Agggoe
Ga
su, parcence ASSEMBLY
nos 305644901
SET oncom = sm
(Contry
Figure 6-10.
Cappilaries.
Since the flow control is a closed loop method of control, trouble shooting
and isolating the Proportional Solenoid Valve (PSV) versus the Flow meter
can be slightly tricky. Let's focus first on the control of the PSV. This
proportional valve is ever neither completely closed nor completely open.
During normal operation its duty cycle range is around 45%- 50%, which
means, 45%-50% open. You can read the PSV duty cycle on the monitor
page by viewing the parameter called Flow Duty.
As the reference and sample period timers count down during their cor-
responding cycles, yau can see the flow duty number changing in arder
to maintain the 50 SCCM flow rate, regardless of the path or leg the gas
is flowing through. If you notice that during the Sample count down
period, the flow seems to be controlled, but during the Reference period
the flow seems to go out of tolerance, then you have isolated the flow
problem to the Reference path or leg. Try removing the Reference dryer
and install a jumper or bypass in its place (1/8 inch tubing). There could
be some obstruction in the dryer (internal). Asa result, even when the
PSV valve is at its max. duty cycle, a higher pressure differential will be
‘Troubleshooting | 6-11