Professional Documents
Culture Documents
E
Energy supply systems are facing
significant changes in many countries around
the globe. A good example of such a trans-
formation is the German power system,
where renewable energy sources (RESs)
are now contributing 25% of the power
needed to meet electricity demand,
compared with 5% only 20 years ago.
In particular, photovoltaic (PV) sys-
tems have been skyrocketing over the
last couple of years. As of September
2012, about 1.2 million PV systems
were installed, with a total installed
peak capacity of more than 31 GWp.
During some hours of 2012, PV already
contributed about 40% of the peak power
demand. It seems that Germany is well on the
way to sourcing a major portion of its energy needs
from solar installations. PV must therefore provide a full
range of services to system operators so as to replace services ©istockphoto.com/Mark Soskolne
92
94
96
98
00
02
04
06
08
pt 10
12 r
20 be
power flows can cause additional
19
19
19
19
19
20
20
20
20
20
20
em
power flows from the distribution
Se
Year system to the transmission system.
3) Grid stability (frequency and volt
figure 1. Historic development of the installed capacity of RES compared age): Today, conventional power
with conventional power sources as of March 2012 (source: German Federal plants must guarantee the system’s
Ministry for the Environment, Nature Conservation, and Nuclear Safety). stability. Within the European
Network of Transmission System
PV generation can be found in the sunnier southern region of Operators for Electricity (ENTSO-E) control area, the
Germany. Therefore, south German distribution grids typi- cutoff frequencies for RES still vary; hence, they can
cally experience grid-integration challenges related to PV. cause instabilities in abnormal situations. For further
In some LV grids, the installed PV capacity can even exceed details, see “The 50.2-Hz Risk.”
the peak load by a factor of ten. The graphs in Figure 4 show the load flow and voltages
The impact of high PV penetration rates locally on the for an entire day, as observed in a real LV distribution grid in
distribution system operation is outlined in the following southern Germany. In this particular distribution system, the
section together with a brief overview on the state of the art PV capacity exceeds the peak load by 900%. As a result, the
in Germany. grid is subject to reverse power flows over the transformer
and a rise in voltage.
Impact of High PV
Penetration on the Grid Actions for Smart PV Grid Integration
Three main issues can be identified regarding high PV pen- In what follows, we highlight possible solutions to the tech-
etration in distribution grids: nical issues outlined in the previous section. Note that the
1) Reverse power flows in the distribution system: In technical challenges also have an economic impact on the
distribution systems where the local PV generation stakeholders involved.
exceeds the local load demand, reverse power flows
Supporting Frequency Control
New interconnection requirements—such
as the German VDE AR-N 4105 guideline
0.4 for the low- and medium-voltage grid—
are now in place to support a smoother
Voltage Level (kV)
Electricity Generation
nical reasons, the distribution system
00 .
00 .
00 .
00 .
00 .
00 .
00 .
00 .
.
m
m
are also most commonly resolved via
a.
a.
a.
a.
a.
a.
p.
p.
p.
p.
p.
p.
00
0
grid reinforcement and/or congestion
:0
:0
:0
0:
2:
4:
6:
8:
2:
4:
6:
8:
10
12
10
management. In addition to these con- PV Others Sources Load Time (h)
ventional means, PV systems installed
in Germany must be able to support the
figure 3. Contribution of PV and wind on 26 May 2012 (source: German
local voltage by the provision of reactive transmission system operators and European Network of Transmission System
power and active power curtailment. Operators for Electricity).
Reducing Congestion
Since 2011, the German feed-in tariff
law has required owners of small PV 10 0.75 kW|~6:30 a.m.
Active Power, P (kW)
51.4
51.2
51
50.8
50.6
50.4
50.2
50
49.8
49.6
Zone West
49.4 Zone South East
Zone North East
49.2
49
10:09:30.0 p.m.
10:10:00.0 p.m.
10:10:30.0 p.m.
10:11:00.0 p.m.
10:11:30.0 p.m.
10:12:00.0 p.m.
10:12:30.0 p.m.
10:13:00.0 p.m.
10:13:30.0 p.m.
10:14:00.0 p.m.
10:14:30.0 p.m.
10:15:00.0 p.m.
10:15:30.0 p.m.
10:16:00.0 p.m.
10:16:30.0 p.m.
10:17:00.0 p.m.
10:17:30.0 p.m.
10:18:00.0 p.m.
10:18:30.0 p.m.
10:19:00.0 p.m.
10:19:30.0 p.m.
10:20:00.0 p.m.
figure S1. Frequency recordings after the split of the ENTSO-E control area in 2006 (source: ENTSO-E, final report
on the disturbances of 4 November 2006).
Control Signal
Distribution
Management Optional Control Signal
System (DMS) Communication Interface
HV
MV MV MV
PV Micro
DMS
LV LV LV
Load
Examples of these control strategies, including their inverters can either 1) provide a certain power factor as
economic assessment, are described in detail in the fol- well as reduce active power output, if local overvoltages
lowing sections. are measured (voltage-driven strategies) or 2) simply oper-
ate at a certain fixed power factor at any given time (fixed
Local Voltage-Control Strategies strategies). It is up to the DSO to decide which voltage-
One major topic of several current research projects, such as control strategy should be implemented. In Germany, most
the German PV-Integrated project, is to assess—both tech- DSOs do not use any of these voltage-control strategies. To
nically and economically—local control strategies for PV address the relatively high economic uncertainty that cur-
inverters connected to distribution grids. Using their active rently accompanies the decision-making process (in terms
and reactive power control capabilities, PV inverters them- of technical benefits versus additional costs), cost-benefit
selves can contribute to lowering their impact (in terms of analyses were carried out based on one-year simulations
voltage rise) on the grid in times of high solar irradiation. with real low- and medium-voltage grids. In what follows,
This can, in turn, increase the PV hosting capacity of cer- we present the results of a cost-benefit analysis for a real
tain distribution grid sections. Grid-supporting PV invert- LV grid.
ers are becoming state of the art. They reduce the need for Figure 7 shows the single-line diagram for the radial
additional grid reinforcement measures, which would be LV grid investigated. This particular grid serves a sub-
necessary without any form of additional control capabili- urban residential area with a total of 122 single house-
ties. Cost-benefit analyses were conducted for the differ- holds via a 250-kVA transformer. The household loads
ent voltage-control strategies to determine their economic marked with bold black circles were arbitrarily equipped
impact for the PV plant operator, as well as for the DSO at with 10-kWp PV systems to simulate local congestions
the LV level. and provoke additional grid reinforcement measures to
increase the hosting capacity of the grid for further gen-
Economical Assessment of Local eration capacity.
Voltage-Control Strategies To reduce the extent of the necessary grid reinforcement
According to the definition we have given under “Actions measures, local voltage-control strategies were implemented
for Smart PV Grid Integration,” local control strategies do within the inverter models of the PV systems. Table 1 lists
not require any additional information and communica- the control strategies investigated. Pure local inverter con-
tion infrastructure. Therefore, local voltage-control strate- trol strategies (A–D), as well as a distribution transformer
gies can be easily integrated into the overall grid operation. with on-load tap changer (OLTC), were assessed both tech-
Once installed and parameterized properly, grid-supporting nically and economically.
A Fixed active-power limitation to 70% of installed Required by the beginning of 2013 by PV systems with an
PV capacity installed capacity of less than 30 kWp and no remote-control
capability
B Reactive-power provision depending on active- Can already be required from DSO, according to German
power feed-in medium- and low-voltage guidelines
C Automatic voltage limitation: active-power output is Not yet officially required
reduced so as to maintain a preset voltage threshold
value
D Same as strategy C, except reactive power is Not yet officially required
provided first before active-power output is
reduced
E Distribution transformer equipped with OLTC Not officially required, but first commercialized products are
already available on the market
Strategy A
3,500
Only Grid
Reinforcement Costs Can Be
3,000 Lowered by
Self-Consumption
2,500
Annual Costs (EURO)
Strategy E
2,000
4 4 Strategy B
1,500 Strategy C Strategy D
4
4 4 4
1,000
3 3
2
500
1
5
5 5 5
5 12 5 12
0
Costs for Distribution System Operator (DSO) Costs for PV-Plant Operators
figure 8. Cost comparison of different voltage-control strategies (source: Stetz, Marten, and Braun, 2012).
In the research project called Active, Intelligent Low- The controllable medium- and low-voltage (MV/LV) distri-
Voltage System, the Fraunhofer IWES and its partners bution transformer is able to change the transformer ratio using
investigate decentralized control methods. The aim of an integrated OLTC. The voltage curves of the MV and LV
the components and control approaches developed is to are thus decoupled. In this way, a voltage control method for
assure that the voltage within an LV system is kept within the complete LV system can be achieved that is independent
the allowed voltage tolerance band—under the boundary of grid topology. The compact design of the newly developed
condition of minimal grid reinforcement. OLTC transformer allows the mounting form of standard dis-
tribution transformers to be retained. Additionally, a robust and
Components of an Active, Intelligent LV System maintenance-free design guarantees about 700,000 switching
Figure 9 shows the structure and components of an active, operations. These advantages are accompanied by additional
intelligent LV system. hardware and a marginal increase in no-load losses.
. . .
= = =
CP CP CP CP
. . . .
= = = =
Voltage
Control
Control
Substation
CP = Connection Point
figure 9. Principal design and components of an active, intelligent LV system (source: Bülo, 2012).
Controllable PV inverters offer the possibilities of unit are in place, as well as to the components of the local
reactive-power provision (Q) and active-power reduction (P) LV system.
in order to contribute to grid control. Both local characteris-
tic curves and remote control of P and Q can be implemented. System Concepts
Decentralized voltage controllers influence voltage Depending on the particular case, the available compo-
curves by adding a voltage step using a transformer with nents can be used in different combinations, from which
in-phase regulation. This approach seems to be suitable, several appropriate system concepts can be derived (see
especially for long single-grid branches. Figure 10). The voltage rise caused by DER in the LV grid
The control and operating-control unit contains the intel- is not allowed to exceed 3%. Installing an OLTC trans-
ligence and deploys the grid components in a way to achieve former allows the voltage rise to be mitigated. A voltage
optimal operation of the local grid. The modular approach rise of up to 10% is therefore possible because the voltage
allows for the possibility of upgrades to extend functionality. at the busbar at the transformer can be controlled over a
Bidirectional communication interfaces to the grid control large range.
figure 10. Various concepts for an LV system, including the MV/LV substation being considered for decentralized control
approaches (with communication) and local control approaches (without communication) (source: Bülo, 2012).
SCADA
is of great interest, especially from
a technical perspective. Research Optimizer
results highlight that system con- Optimized
cepts using an OLTC transformer Settings Optimization Unit
allow a significant increase in the
system hosting capacity for PV. In
these cases, the hosting capacity figure 11. Scheme of the central control strategy (source: Yan et al., 2012).
is no longer limited by the narrow
voltage tolerance band. More of the existing grid infra- independently, central control aims for coordinated control
structure capacity can be used. of the complete system from the distribution system control
Decentralized and local control strategies help to center. It thus requires a set of information with which to
stabilize grid operation or relieve the system during peak establish the current system status, as well as knowledge of
feed-in. For an active control of DER during system the boundaries in which the system needs to operate. The
operation, novel central control strategies can be used. information required by a central voltage-control approach
Such control strategies allow for a coordinated operation includes both static and dynamic system information. Static
of grid components so that PV can be used to provide information (e.g., grid topology and the characteristics of
additional ancillary services. components installed in the system) can be acquired directly
from the system operator. Dynamic information (e.g., infor-
Central Voltage-Control Strategies mation on bus voltages and on active and reactive power
In the course of a European research project known as levels of DERs) is acquired from distributed state estima-
HiPerDNO, a central voltage-control approach was devel- tion of the grid. This is because such information is usually
oped for distribution systems. The approach is based on only available for a few locations in the system, where sen-
the provision of reactive power by distributed generators as sors are installed.
well as the control of OLTCs installed in the distribution Figure 11 outlines the architecture of the control mech-
system. In contrast to decentralized voltage-control strate- anism developed. The voltage controller contains a grid
gies, where subsets of the distribution system are controlled simulation unit and an optimization unit. The optimization
1.03
Voltage (per unit)
0.97
0.95
0:00 6:00 12:00 6:00 0:00 0:00 6:00 12:00 6:00 0:00
a.m. a.m. p.m. p.m. a.m. a.m. a.m. p.m. p.m. a.m.
Time (h) Time (h)
(a) (b)
figure 12. Minimum and maximum voltage magnitude (a) without and (b) with central voltage control (source: Yan
et al., 2012).