Professional Documents
Culture Documents
RH5Z1-OL/-2OL
Medium voltage aluminium cable, XLPE insulation,
halogen free with longitudinal aluminium strip screen.
ACCORDING TO: UNE 211620 / ENEL Global Standard GSC 001
APPLICATION CHARACTERISTICS
Aluminium cable for fixed installations. Halogen free.
Electrical performance
Suitable for transport and distribution of electric power in medium
Medium voltage: 12/20 kV and 18/30 kV.
voltage networks.
This cable is suitable for indoor, outdoor and buried installations. Thermal performance
Maximum conductor temperature: 90°C.
Minimum service temperature: -15°C.
CONSTRUCTION Minimum installation temperature: 0 °C
Conductor Maximum short-circuit temperature: 250°C (max 5 s).
Aluminium class 2 according to EN 60228 and IEC 60228. Fire performance
Optionally, with longitudinal water tightness (cable type -2OL). Halogen free according to EN 60754-1 / IEC 60754-1.
Conductor screen Low corrosive gases emission according to EN 60754-2 / IEC 60754-
Screen over the conductor, made of thermosetting semiconductor 2.
material. Mechanical performance
Insulation Minimum bending radius permanently installed: 15x cable
Cross-linked polyethylene type DIX-3 according to HD 620-1, natural diameter.
colour. Minimum bending radius while installation: 20x cable diameter.
Cross-linked in catenary line with nitrogen atmosphere. Abrasion resistant.
Insulation screen Environmental performance
Screen over the insulation, made of thermosetting semiconductor UV Resistant according to UNE 211605.
material. Strippable. Water resistance: AD8 Submersion.
Water blocking
Semi-conducting swellable tape under metallic screen. Installation conditions
Open Air.
Metallic screen
Buried.
Aluminium tape of thickness 0,3 mm longitudinally applied on the
water-blocking. The tape is overlapped and bonded 5 mm minimum. In conduit.
The screen is longitudinally and continually fixed in the outer sheath.
Outer sheath
Polyethylene halogen free type DMZ1 according to HD 620-1.
Red colour.
STANDARDS / COMPLIANCE
According to
UNE 211620 / ENEL Global Standard GSC001
sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
DIMENSIONS & ADMISSIBLE INTENSITIES
1
Open air installation according to IEC 60502-2: three single-core cables in trefoil formation and ambient temperature of 30 °C; protected from direct sun
radiation and with adequate ventilation (supported by cleats and hangers or on perforated tray).
2
Buried installation according to IEC 60502-2: three single-core cables in trefoil formation direct buried at a depth of 0,8 m, ground temperature of 20 °C
and soil thermal resistivity of 1,5 K·m/W.
3
Buried installation according to IEC 60502-2: three single-core tubed cables (one cable per tube) in trefoil formation and buried tubes in mutual contact at
a depth of 0,8 m, ground temperature of 20 °C, soil thermal resistivity of 1,5 K·m/W and thermal resistivity of the tube of 1,2 K m/W.
Reactance (X) is calculated at 50 Hz and for three single-core cables (in triangle or trefoil formation).
Capacitance values (C) are calculated in base to dimensional items of the cables that are in this specification.
In all cases are supposed a three-phase circuit.
sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
SHORT-CIRCUIT CURRENT-CARRYING CAPACITIES
0,2 0,5 1 2
sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
CORRECTION FACTORS FOR THERMAL RESISTIVITY OF THE GROUND IN CABLES DIRECTLY BURIED
Thermal resist.
0,8 1 1,5 2 2,5 3
(K·m/W)
2
50 mm 1,26 1,16 1 0,89 0,81 0,74
CORRECTION FACTORS FOR THERMAL RESISTIVITY OF THE GROUND IN TUBED CABLES BURIED
Thermal resist.
0,8 1 1,5 2 2,5 3
(K·m/W)
50 mm2 1,18 1,12 1 0,91 0,84 0,78
2
95 mm 1,19 1,13 1 0,91 0,84 0,78
2
120 mm 1,20 1,13 1 0,91 0,84 0,78
2
150 mm 1,20 1,13 1 0,91 0,84 0,78
2
185 mm 1,21 1,14 1 0,90 0,83 0,77
2
240 mm 1,21 1,14 1 0,90 0,83 0,77
Other correction factors (for grouping cables, for harmonic currents), that are not in this specification, can be applied. Further information can be
found in IEC 60502-2.
sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.