Single conductor cable with aluminum or copper conductors, Design Parameters
triple extruded insulation system consisting of a thermosetting CONDUCTOR: Solid or Class B compact or compressed
semiconducting conductor shield, high dielectric strength concentric strand aluminum alloy 1350 or soft drawn
VOLTALENE™ TRXLPE insulation, thermosetting semiconducting annealed copper per ASTM.
insulation shield, copper concentric neutral wires, black
CONDUCTOR SHIELD: Extruded thermosetting semicon-
encapsulating linear low-density polyethylene (LLDPE) jacket.
ducting shield which is free stripping from the conductor
Specifications Ratings and bonded to the insulation.
CSA - CSA C68.5 -40°C INSULATION: Natural high dielectric strength VOLTENE™
For 90°C continuous, 130°C emergency, TRXLPE insulation, exhibiting an optimum balance of
250°C short-circuit operation. mechanical and electrical properties, insuring resistance
Options to treeing.
- Black LLDPE jacket with no stripes INSULATION SHIELD: Extruded thermosetting semicon-
- Black PVC jacket sleeved over separator tape ducting shield with controlled adhesion to the insulation
- No Jacket providing the required balance between electrical integrity
and ease of stripping.
- EPROTENAX™ (EPR) insulation
- Multiplex cables METALLIC SHIELD: Solid bare copper wires, helically
- Tinned round and flat strap neutrals applied and uniformly spaced.
- Strandseal® JACKET: Black insulating sunlight resistant linear low
- Super smooth conductor shield density polyethylene encapsulating the neutral wires
- Cables made to AEIC CS8 and/or ICEA S-94-649 with three extruded red stripes.
- 46kV
Installations
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 1
A brand of the
m)
)
(mm
er (m
)†† e
s)
km) nce
)†† e
)
km) nce
ius
/km anc
km) ce
(mm
mm
/km anc
km) dance
/km nce
/km nce
(mil
met
(W/ edan
(W/ peda
Rad
(W/ Impeda
)
)
e (W Imped
/km
e (W Imped
††
e (W eda
(mm
e (W eda
ter (
††
a
ess
eter
)
)
i
ps)
e
ps)
D
tral
ing
nce mp
m
nce mp
anc Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
end
Neu
sist ence
I
(W/
acta ence
sist ence
I
acta ence
acta nce
acta nce
sist nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
iam
mB
nce
Re o Sequ
tric
anc
Re Seque
nce
Re equ
tor
Re o Sequ
anc
Re Seque
Re que
Re Seque
Re o Sequ
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
S
e
Product
† Am
† Am
Zero
Insu
Jack
Insu
Cab
Insu
Con
Con
Min
Zer
+/-
+/-
Zer
+/-
+/-
Zer
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited.
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 2
A brand of the
)
(mm
(mm
km) nce
)†† e
s)
)†† e
km) nce
eter
)
ius
/km anc
km) ce
km) ce
(mm
/km anc
mm
/km nce
/km nce
(mil
(W/ mpeda
(W/ edan
(W/ edan
(W/ Impeda
Rad
Diam
)
)
e (W Imped
††
e (W Imped
e (W eda
/km
(mm
e (W eda
††
ter (
ess
eter
)
)
ps)
)
tral
nce Imp
ing
nce Imp
s
anc Imp
anc Imp
t (kg
p
ame
ickn
ield
I
Am
Diam
eter
Am
end
acta ence
sist ence
Neu
sist ence
acta ence
acta nce
acta nce
sist nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
iam
mB
nce
nce
Re o Sequ
Re Sequ
anc
Re que
tric
Re que
tor
Re o Sequ
Re Sequ
anc
Re eque
Re Seque
latio
pac
latio
latio
le W
pac
et D
imu
duc
cen
e
e
S
Product
† Am
S
† Am
Zero
Zero
Insu
Jack
Insu
Insu
Cab
Con
Zer
Con
+/-
Min
+/-
Zer
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 3
A brand of the
)
(mm
(mm
s)
)†† e
)†† e
km) nce
km) nce
eter
)
ius
/km anc
/km anc
km) ce
(mm
(mil
mm
km) ce
/km nce
/km nce
(W/ edan
(W/ Impeda
(W/ edan
(W/ peda
Rad
Diam
e (W Imped
)
e (W Imped
††
/km
e (W eda
(mm
e (W eda
††
ter (
ess
eter
)
)
ps)
ps)
tral
ing
nce Imp
nce Imp
anc Imp
anc Imp
ickn
t (kg
ame
ield
Diam
eter
Am
Am
sist ence
end
sist ence
acta ence
Neu
acta ence
acta nce
acta nce
n Th
sist nce
sist nce
n Sh
eigh
n Di
ity (
ity (
iam
mB
nce
nce
Re o Sequ
anc
Re o Sequ
Re o Sequ
anc
tric
Re que
tor
Re equ
Re que
Re eque
Re Seque
latio
latio
le W
latio
pac
pac
et D
imu
duc
cen
e
Product
S
† Am
† Am
S
Zero
Insu
Insu
Jack
Insu
Cab
Zer
Con
Con
Min
Zer
Zer
+/-
+/-
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 4
A brand of the
)
(mm
(mm
s)
)†† e
km) nce
km) nce
eter
)†† e
)
ius
/km anc
km) ce
(mm
(mil
mm
/km anc
/km nce
/km nce
m) ce
(W/ edan
(W/ peda
(W/ peda
Rad
Diam
W/k dan
)
e (W Imped
)
e (W mped
††
(mm
e (W eda
††
e (W eda
ter (
/km
ess
eter
ps)
)
ps)
e
tral
ing
nce Imp
m
m
anc Imp
ickn
anc Imp
nce Imp
ame
t (kg
ield
I
Diam
eter
Am
Am
I
end
sist ence
Neu
acta ence
acta ence
sist ence
acta nce
n Th
sist nce
n Sh
sist nce
acta nce
n Di
ity (
eigh
ity (
iam
mB
nce
nce
Re equ
anc
tric
Re que
Re equ
tor
Re equ
Re o Sequ
anc
Re Seque
Re que
Re Seque
latio
latio
pac
latio
pac
et D
le W
imu
duc
cen
S
e
S
S
e
Product
† Am
† Am
Zero
Zero
Zero
Insu
Insu
Jack
Insu
Con
Con
Min
+/-
Cab
Zer
+/-
Number Conductor
+/-
+/-
(A) (B) (C) (D) 90°C In Duct 90°C Direct Buried
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 5
A brand of the
)
(mm
(mm
km) nce
s)
)†† e
eter
)†† e
)
km) nce
ius
km) ce
m)
/km nce
km) ce
(mm
/km anc
/km anc
/km nce
(mil
(W/ edan
(W/ edan
(W/ Impeda
r (m
Rad
(W/ peda
iam
e (W eda
m)
e (W Imped
/km
††
e (W Imped
e (W eda
††
ess
eter
)
m
ps)
e
ps)
nce Imp
D
anc Imp
tral
ing
nce Imp
t
anc Imp
m
t (kg
(
ickn
ame
ield
Diam
eter
Am
Am
I
end
acta ence
Neu
sist ence
sist ence
acta ence
acta nce
sist nce
acta nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
iam
mB
nce
Re eque
Re eque
Re o Sequ
tric
nce
Re eque
tor
Re o Sequ
anc
Re o Sequ
anc
Re Seque
Re Sequ
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
S
S
Product
† Am
† Am
Jack
Zero
Insu
Insu
Cab
Insu
+/-
Con
Con
+/-
Zer
Min
+/-
Zer
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 6
A brand of the
)
(mm
(mm
s)
)†† e
)
km) edance
eter
km) nce
)†† e
)
mm
/km anc
ius
km) ce
(mm
km) ce
(mil
/km nce
/km anc
/km nce
(W/ edan
(W/ edan
Rad
(W/ Impeda
Diam
e (W Imped
)
)
ter (
/km
e (W eda
e (W Imped
††
(mm
e (W eda
††
ess
eter
p
ps)
ps)
tral
nce Imp
ing
nce mp
m
anc Imp
ame
anc Imp
ickn
t (kg
ield
Am
Diam
I
eter
Am
sist ence
end
Neu
(W/
I
acta ence
acta ence
sist ence
acta nce
acta nce
sist nce
n Th
n Di
sist nce
n Sh
eigh
ity (
ity (
iam
mB
nce
Re o Sequ
anc
nce
tric
Re Seque
Re Seque
tor
Re o Sequ
Re equ
Re que
Re equ
anc
Re Seque
latio
latio
pac
le W
pac
latio
et D
imu
duc
cen
e
S
Product
† Am
S
† Am
Insu
Insu
Zero
Zero
Jack
Insu
Cab
Zer
Con
Con
+/-
Min
+/-
Zer
+/-
+/-
Number Conductor
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 7
A brand of the
)
(mm
(mm
s)
km) edance
)†† e
eter
km) nce
)†† e
)
(mil
ius
km) ce
(mm
/km anc
mm
/km dance
/km anc
/km nce
/km nce
(W/ edan
Rad
(W/ Impeda
Diam
)
)
e (W Imped
ess
/km
e (W Imped
††
e (W eda
(mm
e (W eda
††
ter (
eter
p
)
)
e
ps)
)
ps)
tral
ing
nce mp
ickn
m
nce Imp
anc Imp
anc Imp
t (kg
ame
ield
I
Diam
eter
Am
Am
end
(W/
Neu
acta ence
sist ence
acta ence
sist ence
n Th
W
acta nce
acta nce
sist nce
sist nce
n Sh
eigh
n Di
ity (
ity (
(
iam
mB
nce
nce
tric
Re Seque
Re o Sequ
tor
Re o Sequ
anc
Re eque
Re Sequ
Re o Sequ
anc
latio
Re Seque
Re Seque
latio
pac
latio
le W
pac
et D
imu
duc
cen
Product
Insu
S
† Am
† Am
Zero
Insu
Jack
Insu
Cab
Con
Con
Min
+/-
Zer
Zer
+/-
Zer
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 8
A brand of the
)
(mm
(mm
s)
km) nce
)†† e
)†† e
km) nce
eter
)
km) ce
)
ius
/km anc
/km anc
(mil
km) ce
(mm
/km nce
mm
/km nce
(W/ edan
(W/ Impeda
(W/ edan
(W/ peda
Rad
Diam
e (W Imped
)
e (W Imped
††
e (W eda
/km
††
(mm
e (W eda
ter (
ess
eter
)
ps)
)
ps)
nce Imp
tral
ing
nce Imp
anc Imp
m
anc Imp
ickn
t (kg
ame
ield
Am
I
Diam
eter
Am
acta ence
sist ence
end
sist ence
Neu
acta ence
acta nce
acta nce
sist nce
n Th
sist nce
n Sh
eigh
ity (
n Di
ity (
iam
mB
nce
nce
Re que
Re Sequ
Re o Sequ
anc
Re o Sequ
anc
tric
Re que
Re eque
Re o Sequ
tor
Re Seque
latio
pac
latio
le W
latio
pac
et D
imu
duc
cen
e
e
S
Product
S
† Am
Zero
† Am
Insu
Insu
Jack
+/-
Insu
Cab
Zer
Con
Con
Zer
Min
+/-
+/-
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 9
A brand of the
)
(mm
(mm
s)
km) edance
)†† e
eter
km) nce
)†† e
)
ius
km) ce
(mm
/km anc
mm
/km dance
/km anc
/km nce
/km nce
(mil
(W/ edan
Rad
(W/ Impeda
Diam
)
)
e (W Imped
/km
e (W Imped
††
e (W eda
(mm
e (W eda
††
ter (
ess
eter
p
)
)
e
ps)
)
ps)
tral
ing
nce Imp
m
nce Imp
anc Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
end
(W/
Neu
acta ence
sist ence
acta ence
sist ence
W
acta nce
acta nce
sist nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
(
iam
mB
nce
nce
tric
Re Seque
Re o Sequ
tor
Re o Sequ
anc
Re eque
Re Sequ
Re o Sequ
anc
Re Seque
Re Seque
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
Product
S
† Am
† Am
Zero
Insu
Jack
Insu
Insu
Cab
Con
Con
Min
+/-
Zer
Zer
+/-
Zer
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 10
A brand of the
)
(mm
(mm
s)
km) nce
)†† e
eter
)†† e
)
/km nce
)
km) nce
ius
km) ce
(mm
/km anc
mm
/km ance
/km anc
/km nce
(mil
(W/ edan
(W/ mpeda
Rad
e (W eda
Diam
(W/ Impeda
)
)
e (W Imped
/km
e (W Imped
††
(mm
e (W eda
ter (
††
d
)
ess
eter
e
ps)
ps)
)
anc Imp
tral
ing
nce Imp
nce Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
end
Neu
acta ence
sist ence
sist ence
sist nce
acta ence
W
acta nce
acta nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
(
iam
mB
Re Seque
nce
tric
Re eque
nce
Re o Sequ
tor
Re o Sequ
anc
Re que
Re o Sequ
anc
Re Seque
Re Sequ
latio
pac
le W
pac
latio
latio
et D
imu
duc
cen
e
Product
S
† Am
† Am
Insu
Jack
+/-
Insu
Cab
Zero
Insu
Con
Con
Min
+/-
Zer
Zer
+/-
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 11
A brand of the
)
(mm
)
(mm
s)
eter
km) nce
)†† e
)†† e
)
)
km) nce
ius
km) ce
mm
/km nce
(mm
(mil
/km anc
/km dance
/km anc
/km nce
(W/ edan
(W/ mpeda
Rad
Diam
(W/ mpeda
)
)
e (W eda
e (W Imped
/km
e (W Imped
††
e (W eda
(mm
ter (
††
ess
eter
e
ps)
ps)
)
tral
ing
nce Imp
anc Imp
nce Imp
anc Imp
ickn
t (kg
ame
ield
I
Diam
Am
eter
Am
I
end
Neu
acta ence
sist ence
sist ence
acta ence
W
acta nce
sist nce
acta nce
n Th
sist nce
n Sh
n Di
eigh
ity (
ity (
(
iam
mB
nce
tric
Re eque
Re Seque
nce
Re o Sequ
tor
Re o Sequ
anc
Re eque
Re o Sequ
anc
Re Seque
Re Sequ
latio
latio
latio
pac
le W
pac
et D
imu
duc
cen
Product
S
† Am
S
† Am
Insu
Insu
Insu
Jack
Zero
Cab
Con
Con
Min
+/-
+/-
Zer
Zer
+/-
Zer
+/-
Number Conductor
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 12
A brand of the
)
(mm
(mm
)†† e
s)
km) edance
eter
)†† e
)
km) nce
ius
/km anc
km) ce
(mm
km) ce
mm
/km anc
/km nce
/km nce
(mil
(W/ edan
(W/ edan
Rad
Diam
(W/ Impeda
)
)
e (W Imped
/km
e (W Imped
††
e (W eda
(mm
e (W eda
ter (
††
ess
eter
p
)
)
ps)
ps)
tral
ing
nce mp
nce Imp
m
anc Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
end
(W/
Neu
sist ence
I
acta ence
sist ence
acta ence
acta nce
acta ce
sist nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
iam
n
mB
nce
tric
Re o Sequ
anc
Re Seque
Re Seque
nce
Re o Sequ
tor
Re o Sequ
anc
Re Seque
Re Seque
Re o Sequ
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
Product
† Am
† Am
Insu
Jack
Insu
Cab
Insu
Con
Con
Min
Zer
+/-
+/-
Zer
Zer
+/-
+/-
Zer
Number Conductor
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: One single cable in plastic duct, direct-buried, 90°C conductor In Duct: Three single cables in plastic duct, direct-buried in a triangular
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 13
A brand of the
)
(mm
(mm
s)
)†† e
km) nce
eter
)†† e
)
km) nce
km) ce
ius
/km anc
km) ce
(mm
(mil
/km nce
mm
/km anc
/km nce
(W/ edan
(W/ edan
(W/ Impeda
Rad
Diam
(W/ Impeda
e (W Imped
)
)
e (W eda
/km
e (W Imped
††
(mm
e (W eda
ter (
ess
††
eter
)
)
ps)
ps)
nce Imp
tral
ing
nce Imp
anc Imp
anc Imp
ickn
t (kg
ame
ield
Diam
eter
Am
Am
sist ence
end
Neu
acta ence
sist ence
acta ence
acta nce
acta nce
sist nce
n Th
sist nce
n Sh
eigh
n Di
ity (
ity (
iam
mB
nce
Re eque
Re o Sequ
anc
tric
Re eque
nce
Re o Sequ
Re Seque
tor
Re o Sequ
anc
Re Seque
Re Sequ
latio
latio
pac
latio
le W
pac
et D
imu
duc
cen
S
Product
† Am
† Am
Insu
Insu
Jack
Insu
Zero
+/-
Cab
Zer
Con
Con
Min
+/-
+/-
Zer
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 14
A brand of the
)
m)
(mm
er (m
s)
)†† e
ius
km) nce
)†† e
)
)
(mil
km) nce
/km anc
km) ce
(mm
mm
/km nce
km) ce
/km anc
/km nce
met
Rad
(W/ edan
(W/ Impeda
(W/ edan
(W/ Impeda
e (W Imped
m)
e (W eda
e (W Imped
ess
††
e (W eda
/km
ter (
††
a
eter
)
m
ing
)
i
ps)
ps)
D
tral
nce Imp
ickn
anc Imp
nce Imp
anc Imp
(
ame
t (kg
ield
end
Diam
eter
Am
Am
sist ence
Neu
acta ence
sist ence
acta ence
n Th
acta nce
sist nce
acta nce
sist nce
n Sh
n Di
eigh
mB
ity (
ity (
iam
nce
Re o Sequ
anc
tric
Re eque
nce
Re o Sequ
tor
Re Seque
Re que
Re o Sequ
anc
Re Seque
latio
Re Sequ
latio
pac
latio
imu
pac
et D
le W
duc
cen
e
Product
S
Insu
S
† Am
† Am
Min
Insu
Jack
Insu
Zero
Con
Con
Zer
Cab
+/-
Zer
+/-
+/-
Zer
+/-
Number Conductor
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 15
A brand of the
)
(mm
(mm
s)
km) nce
km) edance
)†† e
eter
)†† e
)
ius
km) ce
(mm
(mil
/km anc
mm
/km dance
/km anc
/km nce
/km nce
(W/ Impeda
(W/ edan
Rad
Diam
)
)
e (W Imped
††
e (W Imped
/km
††
e (W eda
(mm
e (W eda
ter (
ess
eter
p
)
)
e
ps)
)
ps)
tral
ing
nce Imp
m
nce Imp
anc Imp
anc Imp
ickn
t (kg
ame
ield
I
Diam
eter
Am
Am
end
acta ence
(W/
Neu
acta ence
sist ence
sist ence
W
acta nce
acta nce
n Th
sist nce
sist nce
n Sh
n Di
eigh
ity (
ity (
(
iam
mB
nce
nce
Re Sequ
tric
Re eque
Re o Sequ
tor
Re o Sequ
anc
Re eque
Re o Sequ
anc
Re Seque
Re Seque
latio
latio
pac
latio
pac
le W
et D
imu
duc
cen
Product
S
† Am
† Am
Zero
Insu
Insu
Jack
Insu
Cab
Con
Con
Min
+/-
Zer
Zer
+/-
Zer
+/-
+/-
Number Conductor
† Ampacities are based on the following: †† Zero Sequence Impedance considers all return in the neutral only.
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 16
A brand of the
)
(mm
(mm
s)
)†† e
)†† e
km) edance
eter
)
m)
km) nce
ius
(mil
/km anc
m) ce
/km nce
/km anc
km) ce
(mm
/km nce
W/k dan
(W/ edan
er (m
Rad
Diam
(W/ mpeda
e (W Imped
)
e (W eda
e (W Imped
)
††
(mm
e (W eda
ess
/km
††
eter
p
)
ps)
ps)
nce Imp
anc Imp
tral
ing
nce Imp
m
ickn
anc Imp
ame
t (kg
ield
I
Diam
eter
Am
Am
I
sist ence
end
(W/
sist ence
Neu
acta ence
acta ence
acta nce
sist nce
n Th
acta nce
sist nce
n Sh
n Di
(
eigh
ity (
ity (
iam
mB
nce
Re o Sequ
anc
Re Seque
Re que
Re o Sequ
anc
tric
Re eque
nce
Re o Sequ
tor
Re Seque
Re Sequ
latio
latio
pac
latio
pac
et D
le W
imu
duc
cen
S e
Product
† Am
Insu
† Am
Insu
Jack
Insu
Zero
Zer
+/-
Con
Con
+/-
Cab
Zer
Min
+/-
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 17
A brand of the
)
(mm
(mm
s)
)†† e
km) nce
km) nce
)†† e
eter
)
ius
/km anc
(mil
km) ce
(mm
/km anc
mm
km) dance
/km nce
/km nce
(W/ edan
(W/ peda
(W/ peda
Rad
Diam
e (W Imped
)
)
e (W Imped
††
/km
††
e (W eda
(mm
e (W eda
ter (
ess
eter
)
)
e
ps)
ps)
tral
m
ing
nce Imp
m
nce mp
anc Imp
anc Imp
ickn
t (kg
ame
ield
I
Diam
eter
Am
Am
sist ence
end
acta ence
(W/
Neu
acta ence
sist ence
I
acta nce
n Th
acta nce
sist nce
sist nce
n Sh
eigh
n Di
ity (
ity (
iam
mB
nce
nce
Re equ
anc
Re equ
tric
Re que
Re equ
tor
Re o Sequ
anc
Re Seque
Re que
Re Seque
latio
latio
pac
latio
le W
pac
et D
imu
duc
cen
S
e
S
e
Product
Zero
† Am
† Am
S
Zero
Insu
Zero
Insu
Jack
Insu
Cab
Con
Con
Min
+/-
Zer
+/-
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 18
A brand of the
)
(mm
(mm
s)
)†† e
km) edance
km) nce
eter
)†† e
)
ius
/km anc
/km nce
km) ce
(mm
m) ce
(mil
mm
/km anc
/km nce
(W/ edan
W/k dan
(W/ Impeda
Rad
Diam
e (W eda
e (W Imped
)
e (W Imped
/km
††
††
(mm
e (W eda
ter (
ess
eter
p
e
)
ps)
ps)
anc Imp
tral
ing
nce mp
nce Imp
m
anc Imp
ickn
t (kg
ame
ield
I
Diam
eter
Am
Am
end
(W/
sist ence
Neu
acta ence
acta ence
sist ence
sist nce
acta nce
acta nce
n Th
sist nce
n Sh
eigh
n Di
ity (
(
ity (
iam
mB
nce
nce
Re o Sequ
Re que
anc
tric
Re Seque
Re o Sequ
Re Seque
Re o Sequ
tor
Re o Sequ
anc
Re Seque
latio
latio
pac
latio
le W
pac
et D
imu
duc
cen
S e
Product
† Am
† Am
Insu
Insu
Jack
Insu
Cab
Con
Con
+/-
Zer
Min
+/-
+/-
Zer
Zer
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 19
A brand of the
)
(mm
)
(mm
km) nce
)
eter
s)
km) edance
)†† e
)
)†† e
(mm
ius
/km nce
mm
km) ce
/km anc
km) dance
/km anc
/km nce
(mil
(W/ Impeda
(W/ edan
Rad
)
Diam
e (W eda
)
/km
e (W Imped
††
e (W Imped
ter (
††
(mm
e (W eda
eter
ess
p
)
e
ps)
ps)
tral
anc Imp
ing
nce Imp
m
nce mp
anc Imp
t (kg
ame
ickn
ield
Diam
I
eter
Am
Am
Neu
end
acta ence
(W/
(W/
acta ence
sist ence
I
sist ence
sist nce
acta nce
acta nce
sist nce
n Sh
eigh
n Di
n Th
ity (
ity (
iam
mB
nce
nce
tric
tor
Re Sequ
Re eque
Re eque
Re o Sequ
Re o Sequ
anc
Re Seque
Re o Sequ
anc
Re Seque
latio
le W
latio
pac
latio
pac
et D
duc
cen
imu
S
Product
† Am
† Am
Zero
Insu
Cab
Con
Insu
Jack
Con
Insu
+/-
Min
+/-
Zer
Zer
+/-
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 20
A brand of the
)
(mm
(mm
)†† e
)†† e
km) nce
s)
eter
)
ius
)
km) nce
/km anc
/km anc
m) ce
/km nce
km) ce
(mm
mm
/km nce
(mil
W/k dan
(W/ edan
(W/ Impeda
Rad
Diam
(W/ mpeda
)
e (W Imped
e (W ped
)
e (W eda
/km
††
(mm
e (W eda
ter (
††
ess
eter
e
)
ps)
ps)
nce Imp
m
anc Imp
tral
ing
nce Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
I
end
sist ence
sist ence
Neu
acta ence
acta ence
acta nce
sist nce
acta nce
sist nce
n Sh
n Th
eigh
n Di
(
ity (
ity (
iam
mB
nce
Re o Sequ
Re o Sequ
anc
anc
Re Seque
Re que
tric
Re eque
Re o Sequ
nce
tor
Re Seque
Re Sequ
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
S e
Product
† Am
† Am
Insu
Jack
Insu
Cab
Zero
Insu
Zer
Zer
+/-
Con
Con
Min
+/-
+/-
Zer
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 21
A brand of the
)
(mm
(mm
)†† e
km) nce
s)
km) nce
)†† e
eter
)
ius
/km anc
km) ce
(mm
/km anc
mm
km) dance
/km nce
/km nce
(mil
(W/ edan
(W/ Impeda
(W/ peda
Rad
Diam
e (W Imped
)
e (W Imped
††
/km
††
e (W eda
(mm
e (W eda
ter (
ess
eter
)
)
e
ps)
ps)
tral
nce Imp
ing
m
nce mp
anc Imp
anc Imp
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
end
sist ence
(W/
Neu
acta nce
acta ence
sist ence
I
acta nce
acta nce
sist nce
sist nce
n Sh
n Th
n Di
eigh
ity (
ity (
iam
mB
e
nce
nce
Re o Sequ
anc
Re que
tric
Re o Sequ
Re equ
tor
Re o Sequ
anc
Re Seque
Re que
Re Seque
latio
pac
latio
latio
pac
le W
et D
imu
duc
cen
S
e
S
Product
† Am
† Am
Zero
Insu
Jack
Insu
Insu
Cab
Con
Con
Zer
+/-
Min
Zer
Zer
+/-
+/-
+/-
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature, earth
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial, and shields
subject to normal manufacturing tolerances.
short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 | www.prysmiancanada.com 22
A brand of the
)
(mm
(mm
)†† e
)†† e
s)
km) nce
eter
)
km) nce
ius
/km anc
/km anc
km) ce
/km nce
km) ce
(mm
mm
/km nce
(mil
(W/ edan
(W/ edan
(W/ peda
Rad
Diam
(W/ peda
)
e (W Imped
e (W Imped
)
e (W eda
/km
††
(mm
e (W eda
ter (
††
ess
eter
)
)
ps)
ps)
nce Imp
anc Imp
tral
ing
nce mp
m
anc Imp
m
t (kg
ame
ickn
ield
I
Diam
eter
Am
Am
I
sist ence
end
sist ence
Neu
acta ence
acta ence
acta nce
sist nce
acta nce
sist nce
n Sh
n Th
eigh
n Di
ity (
ity (
iam
mB
nce
Re equ
anc
Re o Sequ
Re que
anc
Re eque
tric
Re Seque
nce
Re equ
tor
Re Seque
Re o Sequ
latio
le W
pac
latio
latio
pac
et D
imu
duc
cen
S
S
S
Product
† Am
Zero
† Am
Zero
Insu
Jack
Insu
Cab
Insu
+/-
Con
Con
Zer
+/-
Min
+/-
+/-
Zer
Number Conductor
PRODUCT NOTES: Single Phase Operation (Full Neutral Design) Three Phase Operation (1/3 Neutral Design)
s Items are Prysmian authorized stock. In Duct: Three single cables in plastic duct, direct-buried in a triangular
In Duct: One single cable in plastic duct, direct-buried, 90°C conductor
temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, configuration, 90°C conductor temperature, 20°C ambient temperature,
The above dimensions are approximate and
100% load factor, 36 inch depth of burial, and shields short-circuited. earth RHO of 90°C-cm/Watt, 100% load factor, 36 inch depth of burial,
subject to normal manufacturing tolerances.
and shields short-circuited.
Single Phase Impedance Values Assume Full Direct Buried: One single cable, direct-buried, 90°C conductor temperature,
Return in the Metallic Shield. 20°C ambient temperature, earth RHO of 90°C-cm/Watt, 100% load factor, Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
36 inch depth of burial, and shields short-circuited. 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-
All metric (SI) dimensions are derived from cm/Watt, 100% load factor, 36 inch depth of burial, and shields short-circuited
a soft conversion.
© PRYSMIAN - A Brand of The Prysmian Group 2013. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form,
either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any
specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued October 2013.
PDN-0025-1013
Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | www.prysmianusa.com