ZITAN Project Dear Sir, Find herewith our computation: (Reference: Copper Development Asso. Publication no. 22). A. FOR COMMON BUS 3200 AMPS. Bus Bar rating: 3200 AMPS. Conductors + 3 ply, 5 x 100 mm rectangular Cu, Bus bars Cross sectional area (A) sq.mm. : A= 5x 100=500 sq.mm, Perimeter of conductor (P) mm, : P= 100+ 100 +5+5=210 mm Multiplying factor (3 bars) 125 0 Solving for the rated current per bar: 1 =7,73A 0p 0%) =7.73 (500) 5x (210) © I =7.73 (22.36068x 8.047584) I 391 amps per bar. For 3 bars, total bus bar rating will be: 1 = 1,391 x multiplying factor for 3 bars = 1391 x 2.5 = 3477 > 32004, ‘Therefore, the bus bar size considered is more than enough for the required rating, For your consideration, and acceptance. Edwin ‘angilinan, PEE PRC no. 3252 Date of Registration Nov. 11, 2000. ‘Valid until May 27, 2019 PTR No: 0366310 Date/Place issued : Jan 13, 2016 at San Pedro, Laguna