You are on page 1of 4

X-VOLT® AL

RH5Z1-OL/-2OL
Medium voltage aluminium cable, XLPE insulation,
halogen free with longitudinal aluminium strip screen.
ACCORDING TO: UNE 211620 / ENEL Global Standard GSC 001

APPLICATION CHARACTERISTICS
Aluminium cable for fixed installations. Halogen free.
Electrical performance
Suitable for transport and distribution of electric power in medium
Medium voltage: 12/20 kV and 18/30 kV.
voltage networks.
This cable is suitable for indoor, outdoor and buried installations. Thermal performance
Maximum conductor temperature: 90°C.
Minimum service temperature: -15°C.
CONSTRUCTION Minimum installation temperature: 0 °C
Conductor Maximum short-circuit temperature: 250°C (max 5 s).
Aluminium class 2 according to EN 60228 and IEC 60228. Fire performance
Optionally, with longitudinal water tightness (cable type -2OL). Halogen free according to EN 60754-1 / IEC 60754-1.
Conductor screen Low corrosive gases emission according to EN 60754-2 / IEC 60754-
Screen over the conductor, made of thermosetting semiconductor 2.
material. Mechanical performance
Insulation Minimum bending radius permanently installed: 15x cable
Cross-linked polyethylene type DIX-3 according to HD 620-1, natural diameter.
colour. Minimum bending radius while installation: 20x cable diameter.
Cross-linked in catenary line with nitrogen atmosphere. Abrasion resistant.
Insulation screen Environmental performance
Screen over the insulation, made of thermosetting semiconductor UV Resistant according to UNE 211605.
material. Strippable. Water resistance: AD8 Submersion.
Water blocking
Semi-conducting swellable tape under metallic screen. Installation conditions
Open Air.
Metallic screen
Buried.
Aluminium tape of thickness 0,3 mm longitudinally applied on the
water-blocking. The tape is overlapped and bonded 5 mm minimum. In conduit.
The screen is longitudinally and continually fixed in the outer sheath.
Outer sheath
Polyethylene halogen free type DMZ1 according to HD 620-1.
Red colour.

STANDARDS / COMPLIANCE

According to
UNE 211620 / ENEL Global Standard GSC001

Standards and approvals


AENOR

sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
DIMENSIONS & ADMISSIBLE INTENSITIES

X-VOLT® RH5Z1-OL 12/20 kV


Cross- Conductor Insulation Ext Width Section Open In
Weight R X C Buried
section Diameter Diameter Diameter tape screen air conduit
(Kg/Km) (Ω/km) (Ω/km) (µF/km) (A) 2
(mm2) (mm) (mm) (mm) (mm) (mm2) (A) 1 (A) 3
1 x 50 8,0 18,2 25,3 70 21 585 0,817 0,131 0,185 184 152 144
1 x 95 11,1 21,3 28,4 80 24 795 0,320 0,118 0,231 280 221 210
1 x 120 12,7 22,9 30,0 90 27 915 0,253 0,113 0,254 324 252 240
1 x 150 13,9 24,1 31,2 95 28,5 1.020 0,206 0,110 0,271 368 281 267
1 x 185 15,5 25,9 33,0 100 30 1.165 0,164 0,106 0,296 424 317 303
1 x 240 18,0 28,2 35,3 105 31,5 1.385 0,125 0,102 0,33 502 367 351
1 x 300 20,0 30,2 37,3 110 33 1.580 0,100 0,098 0,368 577 414 397
1 x 400 22,8 33,2 40,3 120 36 1.920 0,0778 0,095 0,401 673 470 451
1 x 500 26,3 37,0 44,1 130 39 2.280 0,0605 0,092 0,456 777 542 519
1 x 630 29,8 40,2 47,3 145 43,5 2.750 0,0469 0,088 0,502 895 615 588

X-VOLT® RH5Z1-OL 18/30 kV


Cross- Conductor Insulation Ext Width Section Open In
Weight R X C Buried
section Diameter Diameter Diameter tape screen air conduit
(Kg/Km) (Ω/km) (Ω/km) (µF/km) (A) 2
(mm2) (mm) (mm) (mm) (mm) (mm2) (A) 1 (A) 3
1 x 50 8,0 22,4 29,5 90 27 770 0,817 0,141 0,143 184 152 144
1 x 95 11,1 25,5 32,6 100 30 995 0,320 0,127 0,175 280 221 210
1 x 120 12,7 27,1 34,2 100 30 1.115 0,253 0,121 0,191 324 252 240
1 x 150 13,9 28,3 35,4 110 33 1.235 0,206 0,118 0,203 368 281 267
1 x 185 15,5 30,6 37,7 110 33 1.405 0,164 0,113 0,222 424 317 303
1 x 240 18,0 32,4 39,5 120 36 1.625 0,125 0,109 0,244 502 367 351
1 x 300 20,0 35,0 41,1 130 39 1.770 0,100 0,103 0,27 577 414 397
1 x 400 22,8 37,4 44,5 140 42 2.195 0,0778 0,101 0,293 673 470 451
1 x 500 26,3 41,2 48,3 150 45 2.580 0,0605 0,097 0,331 777 542 519
1 x 630 29,8 44,4 51,5 160 48 3.060 0,0469 0,094 0,363 895 615 588
1 x 800 34,0 48,9 56,0 170 51 3.680 0.0367 0,090 0,407 1.036 700 670

1
Open air installation according to IEC 60502-2: three single-core cables in trefoil formation and ambient temperature of 30 °C; protected from direct sun
radiation and with adequate ventilation (supported by cleats and hangers or on perforated tray).
2
Buried installation according to IEC 60502-2: three single-core cables in trefoil formation direct buried at a depth of 0,8 m, ground temperature of 20 °C
and soil thermal resistivity of 1,5 K·m/W.
3
Buried installation according to IEC 60502-2: three single-core tubed cables (one cable per tube) in trefoil formation and buried tubes in mutual contact at
a depth of 0,8 m, ground temperature of 20 °C, soil thermal resistivity of 1,5 K·m/W and thermal resistivity of the tube of 1,2 K m/W.
Reactance (X) is calculated at 50 Hz and for three single-core cables (in triangle or trefoil formation).
Capacitance values (C) are calculated in base to dimensional items of the cables that are in this specification.
In all cases are supposed a three-phase circuit.

sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
SHORT-CIRCUIT CURRENT-CARRYING CAPACITIES

Time (s) 0,1 0,2 0,3 0,5 1 1,5 2 2,5 3


2
A/mm 299 211 173 134 94 77 67 60 55

MAXIMUM CURRENT-CARRYING IN THE SCREEN, ACCORDING TO UNE 21192, TAKING 75ºC AS


INITIAL TEMPERATURE AND 150ºC AS FINAL TEMPERATURE

Tape width (mm) Time (s)

0,2 0,5 1 2

70 3,98 2,77 2,14 1,69

80 4,55 3,16 2,45 1,93

90 5,12 3,56 2,75 2,17

100 5,69 3,95 3,06 2,41

105 5,98 4,15 3,21 2,53


Maximum short-circuit current in
110 6,26 4,35 3,37 2,65
metallic screen (kA)
120 6,83 4,75 3,67 2,90

130 7,40 5,14 3,98 3,14

140 7,97 5,54 4,29 3,38

145 8,26 5,73 4,44 3,50

150 8,54 5,93 4,59 3,62

160 9,11 6,33 4,90 3,86

170 9,68 6,72 5,21 4,10

CORRECTION FACTORS FOR AIR TEMPERATURE


Air T. (ºC) 20 25 30 35 40 45 50 55 60
Factor 1,08 1,04 1 0,96 0,91 0,87 0,82 0,76 0,71

CORRECTION FACTORS FOR GROUND TEMPERATURE


Ground T.
10 15 20 25 30 35 40 45 50
(ºC)
Factor 1,07 1,04 1 0,96 0,93 0,89 0,85 0,80 0,76

sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.
X-VOLT® AL
RH5Z1-OL/-2OL
CORRECTION FACTORS FOR THERMAL RESISTIVITY OF THE GROUND IN CABLES DIRECTLY BURIED
Thermal resist.
0,8 1 1,5 2 2,5 3
(K·m/W)
2
50 mm 1,26 1,16 1 0,89 0,81 0,74

95 mm2 1,28 1,18 1 0,89 0,80 0,74

120 mm2 1,28 1,18 1 0,88 0,80 0,74

150 mm2 1,28 1,18 1 0,88 0,80 0,74


2
185 mm 1,29 1,18 1 0,88 0,80 0,74
2
240 mm 1,29 1,18 1 0,88 0,80 0,73
2
300 mm 1,30 1,19 1 0,88 0,80 0,73
2
400 mm 1,30 1,19 1 0,88 0,79 0,73

CORRECTION FACTORS FOR THERMAL RESISTIVITY OF THE GROUND IN TUBED CABLES BURIED
Thermal resist.
0,8 1 1,5 2 2,5 3
(K·m/W)
50 mm2 1,18 1,12 1 0,91 0,84 0,78
2
95 mm 1,19 1,13 1 0,91 0,84 0,78
2
120 mm 1,20 1,13 1 0,91 0,84 0,78
2
150 mm 1,20 1,13 1 0,91 0,84 0,78
2
185 mm 1,21 1,14 1 0,90 0,83 0,77
2
240 mm 1,21 1,14 1 0,90 0,83 0,77

300 mm2 1,21 1,14 1 0,90 0,83 0,77

400 mm2 1,21 1,14 1 0,90 0,83 0,77

Other correction factors (for grouping cables, for harmonic currents), that are not in this specification, can be applied. Further information can be
found in IEC 60502-2.

sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 7 - 17.06.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.