You are on page 1of 90

M

Technical Catalogue
ModBreak Moulded Case Circuit Breakers 2019

Moulded Case Circuit Breakers, Chassis, Transfer Switches

An economical and flexible line of MCCBs for general purpose applications

1
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODBreak MCCBs

CONTENTS

MODbreak MCCBs Page Number


Product overview 3
3 pole MCCBs 5
4 pole MCCBs 6
Internal accessories 7
External accessories 8 - 13
MB Chassis 14 - 15
MBC Chassis 16 - 21
Transfer switches 22
Transfer switch controllers 23 - 32
MCCB ratings chart 33
Selectivity and Cascade tables 34 - 38
MODcurve Selectivity Software 39
Motor start tables 40 - 41
Watts loss 42
Temperature ratings 42
Harmonics 42
Shock data 42
Let through and cut off values 43
Let through curves 43 - 45
Characteristic curves – thermal magnetic MCCBs 46
Characteristic curves – electronic MCCBs 47
Electronic MCCB OCR setting 48 - 51
Dimensions MCCBs and accessories 52 - 60
Transfer Switches 61 - 64
MODbreak OCR Tester 65 - 66
MCCB installation details 67 - 71
Internal & external accessory fitting installation details 72 – 89
Clearance requirements for MCCB installation 89

2
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

MODbreak range overview

• From 16 A to 1250 A
• 3 Pole & 4 Pole
• Choice of 36kA and 50kA breaking capacities.
• Icu = Ics
• With Electronic and Thermal Magnetic protection relays
• MCCBs for motor backup protection
• MCCBs for distribution systems
• Manual, rotary handle or motorised versions
• Wide range of internal and external accessories
• Chassis options
• Transfer switch and controllers MB2 MB3 MB4

MODbreak frame sizes and ampere ratings


MB2
Rated current 63 (50A to 63A), 80, 100, 125, 160, 200, 250 A 40 (16A to 40A), 63, 100, 160, 250 A
Over Current Relay Thermal magnetic Electronic
MB3
Rated current 320, 400, 500, 630 A 400, 630 A
Over Current Relay Thermal magnetic Electronic
MB4
Rated current 800, 1000, 1250 A
Over Current Relay Electronic

Thermal Magnetic Over Current Relay Features of Thermal Magnetic OCR


• Adjustable overload setting 80% to 100% of ln
• Adjustable magnetic short circuit setting 6 – 10 ln
• Push to trip button
• True RMS sensing
• Infinite adjustment thermal and magnetic dials
• Refer ratings chart for additional setting details

MTX1 Electronic Over Current Relay Features of MTX1 Electronic OCR


• Overload protection LT with selectable inverse time delay
• Adjustable Short Time ST characteristic
• Short circuit (ST) characteristic with selectable time delay
• LT and ST characteristic can be switched OFF
• Fixed instantaneous trip
• DIP switch OCR setting
• Push to trip button
• Thermal memory enable / disable
• Power ON / pick-up LED
• LED blinks at 85% and rapidly at 120% Ir prior to tripping
• True RMS sensing
• Refer ratings chart for additional setting details

3
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

Faster tripping
The unique speed contact system accelerates the opening of contacts during
short circuit. This ensures faster tripping an ultimate current limiting feature.
The result-very low let-through, cut-off current and fault clearing time

Mechanical Anti-reclosing
This unique feature ensures that under short circuit conditions, the contacts open
and latch even before the release gives a trip command to the mechanism.
This avoids contact re-closing and bounce

Low Watts loss


The entire current carrying path is optimally designed to achieve very low watt loss.
Silver contacts offer low contact resistance, which help to achieve a low heat connection.

Positive Isolation
The MCCB toggle indicates the true position of the main
switching contacts

Double Insulation
Internal accessories are housed in insulated casings to ensure
a first level of insulation. When the front cover is opened for
the fixing of internal accessories, the MCCB is totally insulated
ensuring double insulation.

Standards Compliance
MODbreak complies with AS 60947-2, AS/NZS 3947-6, IEC
60947, and the European CE Mark.

Forward or Reverse connection


MODbreak MCCBs can be forward or reverse connected to allow
reversal of line and load connections. This is especially important
for MB and MBC chassis where MODbreak MCCBs are reverse
connected on the chassis as standard.

Mounting angle
Vertical and 90⁰ to the left or right

4
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

Features
▪ Electronic and thermal magnetic types
▪ 3 pole types Quick reference
▪ 36kA and 50kA interrupting capacities guide
▪ Fault interruption ratings Icu = Ics
▪ Internal and external accessory range
▪ Cascading, Selectivity, motor starting and other data available
▪ NHP MODcurve selectivity and Cadblocks available
▪ Chassis options for 3 pole MCCB’s up to 630A frame
▪ Transfer switches available to 630A frame

MB2 250 MCCB

3 pole MCCB’s

Ampere Trip unit 415V kA MCCB type Current Catalogue 3 pole


Frame Rating (A) ICU ICS Adjustment Number Price $
63 MB263D3TM 0.00
100 MB2100D3TM 0.00
250AF 125 36 36 Thermal Magnetic 80-100% MB2125D3TM 0.00
160 MB2160D3TM 0.00
250 MB2250D3TM 0.00
63 MB263N3TM
0.00
80 MB280N3TM
100 MB2100N3TM 0.00
250AF 125 50 50 Thermal Magnetic 80-100% MB2125N3TM 0.00
160 MB2160N3TM 0.00
250 MB2250N3TM 0.00
40 MB240D3SE 0.00
250AF 100 36 36 Electronic 40-100% MB2100D3SE 0.00
250 MB2250D3SE 0.00
40 MB240N3SE 0.00
250AF 100 50 50 Electronic 40-100% MB2100N3SE 0.00
250 MB2250N3SE 0.00
320 MB3320D3TM 0.00
630 AF 400 36 36 Thermal Magnetic 80-100% MB3400D3TM 0.00
630 MB3630D3TM 0.00
320 MB3320N3TM 0.00
630 AF 400 50 50 Thermal Magnetic 80-100% MB3400N3TM 0.00
630 MB3630N3TM 0.00
630AF 400 MB3400D3SE 0.00
36 36 Electronic 40-100%
630 MB3630D3SE 0.00
630AF 400 MB3400N3SE 0.00
50 50 Electronic 40-100%
630 MB3630N3SE 0.00
800 MB4800N3SE 0.00
800 / 1250AF 1000 50 50 Electronic 40-100% MB41000N3SE 0.00
1250 MB41250N3SE 0.00
Ordering notes:
1. Refer following pages for internal and external accessories, chassis and transfer switch options.
2. Refer following pages for Selectivity and Cascade tables.

5
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

Features
▪ Electronic and thermal magnetic types
▪ 4 pole types
▪ 36kA and 50kA interrupting capacities
▪ Fault interruption ratings Icu = Ics
▪ Internal and external accessory range
▪ Cascading, Selectivity, motor starting and other data available
▪ NHP MODcurve selectivity and Cadblocks available
▪ Transfer switches available to 630A frame

250A 4 pole MODbreak MCCB


4 pole MCCB’s

Ampere Trip unit 415V kA MCCB type Current Catalogue 4 pole


Frame Rating (A) ICU ICS Adjustment Number Price $
63 MB263D4TM 0.00
100 MB2100D4TM 0.00
250AF 125 36 36 Thermal Magnetic 80-100% MB2125D4TM 0.00
160 MB2160D4TM 0.00
250 MB2250D4TM 0.00
63 MB263N4TM 0.00
100 MB2100N4TM 0.00
250AF 125 50 50 Thermal Magnetic 80-100% MB2125N4TM 0.00
160 MB2160N4TM 0.00
250 MB2250N4TM 0.00
40 MB240D4SE 0.00
250AF 100 36 36 Electronic 40-100% MB2100D4SE 0.00
250 MB2250D4SE 0.00
40 MB 240N4SE 0.00
250AF 100 50 50 Electronic 40-100% MB2100N4SE 0.00
250 MB2250N4SE 0.00
320 MB3320D4TM 0.00
630 AF 400 36 36 Thermal Magnetic 80-100% MB3400D4TM 0.00
630 MB3630D4TM 0.00
320 MB3320N4TM 0.00
630 AF 400 50 50 Thermal Magnetic 80-100% MB3400N4TM 0.00
630 MB3630N4TM 0.00
630AF 400 MB3400D4SE 0.00
36 36 Electronic 40-100%
630 MB3630D4SE 0.00
630AF 400 MB3400N4SE 0.00
50 50 Electronic 40-100%
630 MB3630N4SE 0.00
800 MB4800N4SE 0.00
800 / 1250AF 1000 50 50 Electronic 40-100% MB41000N4SE 0.00
1250 MB41250N4SE 0.00

Ordering notes:
1. Refer following pages for internal and external accessories and transfer switch options.
2. Refer following pages for Selectivity and Cascade tables.

6
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

Internal Accessories – MODbreak MCCBs

Common Internal accessories


• Common Internal accessories, except UVTs.
• Field fit by the user.
• Internal accessories easily clip into an MCCB, and only require
a flat or Posidrive screwdriver to first remove the MCCB cover.
• No live parts are exposed during accessory fitting.
• Internal accessories come with 600mm wire leads as standard.

Accessory types
• Auxiliary Contacts 1 C/O and 2C/O
• Auxiliary Contact 2 C/O
• Trip Alarm Contact
• Auxiliary & Trip Alarm Contact
• Shunt Release
• Under Voltage Release Easy fit clip-in accessories

MCCBs with accessory covers removed, showing internal


accessories fitted

Accessory Electrical Data


Shunt Trip
110 - 415VAC 15mA at 250V AC Excitation current
UVT
240V AC 1.4 VA Latching current
5A at 250V AC Resistive
Auxiliaries/Alarms 3A at 250V AC Inductive
(common ratings) 0.5A at 250V DC Resistive
1A at 250V DC Inductive

MCCB internal accessory fitting configurations

Internal accessory selection catalogue numbers


Accessory type Description Suits Catalogue Number
Shunt Trip 110 – 415V AC, 50/50Hz MB2, 3, 4 MBSHUNTAC110415
240V AC, 50/60Hz MB2, 3 MB23UVT240VAC
Under Voltage Trip
240V AC, 50/60Hz MB4 MB4UVT240VAC
1 C/O Auxiliary MB2, 3, 4 MBAUX1C
2 C/O Auxiliary MB2, 3, 4 MBAUX2C
Auxiliary & Alarm contacts
1 C/O Aux – 1C/O Alarm MB2, 3, 4 MBAUX1CALRC
1 C/O Alarm MB2, 3, 4 MBALR1C

7
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs


• External accessories are field fitted, except for motors which are fitted by NHP.
• Refer following pages for additional product information.

250A Price 320A, 400A, 630A Price 800A, 1250A Price


Accessory type
MB2 $ MB3 $ MB4 $
Handle Operators

Extension handle and shaft


• OFF lockable as standard with up to 3 padlocks or hasps, IP54, door interlocking.
• Additional ON position locking available via field conversion to obtain OFF/ON locking.

Lock OFF MB2HANDLESTD 0.00 MB3HANDLESTD 0.00 MB4HANDLESTD 0.00


Direct mount handle
• Padlockable up to 3 locks, no door interlocking,

Lock OFF handle MB2HANDLEDIRECT 0.00 MB3HANDLEDIRECT 0.00 - 0.00


MCCB toggle lock – captive
Suits single 5-7 mm padlock MB2CAPLOCK 0.00 MB3CAPLOCK 0.00 MB4CAPLOCK 0.00
Motor operator
• Includes motor and internal MCCB mounted motor indication flag auxiliary block – must be NHP factory or branch installed
240V AC control, 50-60Hz MB2MOTOR240VAC 0.00 MB3MOTOR240VAC 0.00 -
Terminal covers & interpole barriers
• Terminal covers supplied in sets of 2, IP20 entry insert covers supplied as standard
• Interpole barriers supplied with new MCCBs as standard for the line side only, 1 per pole.

Standard 3P MB2TCSTD3P 0.00 MB3TCSTD3P 0.00 MB4TCSTD3P 0.00


Standard 4P - 0.00 - 0.00 MB4TCSTD4P 0.00
Wide 3P MB2TCWIDE3P 0.00 MB3TCWIDE3P 0.00 -
Wide 4P MB2TCWIDE4P 0.00 MB3TCWIDE4P 0.00 -
Flush 3P MB2TCFLUSH3P 0.00 MB3TCFLUSH3P 0.00 -
Flush 4P - 0.00 - 0.00 -
Interpole barrier (set of 2) UXQH0004B UXQH0004B -
Attached busbar
3 pole set of 3 MB2ATTBAR3P 0.00 MB3ATTBAR3P 0.00 MB4FCB3P 0.00
4 pole set of 4 MB2ATTBAR4P 0.00 MB3ATTBAR4P 0.00 MB4FCB4P 0.00
Mechanical Interlock
Rear mounting, MCCB MB2MECHINT250 0.00 MB3MECHINT400 0.00 -
mounting plate included - MB3MECHINT630 0.00 -
Electronic MCCB OCR tester MBOCRTESTER

8
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs

Extension shaft handles


• Available for MCCBs to 1250A
• Mounts on front of MCCB without removal of accessory cover
• Padlock OFF as standard
• Padlock OFF handle field conversion to padlock ON
• Suits up to three 5-7mm padlocks or multi lock hasps
• Door interlock in ON position, selectable for padlock OFF.
• Side switch selector prevents or allows door opening if padlocked
• Easy to see ON / OFF / TRIP indication
• MCCB rating label can be seen with handle installed
• Push to trip button accessible while handle installed
• IP 54 degree of protection when door mounted
• 1.5mm diameter Door Defeat access hole at base of handle
• Handle kit includes 275mm x 10mm2 shaft, handle, MCCB mechanism

OFF Padlocking and use of the door interlock feature

Direct mount handles


• Available for MCCBs to 630A
• Mounts on MCCB without removal of accessory cover
• Handles are padlockable OFF as standard
• Handles can be field converted to lock ON
• Suits up to three 5-7mm padlocks or multi lock hasps
• Handles are not door interlocking.
• Easy to see ON / OFF / TRIP indication
• MCCB rating label can be seen with handle installed
• Push to trip button accessible while handle installed
• IP 54 degree of protection

9
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs

Captive Toggle Padlocking Mechanism


Consists of a brushed stainless steel lock attachment, which can be easily customer fitted via 4 hexagonal head mounting screws.

Features
• Suitable for MB2, MB3 and MB4 MCCBs 20A to 1250A. Types: MB2CAPLOCK, MB3CAPLOCK, MB4CAPLOCK.
• MB2 toggle lock bracket fits within the MCCB’s 45mm DIN cut-out for door or escutcheon mounting.
• MB3 toggle lock fits within the MCCBs standard 78mm toggle area cut-out.
• If an MCCB trip occurs, a reset operation can be performed without the need to remove the lock captive attachment.
• No special spacing required between side by side mounted MCCBs.

Captive lock attachment fitted Lock OFF Lock ON

10
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs

Motor Operators

Motor operators
• For 250AF and 630AF MCCBs.
• ON / OFF & Charged/Discharged indication.
• Spring charge mechanism.
• Selector switch for Auto/Manual operation and padlocking.
• Padlock facility for locking in OFF position (up to 3 padlocks).
• Resetting time < 250msec & Closing time < 90 msec.
• High mechanical & electrical endurance.
• Accessible internal back up fuse for extended motor life.
• Access to the protection setting on MCCB possible when motor fitted.
• True indication for ON/OFF & Discharged & charged.
• MCCB right side internal accessory space occupied when motor fitted.
• Replaceable 1.6A fuse as standard.
• OFF/ON terminal wiring is activated by via dry contact closure only.
• MBMOT motor operators are NHP factory or branch fit.

MB MOT Motor operator electrical & mechanical data


MB2 MB3
Operating voltage (V AC) 240 240
Operating voltage (%) 85 – 110% 85 – 110%
Closing time (mS) 60 90
Opening time (mS) 300 450
Power consumption to switch ON (VA) 250 500
Power consumption OFF/RESET (VA) 500 500
Life / No. of operations 12000 10000
Door cut out (mm x mm) 96 x 96 96 x 96
Motors or handles can be fitted to interlocked MCCBs IP protection, on the front IP30 IP30
Operating frequency 2 per min 1 per min
Min. control impulse time ON (mS) 200 200
Motors or handles can be fitted to interlocked MCCBs Min. control impulse time OFF/RESET (mS) 500 500

11
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs

Mechanical interlocks

Allows two MCCBs to be mechanically interlocked using a base plate


and rear walking beam interlock, in a side by side configuration.

• For 250AF and 630AF MCCBs


• Rear walking beam mechanical interlock supplied on mounting plate
• Interlock kit plate pole configurations : 3P+3P, 3P+4P, 4P+3P, 4P+4P
• Mixed frame sizes cannot be interlocked
• Customer can fit interlock using knockout on rear of MCCB
• Internal and external accessories to be fitted Mechanically interlocked 4P+3P MCCBs
• Motor operators available for transfer switching
• MCCB right side internal accessory pocket occupied when motor fitted
• Manual Transfer Switches (MTS) using toggles or handles are customer assembled.
• Basic or Automatic Transfer Switches using motors and external controllers are NHP factory assembled.
• Refer following pages for information on order Basic (BTS) and Automatic transfer switches (ATS).

Mechanical Interlock fitting


• Fail Safe rear walking beam mechanical interlock
• Interlock supplied pre-mounted to a metal mounting plate
• Plate suits MCCB poles: 3P- 3P, 3P- 4P, 4P- 3P and 4P- 4P
• MCCBs of different frame sizes cannot be interlocked
• User fit interlock via removal of rear MCCB knockouts
• Interlocking two MCCBs takes around 5-10 minutes
• MCCB toggle only operation if required
• MCCBs accept motors or handles
• Suitable for mounting MCCBs through an escutcheon or door cut-out
• 250AF MCCB have a DIN, 47mm size toggle cut-out

Motors or handles can be fitted to interlocked MCCBs

Knockout at rear of MCCB MCCBs mounted to the front of MCCB plate with actuators inserted knockout at rear of MCCB

12
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Moulded Case Circuit Breakers

External Accessories – MODbreak MCCBs

Terminal cover options


• Available for MCCBs 250AF to 1250A
• Wide, standard, flush terminal covers
• Wide covers physically longer for larger cables or busbars
• 3 and 4 pole covers
• Covers come complete with IP20 end cover knock outs
• Increases IP Form for switchboard construction
• Rigid rubber interpole barriers supplied with MCCBs as standard
• Covers designed for chassis mounted MCCB
• Hole per pole for electrical probe testing.

• Front IP covers & interpole barriers are supplied with new MCCBs as standard IP20 finger touch protection
using MB terminal covers

Standard cover Wide cover

Flush cover

13
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MB800 MCCB Chassis

MODbreak MB chassis assemblies are designed to suit MODbreak


Moulded Case Circuit Breakers. The busbars are fully dipped and type tested,
and are suitable for 250AF MCCB’s rated 63A to 250A. (50A to 250A)

MB 18 way Chassis for 250AF MCCB’s

MB 12 way chassis showing MCCBs mounted, including flush


terminal covers MB2TCFLUSH3P on the user connection side.
The same covers can also be fitted to the Tee Off connection side
for IP20 touch protection

MCCBs on Total MCCBs Chassis pan


Poles each side on chassis Height (mm) Pan Width Catalogue Number
6 1 2 105 370 MB80006U
12 2 4 210 370 MB80012U
18 3 6 315 370 MB80018U
24 4 8 420 370 MB80024U
30 5 10 525 370 MB80030U
36 6 12 632 370 MB80036U
42 7 14 737 370 MB80042U
48 8 16 840 370 MB80048U
60 10 20 1050 370 MB80060U
72 12 24 1260 370 MB80072U
NOTES:
1. Height dimensions are for pan size only. For cut-out details and other dimensions refer to following page.
2. An MB chassis metal pan width is 370mm. With MCCBs mounted on both sides the total width is 380mm. With flush terminal covers fitted to the MCCB load
side, the total width is 405mm.
3. Main busbar phase connections extend 53.5mm beyond the dimensions shown above, at the top and bottom of the chassis.
4. When using electronic MCCBs, it is recommended that the MCCBs be facing each other on the chassis. Placing electronic and thermal magnetic MCCBs
opposite one another can result in flush terminal covers not fitting to the tee off connection side, and MCCB M4 thread mounting screw misalignment.

Chassis technical details:


Chassis type Amps kA Suit MCCB MCCB dimensions
H W D
MB 800 800 36 kA for 1 second MB250 163 105 96
800 40 kA for 0.5 second

14
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MB800 MCCB Chassis

Dimensions mm:

MB chassis with MB2TCFLUSH3P


cover shown fitted to chassis Tee Off
side of MCCB

15
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC MCCB High Current Chassis


Features:
• Suits 250AF and 630AF MCCBs with trip unit ranging 50A to 630A.
• Double sided chassis types for 3 pole MCCBs
• 1250 A, 1600 A or 2200 A rated main bars.
• 11 enclosure sizes to suit application height space.
• Main bar front connect tags supplied as standard.
• Complies with AS/NZS 3439, AS/NZS 3000 – 2007.
• Form of separation can be up to 4bih. AS/NZS 3439.1: 2000 (Annex ZF).
• Circuit breakers are reverse fed as standard.
• Circuit breakers are front connected to chassis tee offs
• Assembled to order from stocked parts by NHP

Chassis Box Selection (no Tee offs fitted, specify from next page)
Main bar rating Icw kA MCCB unit Overall height Catalogue Price
Chassis Size
(A) for 1 sec space (mm) (mm) Number $
1 15 U 610 MBC12153 0.00
2 18 U 718 MBC12183 0.00
3 21 U 826 MBC12213 0.00
4 24 U 932 MBC12243 0.00
5 27 U 1030 MBC12273 0.00
6 1250A 65 30 U 1150 MBC12303 0.00
7 33 U 1258 MBC12333 0.00
8 2 x 10x20mm bars 36 U 1366 MBC12363 0.00
9 39 U 1474 MBC12393 0.00
10 42 U 1582 MBC12423 0.00
11 45 U 1690 MBC12453 0.00
1 15 U 610 MBC16153 0.00
2 18 U 718 MBC16183 0.00
3 21 U 826 MBC16213 0.00
4 24 U 932 MBC16243 0.00
5 27 U 1030 MBC16273 0.00
6 1600A 65 30 U 1150 MBC16303 0.00
7 33 U 1258 MBC16333 0.00
8 2 x 10x30mm bars 36 U 1366 MBC16363 0.00
9 39 U 1474 MBC16393 0.00
10 42 U 1582 MBC16423 0.00
11 45 U 1690 MBC16453 0.00
1 15 U 610 MBC22153 0.00
2 18 U 718 MBC22183 0.00
3 21 U 826 MBC22213 0.00
4 24 U 932 MBC22243 0.00
5 27 U 1030 MBC22273 0.00
6 2200A 65 30 U 1150 MBC22303 0.00
7 33 U 1258 MBC22333 0.00
8 2 x 10x50mm bars 36 U 1366 MBC22363 0.00
9 39 U 1474 MBC22393 0.00
10 42 U 1582 MBC22423 0.00
11 45 U 1690 MBC22453 0.00
Notes:
• Height excludes extended and attached busbar.
• Overall chassis depth when MCCB’s are fitted is 269 mm.
• Refer next page for chassis Tee Off ordering details.

16
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC MCCB High Current Chassis

TEE OFF’s
MBC Chassis and Tee Offs are NHP FACTORY ASSEMBLED

MCCB Amp MCCB width Double sided Price


Frame
Frame (A) (U = units) Cat. No. $
MB2 250 Narrow 250 3U MBCDN2503 0.00
MB3 400-630 Narrow 400-630 4U MBCDN6303 0.000.00
MB3 400-630 Wide 400-630 6U MBCDW6303 0.00

Ordering notes
1. Add Tee Offs as required to the chassis enclosure to complete the components list required.
2. 1 x double sided tee off kit will accommodate 2 MCCBs, 1 on each side of the chassis.
3. For ordering MBC Chassis an ordering layout form is to be used.
4. Add the price of the tee offs required to the price of the chassis to calculate a list price.
5. MB3 400 / 630A MCCB’s fitted with a same width narrow cover = 4 units in width
6. MB3 400 / 630A MCCB’s fitted with a “wide” width cover = 6 units in width
7. Bottom or top extended main bar are optional.
8. For MCCB terminal cover selection use refer MCCB accessories.
9. Only circuit breakers of the same width can be mounted opposite each other.

Component selection example:

Main chassis components:

Chassis components Quantity


Chassis box 1600 A, less tee offs MBC16183 1
630 A tee off set wide cover MBCDW6303 1
400 A tee off set narrow cover MBCDN6303 1
250 A tee off set MBCDN2503 1
250 A tee off set MBCDN2503 1

Terminal covers are ordered as required for the MCCB line and load
terminals. Flush covers are used for the chassis tee off side.

Testing:
The MBC (HC) chassis has been unconditionally type tested (no MCCBs fitted) by NHP, with an Icw short time rating of 65 kA for 1
second.

17
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC High Current Chassis Order Form

Customer: Account No:

Deliver to: Order No:

Quantity:

Price: $

Contact: Req'd Delivery: / /

UNIT S
CHASSIS SPECIFICATION
1
2
3 POLES X 3 Pole - only
4 MCCB X Double Sided - only
5 Config.
6
7 Top Entry only
Chassis
8 Bottom Entry only
Supply
9 Top and Bottom Entry
Connection
10 No Extended Bar - Connect via MCCB
11 RATING 1250 Amp 2 -10 x 20 mm main bars
12 65kA for 1 1600 Amp 2 -10 x 30 mm main bars
13 sec 2200 Amp 2 -10 x 50 mm main bars
14
Size 1 15 610 mm 3 POLE TEE OFFS - DOUBLE SIDED
16 Qty Units Total Type
17 x 3 = 250A MB2 Narrow Terminal Cover
Size 2 18 718 mm x 5 = 250A MB2 Wide Terminal Cover
19 x 4 = 400A MB3 Narrow Terminal Cover
20 x 6 = 400A MB3 Wide Terminal Cover
Size 3 21 826 mm x 4 = 630A MB3 Narrow Terminal Cover
22 x 6 = 630A MB3 Wide Terminal Cover
23
Size 4 24 934 mm Total units
25
26 * 37.5mm gap each side of MB2 using wide covers (total 75mm)
Size 5 27 1042 mm * 37.5mm gap each side of MB3 using wide covers (total 75mm)
28
29
Size 6 30 1150 mm NOTES
31
32
Size 7 33 1258 mm
34
35
Size 8 36 1366 mm
37
38
Size 9 39 1474 mm * Chassis are supplied crated and without MCCB's fitted
40 * Circuit breakers to be fitted reverse fed by customer
41 * Pan Width = 440 mm including mounting channel
Size 10 42 1582 mm * Depth = 269 mm from rear to escutcheon
43 * 1 Unit = 36 mm
44
Size 11 45 1690 mm

TORQUE SETTINGS
MCCB LINE SIDE BOLTS
250 AMPS M6 7Nm
400 - 630 AMPS M8 14Nm
MAIN BAR CONNECTIONS M10 44Nm
Document version 11/02/13
CUSTOMER REFERENCE DRAWINGS In tern al Use O n ly

MOUNTING, CUT OUT AND CONNECTION DETAILS NHP Branch


Chassis Reference Drawing MD I00581200 Rev 0 NHP Contact
MBCD250 Narrow Tee Off Dwg Set MD L005080 Rev 2 Sales Order
MBCDN630 Narrow Tee Off Dwg Set MD L005083 Rev 2 Works Order
MBCDW630 Wide Tee Off Dwg Set MD L005086 Rev 2 Requested Ex works Date: / /

18
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC MCCB High Current Chassis

Example photo, showing an MBC chassis with MCCBs using direct mount handles, and with terminal covers installed.
The terminal covers are fitted to the tee off side and user connection side of the MCCBs.
The top two MCCBs are fitted with WIDE terminal covers, and the others with same width standard covers.
The tee off side of the MCCBs have flush terminal covers fitted which cover the MCCB terminal area, as well as the exposed tee off
chassis connection points.

Isolator option for Chassis


Where a user wishes to use a load break switch to isolate the chassis, NHP can supply a Socomec 1600A load break switch, plus
busbar connection kit which consists of a set of bars.

MBC double sided chassis showing MCCBs with direct


mount handles and terminal covers fitted. Refer accessories
pages for cover and other accessories selection.

MBC double sided chassis showing Socomec SLB16003P


isolator using a link kit as shown. A clear polycarbonate
cover for the link kit is also available (not shown).

Link kits are available for chassis with 1250A And 1600A
main bars. 2200A main bar kits are not available at this
time. Additional details are available on request.

Catalogue numbers of link kit parts:

Link kit HCCONNTAG16003P


Link kit cover HCSLB1600C

19
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC MCCB High Current Chassis

Reference dimensions

MBC Chassis cut-out details

Notes
1. 1600A Chassis shown above with 2 off 30mm x 10mm busbars per phase.
2. Other busbar options: 1250A busbars, 2 off 20mm x 10mm per phase
2200A busbars, 2 off 50mm x 10mm per phase
3. Cut out dimensions are centred on the MCCB toggles.

20
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MBC MCCB High Current Chassis

Front Connect MCCB mounting on MBC chassis

MCCBs are mounted to the tee offs on an MBC chassis with the MCCB terminals connected to the connection bar coming from the
tee off which fits directly into the MCCB main terminals on the FRONT of the MCCB. MCCBs are also to be reverse connected,
which means the bottom of MCCB where the Over Current Relay is located, is connected to the tee offs. This will allow venting
gasses to be directed away from the chassis in event of a fault.

400A / 630A MCCB


connection tee offs

250A MCCB
connection tee offs

Front Connect mounting method – 400/630A MCCB example:

21
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Transfer Switches

Basic Transfer Switches


MODbreak transfer switches are available from 20A to 630A, and consist of mechanically and electrically interlocked circuit breakers,
with motors fitted. The transfer switches come pre-wired on a metal panel.

Automatic Transfer Switches


Basic Transfer Switches can be coupled with either TemLogic ATL610CIP electronic or TLP2 relay timer changeover controllers to
enable Automatic Transfer Switching (ATS). The changeover controller automatically commences a change over to a standby power
supply in the event of power failure.

Manual Transfer Switches


MODbreak Manual Transfer Switches are available from 20A to 630A, and consist of rear walking beam mechanically interlocked
circuit breakers on a metal mounting plate. Manual transfer switches are assembled by the user, using interlock kits and MCCBs that
are ordered from the MCCB and accessories pages in this catalogue.

Basic Transfer Switches (BTS)

Features:
▪ Poles: 3P+3P or 4P+4P MCCB configurations.
▪ Pre-assembled on a mounting plate
▪ Rear walking beam interlock used
▪ Pre-wired with electrical interlocking
▪ 240V AC control motor operated MCCBs
▪ Includes plug connectors to suit TL101CIP or TLP2 controllers

Ordering:
• MB transfer switches are manufactured to order.
• Contact NHP for availability.
• TM = Thermal Magnetic, E = Electronic Trip Unit.

BTS = Basic Transfer Switch with motors

BTS selection chart and Catalogue numbers

Fault I/C 3P Outline Dims.


Ampere OCR 3 Pole Price 4 Pole Price
MCCB’s used 415V kA (mm)
Range Type BTS Cat No. $ BTS Cat No. $
Icu/Ics H W D

MB263N_TM 50.4-63 MBTSTM6333 0.00 MBTSTM6344 0.00


MB263N_TM 80-100 MBTSTM10033 0.00 MBTSTM10044 0.00
MB263N_TM 100-125 50 TM 305 209 235 MBTSTM12533 0.00 MBTSTM12544 0.00
MB263N_TM 128-160 MBTSTM16033 0.00 MBTSTM16044 0.00
MB263N_TM 200-250 MBTSTM25033 0.00 MBTSTM25044 0.00
MB240N_SE 16-40 MBTSE4033 0.00 MBTSE4044 0.00
MB2100N_SE 40-100 50 E 336 237 241 MBTSE10033 0.00 MBTSE10044 0.00
MB2250N_SE 100-250 MBTSE25033 0.00 MBTSE25044 0.00
MB3320N_TM 256-320 MBTSTM32033 0.00 MBTSTM32044 0.00
MB3400N_TM 320-400 50 TM 550 433 341 MBTSTM40033 0.00 MBTSTM40044 0.00
MB3630N_TM 504-630 MBTSTM63033 0.00 MBTSTM63044 0.00
MB3400N_SE 160-400 50 E 550 433 341 MBTSE40033 0.00 MBTSE40044 0.00
MB3630N_SE 252-630 MBTSE63033 0.00 MBTSE63044 0.00

22
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ATL610 Controller for Automatic Transfer Switching


How to order

23
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ATL610 Controller for Automatic Transfer Switching


Technical Data

ATL610NHP
Rear view

ATL610NHP
Front facia
ATL610NHP
Panel cut-out

ATLEXP expansion modules

24
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ATL610CIP Wiring layout and dimensions

ATL610 Controller & Interface Panel layout for BTS 250AF to 630AF

Side view Controller cut-out

Individual component item reference list / Catalogue numbers.


Item Qty Description Cat. No Item Qty Description Cat. No
1 1 Base plate 280 x 200 mm ATS4D 12 1 Terminal intermediate plate (orange) 281302
2 1 Controller (door mounted) ATL610NHP 13 5 Terminal double deck intermediate plate (orange) 281341
3 1 DIN rail 140 DIN140 14 4 Terminal end clamp 249117
4 1 DIN rail 200 DIN200 15 1 Plug (Normal MCCB) (orange, 12 pole, male) 231642019000
5 6 Fuse holder - 32 A cylindrical, front wired 31110 16 1 Plug (Normal) (orange, 12 pole, female) 231312037000
6 6 Fuse - 6 A 10 x 38mm 31184 17 1 Plug (Emergency MCCB) (grey, 12 pole, male) 231612019000
7 1 Control relay CS840E240VAC 18 1 Plug (Emergency) (grey, 12 pole, female) 231112037000
8 1 Relay Auxiliary CS8P04E 19 1 Loom to Normal plug LTLP2LOOM1
9 2 Terminal (4mm square, Grey) 281101 20 1 Loom to Emergency plug LTLP2LOOM2
10 7 Terminal double deck (4 mm square grey) 281619 21 1 Loom to Controller LTLP2LOOM3
11 3 Terminal earth (4 mm square green/yellow) 281107

25
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ATL610CIP + Basic Transfer Switch Wiring Diagram

For BTS types using 250AF and 630AF MCCBs

26
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ATL610CIP + Basic Transfer Switch Wiring Diagram

NHP drawing number: MD–L007192: R1


Notes: CONTROL CIRCUIT CABLING

415 V AC Size: 0.75 mm C/W boot end pins 24 V DC Size: 0.75 mm C/W Boot end pins
Colours: Red, White & Blue – Phases Colours: Orange – Positive
Black – Neutral Purple – Negative

240 V AC Size: 0.75 mm C/W boot end pins Volt free Size: 0.75 mm C/W Boot end pins
Colours: Red – Active Colour: Pink – Active
Black – Neutral

27
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Transfer Switch Controller

Type: TLP2
Timer / Relay logic controller
The basic timer / relay logic controller includes the following
standard features:

• Voltage and phase sequence sensing relay


• Time delay normal to emergency
• Time delay emergency to normal
• Common power supply relays
• Normal supply phase sequence relay
• 4 supply fuses
• Control wiring terminals
• A 4 position mode selector switch is provided loose (Manual / Automatic / Test / Off)

Description Catalogue Number Price $


Controller for MODbreak Transfer Switches TLP2

28
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Wiring Diagrams

MB MOT Motor Operators


Motor control wire designations are indicated with wire markers
as indicated below.

Red wire numbered: 1


Red wire numbered: 5
Grey wire numbered: 3
Black wire numbered: 2 MB MOT Motor Operator for MB2 and MB3 MCCBs
Blue wire numbered: 4

Wires are also shown in colour in the wiring diagram at the right.

Transfer Switch with remote electrical control - non automatic switching

29
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Automatic Transfer switch TLP2 Controller


Wiring, components and dimensions

30
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Automatic Transfer switch TLP2 Controller


Wiring, components and dimensions

31
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Automatic Transfer switch TLP2 Controller


Wiring, components and dimensions

32
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB ratings chart


MCCB Ampere Frames (AF) 250 A 400A 630A 800/1000/1250

MB2 MB3 MB3 MB4


MCCB Types
D N D N D N N
Poles 3 or 4 3 or 4 3 or 4 3 or 4
OCR (Over Current Relay) data
Current Ratings of OCRs (A) 63, 80, 100, 125, 160, 200, 250 320, 400 630 A 800, 1000, 1250
OCR types Thermal Magnetic & Electronic Thermal Magnetic & Electronic Thermal Magnetic & Electronic Electronic
Thermal magnetic dial adjustment range 0.8 to 1.0 x In and 6 – 10 x Im 0.8 to 1.0 x In and 6 – 10 x Im 0.8 to 1.0 x In and 6 – 10 x Im -
MTX1 Electronic OCR data
OCR adjustments via DIP switches
Adjustment range (LT) 0.4 to 1.0 in steps of 0.05 or OFF
Adjustment of LT time delay Ir 10s at 6 Ir or 3s at 6 Ir and 10s at 7.2 Ir or 3s at 7.2 Ir
LT Thermal memory Enable / Disable (θ = ON or 0 = OFF)
Adjustment range (ST) Ir 1.5, 2.5, 4, 5.5, 6.5, 8 x Ir
Short time setting time delay 100ms / Instantaneous or OFF
Fixed Instantaneous OCR setting 10 x In 10 x In
MCCB data
Impulse withstand Voltage (kV) 8 8 8 8
Rated Operational Voltage (V) (max) 690 690 690 690
Rated Insulation Voltage (V) 750 750 750 750
Standard and approvals AS/NZS / IEC / CE AS/NZS / IEC / CE AS/NZS / IEC / CE AS/NZS / IEC /CE
230 / 240 V AC 65 85 65 85 65 85 85
400 / 415 V AC 36 50 36 50 36 50 50
AS/NZS 60947.2

500 V AC 25 36 25 36 25 36 25
IEC-60947-2

Icu 550 V AC 18 25 15 20 15 20 20
kA 600 V AC 16 18 12 18 12 18 16
690 V AC 10 15 8 15 8 10 10
250VDC (3P in series) 15 25 15 25 15 25 -
500VDC (3P in series) L/ R<15ms 5 10 5 10 5 10 -
Ics as % lcu 100% 100% 100% 100% 100% 100% 100%
Mechanical 25000 15000 15000 8000
Life span
Electrical @1.0 In 10000 4000 4000 750
Operating Frequency (Hz) 50 / 60
Total Opening Time <10 msec <20 msec
Finger-proof Terminals Via use of MB terminal covers
Ambient Temperature -5°C to + 55°C
Storage Temperature - 35°C to + 70°C
Mounting Positions Vertical and 90° to the left and right
3 Pole 105 x 96 x 179 140 x 111.5 x 266 140 x 111.5 x 266 210 x 143 x 370
Dimensions (W x D x H)
4 Pole 140 x 95 x 179 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
Weight (kg) (3/4 Pole) 2.5 / 3.3 5.5 / 7.2 6 / 7/.8 13 / 16
Accessories
Auxiliary Contact 1C/O or 2C/O
Trip Alarm Contact 1C/O
Internal Auxiliary & Trip Alarm Contact 1C/O + 1C/O
Shunt Release 110 - 415V 50/60Hz, 110 - 220V DC
Under Voltage Release 220 - 240 V 50 Hz
Extension handle √ √ √ √
Direct mount handle √ √ √ X
Handle mechanism padlock attachment √ √ √ √
Captive toggle padlock attachment √ √ √ √
Trapped key interlock 4 extension hdle X X X X
Mechanical Interlock √ √ √ X
Motor operator for remote operation √ √ √ X
External Transfer switch controller √ √ √ √
Spreader bars for MCCB terminals √ √ √ √
Terminal covers - same width as MCCB √ √ √ √
Terminal covers - wide width √ √ √ X
Terminal covers - flush √ √ √ X
Interpole barriers – c/w with MCCB √ √ √ √
Chassis rated 800A for 250AF √ √ √ X
Chassis (high current) up to 630AF √ √ √ X

33
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MCCB to MCB Selectivity and Cascading


• Upstream THERMAL MAGNETIC MCCB, either 36kA or 50kA
• Downstream Thermal magnetic MCBs, MOD6 or DIN-T series
• 415V AC system voltage

MB2 NTM MB3 NTM


250AF MCCB Thermal Magnetic, 50kA 400AF MCCB Thermal Magnetic, 50kA

Current MB263N_TM MB2100N_TM MB2125N_TM MB2160N_TM MB2250N_TM MB3320N_TM MB3400N_TM


Downstream
Rating 63A 100A 125A 160A 250A 320A 400A
≤32 25 / 25 25 / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
MOD6 6kA
MCB's & 40 -- / 25 25 / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
RCBO's
50-63 -- / 25 -- / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
≤32 25 / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
DIN-T 6kA
MCB's & 40 -- / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
RCBO's
50-63 -- / 30 -- / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30
DIN-T 10kA
MCB's & 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
RCBO's
50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
80 -- / -- -- / -- -- / 25 15 / 25 15 / 25 10 / 10 10 / 10
DIN-TH
100 -- / -- -- / -- -- / -- 15 / 25 15 / 25 10 / 10 10 / 10
10kA MCB's
125 -- / -- -- / -- -- / -- -- / -- 15 / 25 10 / 10 10 / 10
≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30
DIN-T 15kA
40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
MCB's
50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30

MB2 DTM MB3 DTM


Upstream
250AF MCCB Thermal Magnetic, 36kA 400AF MCCB Thermal Magnetic, 36kA
Current MB263D_TM MB2100D_TM MB2125D_TM MB2160D_TM MB2250D_TM MB3320D_TM MB3400D_TM
Downstream
Rating 63A 100A 125A 160A 250A 320A 400A
≤32 25 / 25 25 / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
MOD6 6kA
MCB's & 40 -- / 25 25 / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
RCBO's
50-63 -- / 25 -- / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / --
≤32 25 / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
DIN-T 6kA
MCB's & 40 -- / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
RCBO's
50-63 -- / 30 -- / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --
≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30
DIN-T 10kA
MCB's & 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
RCBO's
50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
80 -- / -- -- / -- -- / 25 15 / 25 15 / 25 10 / 10 10 / 10
DIN-TH
100 -- / -- -- / -- -- / -- 15 / 25 15 / 25 10 / 10 10 / 10
10kA MCB's
125 -- / -- -- / -- -- / -- -- / -- 15 / 25 10 / 10 10 / 10
≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30
DIN-T 15kA
40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
MCB's
50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30
Notes:
• The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 25 / 30 Cascade
• -- or --/-- Indicates no Selectivity or Cascade.
• Selectivity: The power contacts of the Upstream MCCB do not latch open when a fault is cleared by the downstream MCB.
• Cascading: The upstream MCCB assists the downstream MCB in clearing a higher level fault than the MCBs normal breaking capacity.

34
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MCCB to MCB Selectivity and Cascading


• Upstream ELECTRONIC MCCB either 36kA or 50kA
• Downstream Thermal magnetic MCBs, MOD6 or DIN-T series
• 415V AC system voltage

MB2 NSE MB3 NSE


Upstream
250AF MCCB Electronic OCR, 50kA 400AF MCCB Electronic OCR, 50kA

Current MB240N_SE MB2100N_SE MB2250N_SE MB2250N_SE MB3400N_SE


Downstream
Rating 40A 100A 160A 250A 400A
≤32 20 / 25 20 / 25 20 / 25 20 / 25 -- / --
MOD6 6kA
MCB's & 40 -- / 25 20 / 25 20 / 25 20 / 25 -- / --
RCBO's
50-63 -- / 25 -- / 25 20 / 25 20 / 25 -- / --
≤32 20 / 30 20 / 30 20 / 30 20 / 30 -- / --
DIN-T 6kA
MCB's & 40 -- / 30 20 / 30 20 / 30 20 / 30 -- / --
RCBO's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 -- / --
≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30
DIN-T 10kA
MCB's & 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30
RCBO's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30
80 -- / -- -- / -- 10 / 15 10 / 15 10 / 10
DIN-TH
100 -- / -- -- / -- 10 / 15 10 / 15 10 / 10
10kA MCB's
125 -- / -- -- / -- -- / -- 10 / 15 10 / 10
≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30
DIN-T 15kA
40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30
MCB's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30

MB2 DSE MB3 DSE


Upstream
250AF MCCB Electronic OCR, 36kA 400AF MCCB Electronic OCR, 36kA
Current MB240D_SE MB2100D_SE MB2250D_SE MB2250D_SE MB3400D_SE
Downstream
Rating 40A 100A 160A 250A 400A
≤32 20 / 25 20 / 25 20 / 25 20 / 25 -- / --
MOD6 6kA
MCB's & 40 -- / 25 20 / 25 20 / 25 20 / 25 -- / --
RCBO's
50-63 -- / 25 -- / 25 20 / 25 20 / 25 -- / --
≤32 20 / 30 20 / 30 20 / 30 20 / 30 -- / --
DIN-T 6kA
MCB's & 40 -- / 30 20 / 30 20 / 30 20 / 30 -- / --
RCBO's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 -- / --
≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30
DIN-T 10kA
MCB's & 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30
RCBO's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30
80 -- / -- -- / -- 10 / 15 10 / 15 10 / 10
DIN-TH
100 -- / -- -- / -- 10 / 15 10 / 15 10 / 10
10kA MCB's
125 -- / -- -- / -- -- / -- 10 / 15 10 / 10
≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30
DIN-T 15kA
40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30
MCB's
50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30
Notes:
• The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 30 Cascade
• -- or --/-- Indicates no Selectivity or Cascade.
• Selectivity: The power contacts of the Upstream MCCB do not latch open when a fault is cleared by the downstream MCB.
• Cascading: An upstream MCCB assists a downstream MCB to clear a higher fault than the MCB’s breaking capacity.

35
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MCCB to MCCB Selectivity and Cascade


• 36kA upstream ELECTRONIC MCCB
• Downstream Thermal magnetic or Electronic MCCBs
• 415V AC system voltage

Upstream MB3 DSE MB4 DSE


MCCB MCCB Electronic MTX1.0 OCR, 36kA MCCB Electronic MTX1.0 OCR, 36kA
Downstream Current MB3400D_SE MB3630D_SE MB4800D_SE MB41000D_SE MB41250D_SE
MCCB Rating 400 A 630 A 800 A 1000 A 1250 A
MB240D_SE
40 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB240N_SE
MB263D_TM
MB263N_TM
63 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2100D_SE
MB2100N_SE
MB2100D_TM
MB2100N_TM
80 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2100D_SE
MB2100N_SE
MB2100D_TM
MB2100N_TM
100 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2100D_SE
MB2100N_SE
MB2125D_TM
MB2125N_TM
125 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2125D_SE
MB2125N_SE
MB2160D_TM
MB2160N_TM
160 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2160D_SE
MB2160N_SE
MB2250D_TM
MB2250N_TM
200 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2250D_SE
MB2250N_SE
MB2250D_TM
MB2250N_TM
250 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36
MB2250D_SE
MB2250N_SE
MB3320D_TM
MB3320N_TM
400 A -- -- 36 / 36 36 / 36 36 / 36
MB3400D_SE
MB3400N_SE
MB3630D_TM
MB3630N_TM
630 A -- -- 36 / 36 36 / 36 36 / 36
MB3630D_SE
MB3630N_SE

Notes:
• The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 36 Cascade
• “--“ Indicates no Selectivity or Cascade.
• Selectivity: The Upstream MCCB power contacts do not latch open a fault is cleared by the downstream MCCB.
• Cascading: An upstream MCCB assists a downstream MCCB to clear a higher fault than the MCCB’s breaking capacity.

36
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MCCB to MCCB Selectivity and Cascade


• 50kA upstream ELECTRONIC MCCB
• Downstream Thermal magnetic or Electronic MCCBs
• 415V AC system voltage

Upstream MB3 NSE MB4 NSE


MCCB MCCB Electronic MTX1.0 OCR, 50kA MCCB Electronic MTX1.0 OCR, 50kA
Downstream Current MB3400N_SE MB3630N_SE MB4800N_SE MB41000N_SE MB41250N_SE
MCCB Rating 400 A 630 A 800 A 1000 A 1250 A
MB240D_SE
40 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB240N_SE
MB263D_TM
MB263N_TM
63 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2100D_SE
MB2100N_SE
MB2100D_TM
MB2100N_TM
80 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2100D_SE
MB2100N_SE
MB2100D_TM
MB2100N_TM
100 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2100D_SE
MB2100N_SE
MB2125D_TM
MB2125N_TM
125 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2125D_SE
MB2125N_SE
MB2160D_TM
MB2160N_TM
160 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2160D_SE
MB2160N_SE
MB2250D_TM
MB2250N_TM
200 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2250D_SE
MB2250N_SE
MB2250D_TM
MB2250N_TM
250 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50
MB2250D_SE
MB2250N_SE
MB3320D_TM
MB3320N_TM
400 A -- -- 36 / 50 36 / 50 36 / 50
MB3400D_SE
MB3400N_SE
MB3630D_TM
MB3630N_TM
630 A -- -- 36 / 50 36 / 50 36 / 50
MB3630D_SE
MB3630N_SE

Notes:
• The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 50 Cascade
• “--“ Indicates no Selectivity or Cascade.
• Selectivity: The Upstream MCCB power contacts do not latch open a fault is cleared by the downstream MCCB.
• Cascading: An upstream MCCB assists a downstream MCCB to clear a higher fault than the MCCB’s breaking capacity.

37
MODBreak Technical Catalogue 2019 TECH-001-EN
M

ACB to MCCB Selectivity and Cascade


• 65kA upstream ELECTRONIC AIR CIRCUIT BREAKER
• Downstream Thermal magnetic MCCBs
• 415V AC system voltage

Downstream 36kA Thermal Magnetic MCCBs


Upstream MP1 Frame MP2 Frame MP3 Frame
ACB 65kA 65kA 65kA
Downstream Current MP1S12E MP1S16E MP1S20E MP1S25E MP2S32E MP3H40E
MCCB Rating 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A
MB263D_TM 63 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2100D_TM 80 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2100D_TM 100 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2125D_TM 125 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2160D_TM 160 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2250D_TM 200 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB2250D_TM 250 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB3320D_TM 400 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36
MB3630D_TM 630 A 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36 36 / 36

Downstream 50kA Thermal Magnetic MCCBs


Upstream MP1 Frame MP2 Frame MP3 Frame
ACB 65kA 65kA 65kA
Downstream Current MP1S12E MP1S16E MP1S20E MP1S25E MP2S32E MP3H40E
MCCB Rating 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A
MB263N_TM 63 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2100N_TM 80 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2100N_TM 100 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2125N_TM 125 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2160N_TM 160 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2250N_TM 200 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB2250N_TM 250 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB3320N_TM 400 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
MB3630N_TM 630 A 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50

Notes:
• All ACBs are to have Ii set to NON. (INST switched OFF)
• ACB time settings are to be set higher than MCCB time settings.
• The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 50 / 50 Cascade

38
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODcurve software
MODcurve is a selectivity analysis software package developed by NHP specifically for the Australian and New Zealand markets.
Designed around the MOD series of ACBs and MCBs as well as NHP’s extensive range of MCBs and fuses, MODcurve presents a
user-friendly interface for conducting selectivity studies. (Latest version: MODcurve 1.09)

Features:
• Simple and easy to use
• Can be used for coordination with upstream HV fuses
• Includes both MOD6 and Din T ranges of MCBs
• User defined devices can be added
• Ability to print report with single line diagram and circuit breaker settings included

39
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Motor starting table

Motor circuit application table for DOL starting


General purpose circuit breaker selection for 3 Phase, 4 Pole, 415 V AC motors requiring short circuit protection.

Breaker type and current rating (A)


MOD6 or MB2 MB2 MB3 MB3 MB4
Approximate
Motor kW DINT Thermal Magnetic Electronic Thermal Magnetic Electronic Electronic
FLC (Amps)
MCB MCCB MCCB MCCB MCCB MCCB
0.37 1.1 4
0.55 1.5 4
0.75 1.8 6
1.1 2.6 10
1.5 3.4 10
2.2 4.8 16
3.0 6.5 20
4 8.2 25
4.5 9 32 40
5.5 11 32 40
7.5 14 40 40
10 19 50 100
11 21 50 63 100
15 28 63 63 100
18.5 34 100 3) 100 100
22 40 125 3) 100 100
25 46 125 3) 100 250
30 55 125 250
37 66 125 250
45 80 125 250
55 100 200 250 400
75 135 250 250 320 400
90 160 250 250 320 400
110 200 250 250 320 400
132 230 400 400
160 270 400 400
185 320 400 400
200 361 400 400 800
220 380 630 630 800
250 430 630 630 800
280 480 630 630 800
300 510 630 630 800
375 650 1000
450 750 1000

Notes:
1) The DOL table is based on holding 125 % FLC continuously and 600 % FLC for 10 seconds.
2) The primary task of the above circuit breakers is to provide short circuit and cable protection. The motor starter would normally be supplied with an
overload relay that will detect lower level current overloads or phase loss.
3) 80, 100 and 125 amp refers to Din-T10H type.
4) MOD6 MCBs are C curve MCBs. Din-T MCBs are C or D curve types, and either can be used for motor starting.
5) Thermal magnetic MCCB current adjustment range 0.8 to 1.0 x In. Set magnetic trip to maximum or equivalent to 15 x motor FLC.
6) Electronic MCCB base current adjustment ranges 0.4 to 1.0 x In. Set Short Time setting to maximum or equivalent to 15 x Motor FLC.
7) Lower ampere rated MCCBs are possible for many applications. The above MCCB sizes generally provide additional ampere capacity.
8) MODbreak MCCBs have a maximum instantaneous trip setting of 10 x In. Consideration should be given to the use of high efficiency motors with a short
time current inrush of between 15 to 20 x In.
9) Refer NHP for tables for reduced voltage, and Type 2 coordination motor starting.

40
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Motor starting table

Motor circuit application table for DOL FIRE PUMP starting duty
Circuit breaker selection for 3 Phase, 4 Pole, 415 V AC motors requiring short circuit protection

Breaker type and current rating (A)


MOD6 or MB2 MB2 MB3 MB3 MB4
Approximate
Motor kW DINT Thermal Magnetic Electronic Thermal Magnetic Electronic Electronic
FLC (Amps)
MCB MCCB MCCB MCCB MCCB MCCB
0.37 1.1 4
0.55 1.5 6
0.75 1.8 6
1.1 2.6 10
1.5 3.4 10
2.2 4.8 20
3.0 6.5 25
4 8.2 32
4.5 9 32 40
5.5 11 32 40
7.5 14 50 40
10 19 63 100
11 21 63 63 100
15 28 100 100 100
18.5 34 125 3) 100 100
22 40 125 3) 125 100
25 46 125 3) 125 250
30 55 160 250
37 66 160 250
45 80 250 250
55 100 250 250 320
75 135 250 320
90 160 400 400
110 200 400 400
132 230 400 400
160 270 400 400
185 320 400 400
200 361 630 630
220 380 630 630
250 430 630 630
280 480 800
300 510 800
375 650 1000
450 750 1000

Notes:
1) The DOL table is based on holding 125 % FLC continuously and 600 % FLC for 20 seconds.
2) The primary task of the above circuit breakers is to provide short circuit and cable protection. The motor starter would normally be supplied with an
overload relay that will detect lower level current overloads or phase loss.
3) 80, 100 and 125 amp refers to Din-T10H type.
4) MOD6 MCBs are C curve MCBs. Din-T MCBs are C or D curve types, and either can be used for motor starting.
5) Thermal magnetic MCCB current adjustment range 0.8 to 1.0 x In. Set magnetic trip to maximum or equivalent to 15 x motor FLC.
6) Electronic MCCB base current adjustment ranges 0.4 to 1.0 x In. Set Short Time setting to maximum or equivalent to 15 x Motor FLC.
7) MODbreak MCCBs have a maximum instantaneous trip setting of 10 x In. Consideration should be given to the use of high efficiency motors with a short
time current inrush of between 15 to 20 x In.
8) Refer NHP for tables for reduced voltage, and Type 2 coordination motor starting.

41
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak technical data

Watts Loss for Thermal Magnetic and Electronic MCCBs


MCCB Watts loss per pole (W)
MB2 250 D/N_SE 40A 7.8
MB2 250 D/N_TM/SE 63A 8.5
MB2 250 D/N_TM/SE 100A 11
MB2 250 D/N_TM/SE 160A 13
MB2 250 D/N_TM/SE 250A 18
MB3 400 D/N_TM/SE 400A 22
MB3 630 D/N_TM/SE 630A 47
MB4 800 N_SE 800A 32
MB4 1000 N_SE 1000A 50
MB4 1250 N_SE 1250A 78

Temperature Ratings for Thermal Magnetic MCCBs


Ambient Temperature (oC)
MCCB type
40 45 50 55 60 65 70
MB2 63 D/N_TM 63A 63 62 61 60 59 58 57
MB2 100 D/N_TM 100A 100 98 97 95 94 93 91
MB2 125 D/N_TM 125A 125 123 121 119 118 116 114
MB2 160 D/N_TM 160A 160 156 152 148 144 140 136
MB2 200 D/N_TM 200A 200 192 184 176 168 160 152
MB2 250 D/N_TM 250A 250 241 232 224 215 206 198
MB3 400 D/N_TM 400A 400 391 382 373 364 355 346
MB3 630 D/N_TM 630A 630 621 612 603 594 585 576

Temperature Ratings for Electronic MCCBs


Ambient Temperature (oC)
MCCB type
40 45 50 55 60 65 70
MB2 250 D/N_SE 40A 40 40 40 40 40 40 40
MB2 250 D/N_SE 63A 63 63 63 63 63 63 63
MB2 250 D/N_SE 100A 100 100 100 100 100 100 100
MB2 250 D/N_SE 125A 125 125 125 125 125 125 125
MB2 250 D/N_SE 160A 160 160 160 160 160 160 160
MB2 250 D/N_SE 250A 250 250 250 243 236 229 222
MB3 400 D/N_SE 400A 400 400 400 393 386 379 372
MB3 630 D/N_SE 630A 630 630 630 605 585 565 545
MB4 1250 N_SE 800A 800 800 800 790 780 770 760
MB4 1250 N_SE 1000A 1000 1000 1000 1000 1000 990 980
MB4 1250 N_SE 1250A 1250 1250 1250 1235 1220 1205 1190

Shock data
• Shock Strength Test: Bump test at 10 g, 16 ms, 60 Bumps/min, Total: 1000 Bumps
• Shock Resistance Test: Bump test at 10 g, 16 ms, 1 Bump/sec, 20 Bumps / axis, 3 axis, Total: 60 Bumps
• Resistance to Motion and prolonged inclination test: Ship Motion test: ± 15º for 15 min/axis;
Inclination test at 22.5º inclination, 5 min/axis.
Harmonics Inhibition
• MODbreak MTX 1.0 Electronic Over Current Relays are true RMS (current) sensing.
• MTX 1.0 OCRs meet the requirements for harmonic immunity for IEC 60947-2, AS 60947-2, AS/NSZ 3947-2.
• Third harmonic content in excess of 60 % for 3rd Harmonic, 5th > 14%, 7th > 7% with peak factors of 2.1.
• MTX 1.0 OCR immunity has been verified for higher harmonic contents up to the 15th (60%).

42
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak technical data

Let-through and Cut-off values at 415V AC - Thermal Magnetic and Electronic MCCBs
Cut-off (kA) Let-through (x106 A2seconds)
MCCB
36 kA (Icu) MCCB 50 kA (Icu) MCCB 36 kA (Icu) MCCB 50 kA (Icu) MCCB
MB2 250 D/N_TM/SE 250A 19 22 1.4 1.6
MB3 400 D/N_TM/SE 400A 25 26 2.2 2.6
MB3 630 D/N_TM/SE 630A 30 32 3.8 4.4
MB4 800 N_SE 800A - 65 - 40
MB4 1000 N_SE 1000A - 65 - 40
MB4 1250 N_SE 1250A - 65 - 40

Let Through Curves – I2T

MB2 Thermal Magnetic and Electronic

MB2 – 250A

43
MODBreak Technical Catalogue 2019 TECH-001-EN
M

Let Through Curves – I2T

MB3 400A Thermal Magnetic and Electronic MCCBs

MB3 – 400A

MB3 630A Thermal Magnetic and Electronic

MB3 – 630A

44
MODBreak Technical Catalogue 2019 TECH-001-EN
M

Let Through Curves – I2T

MB4 800A to 1250A Electronic

MB4 – 800A to 1250A

45
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Characteristic curves Thermal Magnetic MCCBs

MB2: 63A, 100A, 125A, 160A, 200A, 250A

Typical thermal magnetic MCCB setting facia. To access, unclip the


grey plastic cover on the front of the MCCB.

MB3: 400A / 630A

46
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Characteristic curves Electronic MCCBs: 40A to 1250A

MTX1: MB2 / MB3 / MB4 MTX1: MB2 / MB3 / MB4

MTX1 short Time setting: MB2 / MB3 / MB4

Typical electronic MCCB setting facia. To access, unclip the grey


plastic cover on the front of the MCCB.

47
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Electronic MCCB DIP Switch Setting

Refer below for DIP switch positions and settings.

Long Time Delay (LTD) Overload Protection (It = x IN) Switching the DIP switches UP switches the LTD settings OFF

Thermal Memory
The thermal memory feature is enabled or disabled by switching the DIP switch above the symbol θ on the OCR facia.
Up = BYPASS (OFF) / Down = ON.

The thermal memory feature is similar to the effects of hot and cold starting on an overload relay or thermal magnetic MCCB.
Thermal memory can protect the system from thermal stresses generated by cumulative heating caused by cyclic overload
conditions, thereby allowing the MCCB & system to return to a safe operating temperature. This function also allows for an
optimisation of cables or busbar protection in the case of low amplitude repetitive faults. The “Advance tripping” of the MCCB also
increases overall life and eliminates installation downtime.

48
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Electronic MCCB DIP Switch setting

Refer below for DIP switch positions and the resulting setting

Inverse Overload Curve Type Selection


• Allows a degree of curve adjustment to allow for grading with upstream or downstream devices.
• Adjust the tripping characteristics of the MCCB for motor starting to take into account motor start up times.
• Refer MODbreak characteristic curves on previous pages for each setting characteristic.

Short Time Delay (STD) Short Circuit Setting (IS = x IN) Switching the DIP switches UP switches the STD settings OFF

Time Delay for Short Circuit Protection


Allows for the selection of a short delay just prior to the MCCB tripping if a short circuit occurs.

49
MODBreak Technical Catalogue 2019 TECH-001-EN
M

About MODbreak Electronic MCCB OCRs

Electronic OCR Layout:

• Overload protection LT with selectable inverse time delay


• Adjustable Short Time ST characteristic
• Short circuit (ST) characteristic with selectable time delay
• LT and ST characteristic can be switched OFF (DIP switches UP)
• Fixed instantaneous trip at 10 x In
• Thermal memory enable / disable
• True RMS sensing

Overload Pick-Up Indication LED


Improves uptime and productivity, via a visual indicator LED which can be used to monitor an unbalanced load so that proactive
measures can be taken to avoid overload conditions.

Overload pick-up LED Indicator

% of IR Overload pick-up LED indication


30% Green LED
85% Fast blinking of LED
115% LED operates sequential ON/OFF operations

LED Indicator
• When the current flowing through the MCCB is less than 30% of the preset OCR current setting, the LED is OFF.
• When the current reaches ≥ 30% of IN, the green LED is ON.
• At 85% of Ir the OCR enters alarm mode and starts to blink OFF and ON.
• At 115% of Ir the OCR enters into pick up mode and is indicated by sequential ON OFF operations of the LED.
• Above the 115% level the OCR will trip the MCCB.

50
MODBreak Technical Catalogue 2019 TECH-001-EN
M

About MODbreak Electronic MCCB OCRs

Example of setting the LTD – Long Time Delay setting, which is used to reset the amp rating of the MCCB.

EXAMPLE
250A Trip Unit

The DIP switches allow LTD setting changes - refer examples below. The photo below shows the FACTORY DEFAULT settings.
The raised white indicator indicates the up or down position of the DIP switch (switch in photo is shown down)

EXAMPLE
250A Trip Unit

To calculate the current setting, simply add up the DIP switch multiples.
For example: when the DIP switches are switched DOWN the amp ratings are selected.
• 0.4 + 0.05 + 0.1 + 0.2 + 0.25 = 1, in other words, set at 100% of the trip unit rating = 250A.
• 0.4 + 0.05 + 0.2 = 0.65 x 250A = 162.5A
• 0.4 = 0.4 x 250A = 100A.
• If 0.4 and the other LT settings are switched to the upper position, the Long Time characteristic is switched
OFF. The MCCB is now short time and instantaneous only.

51
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB2: 16A to 250A

M4 threaded mounting hole

ON 7mm
TRIP 17mm
OFF 34mm

28mm Thermal Magnetic MCCBs


26.5mm Electronic MCCBs
Terminal moulding connection area width 24.5 mm per pole

MB2: 16A to 250A with optional spreader busbar tags

Rating Type Dimension mm (A)


63A – 100A Thermal magnetic 25.5
125A – 250A Thermal magnetic 28
40A – 250A Electronic 28

52
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB3: 320A to 630A

M5 threaded mounting hole

Terminal moulding connection area width 33 mm per pole

MB3: 320A to 630A with optional spreader busbar tags

MCCB without spreader bars (top drawing) MCCB with spreader bars (bottom drawing)
MB3 MB4
A 39 41
Dim A Dim B B 37 38
400A Thermal Magnetic: 39mm 400A Thermal Magnetic: 36.6mm C 45 55
400A Electronic: 39mm 400A Electronic: 38mm D 324 344
630A Thermal Magnetic: 43.3mm 630A Thermal Magnetic: 39mm E 370 390
630A Electronic: 43mm 630A Electronic: 39.3mm F 13 11

53
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB4: 800A, 1000A and 1250A

Connection tag height from rear of MCCB is 46.3 mm

Door Mounting
cut-out dimensions

Terminal moulding connection area width 50 mm per pole

MB4: 800A, 1000A and 1250A with optional extension busbar tags.

10.5 24 10.5

Bar size: 116 x 45 x 15 mm 14


Material: Tinned copper

11mm θ

116

8
113mm θ slotted
15

13mm θ

22.5 22.5

45

54
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Direct mount handle mounting

MCCB

DD

L1 = Mounting depth MCCB + handle Type L1 L2 L3 L4 L5 C D


L2 / L3 = Door or escutcheon cut-out MB2 122 96 63 53 66 86 55
L4 / L5 = Breaker position relative to cut-out MB3 146 121 87 78 82 95 55
MB4 156 121 87 78 82

55
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Extension handle mounting

Dimensions (mm) Minimum and maximum depths using extension shaft handle (MCCB + Shaft + Handle)
MCCB Minimum depth Maximum Depth
Frame L1 L L2 L3
MB2 202 mm L1 = 152 420 mm 27 84
MB3 220 L1 = 170 440 39 122
MB4 302 L1 = 252 510 69 170

Total length of shaft is 275mm x 8mm square. Longer shafts not available.

MB4 - example

56
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB2 MCCB with motor operator fitted

MB3 MCCB with motor operator fitted

57
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Mechanical interlock and mounting plate

MB2

MB3

58
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB2 Terminal covers – 250AF MCCBs

Typical internal construction for


MODbreak terminal covers

59
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

MB3 Terminal covers - 630AF MCCBs

MB4 Terminal covers - 1250AF MCCBs

60
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Manual Transfer Switch 250AF – 3 Pole

Manual Transfer Switch 250AF – 4 Pole

61
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Manual Transfer Switch 630AF – 3 Pole

Manual Transfer Switch 630AF – 4 Pole

62
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Basic Transfer Switch 250AF – Motorised 3 Pole

MB2MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2

Basic Transfer Switch 250AF – Motorised 4 Pole

MB2MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2

Note1: Escutcheon height is to the underside of the escutcheon.

63
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak MCCB Dimensions

Basic Transfer Switch 630AF – Motorised 3 Pole

MB3MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2

Basic Transfer Switch 630AF – Motorised 4 Pole

MB3MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2

Note1: Escutcheon height is to the underside of the escutcheon.

64
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODBreak Over-Current Relay (OCR) Tester

General information
• MBOCRTESTER facia shown above
• NHP Catalogue Number: MBOCRTESTER (code: ST374980000 / DNT20)
• NHP MODBreak MCCBs use OCR types “MTX1” which are indicated below
• The MBOCRTESTER is suitable for MODbreak MCCBs (not ACBs)

The MBOCRTESTER tester kit consists of:


• 1 tester. (The tester will need a 240V GPO plug adaptor or a local GPO plug to replace the plug the tester comes with)
• 2 x D shell 9 pin serial connector, to go from the tester to the MCCB (1 spare lead)
• 1 x D shell 9 pin serial connector (For an older OCR series not sold by NHP)

MODbreak electronic MCCB OCR


Tester

MODBreak connector lead

Spare connector

For other MCCB types (ignore this)

Connector lead plugs into MTX1


OCR test socket connection, and to
OCR tester’s rear 9 pin serial port.

65
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODBreak Over-Current Relay (OCR) Tester

Using the MTX1.0 OCR Release Setting Checker Test Kit


• S1 & S2 are OCR checker dial settings that are dependent on the MCCB OCR DIP switch settings
• The rocker switch has 3 positions: TEST / OFF / AUX. Power.
• When the switch is in AUX mode, the GREEN LED will glow indicating AUX supply is provided to the tester.
• The RED LED & display will not be on. When the switch is in TEST mode, the RED LED and display will be on,
indicating that the tester is ready to test. The GREEN LED will not be on, ensuring that only one mode can be activated
at any time.
• Ensure that the MCCB toggle is in ON position when the settings are checked.

For setting S1

Over Current Relay (OCR) Setting Setting on OCR Tester OCR Output
Long Time Short Time
S1 S2
Characteristic Characteristic
MTX1 Over 50 8 A A
At 20mS: OCR trips within 0.06s or 0.00s on display
Current Relay 70 5.5 A A
At 100mS: OCR trips within 0.13s on display
100 4 A A
At 200mS: OCR trips within 0.23s on display
OFF OFF A A

For setting S2

Over Current Relay (OCR) Setting Setting on OCR Tester OCR Output
Long Time Short Time
S1 S2
Characteristic Characteristic
60 OFF A B OCR trips within 20 to 50 seconds
80 OFF A A OCR trips within 86 to 128 seconds
MTX1 Over 40 OFF A E OCR trips within 7 to 12 seconds
Current Relay 60 OFF A H OCR trips within 7 to 12 seconds
40 2.5 A A At 20mS: OCR trips within 0.06s or 0.00s on display
60 2.5 A C At 100mS: OCR trips within 0.13s on display
100 1.5 A A At 200mS: OCR trips within 0.23s on display

66
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODBreak Installation Instructions: MB2, MB3, MB4 MCCBs

MB2, MB3, MB4 – General installation precautions

MB2, MB3, MB4 – MCCB toggle operation and tripping the MCCB

67
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

MB2 Interpole barriers

Exhaust gas vents from


the line side (top) of the
MCCB, which is the
opposite end to where
the current adjustment
dials are located.

MB3 Interpole barriers


Exhaust gas vents from
the line side (top) of the
MCCB, which is the
opposite end to where
the current adjustment
dials are located.

68
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

MB4 Interpole barriers

Exhaust gas vents from


the line side (top) of the
MCCB, which is the
opposite end to where
the current adjustment
dials are located.

MB2 Mounting orientation and termination mounting, torque, capacity and weight

Mount in any one of these three orientations only

69
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

MB3 Mounting orientation and termination mounting, torque, capacity and weight

MB4 Mounting orientation and termination mounting, torque, capacity and weight

70
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions


MB2, MB3 – Adjustment of THERMAL MAGNETIC trip unit

MB2, MB3, MB4 – Adjustment of ELECTRONIC Over Current Relay


Refer previous pages for more detailed setting diagrams

71
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

MB2, MB3, MB4 – Accessory cover removal, internal accessory mounting and wire routing

72
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

MB2, MB3, MB4 – Internal accessory cover fitting

MB2, MB3, MB4 – Internal accessory removal

73
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Under Voltage Trip for MB2 and MB3 MCCBs

MB2, MB3 UNDERVOLTAGE TRIP

Insertion of Under Voltage Trip

74
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Insertion of Under Voltage Trip

Testing of Under Voltage Trip Removal of Under Voltage Trip

75
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operator types: MB2MOTOR240VAC and MB3MOTOR240VAC

1. Caution & Packaging

2. Motor indication and architecture

76
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operators (ROM)

3. Mounting operation
It is recommended that the MCCB be first mounted to a panel before mounting the motor as indicated below.

77
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operators (ROM)

4. Modes of Operation

Operation circuit:
COMMON OFF and ON can be
continuously or momentarily closed.

78
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operators (ROM)

5. Indicator Module Connections

79
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operators (ROM)

6. Manual Mode

80
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Motor Operators (ROM)

7. Lock Mode

81
MODBreak Technical Catalogue 2019 TECH-001-EN
M

Motor Operators (ROM)

8. Trouble Shooting

Situation Cause Solution

Motor not switching ON electrically Incorrect connection Refer item 4 circuit diagram.
Incorrect fitting of motor Refer item 3
Blown fuse Refer item 5
Not in Auto mode Refer item 4
Padlock lever is pulled out and padocked
Motor not charged

Indication on motor reads incorrectly Indicator module in MCCB is absent Refer item 3 and 5
Indicator module incorrectly fitted Refer item 5
Wires of indicator module incorrectly routed Refer item 5
Motor loose / not tightened during fitting Refer item 3

Padlock lever will not pull out Motor not fully charged Refer item 6
(breaker should be in OFF position)
Padlock slider is in “Auto” or “Manual” mode Refer item 7

Installation label on motor operators


Note: MB2 motor label shown. Minimum operating pulse for MB2 motors is 300mS, and for MB3 motors it is 450mS.

82
MODBreak Technical Catalogue 2019 TECH-001-EN
M

Motor Operators (ROM)

Block Schematic: MB2 / MB3 Motorised MCCB AC Wiring Diagram

Terminal functions Wiring Symbols definitions

1 & 5: Motor main power connections External user connection


2&3 Opening operation Internal connection (not user connection)
4&3 Closing operation Internal mechanical linkages

83
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions


Extension Handle Operators

1. Box contents - handles come complete with MCCB mechanism, door mount handle, extension shaft

2. Mounting of handle Mechanism on MCCB

3. Mounting handles for different MCCB mounting orientations 4. Mounting of handle assembly

84
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions


Extension Handle Operators

5. Operation

6. Mounting dimensions
MB2 handles

MB3 / MB4 handles

85
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions


Extension Handle Operators

7. Padlocking – without door interlock

8. Padlocking – with door interlock

9. Interlocking / door defeat

86
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Extension Handle Operators

10. Auto Restoration

11. Padlock in ON operation (Standard Lock-OFF handles can be converted to Lock ON)

87
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions

Direct Mount Handle Operators for MB2 and MB3 MCCBs

1. Mounting of mechanism onto MCCB

2. Mounting dimensions 3. Operation

88
MODBreak Technical Catalogue 2019 TECH-001-EN
M

MODbreak Installation Instructions & Installation Clearance requirements

Direct Mount Handle Operators for MB2 and MB3 MCCBs

4. Padlocking

Refer NHP for padlocking direct mount handles in the ON position.

Installation clearance requirements (breaker to earthed metal)


To ensure installation safety, the use of phase barriers or terminal covers or other adequate insulation at the top (venting end) of the MCCB is manditory.

MCCB type Left / Right - C Top – A / Bottom - B Front / Back MCCB’s side by side (use terminal covers)
MB2 50 mm 105 mm 0 0 mm
MB3 70 mm 120 mm 0 0 mm
MB4 70 mm 135 mm 0 0 mm

Flush covers installed to Extended-wide terminal covers


Chassis tee off end of a reverse fitted to MCCB line side and load side
connected MCCB

89
MODBreak Technical Catalogue 2019 TECH-001-EN
M

PD TECH’s available:
Section Description

MCB products and Panelboards


1. PD TECH MCBs RCDs 2019 TECH-001-EN Ordering MCBs and Accessories
2. PD TECH Panelboards & Loadcentres 2019 TECH-002-EN Ordering Panelboards, Loadcentres and chassis
3. PD TECH MCBs 2019 TECH-003-EN MCB, RCD, curves and accessories - technical data only
4. PD TECH MOD6 MCBs RCDs and Enclosures 2019 TECH-004-EN MCB, RCCB, RCBO, load centre and panelboard info

MCCBs, Accessories and Transfer Switches


1. PD TECH MCCBs & Accessory Selection 2019 TECH-001-EN MCCB and accessory ordering, ratings charts
2. PD TECH Special Application MCCBs 2019 TECH-002-EN Earth leakage, Mining, Switch disconnectors, DC MCCBs
3. PD TECH MCCB OCRs & Metering 2019 TECH-003-EN MCCB OCR technical data, curves, Metering MCCB info
4. PD TECH MCCB Dimensions 2019 TECH-004-EN MCCB dimensions, cut-outs etc
5. PD TECH MCCB Accessory Tech Data 2019 TECH-005-EN Technical info MCCB accessories
6. PD TECH MCCB Connections Chassis Installation 2019 TECH-006-EN MCCB chassis, installation, connections, rear connect data
7. PD TECH MCB MCCB Application Data 2019 TECH-007-EN Selectivity, Cascade, Type 2 Coord., let through & other data
8. PD TECH MCCB Transfer Switches 2019 TECH-008-EN MCCB transfer switch and controller ordering and tech data
9. PD TECH Mining MCCBs 2019 TECH-001-EN 1000 VAC MCCB selection, installation, some tech data
10. PD TECH TemBreak 1 MCCBs current & obsolete 2019 TECH-009-EN Current and obsolete MCCBs. TB2 conversion info & dims

ACBs
1. PD TECH AR ACBs 2019 TECH-001-EN AR ACB ordering and technical data

Earth Leakage Relays


1. PD TECH Earth Leakage Relays 2019 TECH-001-EN Earth leakage relay ordering and tech data

Fuses and Bases


1. PD TECH Fuses and Bases 2019 TECH-001-EN NHP fuses and holder selection and tech data

Socomec Isolators and Transfer Switches


1. PD TECH Socomec Isolators SCO BCO 2019 TECH-001-EN Socomec Isolator & Fuse sw. SCO, BCO manual transfer sw.
2. PD TECH Socomec ATyS 2019 TECH-002-EN Socomec ATyS transfer switch ordering and technical data
3. PD TECH Socomec PV Switches & Fuses 2019 TECH-003-EN DC load break sw and fuse links 750/1000/1500 VDC

Katko Enclosed switches and Isolators


1. PD TECH Katko 2019 TECH-001-EN Katko enclosed & open isolators ordering and technical data

Switch Board Monitoring


1. PD TECH Arc LogiX 2019 TECH-001-EN ARC LogiX CS, optical arc flash relays and AFDD

Click on any of the above hyperlinks to open that document

NHP Electrical Engineering Products Pty Ltd


A.B.N. 84 004 304 812

Head office: NEW ZEALAND


43-67 River Street 118a Carbine Rd
Richmond Wellington
VIC, 3121 Auckland 1060
AUSTRALIA NEW ZEALAND

Tel: 1300 647 647 0800 647 647

www.nhp.com.au www.nhp-nz.com

Power Distribution Technical Reference: 90


MODBreak Technical Catalogue 2019 TECH-001-EN
MODBreak Technical Catalogue 2019 TECH-001-EN 10/19 NHP
2019