You are on page 1of 46

OPERATION MANUAL

WHISPERWATT™ SERIES
MODEL DCA45SSIU4F
60Hz GENERATOR
(ISUZU 4LE2X DIESEL ENGINE)

Revision #3 (01/16/18)
To find the latest revision of this
publication, visit our website at:
www.mqpower.com

THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.


PROPOSITION 65 WARNING

Diesel engine exhaust and some of

PAGE 2 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


TABLE OF CONTENTS
DCA45SSIU4F 60 Hz
Generator
Proposition 65 Warning............................................ 2
Safety Information................................................. 4-9
Generator/Engine Specifications............................ 10
Generator Dimensions............................................ 11
Installation......................................................... 12-13
General Information................................................ 14
Generator Major Components................................ 15
Engine/Generator Control Panel....................... 16-17
Output Terminal Panel Familiarization............... 18-20
Load Application..................................................... 21
Generator Outputs............................................. 22-23
Gauge Reading...................................................... 23
Output Terminal Panel Connections.................. 24-25
Inspection/Setup................................................ 26-30
Generator Start-Up Procedure (Manual Mode)...... 31
Generator Start-Up Procedure (Auto Mode)........... 32
Generator Shut-Down Procedures......................... 33
Maintenance...................................................... 34-38
Troubleshooting Diagnostic (Lamp) ....................... 39
Troubleshooting Generator .................................... 40
Troubleshooting Engine.................................... 41-42
Generator Wiring Diagram...................................... 43
Engine Wiring Diagram........................................... 44
Controller Wiring Diagram...................................... 45
NOTICE
Specifications are subject to change without notice.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 3


SAFETY INFORMATION
Do not operate or service the equipment before reading the Potential hazards associated with the operation of this
entire manual. Safety precautions should be followed at all equipment will be referenced with hazard symbols which
times when operating this equipment. Failure to read and may appear throughout this manual in conjunction with
understand the safety messages and operating instructions safety messages.
could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you
about potential hazards that could injure you or others. The
safety messages specifically address the level of exposure
to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION or NOTICE.
SAFETY SYMBOLS

DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.

WARNING
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.

CAUTION
Indicates a hazardous situation which, if not avoided,
COULD result in MINOR or MODERATE INJURY.

NOTICE
Addresses practices not related to personal injury.

PAGE 4 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


SAFETY INFORMATION
GENERAL SAFETY  NEVER use accessories or attachments that are not
recommended by MQ Power for this equipment. Damage
CAUTION to the equipment and/or injury to user may result.
 NEVER operate this equipment without proper protective  ALWAYS know the location of the nearest
clothing, shatterproof glasses, respiratory protection, fire extinguisher.
hearing protection, steel-toed boots and other protective
devices required by the job or city and state regulations.  ALWAYS know the location of the nearest
first aid kit.
 ALWAYS know the location of the nearest
phone or keep a phone on the job site. Also, know the
phone numbers of the nearest ambulance, doctor and
 NEVER operate this equipment when not fire department. This information will be invaluable in
feeling well due to fatigue, illness or when the case of an emergency.
under medication.
 NEVER operate this equipment under the influence of
drugs or alcohol.
GENERATOR SAFETY
DANGER
 NEVER operate the equipment in an explosive
 ALWAYS check the equipment for loosened threads or atmosphere or near combustible materials. An
bolts before starting. explosion or fire could result causing severe
bodily harm or even death.
 DO NOT use the equipment for any purpose other than
its intended purposes or applications. WARNING
NOTICE  NEVER disconnect any emergency or safety devices.
These devices are intended for operator safety.
 This equipment should only be operated by trained and Disconnection of these devices can cause severe injury,
qualified personnel 18 years of age and older. bodily harm or even death. Disconnection of any of these
 Whenever necessary, replace nameplate, operation and devices will void all warranties.
safety decals when they become difficult read. CAUTION
 Manufacturer does not assume responsibility for any  NEVER lubricate components or attempt service on a
accident due to equipment modifications. Unauthorized running machine.
equipment modification will void all warranties.
NOTICE
 ALWAYS ensure generator is on level ground before use.
 ALWAYS keep the machine in proper running condition.
 Fix damage to machine and replace any broken parts
immediately.
 ALWAYS store equipment properly when it is not being
used. Equipment should be stored in a clean, dry location
out of the reach of children and unauthorized personnel

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 5


SAFETY INFORMATION
ENGINE SAFETY NOTICE
DANGER  NEVER run engine without an air filter or with a dirty air
filter. Severe engine damage may occur. Service air filter
 The engine fuel exhaust gases contain poisonous carbon
frequently to prevent engine malfunction.
monoxide. This gas is colorless and odorless, and can
cause death if inhaled.  NEVER tamper with the factory settings
of the engine or engine governor. Damage
 The engine of this equipment
to the engine or equipment can result
requires an adequate free
if operating in speed ranges above the
flow of cooling air. NEVER
maximum allowable.
operate this equipment in
any enclosed or narrow area  Wet stacking is a common problem with diesel engines
where free flow of the air is which are operated for extended periods with light or
restricted. If the air flow is no load applied. When a diesel engine operates without
restricted it will cause injury to people and property and sufficient load (less than 40% of the rated output), it will
serious damage to the equipment or engine. not operate at its optimum temperature. This will allow
unburned fuel to accumulate in the exhaust system,
WARNING
which can foul the fuel injectors, engine valves and
 DO NOT place hands or fingers inside engine exhaust system, including turbochargers, and reduce
compartment when engine is running. the operating performance.
 NEVER operate the engine with heat shields or In order for a diesel engine to operate at peak efficiency,
guards removed. it must be able to provide fuel and air in the proper ratio
and at a high enough engine temperature for the engine
 Keep fingers, hands hair and clothing away to completely burn all of the fuel.
from all moving parts to prevent injury.
Wet stacking does not usually cause any permanent
 DO NOT remove the radiator cap while the damage and can be alleviated if additional load is
engine is hot. High pressure boiling water applied to relieve the condition. It can reduce the system
will gush out of the radiator and severely performance and increase maintenance. Applying an
scald any persons in the general area of increasing load over a period of time until the excess
the generator. fuel is burned off and the system capacity is reached
 DO NOT remove the coolant drain plug while the engine usually can repair the condition. This can take several
is hot. Hot coolant will gush out of the coolant tank and hours to burn off the accumulated unburned fuel.
severely scald any persons in the general area of the  State Health Safety Codes and Public Resources
generator. Codes specify that in certain locations, spark arresters
 DO NOT remove the engine oil drain plug while the must be used on internal combustion engines that use
engine is hot. Hot oil will gush out of the oil tank and hydrocarbon fuels. A spark arrester is a device designed
severely scald any persons in the general area of the to prevent accidental discharge of sparks or flames
generator. from the engine exhaust. Spark arresters are qualified
and rated by the United States Forest Service for this
CAUTION purpose. In order to comply with local laws regarding
 NEVER touch the hot exhaust manifold, spark arresters, consult the engine distributor or the
muffler or cylinder. Allow these parts to cool local Health and Safety Administrator.
before servicing equipment.

PAGE 6 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


SAFETY INFORMATION
FUEL SAFETY  Make sure the hitch and coupling of the towing vehicle
are rated equal to, or greater than the trailer “gross
DANGER vehicle weight rating.”
 DO NOT start the engine near spilled fuel or combustible  ALWAYS inspect the hitch and coupling for wear. NEVER
fluids. Diesel fuel is extremely flammable and its vapors tow a trailer with defective hitches, couplings, chains, etc.
can cause an explosion if ignited.
 Check the tire air pressure on both towing vehicle and
 ALWAYS refuel in a well-ventilated area, away from trailer. Trailer tires should be inflated to 50 psi cold.
sparks and open flames. Also check the tire tread wear on both vehicles.
 ALWAYS use extreme caution when working with  ALWAYS make sure the trailer is equipped with a safety
flammable liquids. chain.
 DO NOT fill the fuel tank while the engine is running  ALWAYS properly attach trailer’s safety chains to towing
or hot. vehicle.
 DO NOT overfill tank, since spilled fuel could ignite if it  ALWAYS make sure the vehicle and trailer directional,
comes into contact with hot engine parts or sparks from backup, brake and trailer lights are connected and
the ignition system. working properly.
 Store fuel in appropriate containers, in well-ventilated  DOT Requirements include the following:
areas and away from sparks and flames.
• Connect and test electric brake operation.
 NEVER use fuel as a cleaning agent.
• Secure portable power cables in cable tray with tie
 DO NOT smoke around or near the wraps.
equipment. Fire or explosion could result
from fuel vapors or if fuel is spilled on a  The maximum speed for highway towing is 55 MPH unless
hot engine. posted otherwise. Recommended off-road towing is not to
exceed 15 MPH or less depending on type of terrain.
TOWING SAFETY
 Avoid sudden stops and starts. This can cause skidding,
CAUTION or jack-knifing. Smooth, gradual starts and stops will
improve towing.
 Check with your local county or state safety
towing regulations, in addition to meeting  Avoid sharp turns to prevent rolling.
Department of Transportation (DOT)  Trailer should be adjusted to a level position at all times
Safety Towing Regulations, before towing when towing.
your generator.
 Raise and lock trailer wheel stand in up position when
 Refer to MQ Power trailer manual for additional safety towing.
information.
 Place chock blocks underneath wheel to prevent rolling
 In order to reduce the possibility of an accident while while parked.
transporting the generator on public roads, ALWAYS
make sure the trailer that supports the generator and  Place support blocks underneath the trailer’s bumper
the towing vehicle are mechanically sound and in good to prevent tipping while parked.
operating condition.
 Use the trailer’s swivel jack to adjust the trailer height to
 ALWAYS shutdown engine before transporting a level position while parked.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 7


SAFETY INFORMATION
ELECTRICAL SAFETY  Make sure power cables are securely connected to the
generator’s output receptacles. Incorrect connections
DANGER may cause electrical shock and damage to the
 DO NOT touch output terminals during generator.
operation. Contact with output terminals NOTICE
during operation can cause electrocution,
electrical shock or burn.  ALWAYS make certain that proper power or extension
cord has been selected for the job. See Cable Selection
 The electrical voltage required to Chart in this manual.
operate the generator can cause severe
injury or even death through physical contact with live Grounding Safety
circuits. Turn generator and all circuit breakers OFF
before performing maintenance on the generator or DANGER
making contact with output terminals.  ALWAYS make sure that electrical circuits are properly
 NEVER insert any objects into the output grounded to a suitable earth ground (ground rod) per
receptacles during operation. This is the National Electrical Code (NEC) and local codes
extremely dangerous. The possibility exists before operating generator. Severe injury or death by
of electrical shock, electrocution or electrocution can result from operating an ungrounded
death. generator.

 Backfeed to a utility system can cause  NEVER use gas piping as an electrical ground.
electrocution and/or property damage. BATTERY SAFETY
NEVER connect the generator to a
building’s electrical system without DANGER
a transfer switch or other approved
 DO NOT drop the battery. There is a possibility that the
device. All installations should be
battery will explode.
performed by a licensed electrician in accordance with
all applicable laws and electrical codes. Failure to do so  DO NOT expose the battery to open flames,
could result in electrical shock or burn, causing serious sparks, cigarettes, etc. The battery contains
injury or even death. combustible gases and liquids. If these
gases and liquids come into contact with a
Power Cord/Cable Safety flame or spark, an explosion could occur.
DANGER WARNING
 NEVER let power cords or cables lay in water.  ALWAYS wear safety glasses when
 NEVER stand in water while AC power from the handling the battery to avoid eye irritation.
generator is being transferred to a load. The battery contains acids that can cause
injury to the eyes and skin.
 NEVER use damaged or worn cables or cords when
connecting equipment to generator. Inspect for cuts in  Use well-insulated gloves when picking up the battery.
the insulation.  ALWAYS keep the battery charged. If the battery is not
 NEVER grab or touch a live power charged, combustible gas will build up.
cord or cable with wet hands. The  ALWAYS recharge the battery in a well-ventilated
possibility exists of electrical shock, environment to avoid the risk of a dangerous concentration
electrocution or death. of combustible gasses.

PAGE 8 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


SAFETY INFORMATION
 If the battery liquid (dilute sulfuric acid) comes into EMISSIONS INFORMATION
contact with clothing or skin, rinse skin or clothing
immediately with plenty of water. NOTICE
 If the battery liquid (dilute sulfuric acid) comes into The diesel engine used in this equipment has been
contact with eyes, rinse eyes immediately with plenty designed to reduce harmful levels of carbon monoxide
of water and contact the nearest doctor or hospital to (CO), hydrocarbons (HC) and nitrogen oxides (NOx)
seek medical attention. contained in diesel exhaust emissions.

CAUTION This engine has been certified to meet US EPA Evaporative


emissions requirements in the installed configuration.
 ALWAYS disconnect the NEGATIVE battery terminal
before performing service on the generator. Attempting to modify or make adjustments to the engine
emission system by unauthorized personnel without proper
 ALWAYS keep battery cables in good working condition. training could damage the equipment or create an unsafe
Repair or replace all worn cables. condition.
ENVIRONMENTAL SAFETY/DECOMMISSIONING Additionally, modifying the fuel system may adversely affect
evaporative emissions, resulting in fines or other penalties.
NOTICE
Emission Control Label
Decommissioning is a controlled process used to safely
retire a piece of equipment that is no longer serviceable. The emission control label is an integral part of the emission
If the equipment poses an unacceptable and unrepairable system and is strictly controlled by regulations.
safety risk due to wear or damage or is no longer cost
effective to maintain (beyond life-cycle reliability) and is to The label must remain with the engine for its entire life.
be decommissioned (demolition and dismantlement),be If a replacement emission label is needed, please contact
sure to follow rules below. your authorized engine distributor.
 DO NOT pour waste or oil directly onto the ground, down
a drain or into any water source.
 Contact your country's Department of
Public Works or recycling agency in your
area and arrange for proper disposal of
any electrical components, waste or oil
associated with this equipment.
 When the life cycle of this equipment is over, remove
battery and bring to appropriate facility for lead
reclamation. Use safety precautions when handling
batteries that contain sulfuric acid.
 When the life cycle of this equipment is over, it is
recommended that the trowel frame and all other metal
parts be sent to a recycling center.
Metal recycling involves the collection of metal from
discarded products and its transformation into raw
materials to use in manufacturing a new product.
Recyclers and manufacturers alike promote the process
of recycling metal. Using a metal recycling center
promotes energy cost savings.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 9


GENERATOR/ENGINE SPECIFICATIONS
Table 1. Generator Specifications
Model DCA45SSIU4F
Revolving field, self ventilated,
Type
open protected type synchronous generator
Armature Connection Star with Neutral Zigzag
Phase 3Ø 3Ø
Standby Output 40 KW (50 KVA) 28.8 KW
Prime Output 36 KW (45 KVA) 26 kW
3Ø Voltage (L-L/L-N)
208Y/120, 220Y/127, 240Y/139 N/A
Voltage Selector Switch at 3Ø 240/139
3Ø Voltage (L-L/L-N)
416Y/240, 440Y/254, 480Y/277 N/A
Voltage Selector Switch at 3Ø 480/277
1Ø Voltage (L-L/L-N)
N/A 240/120
Voltage Selector Switch at 1Ø 240/120
Power Factor 0.8 1.0
Frequency 60 Hz
Speed 1800 rpm
Aux. AC Power Single Phase, 60 Hz
Aux. Voltage/Output 4.8 Kw (2.4 kW x 2)
Dry Weight 2,337 lbs. (1,060 kg)
Wet Weight 2,976 lbs. (1,350 kg)
Table 2. Engine Specifications
Model Isuzu 4LE2X Tier 4 Final
Water-cooled, direct injection, turbo-charged
Type
air cooled EGR
No. of Cylinders 4 cylinders
Bore x Stroke 3.35 in. x 3.78 in. (85 mm x 96 mm)
Displacement 133 cu. in. (2.17 liter)
Rated Output 59 HP at 1800 rpm
Starting Electric
Coolant Capacity (Radiator) 4.44 gallons (16.8 liters)1
Lube Oil Capacity 3.2 gallons (12.2 liters)2
Lubricating Type Oil API service class CJ-4 SAE 15W-40
Fuel Type #2 Diesel Fuel (Ultra low sulfur diesel fuel only)
Fuel Leak Warning Capacity 21.1 gal. (80 liters)
Fuel Tank Capacity 79.2 gallons (300 liters)
2.93 gal. (11.1 L)/hr at full load 2.20 gal. (8.31 L)/hr at 3/4 load
Fuel Consumption
1.60 gal. (6.04 L)/hr at 1/2 load 1.04 gal. (3.92 L)/hr at 1/4 load
Battery 27 (CCA 0°F 525A) X 1
1
Includes engine and radiator hoses
2
Includes filters

PAGE 10 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


GENERATOR DIMENSIONS
B C

MAXIMUM
LIFTING
POINT
TOP VIEW
5,150 lbs. D
(2,325 kg)

A E

45

SIDE VIEW

FRONT VIEW
Figure 1. Dimensions

Table 3. Generator Dimensions


G Reference
Dimension in. (mm) Reference Letter Dimension in. (mm)
Letter
A 28.34 (720) E 26.18 (665)
B 28.34 (720) F 83.86 (2,130)
C 26.18 (665) G 61.02 (1,550)
D 32.28 (820) H 37.40 (950)

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 11


INSTALLATION
CONNECTING THE GROUND The ground cable should be #8 size wire (aluminum)
minimum. If copper wire is used, #10 size wire minimum
Consult with local Electrical and Safety Codes for proper should be used.
connection based on condition of use.
Connect one end of the ground cable terminal to the
EXAMPLE of how to ground the unit if the condition generator ground point (Figure 2). Connect the other end
of use requires such a device: of the ground cable to a suitable earth ground (ground rod).
The ground terminal on the generator should always be
used to connect the generator to a suitable ground when
required.

GENERATOR
GROUND LUG

IF THE GENERATOR IS PROVIDING


ELECTRIC POWER TO A BUILDING
VIA A TRANSFER SWITCH IT MUST
GROUND CABLE BE CONNECTED TO A GROUND ROD.

U M)
NIM
M (MI
4
./2.
REFERENCE 8 FT
NEC 250

Figure 2. Typical Generator Grounding Application

PAGE 12 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


INSTALLATION
OUTDOOR INSTALLATION GENERATOR GROUNDING
Install the generator in a area that is free of debris, NOTICE
bystanders, and overhead obstructions. Make sure the The Occupational Safety and Health Administration
generator is on secure level ground so that it cannot slide (OSHA) and the National Electrical Code (NEC)
or shift around. Also install the generator in a manner so recommend that if the generator is providing electrical
that the exhaust will not be discharged in the direction of power to a structure (home, office shop, trailer or
nearby homes. similar) it must be connected to a grounding electrode
The installation site must be relatively free from moisture system, such as driven ground rod (Figure 2).
and dust. All electrical equipment should be protected from If applicable, to guard against electrical shock and possible
excessive moisture. Failure to do will result in deterioration damage to the equipment, it is important to provide a good
of the insulation and will result in short circuits and EARTH ground, (Figure 2).
grounding.
NOTICE
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to ALWAYS check with State, Province, District and
engine and alternator parts. Municipalities for electrical grounding requirements
before using generator.
CAUTION
Pay close attention to ventilation when operating the Article 250 (Grounding) of the NEC handbook provides
generator inside tunnels and caves. The engine exhaust guidelines for proper grounding and specifies that the cable
contains noxious elements. Engine exhaust must be ground shall be connected to the grounding system of the
routed to a ventilated area. building as close to the point of cable entry as practical.
NEC article 250 specifices the following grounding
INDOOR INSTALLATION requirements:
Exhaust gases from diesel engines are extremely 1. Use one of the following wire types to connect the
poisonous. Whenever an engine is installed indoors the generator to earth ground.
exhaust fumes must be vented to the outside. The engine a. Copper 10 AWG (5.3 mm2) or larger.
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can b. Aluminum 8 AWG (8.4 mm2) or larger.
cause excessive back pressure which will cause the engine
2. When grounding of the generator (Figure 2) is required,
to heat excessively and possibly burn the valves.
connect one end of the ground cable to the ground lug
MOUNTING on the generator. Connect the other end of the ground
cable to the ground rod (earth ground).
The generator must be mounted on a solid foundation such
as concrete) and set firmly on the foundation to isolate 3. NEC article 250 specifies that the earth ground rod
vibration of the generator when it is running. The generator should be buried a minimum of 8 ft. into the ground.
must set at least 6 inches above the floor or grade level NOTICE
(in accordance to NFPA 110, Chapter 54.1). DO NOT
remove the metal skids on the bottom of the generator. When connecting the generator to any buildings
They are to resist damage to the bottom of the generator electrical system ALWAYS consult with a licensed
and to maintain alignment. electrician.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 13


GENERAL INFORMATION
GENERATOR OPEN DELTA EXCITATION SYSTEM
This generator (Figure 3) is designed as a high quality Each generator is equipped with the state of the art “Open-
portable (requires a trailer for transport) power source for Delta” excitation system. The open delta system consist
telecom sites, lighting facilities, power tools, submersible of an electrically independent winding wound among
pumps and other industrial and construction machinery. stationary windings of the AC output section.
ENGINE OPERATING PANEL There are four connections of the open delta A, B, C and
The “Operating Panel” is provided with the following: D. During steady state loads, the power from the voltage
„„ECU Controller regulator is supplied from the parallel connections of A to
„„Gauge Unit Assembly B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectified and are the
• Oil Pressure Gauge
excitation current for the exciter section.
• Water Temperature Gauge
• Charging Voltmeter When a heavy load, such as a motor starting or a short
• Fuel Gauge circuit occurs, the automatic voltage regulator (AVR)
• Tachometer switches the configuration of the open delta to the series
„„Panel Light/Panel Light switch connection of B to C. This has the effect of adding the
„„Hour Meter voltages of each phase to provide higher excitation to the
„„Auto Start/Stop Switch/Engine Speed Switch exciter section and thus better voltage response during the
„„Fuel Leak Detected Alarm Lamp/Pre-Heat Lamp application of heavy loads.
„„Engine Warning Lamp (Diagnostics) The connections of the AVR to the AC output windings are
GENERATOR CONTROL PANEL for sensing only. No power is required from these windings.
The “Control Panel” is provided with the following: The open-delta design provides virtually unlimited excitation
„„Frequency Meter (Hz) current, offering maximum motor starting capabilities. The
„„AC Ammeter (Amps) excitation does not have a “fixed ceiling” and responds
„„AC Voltmeter (Volts) according the demands of the required load.
„„Ammeter Change-Over Switch ENGINE
„„Voltmeter Change-Over Switch This generator is powered by a 4 cylinder, 4-cycle water
„„Voltage Regulator cooled, direct injection, turbocharged, air cooled and EGR
„„3-Pole, 110 amp Main Circuit Breaker Isuzu 4LE2X diesel engine. This engine is designed to
„„“Control Box” (Located Behind Control Panel) meet every performance requirement for the generator.
• Automatic Voltage Regulator Reference Table 2 for engine specifications.
• Current Transformer In keeping with MQ Power’s policy of constantly improving
• Over-Current Relay its products, the specifications quoted herein are subject
• Starter Relay to change without prior notice.
OUTPUT TERMINAL PANEL ELECTRIC GOVERNOR SYSTEM
The “Output Terminal Panel” is provided with the following: The electric governor system controls the RPMs of the engine.
„„Three 120/240V output receptacles (CS-6369), 50A When the engine demand increases or decreases, the
„„Three auxiliary circuit breakers, 50A governor system regulates the frequency variation to ±.25%.
„„Two 120V output receptacles (GFCI), 20A EXTENSION CABLES
„„Two GFCI circuit breakers, 20A When electric power is to be provided to various tools or
„„Five output terminal lugs (3Ø power) loads at some distance from the generator, extension cords
OPTIONS are normally used. Cables should be sized to allow for
„„Battery Charger distance in length and amperage so that the voltage drop
„„Jacket Water Heater between the generator and point of use (load) is held to
„„Camlock Connector a minimum. Use the cable selection chart (Table 6) as a
„„Low Coolant Level Switch guide for selecting proper extension cable size.
PAGE 14 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)
GENERATOR MAJOR COMPONENTS

3 PHASE 1 PHASE
480/277 240/120

45
PRESS TO LOCK

U V W O

1
3

9 8 7 6 5 4

10 11 12
Table 4. Generator Major Components
25
50
75 140
180
220 12
18
24
ITEM NO. DESCRIPTION
1 Muffler Assembly
PSI °F VOLTS
0 100 100 260 6 30
INCREASE DECREASE
OIL PRESS WATER TEMP BATTERY
®
ECU Intergrated Gauge Control

Low Oil Pressure ½ 150


120 180
High Temp. 60
Over Crank °F RPMX10
E F 0 210
Over Speed
V Engine Started
FUEL SPEED

U W

2 Voltage Selector Switch Assembly


OFF

V-W

U-V W-U

OFF

3 Generator Assembly
4 Output Terminal Assembly
5 Circuit Breaker Assembly
6 Battery Assembly
7 Engine Assembly
8 Fuel Tank Assembly
9 Enclosure Assembly
10 Main Circuit Breaker
11 Generator Control Panel Assembly
Figure 3. GeneratorMajor Components 12 Gauge Unit Assembly

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 15


ENGINE/GENERATOR CONTROL PANEL

25
50
75
A 180
B 18
C
140 220 12 24

PSI °F VOLTS
0 100 100 260 6 30

OIL PRESS WATER TEMP BATTERY

ECU®Intergrated Gauge Control

F Low Oil Pressure D ½ E 120


150
180
G High Temp. 60
°F RPMX10
H Over Crank E F 0 210
I Over Speed

J Engine Started FUEL SPEED

3 4

5
8 25
50
75
180 18
140 220 12 24
2 0
PSI
100 100
°F
260 6
VOLTS
30
INCREASE DECREASE
OIL PRESS WATER TEMP BATTERY

ECU®Intergrated Gauge Control

Low Oil Pressure ½ 150


120 180
High Temp. 60
Over Crank
9 Over Speed
E
°F
F 0
RPMX10
210

V Engine Started
FUEL SPEED

6 U W

OFF
11 13
10
V-W
12 14
7 U-V W-U

OFF
15 16

Figure 4. Engine/Generator Control Panel

PAGE 16 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


ENGINE/GENERATOR CONTROL PANEL
The definitions below describe the controls and functions 3. Panel Light Switch — When activated will turn on
of the Engine/Generator Control Panel (Figure 4). control panel light.
1. Gauge Unit Assembly — This assembly houses the 4. Panel Light — For operation at night, panel light
various engine monitoring gauges. These gauges illuminates control panel for ease of reading meters
indicate: oil pressure, water temperature, charging and gauges. Make sure panel light switch is in the OFF
voltmeter, fuel and engine speed RPM (tachometer). position when light is not in use.
A. Oil Pressure Gauge — During normal operation 5. Voltage Regulator Control — Allows ±15% manual
this gauge should read approximately 50 psi. (345 adjustment of the generator’s output voltage.
kPa). When starting the generator the oil pressure
may read a little higher, but after the engine warms 6. Ammeter Change-Over Switch — This switch allows
up the oil pressure should return to the correct the AC ammeter to indicate the current flowing to the load
pressure range. connected to any phase of the output terminals, or to be
switched off. This switch does not effect the generator
B. Water Temperature Gauge — During normal output in any fashion, it is for current reading only.
operation this gauge should read approximately
180°F (82°C). 7. Voltmeter Change-Over Switch — This switch allows
the AC voltmeter to indicate phase to phase voltage
C. Charging Voltmeter Gauge — During normal between any two phases of the output terminals or to
operation this gauge indicate minimum 14 VDC. be switched off.
D. Fuel Gauge — Indicates amount of diesel fuel 8. Frequency Meter — Indicates the output frequency
available. in hertz (Hz). Normally 60 Hz.
E. Tachometer Gauge — Indicates engine speed. 9. AC Ammeter — Indicates the amount of current the
This gauge should indicate 1,000 rpm's when the load is drawing from the generator per leg selected by
engine speed switch is placed in the low position.
the ammeter phase-selector switch.
1800 RPM’s when the engine speed switch is
placed in the high position (60 Hz operation). 10. AC Voltmeter — Indicates the output voltage present
F. Low Oil Pressure Warning LED — When on, at the U,V, and W Output Terminal Lugs.
indicates that the engine oil pressure has dropped 11. Fuel Leak Detected Alarm Lamp — This lamp when
to 14.2 psi (98 kPa). This condition will cause the ON indicates that fluids in the containment area have
engine to shutdown. reach a high level.
G. High Temperature Warning LED — When on, 12. Diagnostic Warning Lamp — This lamp will turn on
indicates that the engine coolant has exceeded when an engine fault has occured. Refered to engine
212°F (100°C). This condition will cause the engine fault diagnostics table.
to shutdown. 13. Hour Meter — Indicates amount of time generator
H. Over Crank Warning LED — When on, indicates has been in use.
that the generator has attempted to start and failed
14. Pre Heat Lamp — This lamp will illuminate to indicate
after 3 attempts. The intervals between the 3 start
preheating of the engine glow plugs. When the lamp
cycles is approximately 10 seconds.
turns off, this indicates that the preheat cycle is
I. Over Speed LED — When on, indicates that the complete and the engine will start automatically.
engine is operating at an unsafe speed. This
15. Auto/Start Switch — This switch selects either manual
condition will cause the engine to shutdown.
or automatic operation. Center position is OFF (reset).
J. Engine Started Status LED — When on, indicates
that the generator is operating normally. 16. Engine Speed Switch — This switch controls the
speed of the engine (low/high).
2. Main Circuit Breaker — This three-pole, 110 amp
main breaker is provided to protect the U,V, and W
Output Terminal Lugs from overload.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 17


OUTPUT TERMINAL PANEL FAMILIARIZATION
OUTPUT TERMINAL PANEL OUTPUT TERMINAL FAMILIARIZATION
The Output Terminal Panel (Figure 5) shown below is The “Output Terminal Panel ” (Figure 5) is provided with
located on the right-hand side (left from control panel) of the following:
the generator. Lift up on the cover to gain access to
„„Three 240/139V output receptacles @ 50 amps
receptacles and terminal lugs.
„„Three Aux. Circuit Breakers @ 50 amps
NOTICE
„„Two 120V GFCI receptacles @ 20 amp
Terminal legs “O” and “Ground” are considered bonded
grounds „„Two GFCI Circuit Breakers @ 20 amps
„„Five Output Terminal Lugs ( U, V, W, O, Ground)

1Ø AND 3Ø,
NEUTRAL GROUND
480 -120 VAC
TERMINAL TERMINAL
OUTPUT TERMINALS

HARD WIRE
HOOKUP PANEL

U V W O

BLACK RED BLUE WHITE GREEN

MQ
PO
WE
R

CIRCUIT BREAKERS
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
FOR CS-6369 TWIST
LOCK RECEPTACLES

120 VAC, 20 AMP


GFCI RECEPTACLES

ACCESS DOOR
LIFT TO OPEN

RECEPTACLE
AND
CIRCUIT BREAKER
PANEL Y

W X
CS-6369
TWIST-LOCK
AUX. POWER RECEPTACLES
240/139V, 50 AMPS

Figure 5. Output Terminal Panel

PAGE 18 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) GFCI receptacles. Remember the load output (current) on
receptacles provided on the output terminal panel. These all three receptacles is dependent on the load requirements
receptacles can be accessed in any voltage selector of the output terminal lugs.
switch configuration. Each receptacle is protected by a
20 amp circuit breaker. These breakers are located directly Turn the voltage regulator control knob (Figure 8) on the
above the GFCI receptacles. Remember the load output control panel to obtain the desired voltage. Turning the knob
(current) of both GFCI receptacles is dependent on the clockwise will increase the voltage, turning the knob
load requirements of the U, V, and W output terminal lugs. counter-clockwise will decrease the voltage.
Pressing the reset button resets the GFCI receptacle after
being tripped. Pressing the test button (See Figure 6) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Figure 8. Voltage Regulator Control Knob

Removing the Plastic Face Plate (Hard Wire


Hookup Panel)
The Output Terminal Lugs are protected by a plastic
face plate cover (Figure 9). Un-screw the securing bolts
and lift the plastic terminal cover to gain access to the
terminal enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
Figure 6. G.F.C.I. Receptacle

Twist Lock Dual Voltage 120/240 VAC Receptacles


There are three 240/139V, 50 amp auxiliary twist-lock (CS-
6369) receptacles (Figure 7) provided on the output
terminal panel. These receptacles can only be accessed
when the voltage selector switch is configured for single-
phase 240/120 application

Figure 9. Plastic Face Plate


(Output Terminal Lugs)

Figure 7. 240/139V Twist-Lock Auxiliary


Receptacles

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 19


OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads Over Current Relay
Loads can be connected to the generator by various An over current relay (Figure 11) is connected to the main
methods, output terminal lugs, camlocks or the convenience circuit breaker. In the event of an overload, both the circuit
receptacles (Figure 10). Make sure to read the operation breaker and the over current relay may trip. If the circuit
manual before attempting to connect a load to the generator. breaker can not be reset, the reset button on the over
current relay must be pressed. The over current relay is
To protect the output terminals from overload, a 3-pole,
located in the control box.
110A main circuit breaker is provided. Make sure to switch
ALL circuit breakers to the OFF position prior to starting
the engine.
CS-6369
TWIST-LOCK
RECEPTACLES

HARD WIRE
HOOKUP PANEL
LOAD

U
V O
W

GFCI
RECEPTACLE

LOAD GROUND LOAD

NEUTRAL

Figure 11. Over Current Relay


CAMLOCKS (OPTION)
NOTICE
Remember the overcurrent relay monitors the current
flowing from the U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or over current condition,
it will automatically trip the 110 amp main breaker.
To restore power to the Output Terminal Panel, press
Figure 10. Connecting Loads the reset button on the overcurrent relay and place the
main circuit breaker in the closed position (ON).

PAGE 20 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


LOAD APPLICATION
SINGLE PHASE LOAD THREE PHASE LOAD
Always be sure to check the nameplate on the generator When calculating the power requirements for 3-phase
and equipment to insure the wattage, amperage, frequency, power use the following equation:
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require NOTICE
130—150% more wattage than the rating on the nameplate, If 3Ø load (kVA) is not given on the equipment
as the wattage is influenced by the efficiency, power factor nameplate, approximate 3Ø load may be determined
and starting system of the equipment. by multiplying voltage by amperage by 1.732
NOTICE
NOTICE
If wattage is not given on the equipment’s nameplate,
approximate wattage may be determined by multiplying Motors and motor-driven equipment draw much greater
nameplate voltage by the nameplate amperage. current for starting than during operation.

An inadequate size connecting cable which cannot carry the


WATTS = VOLTAGE x AMPERAGE
required load can cause a voltage drop which can burn out
The power factor of this generator is 0.8. See Table 5 below the appliance or tool and overheat the cable. See Table 6.
when connecting loads.
„„When connecting a resistance load such as an
Table 5. Power Factor By Load incandescent lamp or electric heater, a capacity of up
Type of Load Power Factor to the generating set’s rated output (kW) can be used.
Single-phase induction motors 0.4-0.75 „„When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set’s rated output (kW)
Electric heaters, incandescent lamps 1.0 multiplied by 0.6 can be used.
Fluorescent lamps, mercury lamps 0.4-0.9
„„When connecting an electric drill or other power tools,
Electronic devices, communication pay close attention to the required starting current
1.0
equipment capacity.
Common power tools 0.8
When connecting ordinary power tools, a capacity of up to
the generating set’s rated output (kW) multiplied by 0.8 can
Table 6. Cable Selection (60 Hz, Single Phase Operation) be used.
Load in Watts Maximum Allowable Cable Length
Current
in
DANGER
At 100 At 200 #10 Wire #12 Wire #14 Wire #16 Wire
Amperes Volts Volts
Before connecting this generator to any building’s
2.5 300 600 1000 ft. 600 ft. 375 ft. 250 ft.
electrical system, a licensed electrician must install
5 600 1200 500 ft. 300 ft. 200 ft. 125 ft.
an isolation (transfer) switch. Serious damage to
7.5 900 1800 350 ft. 200 ft. 125 ft. 100 ft. the building’s electrical system may occur without this
10 1200 2400 250 ft. 150 ft. 100 ft. transfer switch.
15 1800 3600 150 ft. 100 ft. 65 ft.
20 2400 4800 125 ft. 75 ft. 50 ft.
CAUTION: Equipment damage can result from low voltage

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 21


GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES Maximum Amps
A wide range of voltages are available to supply voltage for Table 8 shows the maximum amps the generator can
many different applications. Voltages are selected by using provide. DO NOT exceed the maximum amps as listed.
the voltage selector switch (Figure 12). To obtain some of
the voltages as listed in Table 7 (see below) will require a Table 8. Generator Maximum Amps
fine adjustment using the voltage regulator (VR) control Rated Voltage Maximum Amps
knob located on the control panel.
100 amps (4 wire)
1Ø 120 Volt
Voltage Selector Switch 108 amps X 2 (Zigzag)
50 amps (4 wire)
The voltage selector switch (Figure 12) is located above 1Ø 240 Volt
108 amps (Zigzag)
the output terminal panel’s Hard Wire Hook-up Panel. It
3Ø 240 Volt 108 amps
has been provided for ease of voltage selection..
3Ø 480 Volt 54 amps

GFCI Receptacle Load Capability


The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist lock auxiliary receptacles.
Figure 15 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
Figure 12. Voltage Selector Switch
Table 9. 1Ø GFCI Receptacle Load Capacity
CAUTION KW in Use Available Load
Twist Lock (C6369) Current (Amps)
NEVER change the position of the voltage selector GFCI Duplex
Switch while the engine is running. ALWAYS place 1Ø 240/120V
5-20R 120V
circuit breaker in the OFF position before selecting 26 0
voltage. 24.8 5 amps/receptacle
23.6 10 amps/receptacle
Table 7. Voltages Available 22.4 15 amps/receptacle
UVWO Output Voltage Selector Switch Voltage Selector Switch 21.2 20 amps/receptacle
Terminal Lugs 3-Phase 240/139V Position 3-Phase 480/270V Position

3Ø Line-Line 208V 220V 240V 416V 440V 480V


Table 10. 3Ø Generator Maximum Amps
1Ø Line-Neutral 120V 127V 139V 240V 254V 277V
KVA in Use Available Load
Voltage Selector Switch Single-Phase 240/120V Position (UVWO Terminals) Current (Amps)
1Ø Line-Neutral/ 120V 240V GFCI Duplex
N/A N/A N/A N/A
Line-Line Line-Neutral Line-Line 3Ø 240/480V
5-20R 120V
45 0 amps/receptacle
40.9 5 amps/receptacle
36.7 10 amps/receptacle
32.6 15 amps/receptacle
28.4 20 amps/receptacle

PAGE 22 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


GENERATOR OUTPUTS/GAUGE READING
HOW TO READ THE AC AMMETER AND AC AC Ammeter Gauge Reading
VOLTAGE GAUGES
Place the AC Ammeter Change-Over Switch (Figure 16)
The AC ammeter and AC voltmeter gauges are controlled in the U position and observe the current reading (load
by the AC ammeter and AC voltmeter change-over switches. drain) on the U terminal as indicated on the AC Ammeter
Gauge (Figure 17). This process can be repeated for
Both of these switches are located on the control panel and terminals V and W.
DO NOT effect the generator output. They are provided to
help observe how much power is being supplied, produced
at the UVWO terminals lugs.
Before taking a reading from either gauge, set the Voltage
Selector switch (Figure 13) to the position which produces
the required voltage (For example, for 3Ø 240V, choose the
center 3Ø 240/139V position on the voltage selector switch.
Figure 16. AC Ammeter Figure 17. AC Ammeter
Change-Over Switch (Amp reading on U Lug)

NOTICE
The ammeter gauge will only show a reading when
the Output Terminal Lugs are connected to a load
and in use.

Figure 13. Voltage Selector Switch-


240/3Ø Position

AC Voltmeter Gauge Reading


Place the AC Voltmeter Change-Over Switch (Figure 14)
in the W-U position and observe the phase to phase voltage
reading between the W and U terminals as indicated on
the AC Voltmeter Gauge (Figure 15).

Figure 14. AC Voltmeter Figure 15. AC Voltmeter Gauge


Change-Over Switch (Volt reading on W-U Lug)

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 23


OUTPUT TERMINAL PANEL CONNECTIONS
UVWO TERMINAL OUTPUT VOLTAGES 3. Turn the voltage regulator knob (Figure 20) clockwise
to increase voltage output, turn counterclockwise to
Various output voltages can be obtained using the UVWO decrease voltage output. Use voltage regulator
output terminal lugs. The voltages at the terminals are adjustment knob whenever fine tuning of the output
dependent on the position of the Voltage Selector Switch voltage is required.
and the adjustment of the Voltage Regulator Control
Knob.
Remember the voltage selector switch determines the
range of the output voltage. The voltage regulator (VR) Figure 20. Voltage Regulator Knob
allows the user to increase or decrease the selected
3Ø-208V/1Ø-120V UVWO Terminal Output Voltages
voltage.
1. Place the voltage selector switch in the 3Ø 240/139
3Ø-240V UVWO Terminal Output Voltages position as shown in Figure 18.
1. Place the voltage selector switch in the 3Ø 240/139 2. Connect the load wires to the UVWO terminals as
position as shown in Figure 18. shown in Figure 21.

Figure 21. UVWO Terminal Lugs


Figure 18. Voltage Selector Switch
3Ø-208/1Ø-120V Connections
3Ø-240/139V Position
2. Connect the load wires to the UVWO terminals as NOTICE
shown in Figure 19. To achieve a 3Ø 208V output the voltage selector switch
must be in the 3Ø-240/139 position and the voltage
regulator must be adjusted to 208V.

Figure 19. UVWO Terminal Lugs

PAGE 24 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480/277V UVWO Terminal Output Voltages 1Ø-240/120V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 3Ø 480/277 1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 22. position as shown in Figure 24.

Figure 22. Voltage Selector Switch Figure 24. Voltage Selector Switch
3Ø-480/277V Position 1Ø-240/120V Position
2. Connect the load wires to the UVWO terminals as 2. Connect the load wires to the UVWO terminals as
shown in Figure 23. shown in Figure 25.

Figure 23. UVWO Terminal Lugs 3Ø-480V Figure 25. UVWO Terminal Lugs
Connections 1Ø-240/120V Connection
NOTICE 3. Turn the voltage regulator knob (Figure 20) clockwise
ALWAYS make sure that the connections to the UVWO to increase voltage output, turn counterclockwise
terminals are secure and tight. The possibility of arcing to decrease voltage output. Use voltage regulator
exists, that could cause a fire. adjustment knob whenever fine tuning of the output
voltage is required.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 25


INSPECTION/SETUP
CIRCUIT BREAKERS DANGER
To protect the generator from an overload, a 3-pole, 110
Fuel spillage on a hot engine can cause
amp, main circuit breaker is provided to protect the U,V,
a fire or explosion. If fuel spillage occurs,
and W Output Terminals from overload. In addition two
wipe up the spilled fuel completely to
single-pole, 20 amp GFCI circuit breakers are provided to
prevent fire hazards. NEVER smoke
protect the GFCI receptacles from overload. Three 50 amp
around or near the generator.
load circuit breakers have also been provided to protect the
auxiliary receptacles from overload. Make sure to switch
ALL circuit breakers to the OFF position prior to starting Refilling the Fuel System
the engine.
CAUTION
LUBRICATION OIL
Fill the engine crankcase with lubricating oil through the ONLY properly trained personnel who have read
filler hole, but DO NOT overfill. Make sure the generator is and understand this section should refill the fuel tank
level and verify that the oil level is maintained between the system.
two notches (Figure 26) on the dipstick. See Table 11 for
proper selection of engine oil. This generator may have a fuel tank (Figure 27) located
inside the trailer frame. ALWAYS fill the fuel tank with clean
fresh #2 diesel fuel. DO NOT fill the fuel tank beyond its
capacity.
Pay attention to the fuel tank capacity when replenishing
fuel. The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does
Figure 26. Engine Oil Dipstick not have a spout, use a funnel. Wipe up any spilled fuel
When checking the engine oil, be sure to check if the oil is immediately.
clean. If the oil is not clean, drain the oil by removing the
oil drain plug, and refill with the specified amount of oil as
outlined in the John Deere Engine Owner’s Manual. Oil 45
should be warm before draining.
Delo® engine oil is the recommended engine oil for this
generator. When replacing engine oil please refill using FUEL TANK

Delo® 400 LE SAE 15W-40 (API CJ-4) engine oil.


CAP

Table 11. Recommended Motor Oil

FUEL TANK

Figure 27. Trailer Mounted Fuel Tank

FUEL CHECK

PAGE 26 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


INSPECTION/SETUP
Refueling Procedure: 3. NEVER overfill fuel tank — It is important to read the
fuel gauge when filling trailer fuel tank. DO NOT wait
WARNING for fuel to rise in filler neck (Figure 30).
Diesel fuel and its vapors are dangerous
to your health and the surrounding
environment. Avoid skin contact and/or
inhaling fumes.

1. Level Tanks — Make sure fuel cells are level with the
ground. Failure to do so will cause fuel to spill from the
tank before reaching full capacity (Figure 28). Figure 30. Full Fuel Tank
CAUTION CAUTION
ALWAYS place trailer on firm level ground before DO NOT OVERFILL fuel system. Leave room for fuel
refueling to prevent spilling and maximize the amount expansion. Fuel expands when heated (Figure 31).
of fuel that can be pumped into the tank.

300
DO NOT fill on
45 unlevel ground

=
!
!
und
und Gro
ro n le vel
el G U
Figure 31. Fuel Expansion
v
Unle Level Ground
Level Ground

Figure 28. Only Fill on Level Ground


NOTICE
ONLY use #2 diesel fuel when refueling.

2. Open cabinet doors on the “right side” of the generator


(from generator control panel position). Remove fuel
cap and fill tank (Figure 29).

Figure 29. Fueling the Generator

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 27


INSPECTION/SETUP
COOLANT (ANTIFREEZE/SUMMER COOLANT/ Cleaning the Radiator
WATER)
The engine may overheat if the radiator fins become
Isuzu recommends antifreeze/summer coolant for use in their overloaded with dust or debris. Periodically clean the
engines, which can be purchased in concentrate (and mixed radiator fins with compressed air. Cleaning inside the
with 50% demineralized water) or pre-diluted. See the Isuzu machine is dangerous, so clean only with the engine turned
Engine Owner’s Manual for further details. off and the negative battery terminal disconnected.

WARNING AIR CLEANER


If adding coolant/antifreeze mix to the Periodic cleaning/replacement is necessary. Inspect air
radiator, DO NOT remove the radiator cap cleaner in accordance with the Isuzu Engine Owner’s
until the unit has completely cooled. The Manual.
possibility of hot! coolant exists which can
FAN BELT TENSION
cause severe burns.
A slack fan belt may contribute to overheating, or to
Day-to-day addition of coolant is done from the recovery insufficient charging of the battery. Inspect the fan belt for
tank. When adding coolant to the radiator, DO NOT remove damage and wear and adjust it in accordance with the
the radiator cap until the unit has completely cooled. See Isuzu Engine Owner’s Manual.
Table 12 for engine, radiator, and recovery tank coolant
capacities. Make sure the coolant level in the recovery tank The fan belt tension is proper if the fan belt bends 10 to 15
is always between the “H” and the “L” markings. mm (Figure 32) when depressed with the thumb as shown
below.
Table 12. Coolant Capacity
Engine and Radiator 4.44 gal (16.8 liters)
Reserve Tank N/A
Operation in Freezing Weather
When operating in freezing weather, be certain the proper
amount of antifreeze (Table 13) has been added.
Figure 32. Fan Belt Tension

Table 13. Anti-Freeze CAUTION


Operating Temperatures NEVER place hands near the belts or fan
Vol % Freezing Point while the generator set is running.
Anti-Freeze °C °F

50 -37 -34

NOTICE
When the antifreeze is mixed with water, the antifreeze
mixing ratio must be less than 50%.

PAGE 28 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


INSPECTION/SETUP
BATTERY When connecting battery do the following:
This unit is of negative ground DO NOT connect in reverse. 1. NEVER connect the battery cables to the battery
Always maintain battery fluid level between the specified terminals when the Auto-Off/Reset-Manual Switch
marks. Battery life will be shortened, if the fluid level are is in either the AUTO or MANUAL position. ALWAYS
not properly maintained. Add only distilled water when make sure that this switch is in the OFF/RESET
replenishment is necessary. position when connecting the battery.
DO NOT over fill. Check to see whether the battery 2. Place a small amount of battery terminal treatment
cables are loose. Poor contact may result in poor starting compound around both battery terminals. This will
or malfunctions. Always keep the terminals firmly ensure a good connection and will help prevent
tightened. Coating the terminals with an approved battery corrosion around the battery terminals.
terminal treatment compound. Replace battery with only NOTICE
recommended type battery. The battery type used in this
generator is BCI Group 27. If the battery cable is connected incorrectly, electrical
damage to the generator will occur. Pay close attention
The battery is sufficiently charged if the specific gravity to the polarity of the battery when connecting the battery.
of the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
CAUTION
dead and needs to be recharged or replaced.
Inadequate battery connections may cause poor
Before charging the battery with an external electric source,
starting of the generator, and create other malfunctions.
be sure to disconnect the battery cables.
Battery Cable Installation
ALTERNATOR
ALWAYS be sure the battery cables (Figure 33) are
properly connected to the battery terminals as shown below. The polarity of the alternator is negative grounding type.
The red cable is connected to the positive terminal of the When an inverted circuit connection takes place, the
battery, and the black cable is connected to the negative circuit will be in short circuit instantaneously resulting the
terminal of the battery. alternator failure.

CAUTION DO NOT put water directly on the alternator. Entry of water


into the alternator can cause corrosion and damage the
ALWAYS disconnect the negative terminal FIRST and alternator.
reconnect negative terminal LAST.
WIRING
NEGATIVE Inspect the entire generator for bad or worn electrical wiring
or connections. If any wiring or connections are exposed
POSITIVE (insulation missing) replace wiring immediately.
PIPING AND HOSE CONNECTION
Inspect all piping, oil hose, and fuel hose connections for
wear and tightness. Tighten all hose clamps and check
hoses for leaks.
If any hose (fuel or oil) lines are defective replace them
immediately. Before Starting

Figure 33. Battery Connections

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 29


INSPECTION/SETUP
BEFORE STARTING STARTING (MANUAL)
CAUTION 1. Place the Auto-Off/Reset Manual Switch in the
MANUAL position to start the engine (Figure 36).
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.

WARNING Figure 36. Auto-Off/Reset Manual Switch


NEVER manually start the engine with the main, GFCI (Manual Position)
or auxiliary circuit breakers in the ON (closed) position. NOTICE
1. Place the main, G.F.C.I., and aux. circuit breakers If engine fails to start in a specified number attempts,
(Figure 34) in the OFF position prior to starting the the shutdown lamp will illuminate and the Auto-Off/
engine. Reset Switch must be place in the Off/Reset position
before the engine can be restarted.
2. Once the engine starts, let the engine run for 1-2
minutes. Let engine idle longer in cold weather
conditions. Listen for any abnormal noises. If any
abnormalities exist, shut down the engine and correct
the problem.
3. The generator’s frequency meter (Figure 37) should be
Figure 34. Main, Aux. and GFCI displaying the 60 cycle output frequency in HERTZ.
Circuit Breakers (OFF)
2. Make sure the voltage change-over board has been
configured for the desired output voltage.
3. Connect the load to the receptacles or the output
terminal lugs as shown in Figure 10. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup Figure 37. Frequency Meter
panel. 4. The generator’s AC-voltmeter (Figure 38) will display
4. Tighten terminal nuts securely to prevent load wires the generator’s output in VOLTS. If the voltage is not
from slipping out. within the specified tolerance.
5. Close all engine enclosure doors (Figure 35).

Figure 38. Voltmeter


CORRECT INCORRECT

Figure 35. Engine Enclosure Doors

PAGE 30 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


GENERATOR START-UP PROCEDURE (MANUAL MODE)
5. Use the voltage adjustment control knob (Figure 39) 9. The tachometer gauge (Figure 43) will indicate the
to increase or decrease the desired voltage. speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.

150
120 180
60
Figure 39. Voltage Adjust Control Knob 0
RPMX10
210

6. The ammeter (Figure 40) will indicate zero amps with


SPEED
no load applied. When a load is applied, the ammeter
will indicate the amount of current that the load is
drawing from the generator. Figure 43. Engine Tachometer Gauge
10. Place the main, GFCI, and aux. circuit breakers in the
ON position (Figure 44).

Figure 40. Ammeter (No Load)


7. The engine oil pressure gauge (Figure 41) will indicate
the oil pressure of the engine. Under normal operating
conditions the oil pressure is approximately 35 to 65 Figure 44. Main, Aux. and GFCI
psi. (193~586 kPa). Circuit Breakers (ON)

25
50
75 11. Observe the generator’s ammeter (Figure 45) and
PSI
verify it reads the anticipated amount of current with
0 100
respect to the load. The ammeter will only display a
OIL PRESS
current reading if a load is in use.

Figure 41. Oil Pressure Gauge


8. The coolant temperature gauge (Figure 42) will
indicate the coolant temperature. Under normal
operating conditions the coolant temperature should
be between 180°~225°F (75°~95°C) (Green Zone).
Figure 45. Ammeter (Load)
140
180
220 12. The generator will run until manually stopped or an
°F abnormal condition occurs.
100 260

WATER TEMP

Figure 42. Coolant Temperature Gauge

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 31


GENERATOR START-UP PROCEDURE (AUTO MODE)
STARTING AUTO MODE NOTICE
DANGER When the Auto Off/Reset Manual Switch is placed
Before connecting this generator to any in the AUTO position, the engine glow plugs will be
building’s electrical system, a licensed warmed and the engine will start automatically.
electrician must install an isolation When starting generator in AUTO mode use the “Manual
(transfer) switch. Serious damage to Start-up” procedure except where noted (see below).
the building’s electrical system may occur
without this transfer switch. 1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
CAUTION 2. Place the Auto Off/Reset Manual Switch (Figure 46)
in the AUTO position.
When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

NOTICE Figure 46. Auto Off/Reset Manual Switch (AUTO)


When the generator is set in the AUTO mode, the 3. Continue operating the generator as outlined in the
generator will automatically start in the event of Manual Start-up procedure (start at step 3).
commercial power falling below a prescribed level
by means of a contact closure that is generated WARNING
automatically by a transfer switch. NEVER stop the engine suddenly except in an
emergency.
WARNING
When running the generator in the AUTO mode,
remember the generator can start up at any time without
warning. NEVER attempt to perform any maintenance
when the generator is in the auto mode.

CAUTION
The engine speed switch must be set to the “High”
position when running in the auto-start mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.

PAGE 32 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


GENERATOR SHUT-DOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE EMERGENCY SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure: 1. To shut-down the engine in the event of an emergency,
switch the MAIN, GFCI and LOAD (Figure 49) circuit
1. Place both the MAIN, GFCI and LOAD circuit breakers
breakers to OFF position.
as shown in Figure 47 to the OFF position.

Figure 49. Main, Aux. and GFCI


Figure 47. Main, Aux. and GFCI
Circuit Breakers (Emergency OFF)
Circuit Breakers (Normal OFF)
2. Let the engine cool by running it at low speed for 3-5 AUTOMATIC SHUT-DOWN SYSTEM
minutes with no load applied. This unit is equipped with safety devices to automatically
3. Place the Auto Off/Reset Manual Switch (Figure 48) stop the engine in the event of low oil pressure, approximately
in the OFF/RESET position. 14 psi (97 kPa), or high water temperature, approximately
212° F (100° C), overspeed approximately +15%. The alarm
lamps on the ECU illuminate to signify the reason for the
shutdown.
NOTICE
Figure 48. Auto Off/Reset Manual Switch Before inspecting generator, check that the Auto/
(Off/Reset) Manual Switch is in the OFF/RESET position, and
place all circuit breakers in the OFF position. Allow
4. Verify that all status LEDs on the ECU control panel
sufficient time for adequate cooling. When ready to
are OFF (not lit).
restart, complete all steps in the Generator Startup
5. Remove all loads from the generator. Procedure section of this manual.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 33


MAINTENANCE

500 Hrs 3000 Hrs


10 Hrs
Table 14. Inspection/Maintenance 250 Hrs or Every or Every OTHER
DAILY
12 Months 36 Months
Check Engine Oil and Coolant Levels X
Check Fuel Filter/Water Separator Bowl X
Check Air Cleaner X
Check Air Cleaner Element X
Check for Leaks/Hoses/Clamps X
Check for Loosening of Parts X
Change Engine Oil and Oil Filter * 1 X
Clean Unit, Inside and Outside X
Replace Fuel Filter Elements (main and pre) X
Check Engine Mounts X
Service Battery X
Check Air Intake Hoses X
Engine Check Fan Belt Condition X
Check Automatic Belt Tensioner X
Check Electrical Ground Connection X
Drain Inter-cooler X
Clean Radiator, Check Cooling System X
Coolant Solution Analysis, Add SCA's As Required X
Pressure Test Cooling System X
Check Engine Speed X
Test Thermostats X
Test Glow Plugs X
Flush and Refill Cooling System 2 yrs. or 2000 hrs.
Clean Inside of Fuel Tank 1000 hrs.
Replace Air Cleaner Elements * 2
As Required
Measure Insulation Resistance Over 3M ohms X
Generator
Check Rotor Rear Support Bearing X

*1 During initial operation of a new engine, change oil and filter between a minimum of 100 hrs. and a maximum of 250 hrs. Service interval depends
on type of oil.
*2 Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H20).

PAGE 34 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


MAINTENANCE
GENERAL INSPECTION FUEL ADDITION
Prior to each use, the generator should be cleaned and Add diesel fuel (the grade may vary according to season
inspected for deficiencies. Check for loose, missing or and locations).
damaged nuts, bolts or other fasteners. Also check for
fuel, oil, and coolant leaks. Use Table 14 as a general Removing Water from the Fuel Tank
maintenance guideline Engine Side (Refer to the Engine
Instruction Manual). After prolonged use, water and other impurities accumulate
in the bottom of the tank. Occasionally inspect the fuel tank
AIR CLEANER for water contamination and drain the contents if required.
Every 250 hours: Remove air cleaner element (Figure 50)
and clean the heavy duty paper element with light spray of During cold weather, the more empty volume inside the
compressed air. Replace the air cleaner as needed. tank, the easier it is for water to condense. This can be
reduced by keeping the tank full with diesel fuel.
Air Cleaner with Dust Indicator
This indicator (Figure 50) is attached to the air cleaner. Cleaning Inside the Fuel Tank
When the air cleaner element is clogged, air intake Drain the fuel inside the fuel tank completely. Using a spray
restriction becomes greater and the dust indicator signal washer (Figure 51) wash out any deposits or debris that
shows RED meaning the element needs changing or have accumulated inside the fuel tank.
service. After changing the air element, press the dust
indicator button to reset the indicator.

Figure 50. Air Cleaner/Indicator

NOTICE
Figure 51. Fuel Tank Cleaning
The air filter should not be changed until the indicator
reads “RED”. Dispose of old air filter. It may not be
cleaned or reused..

If the engine is operating in very dusty or dry grass


conditions, a clogged air cleaner will result. This can lead to
a loss of power, excessive carbon buildup in the combustion
chamber and high fuel consumption. Change air cleaner
more frequently if these conditions exist.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 35


MAINTENANCE
FUEL TANK INSPECTION CHECK OIL LEVEL
In addition to cleaning the fuel tank, the following Check the crankcase oil level prior to each use, or when the
components should be inspected for wear: fuel tank is filled. Insufficient oil may cause severe damage
to the engine. Make sure the generator is level. The oil
„„Rubber Suspension — look for signs of wear or level must be between the two notches on the dipstick as
deformity due to contact with oil. Replace the rubber shown in Figure 26.
suspension if necessary.
Replacing Oil Filter
„„Fuel Hoses — inspect nylon and rubber hoses for signs
of wear, deterioration and hardening. „„Remove the old oil filter.
„„Fuel Tank Lining — inspect the fuel tank lining for signs „„Apply a film of oil to the gasket on the new oil filter.
of excessive amounts of oil or other foreign matter.
„„Install the new oil filter.
Replacing Fuel Filter „„After the oil cartridge has been replaced, the engine oil
„„Replace the fuel filter cartridge with new one every 500 will drop slightly. Run the engine for a while and check for
hours or so. leaks before adding more oil if needed. Clean excessive
oil from engine.
„„Loosen the drain plug at the lower top of the fuel filter.
Drain the fuel in the fuel body together with the mixed FLUSHING OUT RADIATOR AND REPLACING
water. DO NOT spill the fuel during disassembly. COOLANT
„„Vent any air. „„Open both cocks located at the crankcase side and at
the lower part of the radiator and drain coolant. Open
AIR REMOVAL the radiator cap while draining. Remove the overflow
If air enters the fuel injection system of a diesel engine, tank and drain.
starting becomes impossible. After running out of fuel, „„Check hoses for softening and kinks. Check clamps for
or after disassembling the fuel system, bleed the system signs of leakage.
according to the following procedure. See the Isuzu
Engine Manual for details. „„Tighten both cocks and replace the overflow tank.
To restart after running out of fuel, turn the switch to the „„Replace with coolant as recommended by the engine
“ON” position for 15-30 seconds. Try again, if needed. This manufacturer.
unit is equipped with an automatic air bleeding system. „„Close radiator cap tightly.
„„Flush the radiator by running clean tap water through
radiator until signs of rust and dirt are removed. DO
NOT clean radiator core with any objects, such as a
screwdriver.
WARNING
Allow engine to cool when flushing out
radiator. Flushing the radiator while hot
could cause serious burns from water or
steam.

PAGE 36 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


MAINTENANCE
RADIATOR CLEANING The purpose of these receptacles is to provide power
via commercial power to the water heater and internal
The radiator (Figure 52) should be sprayed (cleaned) with battery charger.
a high pressure washer when excessive amounts of dirt
and debris have accumulated on the cooling fins or tube. These receptacles will ONLY function when commercial
When using a high pressure washer, stand at least 5 feet power has been supplied to them (Figure 53). To apply
(1.5 meters) away from the radiator to prevent damage to commercial power to these receptacles, a power cord of
the fins and tube. adequate size will be required (See Table 6).
When using the generator in hot climates there is no
reason to apply power to jacket water heater. However, if the
generator will be used in cold climates it is always a good
idea to apply power to the jacket water heater at all times.
To apply power to the jacket water heater simply apply
power to the jacket water heater receptacle via commercial
power using a power cord of adequate size.
OU
T
PA PU
NE T T
L A ER
SS MI
BATTERY CHARGER EM NA
120 VAC INPUT BL L
Y
RECEPTACLE

Figure 52. Radiator Cleaning REFERENCE TABLE 7


FOR PROPER SIZE
EXTENSION CORD
GENERATOR STORAGE
For long term storage of the generator the following is WATER HEATER
120 VAC INPUT
recommended: RECEPTACLE

„„Drain the fuel tank completely. Treat with a fuel stabilizer


if necessary.
CONNECT TO
„„Completely drain the oil from the crankcase and refill if EXTERNAL

necessary with fresh oil.


120 VAC POWER
SOURCE

„„Clean the entire generator, internal and external. Figure 53. Battery Charger and Water Heater
„„Cover the generating set and store in a clean, dry place. Power Connections

„„Disconnect the battery. If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
„„Make sure engine coolant is at proper level. (not used) for long periods of time, apply power to the
„„If generator is mounted on a trailer, jack trailer up and battery charger receptacle via commercial power using a
place on blocks so tires do not touch the ground or block power cord of adequate size.
and completely remove the tires. NOTICE
WATER HEATING ELEMENT AND INTERNAL If the generator will be idle (not used) for long periods
BATTERY CHARGER 120VAC INPUT RECEPTACLES of time and to ensure adequate starting capability,
(OPTIONAL) always have power applied to the generator's internal
battery charger.
This generator can be optionally equipped with two 120
VAC, 20 amp input receptacles located on the output
terminal panel.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 37


MAINTENANCE
EMISSION CONTROL
The emission control system employed with the Isuzu
4LE2X diesel engine consist of a Diesel Oxidation Catalyst
(DOC).
This device oxidizes large amounts of harmful nitrogen
oxides (NOx) and particulate matter (PM) which are emitted
by diesel engines. These exhaust emissions pose serious
environmental and health risks. No maintenance or service
is required for the DOC device used on this generator.
Diesel Oxidation Catalyst (DOC)
The DOC does not filter particles it oxidizes them. This
catalyst (honeycomb like structure) uses a chemical
process to break down pollutants in the exhaust stream
into less harmful components. In general this catalyst
collects/burns accumulated particulates. The DOC contains
palladium and platinum which serve as a catalysts to oxidize
hydrocarbons and carbon monoxide.

PAGE 38 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


TROUBLESHOOTING DIAGNOSTIC (LAMP)
The engine controller of this generator diagnoses problems 6. Push and hold the diagnostic button to identify the
(faults/errors) that arise from the engine control system and fault. and verify the following:
the engine itself.
• Diagnostic lamp will start blinking with a pattern
When any engine faults occur during operation of the according to the detected fault code 3 times at a interval
generator the warning lamp (diagnostic lamp) located on rate of 2.4 seconds.
the control panel will turn on. If this conditions occurs please
• If two or more faults code are detected the diagnostic
perform immediately the engine fault code diagnostic
lamp will repeat the detected fault codes blinking
procedure below.
pattern in ascending order. After all the detected fault
ENGINE FAULT CODE DIAGNOSTIC PROCEDURE codes are shown, the process will repeat starting with
the first fault code.
1. Remove all loads from the generator and place all
circuit breakers in the OFF position. • If no fault is detected the diagnostic lamp will blink
repeatedly at a interval rate of 2.4 seconds.
2. Stop the engine, release the retaing screws that secure
the control panel to the generator frame. NOTICE
3. Next, slowly let the control panel fall forward so that For a complete understanding of error codes and
the control box is exposed. troubleshooting procedures, refer to the enclosed
engine instruction manual.
4. To start the diagnostic process, place the diagnostic
switch to the ON (Figure 54) position.
NOTICE
ON The diagnostic lamp will indicate the current fault code
DIAGNOSTIC
SWITCH with the previous fault code in ascending order.
OFF

DIAGNOSTIC
LAMP
DIAGNOSTIC
BUTTON
Also when a fault is detected the fault code will
automatically be saved as the previous code in the
FUEL PUMP
SWITCH
ON ECM even after the fault has been repaired.

NOTICE
If a fault occurs while the engine is running the
Figure 54. Diagnostic Panel diagnostic lamp will turn on indicating only the current
fault. Please note that the fault code (blinking pattern)
NOTICE cannot be shown while the engine is running.
Make sure to place the diagnostic switch back to
the OFF position after completing engine fault code
diagnostic procedures.

5. Verify that the diagnostic lamp is ON. This indicates


that there is a fault/error in the engine or the engine
control system.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 39


TROUBLESHOOTING GENERATOR
Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a
breakdown, use Table 15 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our
company’s business office or service plant.

Table 15. Generator Troubleshooting


Symptom Possible Problem Solution
AC Voltmeter defective? Check output voltage using a voltmeter.
Is wiring connection loose? Check wiring and repair.
No Voltage Output Is AVR defective? Replace if necessary.
Defective Rotating Rectifier? Check and replace.
Defective Exciter Field? Check for approximately 19 ohms across J & K on CN1
Is engine speed correct? Turn engine throttle lever to “High”.
Low Voltage Output Is wiring connections loose? Check wiring and repair.
Defective AVR? Replace if necessary.
Is wiring connections loose? Check wiring and repair.
High Voltage Output
Defective AVR? Replace if necessary.
Short Circuit in load? Check load and repair.
Over current? Confirm load requirements and reduce.
Circuit Breaker Tripped
Defective circuit breaker? Check and replace.
Over current Relay actuated? Confirm load requirement and replace.

PAGE 40 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


TROUBLESHOOTING ENGINE

Troubleshooting (Engine)
Symptom Possible Problem Solution
No Fuel reaching injection pump? Add fuel. Check entire fuel system.
Defective fuel pump? Replace fuel pump.
Fuel filter clogged? Replace fuel filter and clean tank.
Faulty fuel supply line? Replace or repair fuel line.
Check piston, cylinder and valves. Adjust or
Compression too low?
repair per engine repair manual.
Engine will not start or start is delayed,
although engine can be turned over. Fuel pump not working correctly? Repair or replace fuel pump.
Oil pressure too low? Check engine oil pressure.
Comply with cold starting instructions and
Low starting temperature limit exceeded?
proper oil viscosity.
Defective battery? Charge or replace battery.
Check carefully for loosened fuel line
Air or water mixed in fuel system?
coupling, loose cap nut, etc.
Refill engine crankcase with correct type of
Engine oil too thick?
At low temperatures engine will not start. oil for winter environment.
Defective battery? Replace battery.
Fuel filter blocked? Replace fuel filter.
Engine fires but stops soon as starter is
Fuel supply blocked? Check the entire fuel system.
switched off.
Defective fuel pump? Replace fuel pump.
Fuel tank empty? Add fuel.
Fuel filter blocked? Replace fuel filter.
Engine stops by itself during normal
operation. Defective fuel pump? Replace fuel pump.
Mechanical oil pressure shutdown sensor Add oil. Replace low oil shutdown sensor if
stops the engine due to low oil? necessary.
Fuel tank empty? Replace fuel filter.
Fuel filter clogged? Replace fuel filter.
Fuel tank venting is inadequate? Ensure that tank is adequately vented.
Check threaded pipe unions tape and tighten
Leaks at pipe unions?
unions a required.
Low engine power, output and speed. Speed control lever does not remain in
See engine manual for corrective action.
selected position?
Engine oil level too full? Correct engine oil level.
Use No. 2-D diesel fuel only. Check the fuel
Injection pump wear? injection pump element and delivery valve
assembly and replace as necessary.

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 41


TROUBLESHOOTING ENGINE (CONTINUED)
Troubleshooting (Engine) - continued
Symptom Possible Problem Solution
Air filter blocked? Clean or replace air filter.
Low engine power output and low speed,
Incorrect valve clearances? Adjust valves per engine specification.
black exhaust smoke.
Malfunction at injector? See engine manual.
Drain off engine oil down to uppermark on
Too much oil in engine crankcase?
dipstick.
Entire cooling air system contaminated/ Clean cooling air system and cooling fin
blocked? areas.
Fan belt broken or elongated? Change belt or adjust belt tension.
Engine overheats. Coolant insufficient? Replenish coolant.
Radiator net or radiator fin clogged with dust? Clean net or fin carefully.
Fan, radiator, or radiator cap defective? Replace defective part.
Thermostat defective? Check thermostat and replace if necessary.
Head gasket defective or water leakage? Replace parts.

PAGE 42 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


GENERATOR WIRING DIAGRAM

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 43


ENGINE WIRING DIAGRAM

PAGE 44 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (01/16/18)


CONTROLLER WIRING DIAGRAM

DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (01/16/18) — PAGE 45


OPERATION MANUAL

HERE’S HOW TO GET HELP


PLEASE HAVE THE MODEL AND SERIAL
NUMBER ON-HAND WHEN CALLING
UNITED STATES
Multiquip Corporate Office MQ Parts Department
18910 Wilmington Ave. Tel. (800) 421-1244 800-427-1244 Fax: 800-672-7877
Carson, CA 90746 Fax (310) 537-3927 310-537-3700
Contact: mq@multiquip.com
Service Department Warranty Department
800-421-1244 800-421-1244 Fax: 310-943-2249
310-537-3700 310-537-3700
Technical Assistance
800-478-1244 Fax: 310-943-2238
CANADA UNITED KINGDOM
Multiquip Multiquip (UK) Limited Head Office
4110 Industriel Boul. Tel: (450) 625-2244 Unit 2, Northpoint Industrial Estate, Tel: 0161 339 2223
Laval, Quebec, Canada H7L 6V3 Tel: (877) 963-4411 Globe Lane, Fax: 0161 339 3226
Contact: infocanda@multiquip.com Fax: (450) 625-8664 Dukinfield, Cheshire SK16 4UJ
Contact: sales@multiquip.co.uk

© COPYRIGHT 2018, MULTIQUIP INC.

Multiquip Inc, the MQ logo and the MQ Power logo are registered trademarks of Multiquip Inc. and may not be used, reproduced, or altered without written permission. All other
trademarks are the property of their respective owners and used with permission.

This manual MUST accompany the equipment at all times. This manual is considered a permanent part of the equipment and should remain with the unit if resold.

The information and specifications included in this publication were in effect at the time of approval for printing. Illustrations, descriptions, references and technical data contained in
this manual are for guidance only and may not be considered as binding. Multiquip Inc. reserves the right to discontinue or change specifications, design or the information published
in this publication at any time without notice and without incurring any obligations.

Manufactured for
MQ Power Inc.
by
Your Local Dealer is: DENYO CO., LTD, JAPAN

You might also like