consumption: 3 VA. Pulse Width Modulation: 6 to 180 sec pulse width (for
Battery: Lithium/Manganese Dioxide; 3 Vdc, 170 mAh European electric current valves).
(approximate life: 8 years).
Sensor Ratings:
Wiring: Temperature Range:
Maximum Wiring Run from Controller to All Devices: Pt 1000: -22°F to 266°F (-30°C to +130°C).
18 AWG: 328 ft (100m). NTC 20K ohms: -22°F to 266°F (-30°C to +130°C).
16 AWG: 492 ft (150m). Characteristics:
Offset Due to Wire Resistance: See Table 1. Pt 1000: 1000 ohms at 32°F (0°C).
NTC 20K ohms: 20K ohms at 77°F (25°C).
Ambient Ratings:
Temperature: Approvals:
Operating: 32°F to 122°F (0°C to 50°C). Protection class II.
Storage: -31°F to +158°F (-35°C to +70°C). NEMA 1, IP30 or (with front panel mounting only) IP40.
Humidity: 5 to 95% relative humidity, non-condensing. FCC Part 15, Class B.
Meets CE requirements.
Control Point Adjustment (CPA)/Setpoint Adjustment
(SPA) Input: See Accessories and Table 2. Accessories:
43193862-001 Front panel mounting frame.
Control ranges: NTC 20K ohm sensors:
32°F to 130°F. C7031B1033: For duct discharge air, hot water.
32°F to 260°F. C7031D1062: For hot or chilled water.
C7031F1018: For outdoor air temperature.
Input (Temperature Sensors): C7031J1050: For duct discharge air (averaging).
I01: Main. C7031K1017: For hot or chilled water (strap-on).
I02: Limit or cascade. T7770A1006: Wall module with locking cover.
I03: Compensation. T7770B1004: Wall module with locking cover and setpoint
adjustment knob (55°F to 85°F) for CPATYP 3.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2564—1 2
R7426A,B,C TEMPERATURE CONTROLLER
Pt 1000 sensors:
C7031D1070: For hot or chilled water.
INSTALLATION
C7031F1026: For outdoor air temperature.
C7031J1068: For duct discharge air (averaging).
C7031K1025: For hot or chilled water (strap-on).
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
Table 1. Sensor Offset Per 33 ft (10m) of Wire. could damage the product or cause a hazardous
condition.
Wire Type Temperature offset in °F (°C) 2. Check the ratings given in the instructions and on the
in AWG (mm2) Pt 1000 NTC product to make sure the product is suitable for your
application.
20 (0.5) 0.32 (0.18) negligible 3. Installer must be a trained, experienced service
17 (1.0) 0.16 (0.09) technician.
15 (1.5) 0.11 (0.06) 4. After installation is complete, check out product
operation as provided in these instructions.
4-1/8
SEL +
CAUTION
(105)
SET –
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
4-5/8 (118) 1/8 (3) DIAMETER
Mounting
The controller can be mounted in an electric cabinet or other
suitable enclosure. They are suitable for back panel, wall, and
3-7/16
(87) DIN rail mounting.
Wiring
Connect the wires to the device:
1. Strip 3/8 in. to 1/2 in. of insulation from controller end of
wire.
2. Push stripped end of each wire into appropriate terminal
(see Fig. 2 to 4).
3. Apply power to device.
3 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
UNOCCUPIED MAIN
TEMPERATURE
SENSOR
1 2 3 4 5 6 7 8 9 10 11 12 13 14
R7426A
UNOCCUPIED MAIN
TEMPERATURE
SENSOR
1 2 3 4 5 6 7 8 9 10 11 12 13 14
63-2564—1 4
R7426A,B,C TEMPERATURE CONTROLLER
UNOCCUPIED MAIN
TEMPERATURE
SENSOR
IO1 FREEZE
OCCUPIED LIMIT OR PROTECTION
+ CASCADE COMPENSATION
CPA/SPA SENSOR SENSOR OFF ALARM
IO2 IO3 ON NORMAL
+ +
2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14
R7426C
O1 O2 O3
0/2 TO 10 Vdc 0/2 TO 10 Vdc 0/2 TO 10 Vdc
OUTPUT OUTPUT OUTPUT 1 POWER SUPPLY. PROVIDE DISCONNECT
+ + + MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
5 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
CAUTION
Equipment Damage Hazard.
Can damage the controller beyond repair.
Keep floating output load below 450 mA.
Fig. 5. R7426A cooling or heating control output.
On the R7426C controller the characteristic of each output
NOTES: Limit control is active only if either: can be selected via the parameters DIR/REVx (where x is O1,
— I02 temperature sensor (parameter I02ext is 0) is O2 or O3). See Fig. 8 for Dir characteristic for all outputs.
connected, or
— I01 sensor (control parameter I02ext is 1) Temperature Cascade Control
supplies the control loop. This application will be active with the R7426B,C controllers if
parameter Wcas is set to any value other than Off. It can be
Cascade Control (Wcas, Rcas and tr2) used for sequence control of a heating valve, an energy
recovery system, or mixed air damper and cooling valve.
The R7426A provides cascade control using two control loops
(master and submaster) to maintain setpoint (CTRP1). Two cascade control modes are available:
• With occupied (contact closed) mode. (see Fig. 6).
At zero room temperature deviation (XWMaster), discharge • With unoccupied (contact open) mode. (See Fig. 7.)
temperature (I02) is controlled by the programmed setpoint — CTRP2 high limit is performed if parameter LimTyp is 1.
(Wcas = CTRP2). If room temperature deviates, submaster — CTRP2 low limit is performed if parameter LimTyp is 0.
setpoint (CTRP2) is altered. See Fig. 6.
CTRP2
— Reset span adjustment (Rcas) determines degree of reset MASTER: C MODE = UNOCCUPIED
P CONTROL
effect. WLIM
— Integral reset time and throttling range of submaster P+I 1
control can be adjusted with tr2 and Xp2. 2x W
— CTRP2 high limit is performed if LimTyp is 1. R CAS
CAS
On the R7426C controller each output characteristic can be NOTE: See Table 3 for control logic and Fig. 9. for sequence
selected via parameters DIR/REVx (where x is O1, O2 or O3). output operation.
Fig. 8 shows:
• Dir characteristic for all outputs. Table 3. Economizer Mixed Air Damper Mode.
• Control of damper signal within the range Xp2.
Outside Air Temperature O1
NOTE: If no cooling actuator is available, the parameter Xpc Greater than return air MINPOS
can be set to Off. temperature
Less than return air Included in sequence control
If parameter Xpc is Off, the cooling signal is set to 0 percent temperature
and damper output is maintained at 100 percent above control
point (CTRP2).
NOTE: A fixed hysteresis of 2°F is used to switch between
MINPOS and actual O1 control output signal.
7 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
63-2564—1 8
R7426A,B,C TEMPERATURE CONTROLLER
2-STAGE ON/OFF SEQUENCE CONTROL NOTE: Same connection for 3-stage binary control as for
The R7426A,B controllers convert the output signal into a 2-stage control on R7426A and R7426B used for
2-stage On/Off sequence output signal suitable for operating electric heating control (output O3).
relays. Two relays can be connected to provide sequence
control of two stages (such as electric heat stages). Outputs for R7426B only
Parameter setting for Output Switching Position: 4-STAGE ON/OFF ELECTRIC HEATING OR COOLING
• OMode is 0, 1, 2, 3 or 4 (R7426B only).
When OMode is 2, the output sequence of O3/O1 is controlled
• OxMode (where x is 1, 2 or 3) is 1.
from the heating signal and O2 is controlled from the cooling
signal. When OMode is 3 the output sequence of O3/O1 is
controlled from the cooling signal and O2 is controlled from
the heating signal.
NOTES:
— Mixed air damper operation is not available.
— Output O2 operates in accordance with O2Mode.
— O1Mode and O3Mode are 4.
9 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
NOTE: The start-up routine must be disabled. Temperature Sensor Calibration (I01CAL, I02CAL
and I03CAL)
Analog Output (R7426C only) In case of an offset resulting from long wiring lengths, the
Three dc output control signals are provided to control temperature sensor inputs (I01, I02 and I03) can be adjusted
actuators for valves, dampers, or pneumatics (through E/P separately using parameters I01CAL, I02CAL and I03CA.
transducers).
PARAMETER/VALUE
CONFIRMATION SET M21047
63-2564—1 10
R7426A,B,C TEMPERATURE CONTROLLER
AND
SET SET SEL AND SET
PARAMETER/ PARAMETER/
OUTPUT OUTPUT STANDARD CONFIG. CONFIG.
OR ADJUSTMENT SELECTION DISPLAY SELECTION ADJUSTMENT OR
TO ADJUST MODE MODE MODE TO ADJUST
MODE MODE VALUE
VALUE
OUTPUT FIXING
SET SEL SEL SET
NO NO PARAMETER
SEL SEL VALUE CHANGE
OUTPUT FIXING
RELEASE OF
AND
OUTPUT FIXING
M21038
11 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
When the occupied or unoccupied mode is taken from the 1. Press and hold the SET and - buttons to display
schedule and an occupancy switch connected, control mode Programming mode for clock/date and schedule.
is determined by occupancy input: 2. Press the + or - button to change the programming
• Occupied (contact closed): Controller mode is occupied. mode (see Table 11).
• Unoccupied (contact open): Controller mode is
unoccupied. NOTE: If, at any time, you press SEL, the device will
return to the previous display, aborting all
NOTE: Off and night control modes are not influenced by changes made since you last pressed SET.
occupancy input.
Table 11. Programming Modes.
The clock automatically changes controller mode according to
the programmed schedule. In unoccupied or night mode, the Programming Mode Display
SOFFS or NOFFS is added to (cooling) or subtracted from Clock/Date RtC
(heating) the calculated control point. A one-week schedule Schedule SCH
with up to six switching points per day can be programmed in
advance and repeated weekly. Holiday HoL
63-2564—1 12
R7426A,B,C TEMPERATURE CONTROLLER
11. Press SET to place this information into the EEPROM. 6. Adjust the day to the proper value.
The device will cycle back to the hour. 7. Press SET to confirm this information and advance to
12. If no more changes are needed to the clock or date, set the holiday type.
press SEL to return to the display of RtC. 8. Select the proper holiday type.
13 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
APPENDIX A
Control and Configuration Parameters NOTES: Parameter Ctrltyp determines the setting:
— Ctrltyp Lo selects setting I.
The controller includes two groups of settings (I and II) for — Ctrltyp Hi1 and Hi2 select setting II.
control and configuration parameters. These settings are
automatically selected during programming. See Tables 13
and 14.
63-2564—1 14
R7426A,B,C TEMPERATURE CONTROLLER
15 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
NOTE: All configuration parameters (see Table 14) have to After power up reset (initial start) or the controller mode
be set to select the correct control functions required changes to night, unoccupied or occupied, the outdoor air and
by the job application and, in some cases, to start exhaust air dampers (O1) will stay in the closed position (0
control operation and synchronization of the final percent). After an adjustable time (1 to 10 minutes) of
control devices. operation, O1 returns to normal operation.
On the R7426A,B controllers the change of the direction can Control Function: O1CTRF (C.15)
be performed by exchange of the wiring connections open- If parameter O1CTRF is 2 (R7426A only), output O1 action
close (OUT2-OUT1). depends on occupancy input (see Summer/Winter
Changeover Function).
Operating Range Selection: Ctrltyp (C.04) If the parameter is set to 0, output O1 is selected for cooling
Changing parameter Ctrltyp value from Lo to Hi control range (R7426A), or mixed air control is selected (R7426B,C).
or vice versa causes the R7426A controller to change all
parameter values to the appropriate default. If the parameter is set to 1, heating (R7426A) or energy
recovery is selected (R7426B,C).
For manual parameter reset see How to Reset Parameter
Values to Default Values section.
Time Change: AddHour / SubHour (C.16 / C.17)
These parameters are required to adjust the time for Daylight
Saving Time. The one hour clock change occurs at 2:00 AM
the last Sunday of the month selected.
63-2564—1 16
R7426A,B,C TEMPERATURE CONTROLLER
Prestart Gradient: PSTG_H / PSTG_C (C.18 / C.19) For cascade control, limit setpoint Wlim determines the control
These parameters determine the necessary prestart gradients point at which:
to reach the occupied setpoint at occupancy start. The • Submaster setpoint (Wcas) maintains the limit value.
controller modifies the prestart gradient to optimize the start • Wlim is not shifted by the master control loop.
cycle through a self-adaptation routine.
NOTE: High or low limit control is in accordance with the
NOTE: Disable the optimum start cycle for heating and/or configuration parameter LimTyp (C.13).
cooling by setting PSTG_H or PSTG_C to 0.
Compensation Changeover Point: Wcomp (P.03)
Damper Prestart Time: tvd (C.20) The parameter Wcomp defines the start point of summer or
The parameter tvd is active with the optimum start program winter compensation.
only. It sets the time before occupied mode switches the
output signal O1 to supply fresh air to the space in mixed air Compensation is performed:
applications. • Above Wcomp for summer compensation.
• Below Wcomp for winter compensation.
17 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
Table 16. Throttling Range and Reset Time Reference Reset Time: tr1/tr2 (P.12/P13)
With P+I control, reset time (tr) is defined as the required time
Sensor
after which the integral part is equal to the change due to the
Xph
Xp1
Xp2
Xpc
tr1
tr2
Application proportional action for a predetermined step change in the
input variable. See Fig. 20.
R7426A
Main Temperature Control I01 x x The control parameter tr1 sets the reset time of the P+I main
temperature control loop.
High or Low Limit Temperature I02 x x
Control
For limit or submaster cascade control the control parameter
Master Cascade Control I01 x x tr2 sets the reset time of these control loops (such as
Submaster Cascade Control I02 x x discharge temperature I02. See Table 16.)
R7426B,C (Main Temperature Sequence Control) NOTE: If only proportional control is required, set tr to Off.
Mixed Air Damper I01 x x
Energy Recovery I01 x x
Heating I01 x x Xw
Cooling I01 x x
PROPORTIONAL CONTROL
R7426B,C (Temperature Cascade Sequence Control)
Master I01 x x 0
Submaster t
Calculate Xp for discharge air control using the following: SETTING GUIDELINES FOR P+I CONTROL RESET TIME
Xh Adjust reset time (tr) to 2 to 3 times the response time (Tu).
X p = ------
5 NOTE: Tu is the time interval between the beginning of a
For room temperature control use the following: sustained disturbance (such as a rapid step change
Xh ∆tmax of valve position) and the instant when the resulting
X p = ------ or -------------- output signal change reaches a specified fraction of
10 10 its final steady-state value, either before or in the
NOTE: ∆tmax (Xh) of the discharge air for mixed air damper absence of overshoot.
control is the maximum difference between OAT and
return air temperature. • Discharge air control: Tu normally ranges from 0.1 to 0.6
min. Therefore tr adjustment can range from 0.2 to 2 min.
The often specified accuracy for room control of ±2°F (where • Room control: Tu ranges from 0.5 to 5 minutes. This
Xp is 4.0°F) allows a discharge air alteration of 36°F. results in a tr setting of 1 to 15 minutes.
P+I and proportional control can use the same throttling Minimum Position: MINPOS (P.14)
range. Use the following formula for P+I control: Xh Adjustment of parameter MINPOS is available only with
X p = ------
x R7426B,C controllers. MINPOS determines the outdoor air
• Discharge air control: x ranges from 4 to 5.
damper actuator minimum position. It maintains the minimum
• Room control: x ranges from 8 to 10.
outdoor air damper setting even when temperature conditions
call for a fully closed position.
63-2564—1 18
R7426A,B,C TEMPERATURE CONTROLLER
Calibrate Ostart in degrees Fahrenheit. It is equal to the offset With the main sensor installed in the room and with a constant
(plus or minus) from the set values or calculated control points offset between room and return air conditions, this offset value
at which O1 is at 50 percent. can be adjusted from 0°F to 10°F using RetOffs. This value is
added to the measured room temperature to simulate return
NOTE: In P+l control, the start point should be set at zero. air conditions.
Occupied/Unoccupied Function: SOFFS (P.16) When RetOffs is programmed to Off, or with no OAT sensor
connected, Economizer mode is disabled.
A potential free contact can be used between terminals 1 and
4 to switch between occupied (contact closed) and
unoccupied (contact open) modes. RuntimeO1, O2, O3 (P.21,P.22,P.23)
Parameters RuntimeO1,O2,O3 are available on R7426A,B
Control point calculation: controllers only.
• Occupied mode: Use temperature setpoint (W1).
• Unoccupied mode: SOFFS parameter value is added to For three-position floating actuator control, the controller
(cooling) or subtracted from (heating) the calculated control converts the deviation signal to a proportional output pulse.
point. This pulse drives the actuators based on the Runtime value.
• Heating and cooling sequence applications: SOFFS value
is added to cooling control point (CTRPC) and subtracted An automatic synchronization function ensures correct
from heating control point (CTRPH). See Fig. 21. actuator positioning. Synchronization run time is derived by
multiplying Runtime by 1.25.
IMPORTANT
Set R7426A parameter O1CTRF to 0 or 1 to match By selecting pwm mode for output O1 or O3, the pwm output
the required application. If parameter O1CTRF is 2 (suitable for driving electric heat current valves) is controlled
(summer/winter changeover), SOFFS is ignored. from the heating signal. Interval and total cycle time is set by
the parameter RuntimeO1 or RuntimeO3.
O(%)
Night Cycle: NightLow and NightHigh (P.24/P.25)
100 Parameters NightLow and NightHigh are used by the night
UNOCCUPIED cycle program (controller mode is Off).
OCCUPIED
NOTE: Disable this function by setting these parameters Off.
OFFS OFFS
Night Mode Offset: NOFFS (P.26)
T
XpH XpC This control parameter is used to set the night mode offset.
XpH XpC During night mode, freeze protection is active and the
CTRPH CTRPC M17454 occupied/unoccupied function is disabled.
Fig. 21. Sequence control occupied/unoccupied function. • Night Mode: NOFFS parameter value is added to (cooling)
or subtracted from (heating) the calculated control point.
• Heating and cooling sequence applications: NOFFS value
is added to cooling control point (CTRPC) and subtracted
from heating control point (CTRPH). See Fig. 21.
19 63-2564—1
R7426A,B,C TEMPERATURE CONTROLLER
APPENDIX B
Programming Charts
Table 17. Weekly and Holiday Switching Points.
Switching Point 1 Switching Point 2 Switching Point 3 Switching Point 4 Switching Point 5 Switching Point 6
Control Control Control Control Control Control
Day Time Mode Time Mode Time Mode Time Mode Time Mode Time Mode
Mo
Tu
We
Th
Fr
Sa
Su
H1
H2
H3
Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American
Honeywell Honeywell Limited-Honeywell Limitée Control Products 3 Avenue du Bourget Region
1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway
Golden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200
M1V 4Z9 Singapore 486073 Sunrise FL 33325