Equipment Name : U2 ESP Transformer-Rectifier 508A

Rating Voltage : 380 V / 75 kVDC


Class :B

Breakdown Voltage Criteria Table (IEC 60422-2013)


Breakdown Voltage (kV)
Class Rating Voltage (kV)
Good Fair Poor
O ≥400 >60 50-60 <50
A 170-400 >60 50-60 <50
B 72.5-170 >50 40-50 <40
C <72.5 >40 30-40 <30
Equipment Name : U2 Unit Transformer B
Rating Voltage : 22.8 / 10.5 kV
Class :C

Breakdown Voltage Criteria Table (IEC 60422-2013)


Breakdown Voltage (kV)
Class Rating Voltage (kV)
Good Fair Poor
O ≥400 >60 50-60 <50
A 170-400 >60 50-60 <50
B 72.5-170 >50 40-50 <40
C <72.5 >40 30-40 <30

Equipment Name : U2 Excitation Transformer


Rating Voltage : 22.8 kV / 890 VDC
Class :C

Breakdown Voltage Criteria Table (IEC 60422-2013)


Breakdown Voltage (kV)
Class Rating Voltage (kV)
Good Fair Poor
O ≥400 >60 50-60 <50
A 170-400 >60 50-60 <50
B 72.5-170 >50 40-50 <40
C <72.5 >40 30-40 <30

Equipment Name : U2 Generator Transformer


Rating Voltage : 525 / 22.8 kV
Class :O

Breakdown Voltage Criteria Table (IEC 60422-2013)


Breakdown Voltage (kV)
Class Rating Voltage (kV)
Good Fair Poor
O ≥400 >60 50-60 <50
A 170-400 >60 50-60 <50
B 72.5-170 >50 40-50 <40
C <72.5 >40 30-40 <30