This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC
61850 interface in
Relion 670 series (REB670, REC670, RED670, REG670, REL670, RER670, RES670 and RET670),
Relion 650 series (REB650, REC650, RED650, REL650, REQ650 and RET650) and
Relion SAM600-IO
all of version 2.2.5 and when configured in Edition 2 mode
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-10. The “Ed”
column indicates if the entry is applicable for IEC 61850 Edition 1 and/or Edition 2. A hyphen (“-“) in the
Ed column indicates the PIXIT entry is not applicable for any version.
Do1 2 How to expose required firmware versions not Firmware versions are presented
present in the datamodel on the local HMI
<additional items>
As6 1,2 If association parameters are necessary for Transport selector 0001
association, describe the correct values e.g. Session selector 0001
Presentation selector 00000001
Called values
AP Title n/a
AE Qualifier n/a
As7 1,2 What is the maximum and minimum MMS Max MMS PDU size 32000 bytes
PDU size Min MMS PDU size 1024 bytes
As8 1,2 What is the maximum start up time after a 180 seconds
power supply interrupt
<additional items>
Sr1 1,2 Which analogue value (MX) quality bits are Validity:
supported (can be set by server) Y Good,
Y Invalid,
N Reserved,
Y Questionable
Detail Quality
Y Overflow
Y OutofRange
N BadReference
N Oscillatory
N Failure
Y OldData
N Inconsistent
N Inaccurate
Miscellaneous:
Y Source
Y Test
Y OperatorBlocked
See Remark 1.
Sr2 1,2 Which status value (ST) quality bits are Validity:
supported (can be set by server) Y Good,
Y Invalid,
N Reserved,
Y Questionable
Detail Quality
N BadReference
N Oscillatory
N Failure
Y OldData
N Inconsistent
N Inaccurate
Miscellaneous:
Y Source
Y Test
Y OperatorBlocked
Note: Operator blocked
functionality is only supported
on LN class XCBR and XSWI
containing DPC. No other CDCs
are supported.
See Remark 1.
1
IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set is supported, this shall be indicated within an ICD
file by an enumeration type, where the unsupported values are missing
<additional items>
Remark 1: Writes to the data attribute subQ accepts the values Invalid, Good, Test, Questionable +
OperatorBlocked and Invalid + OperatorBlocked.
Ds2 1 How many persistent data sets can be created No online creation
by one or more clients
(this number includes predefined datasets)
<additional items>
<additional items>
Sg2 1,2 What is the effect of when and how the non- The settings are directly stored
volatile storage is updated in volatile memory, the non-
(compare IEC 61850-8-1 $16.2.4) volatile storage is updated by a
background process. Normally
within a minute after
ConfirmEditSGValues.
Sg4 1 What happens if the association is lost while The SE values changes are
editing a setting group lost, the EditSG is reset to 0
<additional items>
Rp4 1,2 Mechanism on second internal data change Send report immediately
notification of the same analogue data value
within buffer period (Compare IEC 61850-7-2
Ed2 $17.2.2.9)
Rp7 1,2 What is the buffer size for each BRCB or how 50000 bytes for each used
many reports can be buffered BRCB (max. 100 BRCB
instances)
Rp12 2 After restart of the server is the value of Restored from original
ConfRev restored from the original configuration
configuration or retained prior to restart
Rp13 1,2 Does the server accept any client to N (ResvTms not supported)
configure / enable a BRCB with
ResvTms=-1?
AP-Title N/A
What fields are used to do the identification?
AE-Qualifier N/A
or
(must be >= 0)
<additional items>
(*) In case of unbuffered reporting the Resv attribute will be set to 'true' for pre-assigned URCBs.
However the device will not block other clients from connecting the RCBs. Client has to utilise the
pre-assign information from SCL to enable the correct RCB instance.
Lg3 1,2 Are there are multiple Log Control Blocks that N/A
specify the Journaling of the same MMS
NamedVariable and TrgOps and the Event
Condition
(Compare IEC 61850-8-1 $17.3.3.3.2)
integrity N/A
<additional items>
Gp3 1,2 Published FCD supported common data ACD, ACT, APC, ASG, BSC,
classes are CMV, DPC, INC, ING, INS, MV,
ORG, SPC, SPG, SPS, ENC,
ENS
Arrays are not supported
<additional items>
Note 3: Following
wrong/missmatching
elements in the GOOSE
header are leading to invalid
data for the application after
2*TAL timeout:
- AppID
- gocbRef
- missing goID
Following
wrong/missmatching
elements in the GOOSE
header are leading to
immediate invalid data for the
application:
- datSet
- goID
- test
- confRev
- ndsCom
- numDatSetEntries,
checked in header of the
message, but not that actual
DatSetEntries match
Note 4:
DataSetEntries are checked
for type match. Not matching
types will result in not
updating data with
mismatching type values.
Note 5:
Mismatching
numDatSetEntries in header
compared to real entries lead
to updating the matching
ones and ignoring the non-
existing or too many ones.
Gs4 1,2 What is the behaviour when a subscribed sqNum is monitored for internal
GOOSE message is out-of-order error tracking, but data is still
accepted in case of stNum
change.
Gs6 1 Does the device subscribe to GOOSE Y, with the VLAN tag
messages with/without the VLAN tag Y, without the VLAN tag
Gs8 1,2 Subscribed FCD supported common data ACD, ACT, ASG, BSC, CMV,
classes are DPC, INC, ING, INS, MV, SPC,
SPG, SPS, ENC, ENS
Arrays are not supported
<additional items>
Min. 3 ms
DOes: N
SBOes: Y
Ct6 - What are the conditions for the time (T) Deprecated
attribute in the SelectWithValue and/or
Operate request
supported Y Not-supported
Y Blocked-by-switching-hierarchy
N Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
Y Blocked-by-Mode
Y Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected
Ct10 1,2 How to force a “test-not-ok” respond with Issued on negative response due
SelectWithValue request to addCause values e.g. Time-
limit-over, blocked-by-interlocking
etc. And the TEST-bit is set when
issuing the command.
Ct12 1,2 How to force a “test-not-ok” respond with DOns: Issues on negative
Operate request response due to e.g. wrong
switching hierarchy or
interlocking.
SBOns: Not Supported
DOes: Not Supported
SBOes: Issued on negative
response due to addCause
values e.g. Time-limit-over,
blocked-by-interlocking etc. And
the TEST-bit is set when issuing
the command.
Ct14 1,2 What happens if the orCat value is not DOns: Rejected for the above(*)
supported or invalid
SBOns: Not Supported
DOes: Not Supported
SBOes: Rejected for the above(*)
Rejected means returning
addCause Blocked-by-switching-
hierarchy
Ct18 1 Deprecated
<additional items>
Tm2 1,2 Describe the behaviour when the time The Relion 670 series can have 2
server(s) ceases to respond configured SNTP Servers. If the
first fails, the second is taken into
use. There is an automatic switch
‘back’ if an erroneous one comes
operable. If all SNTP servers are
off-line the event timestamps get
ClockFailure and
ClockNotSynchronized status.
The SNTP servers are polled
with an interval up to 64 seconds.
If the SNTP server don’t respond
two extra tries will be done with
short interval. After that the
second SNTP server is polled.
If no backup server is defined,
there is a timeout of 5 minutes.
Tm3 1,2 How long does it take to take over the new Depends on how much the time
time from time server differ, from 2 seconds to 12
minutes. The time also depends
on several parameters.
To reach the supported time
accuracy the SNTP server need
to be stable.
Tm4 1,2 When is the time quality bit “ClockFailure” Upon start of the IED, until
set synchronization is received.
As the time system is self-
adjusted, the clock failure is set
when the estimated deviation
exceeds a certain value. Due to
the good internal accuracy, this
deviation occurs in the order of >
30 days.
Tm5 1,2 When is the timequality bit “Clock not When connection to all time
Synchronized” set servers is lost (see PIXIT-Tm2)
Tm8 1,2 Which attributes of the SNTP response Y Leap indicator not equal to 3
Y OriginateTimestamp is equal
to value sent by the SNTP
client as Transmit Timestamp
N other (describe)
Tm9 1,2 Do the COMTRADE files have local time or The file attribute is in UTC. The
UTC time and is this configurable START Time inside the
COMTRADE file is in local time.
No not configurable.
<additional items>
Ft1 1 What is structure of files and directories Flat file system with pseudo
folder
Are comtrade files zipped and what files are For COMTRADE 1999 there are
included in each zip file two Zip files
drec_x.zip incl.: .hdr, .cfg and .dat
drec_xh.zip incl.: .hdr
The .hdr file in the drec_x.zip file
contain extra information.
For COMTRADE 2013 there is
one drec_x.zip incl.: .cff file.
Ft2 1,2 Directory names are separated from the file “/” or “\” for FTP
name by “/” for MMS
Ft3 1 The maximum file name size including path 200 chars
(recommended 64 chars)
Ft4 1,2 Are directory/file name case sensitive Not Case sensitive
Ft5 1,2 Maximum file size for SetFile SetFile not supported
Ft7 1 Is the wild char supported in the MMS Yes, wild card = * or “.” or empty
fileDirectory request string
Ft8 1,2 Is it allowed that 2 clients get a file at the Y same file
same time Y different files
Ft9 1,2 Which files can be deleted Only these files in catalogues
drec and frep can be deleted.
Drec_x.zip, See Remark1.
Frep_x.zip
Other files are not accessible
through IEC 61850
<additional items>
Remark1: When one of the files (drec_x.zip, drec_xh.zip) is deleted, the IED itself will remove the other
disturbance file.