Professional Documents
Culture Documents
Intelilite: Ib-Lite Communication Module
Intelilite: Ib-Lite Communication Module
InteliLite
IB-Lite Communication Module
Revision: 5.3
Date: 5/3/2015
Table of Contents
1 Preface ..................................................................................................................... 2
1.1 Requirements ..................................................................................................... 2
1.2 Installation .......................................................................................................... 3
2 Network configuration ............................................................................................... 5
2.1 Automatic IP configuration ................................................................................. 5
2.2 Fixed IP configuration ........................................................................................ 5
3 Setup ........................................................................................................................ 9
3.1 Understanding the Setpoints .............................................................................. 9
3.2 IB-Lite Setup using LiteEdit .............................................................................. 10
3.2.1 IB-Lite Configuration .................................................................................. 10
3.2.2 SMTP Configuration .................................................................................. 11
3.2.3 Email to Text Message .............................................................................. 12
3.3 Configure IB-Lite Using Service Web Pages .................................................... 13
3.4 Restore default settings ................................................................................... 16
3.5 IB-Lite Firmware Upgrade ................................................................................ 17
3.6 Other Related Controller Adjustment ............................................................... 19
4 Remote Connection types ...................................................................................... 19
4.1 Direct connection using ComAp PC tools ........................................................ 19
4.2 AirGate connection using ComAp PC tools ...................................................... 20
4.3 MODBUS over TCP ......................................................................................... 21
4.4 SNMP Protocol................................................................................................. 22
4.5 Web connection ............................................................................................... 23
4.6 SCADA ............................................................................................................. 24
4.6.1 Measurement............................................................................................. 24
4.6.2 Setpoints.................................................................................................... 24
4.7 Web server adjustment .................................................................................... 24
i
FAQ – InteliLite – IB-Lite Communication Module
1 Preface
IB-Lite is a plug-in ethernet communication module for InteliLite and InteliDrive
controllers including:
ID-Lite
ID-FLX
IL-NT AMF20 & AMF25
IL-NT MRS10, MRS11, MRS15, MRS16, & MRS19
1.1 Requirements
Software Requirements:
LiteEdit
Hardware Requirements:
2
FAQ – InteliLite – IB-Lite Communication Module
1.2 Installation
Disconnect power source from controller, remove cover of the slot labeled
"Communication module" located at rear side of the controller Plug module into the slot
Error! Reference source not found. & Error! Reference source not found..
An optional method to remove and install the new module is to remove the plastic cover
using a flat bladed screw driver (Picture ).
If a RS232 card comes with controller, remove RS232 card and replace with IB-Lite
3
FAQ – InteliLite – IB-Lite Communication Module
Picture 4. IB-Lite.
Picture 5. IB-Lite – 2.
4
FAQ – InteliLite – IB-Lite Communication Module
2 Network configuration
This section describes the configuration procedure of the IB-Lite. Determining the
desired mode of connection and network settings is the first step to successfully setup
your controller.
The related settings are:
IP address
Network mask
Gateway IP address
DNS IP address
CAUTION!
Do not adjust the related setpoints manually while IP Addr Mode is in automatic mode.
This mode creates an AirGate connection, which gives the following functionality:
Websupervisor (websupervisor.comap.cz)
Email support (SMTP)
Lite Edit & InteliMonitor connectivity
For AirGate setup information go to section: AirGate connection using ComAp
PC tools
NOTE:
Automatic configuration mode does not allow HTTP browser connectivity or direct IP
access.
5
FAQ – InteliLite – IB-Lite Communication Module
NOTE:
If the module is used in fixed IP address mode, then the adjustment must match to the
properties and settings of the local network. Consult your IT specialist for proper
settings.
6
FAQ – InteliLite – IB-Lite Communication Module
7
FAQ – InteliLite – IB-Lite Communication Module
For external internet accessibility, the internet gateway (router) must have a fixed IP
address assigned to the IB-Lite. This address must be configured to forward incoming
traffic through HTTP port (80) and through the port configured for ComAp TCP protocol
(Picture 1 – ComAp TCP Protocol Port and Picture 2 Example of Port Forwarding).
8
FAQ – InteliLite – IB-Lite Communication Module
3 Setup
Ensure the latest version of firmware is loaded into controller & IB-Lite – Check the
installation suite spreadsheet to verify which version is most current (Installation Suite
Spreadsheet)
To un-lock some of the advanced features of the IB-Lite it is recommended to update
the controller’s firmware to 2.0 and greater. (For firmware update instructions, click
here)
3.1 Understanding the Setpoints
Disabled (Fixed) or Enabled (automatic). In fixed (disabled) mode the adjusted
IP address, network mask, gateway address, and DNS server address are
IB-Lite DHCP
manually set in controller. In automatic (Enabled) mode the DHCP protocol is
used to obtain the previously mentioned settings from a DHCP server.
IP address of the module. In fixed mode this setpoint must be manually input
into the controller based on gateway (router) settings (for questions, discuss
IBLITE IP ADDR
with IT admin). In automatic mode the set point contains the dynamically
(automatic) assigned address.
Network mask. In fixed mode this set point must be manually input into the
controller based on gateway (router) settings (for questions, discuss with IT
IBLITE NETMASK
admin). In automatic mode the set point contains the dynamically (automatic)
assigned address
IP address of the gateway which connects the network with the neighborhood.
In fixed mode this set point must manually input into the controller based on
IBLITE GATEIP
gateway (router) settings (for questions, discuss with IT admin). In automatic
mode the set point contains the dynamically (automatic) assigned address
This set point specifies the port number used for communication with ComAp
COMAP PORT
tools (LiteEdit & InteliMonitor, utilizing either direct or AirGate connections.
Domain name or IP address of the AirGate server. Typically set to
AIRGATE IP
airgate.comap.cz
User name for the SMTP account used for sending e-mails. If the user name
SMTP USERNAME
is left blank SMTP authentication is not used.
SMTP USERPASS Password for the SMTP account.
Domain name or IP address of the SMTP server being used for sending e-
SMTP SERVERIP
mails.
Senders e-mail address (“from” address in e-mails sent from controller).
CONTR MAILBOX NOTE: Most public SMTP servers refuse sending e-mail if there is not an
existing e- mail address in the "sender e-mail" field.
Time zone in which the controller is located. It is important for e-mails to have
TIME ZONE
proper "sent at" timestamp.
IP address of the domain name server. In fixed mode this set point must be
properly adjusted to enable translation of domain names (including the domain
DNS IP ADDRESS
name in e-mail addresses) to appropriate IP addresses. In automatic mode
the set point is automatically assigned
Table 1
9
FAQ – InteliLite – IB-Lite Communication Module
10
FAQ – InteliLite – IB-Lite Communication Module
Picture 4
11
FAQ – InteliLite – IB-Lite Communication Module
12
FAQ – InteliLite – IB-Lite Communication Module
1) Connect the IB-Lite to the Ethernet (LAN) network. If the current (default) IP
address does not match local network parameters (i.e. because of different
network segment or the IP address is occupied), connect the module directly to
your PC using a cross-wired cable. Some LAN adapters recognize direct point-
to-point connection automatically and then a normal straight UTP cable can be
used for direct connection as well.
2) Temporarily change the IP address, gateway IP, and subnet mask of your PC
Ethernet connection to match the setpoints in the IB-Lite
a) Control Panel – Network and Internet Connections – Network Connections –
Right Click on “Local Area Connection” and go to properties – Select “Internet
Protocol (TCP/IP IV4)” and select properties
b) Use following setting: IP gateway must be identical to IP gateway on IB-Lite,
IP address must be from the same subnet range as the module IP address
currently is (e.g. 192.168.1.1 - 192.168.1.253 for the module default IP
address) and subnet mask identical as the IB-Lite uses (e.g. 255.255.255.0
for the default module mask). After the IB-Lite setup is finished, restore your
PC setting back to original values to reconnect to LAN.
c) Example of a PC setup to connect to an IB-Lite with the following settings:
1. IB-Lite IP Gateway: 192.168.1.1
2. IB-Lite IP Address: 192.168.1.254
3. IB-Lite Subnet mask: 255.255.255.0
13
FAQ – InteliLite – IB-Lite Communication Module
14
FAQ – InteliLite – IB-Lite Communication Module
6) Adjust the IP address, network mask, and gateway IP address. The module
works in fixed IP address mode, ( DHCP is not supported in this situation).
7) Modify the port number that is used for ComAp/TCP protocol (LiteEdit,
InteliMonitor), if needed.
15
FAQ – InteliLite – IB-Lite Communication Module
NOTE:
Port number can be specified in LiteEdit or InteliMonitor using a colon, e.g.
192.168.1.200:999. If the port number is not specified there, the default port 23 is used.
8) Adjust e-mail related setpoints (refer to Section 3.1 for definitions). Consult
settings with your e-mail provider. Tick the box “access verified” and enter SMTP
username and password below if your SMTP server require authentication. Most
SMTP servers requires the e-mails to be sent from an existing e-mail address. In
such a cases put the "IB-Lite sent from” e-mail address into the box IB-Lite
Mailbox setpoint. Adjust the Time Zone according to the gen-set location in order
to receive e-mail with correct sending time/date.
9) When you have completed the configuration, click on the “Save” button to confirm
all changes and write the setpoints to the IB-Lite.
NOTE:
Factory default IP address is 192.168.1.254 and password is comap.
If the controller firmware supports set points for IB-Lite adjustment, then the
settings are always taken from these set points and the "restore default settings"
jumper resets only the password for service web pages to "comap".
If the controller firmware does not support set points for IB-Lite adjustment, then
the jumper resets the IB-Lite IP address to 192.168.1.254, network mask to
255.255.255.0, gateway IP address to 192.168.1.1 and the password to "comap".
CAUTION!
If you are upgrading from version 1.0, you have to program firmware IB-Lite-1.0.1.BIN
first, then wait for restart of the module and then you can upgrade to the latest firmware.
NOTE:
Do not forget to remove the jumper after new adjustment is finished.
NOTE:
The password mentioned here is used for the service pages only. The access to the
controller web pages is secured by the controller access code.
16
FAQ – InteliLite – IB-Lite Communication Module
NOTE:
Before starting this procedure, note the IP-Address of the IB-Lite. For controller
firmware versions 2.0 and later, this can be found in LiteEdit under the Comms Settings
menu. For firmware version older than 2.0, this can be found in the service web pages.
2) Enter password. The service pages homepage will appear then. Factory default
password is "comap".
3) Click the link “IB-Lite Firmware Up loader” at the service homepage
(http://<ib_lite_ip_address>/sp_index.htm). Firmware upload page will appear.
4) Press the button "Browse" and select the appropriate firmware file.
5) Press "Upload new firmware" button. After the firmware upload is finished, the
module will restart.
NOTE:
Interrupting the upload will NOT cause any damage. Just repeat the upload again.
17
FAQ – InteliLite – IB-Lite Communication Module
NOTE:
LiteEdit has functionality to allow easy upgrading of an archive. This is typically
required when the controllers firmware was updated. The newer firmware must have
been downloaded and installed for this procedure to work. Refer to Picture and Picture
9.
18
FAQ – InteliLite – IB-Lite Communication Module
This connection type is active if the setpoint AirGate IP is left empty and IB-Lite DHCP
is Disabled. To connect your PC tool to the controller use the INTERNET connection
type and enter the IB-Lite IP address into the genset address box in the ComAp PC
tool. If you do not use the default port 23, then you also have to specify the port number
using a colon (i.e. 192.168.1.254:24).
19
FAQ – InteliLite – IB-Lite Communication Module
This connection type is active if the setpoint AirGate IP is configured with an AirGate
server address. It can be entered in text form or numeric form as "airgate.comap.cz" or
“80.95.108.26”).
Once the controller is “online” and the AirGate server address is properly configured,
the controller automatically connects to the server and generates an AirGate ID This
can be found on the controller screen or in LiteEdit under “Values” - “Controller I.O” –
“Airgate ID:”.
To connect your PC tool to the controller use the AIRGATE connection, put the same
AirGate address as in the controller into the AIRGATE ADDRESS field and use the
AirGate ID displayed on the controller.
NOTE:
The IB-Lite must be able to send data to the AirGate server at UDP port 6127 and TCP
port 23. The TCP port can be changed in the module setup.
20
FAQ – InteliLite – IB-Lite Communication Module
NOTE:
Comm (2) setting must be change to MODBUS along with ModbusComSpeed to the
desired communication speed, this is typically 57600.
NOTE:
Controller access code must be written into the controller prior to reading any
registers. Use function 16, register address 24534 and number of registers 8. The
access code is a null-terminated string of max. (15 characters) Send the 1st character in
the LSB of the 1st register, 2nd character in the MSB of the 1st register, 3rd character in
the LSB of the 2nd register etc... The fixed IP address mode is preferred for this
connection type. This requirement can be disabled when firmware 1.8 is installed in IB-
Lite through the IB-Lite Service Pages.
21
FAQ – InteliLite – IB-Lite Communication Module
Picture 10
The MIB table of each controller is to be created from the controller configuration using
LiteEdit software.
22
FAQ – InteliLite – IB-Lite Communication Module
CAUTION!
As the OID tree contains serial number of the controller it is absolutely necessary that
the MIB table is created from the configuration downloaded from the respective
controller. If the MIB is created from default archive or archive downloaded from other
controller the SNMP agent will not report error.
If there is a new alarm in controller the IB-Lite sends a TRAP to the predefined IP
address. The device reading the trap see message as "New alarm appeared” along with
bindings which contain the alarmlist of the controller as well as the controller name and
serial number.
SNMP read/write community strings are set by default to "public"/"private" and can be
changed configuration web page.
NOTE:
The web server is optimized for Internet Explorer 6 or higher and screen resolution
1024x768 pixels.
CAUTION!
Do not use the browser navigation buttons "Back", "Forward" or "Reload". Use the links
and the reload button located in the toolbar.
NOTE:
Only one remote client can be connected to the web server at a time. If the web browser
is closed without disconnecting through the IB-Lite web page, the connection will be
blocked for 5 minutes.
NOTE:
This connection type only functions under fixed IP address mode.
23
FAQ – InteliLite – IB-Lite Communication Module
4.6 SCADA
Click the SCADA link in the toolbar to display the SCADA page. The SCADA page is the
main page when accessing the IB-Lite directly from a browser.
NOTE:
The SCADA page layout may differ according to the firmware, version and application.
Firmware versions 1.5 and lower do not support some internet browser.
4.6.1 Measurement
Select the MEASUREMENT link in the toolbar to display the measurement page.
Select the required group name in the left box to display values of the group in
the right box.
NOTE:
The measurement page is automatically refreshed every 60 seconds.
4.6.2 Setpoints
Select the SETPOINTS link in the toolbar to display the setpoints page.
Select the required group name in the left box to display setpoints of the group in
the right box.
Select the required setpoint name or value to change the value. If the respective
setpoint is password protected, which is indicated by a lock icon next to the
setpoint name, click on the "Controller password" icon located in the toolbar and
enter valid password.
NOTE:
The setpoint page is automatically refreshed every 60 seconds. If another user changes
a setpoint from another terminal, the web page will not show this change immediately as
e.g. LiteEdit.
Select the HISTORY link in the toolbar to display the history page.
Use the control buttons to move within the history file.
NOTE:
The history page is automatically refreshed every 5 minutes. If a new record appears in
the controller, the web page will not show it immediately as e.g. LiteEdit.
Select the "Webserver settings" icon in the toolbar to display the settings page.
Select the controller language the web pages will appear in.
Select the rate of automatic refresh of the “SCADA” page.
Change the controller password and access code.
24 a.s.
ComAp
Kundratka 2359/17, 180 00, Prague 8, Czech Republic
(+420) 246 012 111
www.comap.cz