Control
Bay Control Screens
S52mCLSM, 527_ALM
These SELOGIC control equations report breaker close status and breaker alarm
satus. Any bitin the Relay Word, as well as logical operators, can be pro-
grammed into these SELOGic control equations.
S2mRACK, S21 EST
These SELOGiIC control equations modify the display of rack-type breaker mosa-
ies. The settings are shown for both rack-type and non-rack type breakers, but
only impact the display of rack-type breakers. The settings do not have any con-
luol functionality impact on any breaker. See Figure 5.9 on page 5.17 for settings
impact on the rack-lype breaker mosaic display.
Analog Display
If analog display points are not required, leave the setting(s) blank, because the
relay displays only the defined display points.
Click on analog display label HOFL= in the interactive one-line diagram to dis-
play the form shown in Figure 5.25. Click on the Expression Builder button to
display the form shown in Figure 5.26, The Expression Builder helps build the
analog quantity setting string, Press the Expression Builder button on the form
shown in Figure 5.26 to find the Analog or Fixed Element to be displayed.
cae MOET
Figure 5.25 Analog Quantity Setting Ferm
To display fixed text instead of analog quantities, enter the number I in the Ana-
log of Fixed Element field,
SEL-400 Series Relays Instruction Manual Date Code 20220823Control | 5.35
Bay Control Screens
7
en
PUTT
Figure 5.26 Analog Quantity Setting Form
Select the FREQ System Frequency (see Figure 5.27). Bate a Pre-Text, for
‘example Fro=, as shown in Figure 5.27. Set the numerical display format to 5.2;
this displays frequency up to two decimal places. You can scale the numerical
value of FREQ to display a scaled valve ofthe analog quantity. For example, a
scaling value of 0.5 displays only half the value of FREQ, while a scaling value
of 2 displays twice the Value of FREQ. Enter text, such asthe units ofthe analog
‘quantity in the Post-Text field, Test the entries by typing a value of 60.51 in the
preview analog display field, Click the Preview button, and verify that all entries
age cortect and wil fit on the sereen
aie MOELET
recon Perrin
Fema Leng aoe
Figure 5.27 Example of an Analog Quantity Expression
Date Code 20220823 Instruction Manual SEL-400 Series Relays5.36 | Control
‘customizable Sereens
SEL recommends that you use the MDELEn expression builder within QuickSet
or SEL Grid Configurator when creating these settings. However, if you enter the
expression from the ASCII command line, the format of the user input is as fol-
lows:
Analog Quantity Label, "Pre-Text
x.y.t) Post-Text”
where:
X= {otal number of digits of the number to display (includes number of dig-
its following a decimal point)
y= {olal number of digits to display following a decimal point
z= scaling factor
For example, if you wanted to display the VAZFM analog quantity with 3 total
igits with 1 digit following a decimal point and no scaling, enter the following
fn the command line
VAZEM,"VAZ = (3.1.1)
The setting value reported in QuickSet or SEL Grid Configurator is expected to
be reported differently than what is accepted on the ASCH command line.
Customizable Screens
‘SEL--400 series relays support custom mimic display screens. Custom mimic dis-
play screens are developed by the SEL factory by using your requirements, and.
then added to the QuickSet relay driver. The following images show the breaker
and power system variants supported in custom mimic display screens. For a
complete list of mimic display screens available in SEL-400 series relays, see
seline.com/app/mimic-diagrany.
Available Circuit Breakers
SEL-400 Series Relays
Figure 5.28 shows the different types of circuit breakers and disconnects available.
Instruction Manual Date Code 20220823