You are on page 1of 15

ADJUSTABLE-SPEED DRIVES

A
djustable-speed torque. How close this set
SOFT START .........................................................A39
drives adjust the speed remains constant de-
COMMON TERMS .................................................A39
speed of a driven pends on the type of drive
APPLICATION CONSIDERATIONS.........................A41
shaft to a speed selected by and its capabilities, and on
TYPES OF DRIVES ................................................A41
an operator or by an auto- “other variables.” (See
ELECTRICAL ADJUSTABLE-SPEED
matic speed selection device. “Speed regulation.”)
DRIVES ..............................................................A41
These automatic devices in- Armature control — short
MECHANICAL ADJUSTABLE-SPEED
clude speed reference sig- term for “armature voltage
DRIVES ..............................................................A52
nals generated by other control” of a dc motor, this
ADJUSTABLE-SPEED DRIVE ADVERTISING .........A54
drives, process controllers, describes the usual method
programmable controllers, of changing the speed of a dc
or other devices. motor — controlling the ar-
In addition to changing the speed of etc. It also reduces high peak electri- mature voltage. When this method is
a machine, adjustable-speed drives cal currents usually encountered used, most dc motors are capable of
are also used to maintain the speed of while starting an ac motor across the delivering constant torque.
a machine, regardless of load, to very line. These electrical units, covered in Base speed — used primarily in
close tolerances: 6 0.1%, is not un- the Controls and Sensors department specifying dc shunt-wound motors.
common. This is more accurate than in this handbook, under “Motor Con- Base speed is the motor speed while
the speed regulation offered by a con- trollers,” are similar in appearance delivering rated torque with field cur-
ventional ac motor, which can vary and use much of the same technology rent and armature voltage at rated
3%, from no load to full load. as electrical adjustable-speed drives. values.
There are many applications that There are other methods for softly Brushless dc, brushless ac, and
require adjustable-speed capability. starting loads, such as fluid couplings brushless PM servo motor — generally
Just a few include: between the motor and the driven refer to motors with permanent mag-
• Large paper machines and print- load. These are discussed in the Cou- net rotors and wound stators that are
ing presses must accelerate smoothly plings and U-Joints department. wound similar to 3-phase induction
from standstill to running speed with- motors. Often abbreviated BLDC,
out breaking the webs. BDC, and BLAC, this design is also
COMMON TERMS
• Drill presses often use a wide similar to an ac permanent-magnet
range of speeds for a single job: low Most of the following terms apply to synchronous motor. (See “Positioning
speeds for drilling large holes and all types of adjustable-speed drives. drives.”)
high speeds for small holes. Additional information is given for Constant horsepower operation —
• Pump and fan efficiencies greatly some terms as indicated. see “Field control” and Figures 1 and 2.
increase by adjusting their speeds Adjustable-frequency drive (AFD) Drift — speed change at constant
rather than regulating flow by throt- — common term for ac, adjustable- load caused by many factors, most of
tling. frequency drive,
• Metering pumps require differ- inverter, and ac
ent speeds to produce different com- drive. (See “AC
pounds. drives.”)
• Speeds and positions of robots Adjustable
must be precise and change with each speed — where
phase of a task. speed is adjusted
manually or auto-
matically. The set
SOFT START speed (desired op-
One type of unit closely resembles erating speed) is
an adjustable-speed drive, but per- relatively constant
forms only one function — slowly in- regardless of load,
creasing the voltage applied to an ac as opposed to
motor. In essence, it is a solid-state “variable speed.”
reduced-voltage starter — often Adjustable-speed
called “soft start,” because it smoothly drive — a unit that
accelerates the motor to running adjusts the speed of a shaft to a set Figure 1— Output power of dc motor with
speed. This soft acceleration prevents speed that remains relatively constant armature-voltage and field-current
breaking belts, damaging conveyors, regardless of changes in required load control.

1998 PT Design A39


Field control — a Figure 4 — Regenerative power module
shortened term, this for SCR-type dc drive with single-phase
means adjusting the input. (Field supply not shown.) The
speed of a dc motor forward section controls power during
by controlling the motoring, and the reverse section controls
motor field current. power while it is regenerating to the ac
Figure 2 — Typical output power of an ac power source. Power module for three-
motor operating above and below base When the field current is reduced, the
phase power is similar, except each
speed. motor tends to increase speed and de- section has six SCRs.
crease in torque capability. Thus the
motor power output
is essentially con- load overhauls the motor, which puts
stant, Figure 1. power back to the drive controller.
Near-constant- Most mechanical adjustable-speed
horsepower capabil- drives and motor-generator types of
ity can also be ob- electrical adjustable-speed drives in-
tained from ac drives herently offer regenerative capability.
by operating the mo- Therefore, replacement drives must
tor at rated voltage be carefully selected so they have re-
and above rated fre- generative capability if the applica-
quency. This also in- tion requires it.
creases motor speed Regenerative drive — in SCR-type
and decreases motor dc drives, regenerated power is usu-
Figure 3 — DC motor with conventional torque capability, Figure 2. ally put back to the ac power source
dynamic-braking (DB) circuit. When Inverter — usually refers to an elec- through a second set of SCRs, Figure
controller powers motor, the normally
trical adjustable-speed drive that 4. In transistorized dc drives and
open (NO) M contact is closed. Upon
stopping, this NO contact opens, and the uses an ac motor. Actually, this term most AFDs, this power is dissipated
normally closed (NC) contact closes, applies only to the inverter section by a resistor across the dc bus that is
connecting the DB resistor across the that inverts dc to controlled-fre- between the input rectifier and the
motor armature. The DB resistor then quency ac in an ac adjustable-fre- power amplifier, Figure 5.
dissipates the rotating mechanical energy quency drive controller. Designed to control current flow in
as heat. Other variables
— changes in line
which are undefined. voltage, line fre-
Dynamic braking — method of quency, ambient
stopping a dc motor faster than coast- temperature, hu-
ing to rest. This method requires a re- midity, transients
sistor connected across the motor ar- on the ac power
mature. During stopping the DB line, and drift,
resistor dissipates the rotating en- which is caused by
ergy, Figure 3. Dynamic braking does undefined factors.
not offer controlled stopping as does Preset speed —
regeneration, discussed later. one or more speeds
Electrical adjustable-speed drive — at which the drive should operate. Figure 5 — Basic diagram of the power
includes motor and drive controller. Relay contacts or programmable-con- section of transistorized adjustable-speed
drive, including PWM ac and BLDC. PWM
However, in some cases, “drive” is troller outputs select which preset
dc has the same configuration, but with
used to denote only the controller that speed is operational. only four power transistors in the output
converts plant ac power to adjustable- Pulse-width modulation (PWM) — (power amplifier) section. Units that
voltage dc or to adjustable-frequency, inverter technique for chopping (mod- operate from single-phase power have
adjustable-voltage ac. ulating) a dc voltage usually at 2,000 four instead of six rectifiers in the input
Electrically commutated motor to 20,000 Hz to produce adjustable- rectifier section. Although the power-
(ECM) — same as brushless dc frequency, adjustable-voltage ac, or section configurations are similar for the
(BLDC). (Also see later discussion, adjustable-voltage dc. various drive types, the regulator and
“Brushless dc drives.”) Regeneration — occurs when the firing circuits are completely different.

A40 1997 Power Transmission Design


both directions, these drives are used drives that establishes the voltage re- flected load inertia (see Basic Engi-
for controlled stopping (regenerative lationship to the frequency. For exam- neering department in this handbook,
braking) of high-inertia loads. This ple, the controller for a 240-V, 60-Hz Formulas 9-13) is several times the
design also offers contactorless re- motor normally has a V/Hz adjust- motor armature inertia, or if the duty
versing, which is beneficial for high- ment set at 4-V per Hertz. cycle involves several starts and stops
cyclic-duty applications. a minute, a regenerative drive may be
Set speed — the desired operating required.
APPLICATION
speed. When a regulation value is • Communication requirements.
quoted for set speed, the same per- CONSIDERATIONS Will it be necessary, now or in the fu-
centage applies at all speeds. Such ture, to send instructions to the drive
regulation is generally available only Since there are many types of ad- or receive information from the unit?
with drives equipped with complex or justable-speed drives available, it is Will network communications be re-
digital control systems. essential to establish the required quired? These capabilities are often
Slip — the difference between the functions and the application con- needed in coordinated systems con-
electrical and mechanical speeds of a straints. The following lists many of nected to a master or host computer.
motor. For example, slip is the differ- the major factors that should be con- • Diagnostic capabilities. Should
ence between synchronous field speed sidered: the drive or system malfunction, will
(typically 1800 rpm) and rotor speed • Maximum horsepower require- a remote computer interrogate the
(often 1750 rpm) of an induction mo- ments of the driven load, and how the drive to determine the cause of the
tor. This gives a 50 rpm (3%) slip. Slip required power varies with speed. trouble and status of the system dur-
is always manifested as a power loss, • Torque. Constant or variable ing the last moments of operation?
which appears as heat. with speed? Such capabilities require a communi-
Speed regulation — the percentage • Minimum and maximum speeds. cation channel.
of change in speed between full load • Unidirectional or bidirectional?
and no load. • Acceleration. Fast, slow, or ad- TYPES OF DRIVES
justable? Also, are any special accel-
N NL − N FL eration or deceleration characteristics There are three basic types of ad-
R= ×100
N FL required, such as constant jerk so justable-speed drives, and each has
there is no change in acceleration its strengths and weaknesses:
Where: rate, or an S-curve? These are typi- Electrical drives — ac adjustable
R = Speed regulation, % cally required for controlling convey- frequency, dc adjustable voltage, slip-
NNL = No load speed, rpm ors carrying tall bottles. ring (wound-rotor) motor, eddy-cur-
NFL = Full load speed, rpm • Drive response to changes in rent, and special purpose types, in-
speed and direction commands. cluding servo and step.
Unless otherwise stated, regulation • Programmability needed. Will it Fluid drives — hydrostatic, hy-
is assumed to be plus-or-minus a per- be necessary to change frequently the drokinetic, and hydroviscous drives
centage of base speed, not of set speed. operating parameters, thereby re- are discussed in the Fluid-Power
Variable speed — often considered quiring a microprocessor-based drive? Drives department of this handbook.
synonymous with adjustable speed, • Minimum and maximum speed Mechanical drives — metallic-con-
but variable speed is where speed adjustments. Is it necessary to limit tact traction type and adjustable-
varies widely with load. Speed is deter- the minimum and maximum speed ca- sheave type using belts or chains.
mined by the intersection of the speed- pabilities if the drive has a wider speed
torque curves of load and drive. Exam- range than required by the load?
ELECTRICAL
ples include uncontrolled units such as • Speed regulation due to load
series-wound motors, Wound-rotor ac changes and other variables, such as ADJUSTABLE SPEED
motors, eddy-current clutches without temperature, humidity, line-voltage
tachometer feedback, and fluid drives. fluctuation, and drift. Both ac and dc drives receive ac plant
Any of these may be equipped with au- • Maintenance capabilities. What power and convert it to an adjustable
tomatic speed controls, and then oper- types of equipment can the mainte- output for controlling motor operation.
ate as controlled-speed drives. nance personnel service — mechani- DC drives power dc motors, and ac
Vector control — controller for stan- cal, simple electrical, or complex elec- drives control ac motors. Both usually
dard ac induction motors that deliv- trical? What are service capabilities of use solid-state conversion systems.
ers response equivalent to dc servos. suppliers? A dc drive is the simpler of the two
(See “Positioning drives.”) • Control method. Will manual and is frequently used as part of an ac
Voltage boost — adjustment to en- control be used or will a motion or sys- drive controller. Therefore, we will
able an adjustable-frequency drive to tem controller give commands to the discuss the dc design first.
give a larger-than-normal voltage at drive controller?
low frequencies (normally 0 to 10 Hz) • Environments. Will all or part of DC drive
so the motor can start with extra the drive be subjected to hazardous,
short-term torque for breakaway and abrasive, moisture, or other harsh en- Usually, a solid-state power unit
initial acceleration. vironments? converts incoming ac plant power to
V/Hz (Volts per Hertz) — common • Duty cycle, including number of adjustable-voltage dc. This voltage is
adjustment in adjustable-frequency starts and stops per hour. If the re- fed to the dc motor armature. The dc

1997 Power Transmission Design A41


motor speed varies proportionally to fiers) and adding a
the dc armature voltage assuming: back or commutat-
1. The motor is large enough to ing diode across the
power the connected load. dc output.
2. The motor field current is To physically
constant. disconnect the mo-
DC motors, discussed in detail in the tor from the solid-
Motor department, contain two major state power mod-
components — armature and field. In- ule, a motor
teracting magnetic fields from these contactor (M) is
two components turn the armature. connected between
Two basic methods are used for the power module
converting ac to controlled dc — SCRs and the motor, Fig-
(thyristors) and transistors. ure 3. When the
SCR drives — silicon controlled start button is
rectifiers (SCRs) in the power unit pushed, the M con-
convert ac to controlled voltage dc. tactor picks up,
The SCR conducts current when a closing the nor-
small voltage is applied to the SCR mally open (NO) Figure 8 — Four quadrants of motor
gate, Figure 6. contact; then the SCRs are turned on operation. Most systems operate in the
in sequence, sup- first quadrant where both torque and speed
plying power to the are positive. During dynamic braking and
motor. regeneration, speed is positive and torque
Should the appli- is negative — the second quadrant.
cation require the
motor to stop faster Transistor dc drives — Largely
than coasting to because of the capabilities offered by
rest, a normally microprocessors and the availability
closed (NC) contact of power transistors, transistor dc
on the M contactor drives are now rated from fractional
is used to connect a to over 100 hp.
dynamic braking Unlike SCR-type drives, transistor-
resistor across the ized units contain three major power
motor armature, sections, Figure 5. The first converts
Figure 3. Thus, the ac plant power to fixed-voltage dc for
rotating mechani- the dc bus. The second section filters
cal energy in the and regulates the dc bus voltage. If
motor armature is the dc bus voltage goes outside the
Figure 6 — SCR conducts current from the dissipated as heat in this DB resistor. proper values, this section signals a
time of the gate pulse to the end of that Although this is effective for occasional fault and shuts the drive down. The
half cycle.
stopping, each stop requires operating third section contains the power tran-
the M contactor, which eventually sistors and chops (modulates) the
Most SCR-type dc drives designed to wears out contacts. Plus, the motor fixed voltage dc to form adjustable-
operate from a single-phase input have slow-down rate is not controlled, as it voltage dc for powering and control-
four SCRs. Units operating from three- is with regenerative braking. ling the dc motor.
phase ac are frequently built with six Regenerative SCR dc drives — If the load overhauls the dc motor,
SCRs, Figure 7. One variation of these By adding another set of SCRs (labeled it regenerates by sending power back
designs includes replacing the SCRs “Reverse section”) that are connected to the power amplifier section. This,
on the bottom row with diodes (recti- in the reverse polarity, Figure 4, the in turn, sends power to the dc bus
drive has regenera- where the dc bus control dissipates
tive capabilities, the power in a resistor connected
and can operate in across the bus. If the resistor does not
all four quadrants, have the capacity to dissipate the
Figure 8. power, the bus control section will
This configura- sense a bus over-voltage and shut the
tion offers bidirec- drive down.
tional operation DC drive regulator—Instruc-
without using re- tions from an operator’s control sta-
versing contactors tion, or other input, feed into the reg-
and controlled re- ulator, Figure 9. The regulator
Figure 7 — Typical full-wave SCR bridge generative stopping. (See “Regenera- compares the instructions with the
for dc drive operating from three-phase ac tion with ac/dc drives” later in this voltage and current feedbacks and
power. section). sends the appropriate signal to the

A42 1997 Power Transmission Design


Figure 10A — DC drive with speed
On larger mo- feedback in place of voltage feedback.
Figure 9 — DC drive with voltage (for tors, a common practice is to use a
approximate speed) and current (for The motor-driven tach or encoder gives
separately powered blower to force air more accurate signal than estimating
torque) feedbacks. In most drives, the
regulator and firing circuit are in the same through the motor so the motor is speed based on applied voltage.
physical unit. These can be analog, properly cooled,
digital, or a combination of both. For even when it is
more precise speed feedback, a running at low
tachometer-generator (tach) or encoder speeds and deliver-
must be driven by the motor shaft, ing full torque. The
Figure 10A. alternative is to
specify a larger
firing circuit. This section supplies motor that can dis-
the gate pulses that fire the transis- sipate the heat.
tors or SCRs, causing them to con- If a motor field
duct. In some designs, the regulator regulator is added
and firing circuit are combined in one to control the motor
digital circuit. field current, the
The voltage feedback gives an indi- motor can deliver
cation of the motor speed, and current constant horse-
indicates relative motor torque. power above motor
Typical basic adjustments in the base speed, Figure
regulator include minimum speed, 1. Some motors can Figure 10B — Follower drive, which is often confused with speed
regulated drive (Figure 10A). Above voltage-regulated drive
maximum speed, current (torque) run at four to six
follows a speed reference signal, usually produced by a tach on
limit, IR (load) compensation, and ac- times the motor another motor or by a digital command from the master drive’s
celeration rate adjustment. base speed. These speed feedback.
For more precise speed control, an drives have both ar-
encoder or a tachometer-generator — mature voltage and
usually called a tach — is mounted on field control. They
the motor to give a feedback signal, are applied on ma-
Figure 10, that is proportional to ac- chine tool spindles,
tual motor speed. The quality of this center winders, and
tach and of the regulator determine similar applications
the total drive accuracy. where the torque
Applications — DC drives with- requirements de-
out tach feedback frequently offer a crease with an in-
20:1 speed range. If tach feedback is crease in speed.
used, the speed range is usually in- DC drives can
creased to at least 100:1. regulate motor
If the motor has sufficient cooling speed (the most fre-
capacity, the drive can usually deliver quent type of appli-
constant torque over the full speed cation), motor cur-
range. TENV (totally enclosed, non- rent, which is
ventilated) and some TEFC (totally proportional to mo-
enclosed, fan cooled) motors rated to tor torque, and po-
Figure 10C — Combination of a follower drive (Figure 10B) and a
about 5 hp often have sufficient heat sition. Drives with speed-regulated drive (Figure 10A). The above configuration
dissipating capacity to deliver rated current regulators accurately maintains speed established by the reference signal
torque during low-speed operation. are used for un- produced by a source outside the drive.

1997 Power Transmission Design A43


200 to 500 hp. In the larger power
Power semiconductors in a-s drives ranges, GTOs become practical. For
ac drives, SCRs are the least expen-
Silicon controlled rectifiers (SCR) termines when in the ac half cycle to sive power semiconductors, but the
were introduced in the 1950s. Gate turn the SCR on so it conducts to the drives require many capacitors to
turn-off devices (GTO) became avail- end of that half cycle. The earlier in commutate the SCRs off to produce an
able for widespread usage in the late the half cycle the SCR turns on, the ac output.
1970s, then power (giant) transistors higher the average output voltage is Gate turn off device (GTO). A
(GTR) in the early 1980s and, most re- to the motor. To turn the SCR on, the GTO, like an SCR, can handle high
cently, insulated gate bipolar transis- controller applies a current to the current levels — in the thousands of
tors (IGBT). SCR gate, Figure A. amperes. A GTO, Figure B, is similar
Under normal operating condi- SCRs can handle current from to an SCR except that its control con-
tions, they function as one-way 5,000 to 10,000 A. The time it takes an nection can turn the device on and off.
switches; current flows in one direc- SCR to turn fully on after receiving a Turn on occurs when a positive volt-
tion, from the higher voltage potential gate pulse is in the order of 10s of µsec. age is applied to the gate. Applying a
to a lower voltage potential. Connec- In the early 1960s, SCRs were used negative voltage to the gate turns the
tions include terminals for input to control the frequency of ac drives. GTO off and interrupts current flow
power, output power and a control Now, GTOs, GTRs and IGBTs have in the main circuit. Once turned on, a
signal to turn the device on and off. replaced SCRs, particularly in low- GTO will stay on and does not require
Silicon controlled rectifier voltage ac drives, because of their sustaining pulses. To turn a GTO off,
(SCR). In a typical dc drive, SCRs greater efficiency and controlability. the negative or turn-off control signal
control dc motor speed and torque by For dc drives, SCRs are the least must be greater than the current
converting ac line voltage to ad- expensive power semiconductor for flowing through the GTO. Typically,
justable dc voltage. The controller de- applications below a power range of turn-off time of a GTO is about 50
µsec. GTOs require fast-
acting, current-limiting
Relative power-semiconductor characteristics fuses to protect against
overcurrent situations.
Type Speed Gain Efficiency Control method Max. rating, A Efficiency of a GTO is
relatively low due to the
SCR Slow Medium Low Current 10,000 power source required to
GTO Medium Medium Low Current 10,000 supply the negative turn-
GTR Fast Low Medium Current 2,000 off bias. Because GTOs
IGBT Fastest High High Voltage 2,000 turn on relatively slowly,
high switching losses re-
duce efficiency.
Figure A — Silicon controlled rectifier (SCR), also known as a Gate
Giant transistor
thyristor. It conducts current during a positive half cycle from (GTR). In a GTR, the
the time sufficient voltage is applied to the gate to the end of control or base signal
that half cycle. must be maintained to
keep the device turned
on. How much control sig-
Figure B — Gate turn off thyristor (GTO). Similar to an SCR, nal is needed depends on
except a GTO can be turned on and off by the voltage to the how the GTR is operated.
gate. Positive voltage turns the GTO on and a negative voltage For large-gain, low-loss
turns it off. operation, the control sig-
nal must be large. For
large-gain, large-loss op-
Figure C — Giant transistor (GTR) in a Darlington eration, the control signal
Base
configuration so the transistor amplifies the signal can be small.
to the base of the GTR. Current-carrying capa-
bility is in the range of
1,000 to 2,000 A. Switch-
ing speed is about 5 µsec.
Because GTRs are low-
Figure D — Insulated-gate bipolar transistor (IGBT) is the most gain devices (as are all
common power device used in current general-purpose and transistors), they are typ-
servo drive controllers. It can operate with carrier (also called ically mounted with one
chopping and modulation) frequencies to more than 20 kHz. device feeding another in
a Darlington configura-
tion, Figure C.

A44 1997 Power Transmission Design


winders, rewinders, and other web encoder. The sine wave offers reduced
Today, GTRs are gradually being re- handling functions. torque variations (ripple) during each
placed by IGBTs. The faster switching Drives with position regulators are shaft rotation. For example — accord-
speeds of an IGBT produce a so-called installed on machine tools, robots, ing to some manufacturers — a
“quiet ac motor controller.” Commer- winders and unwinders with storage brush-type dc motor may have 2% to
cial pressure for smaller controller loops, electric line shafts, and other 6% torque ripple; PMDC drives with
packages and a simpler control-to- applications where precise component sinusoidal voltage waveforms may
power interface is forcing the early re- position must be controlled. have 3% ripple; and the trapezoidal
tirement of GTRs for ac motor control. voltage can run 4% to 15%.
Insulated-gate bipolar transis- Another factor that determines
tors (IGBT). IGBTs, Figure D, differ
Brushless dc drive torque ripple is the motor winding
from SCRs, GTOs and GTRs by the Considered both an ac drive and a configuration. Some manufacturers
control scheme. To turn on an IGBT, a dc drive — depending on who is speak- offer distributed windings that reduce
voltage is applied to its gate. The ing — this family of drives is fre- the torque ripple produced by a trape-
MOSFET-type input converts the quently called brushless dc (BLDC), zoidal voltage.
voltage to the current required to turn brushless ac, and brushless PM servo. However, methods of measure-
on the output portion (transistor) of To distinguish this type from a drive ment, load inertia, and many other
the IGBT. with a conventional ac motor that is variables determine this ripple for
Thus, the interface from control to usually also brushless, we use “brush- each application.
power is simplified because it re- less dc” to denote this drive type. It
quires little control current to handle can be applied to both general-purpose
large amounts of power current. and precision motion control (position-
AC drives
Small control current also avoids the regulated) installations. AC adjustable-speed drives are
time delays associated with large val- The BLDC motor is constructed growing in popularity, mainly be-
ues of control current. A fast control much like a permanent magnet ac cause ac motors are simpler than dc
change produces a fast power change. synchronous motor with a PM rotor motors. Moreover, recent advances in
Current-carrying capability of an and a wound stator. This BLDC de- inverter technology have reduced con-
IGBT is 1,000 to 2,000 A. sign is often termed an “inside-out” troller cost and improved perfor-
An IGBT’s fast response to signal construction, because most dc motors mance and reliability.
changes — less than 1 µsec — reduces with permanent magnets have the AC drives operate by adjusting the
audible levels in an ac motor while magnets stationary in the stator, and frequency and voltage to ac motors.
controlling torque and speed. And, its the wound armature rotates. How- Frequency determines motor speed.
high switching frequency (carrier fre- ever, the BLDC construction puts the To maintain constant torque, it is nec-
quency) provides a responsive current heat-generating windings on the out- essary to keep voltage and frequency
control. Also, an IGBT’s low losses re- side for fast heat dissipation. in a constant relationship. Called
sult in compact packaging of the ac Most BLDC drives need an accu- Volts per Hertz, this is adjustable on
motor controller. rate method of sensing rotor speed. most ac drive controllers. There is one
Since the introduction of IGBTs, An encoder, or Hall-effect transistor, exception — voltage at low frequen-
concerns have arisen about the effects usually does this. For more precise cies. In this operating range, voltage
of high-frequency switching and har- applications, some use a resolver and may be boosted to give the motor ex-
monic-rich waveforms during trans- a resolver-to-digital (R/D) converter. tra torque for breakaway and initial
mission of power to an ac motor. In The improvement in precision de- acceleration.
some cases, transient voltages can pends on the components selected. General-purpose, ac adjustable-fre-
damage motor winding insulation, The power sections of a BLDC drive quency drive controllers are made in
and cause motor failure. Two factors controller closely resemble a standard four types: variable-voltage input
in particular contribute to this phe- PWM ac drive, Figure 5. However, the (VVI), pulse-width modulated (PWM),
nomenon: controller portions (regulator and fir- current-source input (CSI), and load-
• 460-V ac drives that use the ing circuits) are completely different. commutated inverters (LCI). In addi-
PWM power circuit and use modula- The industry is constantly improv- tion, wound-rotor motors and eddy-
tion (chopping) frequencies of more ing the ability to control the shape of current couplings offer adjustable
than 5 kHz. the current wave form. Generally, the speed with an ac motor connected
• Long cable distances (over 100 ft) be- more closely the current approaches a across the line. Each has specific
tween the drive controller and the motor. sine wave, the better the motor characteristics and advantages.
These reflected waves, along with performance. Variable-voltage input (VVI) —
RFI and grounding issues, are current Originally, the drive controllers Although this design was common in
technical hot buttons. See the “Reduc- produced a square-wave voltage to the the 1970s and early ‘80s, it is now
ing motor problems caused by voltage BLDC motor. With technological ad- generally limited to special applica-
transients” section in Motors for some vances, the drive manufacturers de- tions such as high-speed drives that
solutions to these potential problems. veloped controllers that commonly deliver 400 to 3,000 Hz. The VVI de-
Excerpted from an article by Allen- produce a trapezoidal voltage wave- sign, Figure 5, receives plant ac
Bradley Co., Inc. in the February, form, and some offer a sine wave. Of- power, rectifies and controls it, and
1996 issue of PTD. ten the sine-wave units require a re- delivers variable-voltage dc to the
solver, rather than the more common power amplifier (inverter section).

1997 Power Transmission Design A45


The power amplifier inverts the vari- flux angles to optimize motor operation. feedback signal will improve the
able-voltage dc to variable-frequency, Some vector drives were expected drive’s performance.
variable-voltage ac. It can be built to have open-loop speed regulation Current-source inverter (CSI)
with power transistors or SCRs. (no speed feedback signal from the — Usually applied to drives of 50 hp
The output voltage from a VVI unit is motor) equivalent to a dc drive with and larger, CSI units are well suited
frequently called a six-step wave form. speed feedback. Many units didn’t for powering pumps and fans as an
The VVI was one of the first quite live up to the expectations. Re- energy-saving alternative to throt-
solid-state ac drives to gain general gardless, the basic vector does offer tling for flow control.
acceptance. improved performance, which in some Capable of operating with efficien-
Pulse-width modulated (PWM) cases may be suitable for simple coor- cies close to dc drives, the CSI design
— Many PWM units (also frequently dinated systems. offers economies over both the VVI
termed “volts per Hertz drives” to dis- Vector — More recently, in the mid- and PWM units for pump, fan, and
tinguish them from vector drives) of- 90s, much improved vector regulators similar applications.
fer operation to zero speed. Some pro- were introduced. These have more ad- The CSI inherently offers regenera-
duce frequency ranges near 200:1. vanced microprocessors and DSPs tive capabilities. With an overhauling
This wide range is possible because that significantly enhance drive oper- load, the controller feeds power back
the controller converts ac supply ation, including response and position into the ac power system.
power to fixed-voltage dc for the regulation capa-
power amplifier. In this amplifier, bilities. One rea-
the dc is “chopped” (modulated) to son for the vec-
produce different widths of pulses, tor’s capability
thus varying the effective voltage. Al- to perform so
though the voltage is chopped, the well is its ability
current wave form is closer to sinu- to “see” the
soidal than any other system. counter EMF
PWM units use several types of produced by the
power transistors (including insu- motor, then the
lated gate bipolar transistors (IG- circuitry adjusts
BTs), and gate-turn-off SCRs (GTOs). the start of each
The PWM power circuit requires a PWM pulse
more complex regulator than does the train and the
VVI design. However, the increasing specific duration
use of microprocessors has nearly elim- of each pulse.
inated significant economic differences. Such vector
Because a fixed-voltage dc bus sup- drives are power-
plies the inverter section, a large sin- ing high-speed
gle dc supply can be used to power printing presses,
several inverter sections. paper machines,
Types of regulators — The PWM winders and
power circuit is commonly used with other coordi-
three basic types of regulators. It is nated engi-
these regulators that largely deter- neered systems.
mine the drive capabilities, including Vector drives are
response, speed regulation due to also used on
transient load changes, and low-speed servo positioning
torque capabilities. systems, such as
Volts/Hertz — The most common machine tool
and lowest cost configuration, it is spindle and feed
usually available with or without a drives. Some, de-
speed feedback capability. This de- pending on the
sign generally offers the basic drive rating, can accel-
adjustments — including set speed, erate from stand-
torque limit, V/Hz, voltage boost at still to full speed
low speeds, minimum and maximum in 1 to 200 msec.
speeds, acceleration and deceleration For more on
rates, and other similar adjustments, these position-
which meet the requirements for most ing drives, see a
applications. following sec-
Basic vector — Introduced in the tion, “Position-
mid-80s, this regulator was a signifi- ing Drives.”
cant advancement over the Volts/Hz de- With all types
sign. Such units use an approximation of these drives, a
method to control the stator and rotor speed or position

A46 1997 Power Transmission Design


Load-commutated inverter motors rated in
(LCI) — Designed for controlling syn- hundreds of horse-
chronous motors rated in hundreds or power, a wound-ro-
thousands of horsepower, these units tor motor con-
use the leading power-factor capabili- troller applies
ties of synchronous motors to commu- constant voltage
tate the power SCRs off. These invert- and frequency to
ers, some rated up to 6,000 Vac, the primary of a
control large blowers and induced- wound-rotor mo-
draft fans in power plants. tor. Speed is ad-
Due to the higher cost of syn- justed by varying
chronous motors over conventional in- the resistance of the motor secondary, Figure 11 — Wound-rotor ac motor and
duction motors, LCI systems become Figure 11. As resistance is increased, controller. Increasing the resistance in
the motor secondary decreases motor
economical in the 400-600 hp range, rotor losses increase, thus reducing
speed.
and larger. the motor shaft speed.
Wound-rotor motor control — A solid-state controller effectively currents in nearby metal. These cur-
Another system for controlling ac changes the resistance of the rotor sec- rents, in turn, create their own mag-
ondary; and, netic fields. Properly used, the eddy-
rather than dis- current magnetic fields can interact
sipate the en- with the primary magnetic field.
ergy as heat, it The eddy-current coupling is built
feeds this en- with two parts: one is coupled to the
ergy back to the input shaft, and, in many applica-
ac supply. This tions, powered by an ac motor; the
slip-recovery other is connected to the output shaft.
system greatly There is no mechanical connection be-
increases motor tween the two parts; rather, the con-
efficiency. nection is purely magnetic. An elec-
Wound-rotor tromagnet coil generates the coupling
motor control magnetic force, Figure 12. The mag-
serves many netic strength, (coil current) deter-
pump and fan mines the slip between the input and
installations output parts. There must be some slip
that need a between these two parts, usually a
speed range of minimum of 3 to 5%, depending upon
2:1 or 3:1. the design, for the system to work.
Eddy-cur- (Eddy-current clutches and brakes
rent coupling are discussed in the Clutch and Brake
— A moving department in this handbook.)
magnetic field In some smaller ratings, the mag-
induces eddy net coil rotates with the output shaft.

Notes:
1. These are typical values for each drive type and
do not reflect state-of-the-art products or special
designs.
2. Brush wear becomes critical on high duty-cycle
applications where the motor constantly
accelerates and decelerates. Although the absence
of brush wear is not as important in other
applications, many specifiers select brushless
units to eliminate brush maintenance completely.
3. Many times, load rotary inertia reflected to the
motor shaft can be reduced by installing a speed
reduction means (gears or timing belt) between
the motor and driven load. (The reflected inertia
is reduced by a square of the reduction ratio.) This
technique is frequently used when the load inertia
significantly exceeds the motor rotor inertia.

1996 Power Transmission Design A47


Motor-mounted drive
controllers
Although motors with built-on con-
trollers have been made, they are gen-
erally limited to dc subfractional and
fractional-horsepower motors and ap-
pliance motors. For integral ratings,
the controller has been too big. But,
that is changing.
Technological breakthroughs en-
able integral horsepower ac motors to
include sophisticated controls. Sev-
eral companies have developed an in-
Figure 12 — Typical eddy-current
coupling. tegrated module that contains the Figure 14 — More adjustable-speed
control and power circuits for an ac controllers are mounted in a housing that
adjustable-speed drive, Figure 14. is often attached to the top of the motor.
Moreover, these modules are small
Slip rings carry the current from the enough to fit on ac motors rated 1-hp
supply wires to the rotating coil. In and larger. Benefits of these drives in- protection, selectable modulating fre-
larger units, the coil is stationary and clude: quency from 1.25 to 18 kHz, stall pro-
induces magnetic fields in both the in- • Save space by eliminating the tection, and many others.
put and output members. need for a separate controller (which Within the module, a mathematical
In operation, the operator selects is often as big as the motor). model of the motor accurately calcu-
the desired speed, which establishes • Reduce installed costs because lates motor temperature and im-
the speed reference signal. The ex- power wiring between the motor and proves motor operational stability, es-
citer control converts this signal to controller is eliminated. pecially for larger motors.
the proper dc voltage for the coil, Fig- • Eliminate motor problems A crucial design requirement is to
ure 13. The tachometer-generator caused by high-voltage transients. eliminate the heat generated by the
sends an output speed signal back to • Wipe out the finger pointing be- motor and the control electronics.
the exciter, which makes any needed tween the motor and controller manu- Some solutions use a multifinned as-
change in the coil voltage to maintain facturers when a problem comes up. sembly that mounts on the motor so
the set speed. • Enable using adjustable-speed the air forced by the external motor
Since any slip generates heat, each drives in applications that previously fan goes through the module cooling
coupling must be designed for ade- could not justify the expenses of a sep- fins as well as over the motor shell.
quate cooling. Usually, the smaller arate drive controller.
couplings rated from fractional to The controller modules include
over 100 hp are air cooled, and larger most functions: Start, stop, forward,
Regeneration with ac/dc drives
units that can control thousands of reverse, speed control, preset speeds, Like dc drives, ac drives can regen-
horsepower are water-cooled. adjustable acceleration and decelera- erate when a load pulls the motor
Selection factors include load tion rates and curves (S-curve or faster than its synchronous speed. Be-
(speed-torque) characteristics, rat- other), readouts of speed and motor cause the synchronous speed of an ac
ings, efficiency when slip is consid- current in rpm and amperes or in en- motor is proportional to the applied
ered, and cooling method. gineering units, motor and controller frequency, a four-pole motor operat-
ing on 60-Hz power could encounter
regeneration at speeds over 1,800
rpm, its synchronous speed. At 30
Hz, regeneration could occur at a
speed over 900 rpm.
A typical example of a regenera-
tive application is a fully loaded ele-
vator. The motor is loaded as it lifts
the elevator car and its contents.
When traveling downward, the mo-
tor “holds back” on its descent (nega-
tive torque) and must have some
place to deposit this regenerated en-
ergy. Other examples of regenerative
applications include winders and un-
winders, machine tools, dynamome-
ters, centrifuges, hoists and cranes,
downhill conveyors, press feeders,
Figure 13 — Control scheme for eddy-current coupling. and rolling mill run-out tables.

A48 1997 Power Transmission Design


Many seemingly innocuous appli- fier. Designed as an add-on module • Power dip ride-through using
cations can turn regenerative during to PWM AFCs, this backward-con- phase-back, phase-forward control.
certain parts of their operation. Every ducting bridge is similar to the basic Common dc bus configuration.
load should be examined to determine power bridge in a synchronous recti- To conserve energy and reduce the re-
what an overhauling load can be dur- fier bridge. Bi-directional modules quired capacity of the input ac-to-dc
ing any part of the operating cycle. can be used independently on stand- rectifier, multiple AFCs can share a
To dissipate excess power, users alone, single-section PWM AFCs; or common dc bus. This enables regener-
can: they can be used to augment a multi- ating drives to supply energy to mo-
• De-tune high-inertia loads by ple-AFC, common-bus system. toring drives.
lengthening deceleration time. Self-contained modules monitor If the net power is always away
• Add a resistive snubber across the dc bus voltage. When a predeter- from the ac line (more drives motoring
the dc bus to handle short-term, inter- mined threshold is exceeded, the than regenerating), a regenerative
mittent regenerative loads. In these IGBT bridge switches on at the peak converter isn’t needed. In this case,
units, sensors measure the dc bus of the input power sine wave. Because the regenerated power is immediately
voltage. When it exceeds specific lim- power returns to the line at the exact re-used by the motoring drives.
its, a power circuit connects a resistor center of the sine wave cycle, there is One major advantage with multiple
across the dc bus to dissipate the ex- little angular displacement between AFCs on common dc bus is that you
cess energy. current and voltage. can use a single regenerative module,
• Use a line-regenerative AFC or Current source inverter (CSI). sized for worst case energy return.
add-on regenerative module for more Based on mature SCR technology, Thus, the regenerative module must
severe regenerative situations. AFCs current source inverters (CSI) can have the capacity to handle only the
equipped with line regeneration han- transpose the ac line source and load surplus energy that is unused by the
dle intermittent and continuous over- during regeneration. motoring AFCs.
hauling loads. This AFC is a current source that The engineer designing to a common
Three recent technological ad- regulates motor terminal voltage. At dc bus must coordinate individual AFC
vances have brought the regenerative the heart of the CSI is a large dc protection. Most systems use many
AFC into vogue: better power semi- choke. Its inductance is 10 times the combinations of fusing, circuit break-
conductors, faster microprocessor motor inductance. During regenera- ers, and reactors. Plus, electrolytic ca-
control, and PWM vector AFCs. tion, the voltage across the dc bus in- pacitors in the dc bus store tremen-
Synchronous rectifier drives verts polarity. This action enables the dous amounts of energy. Therefore, it
contain two complete IGBT bridges, unidirectional SCR converter to put is essential to prevent an isolated AFC
both PWM controlled. The input ac power back into the ac line. failure from causing a catastrophic
power currents are nearly sinusoidal PWM with regenerative six- fault to the entire system.
and devoid of the 5th and 7th harmon- pulse SCR rectifier. Typically re- Excerpted from an article by Re-
ics produced by AFCs that use diode ferred to as an S-6R, the six-pulse liance Electric in the June 1995 issue
bridge rectifiers. controlled-bridge rectifier features a of PTD.
In the motoring mode, the IGBT second reverse-connected rectifier. A
rectifier section works with a reso- common practice with regenerative dc
nant-tuned input line reactor and dc drives is to connect both rectifier
Positioning drives
bus capacitor to create dc bus voltage. bridges in parallel to the ac line. On As automation increases, the need
A complex switching pattern enables an AFC, the rectifier must be pro- for special-purpose electrical drives
a higher dc bus voltage than that cre- tected from inverting faults. These constantly expands. Many of these
ated by a conventional diode bridge faults occur when the dc bus voltage applications require not only control-
rectifier. This ability to regulate dc exceeds the peak of the sine-wave, ac ling speed and direction of shaft rota-
voltage can be beneficial during line voltage. This voltage difference tion, but also controlling position of a
brown-out conditions. will usually cause one of the SCRs in part. This part can be an item being
During regeneration, the IGBT the reverse-bridge to remain in con- machined or sorted, or it can be a part
bridge feeds pulses of the excess dc duction while a forward-bridge SCR of a machine that is performing the
bus voltage into the ac power line, also conducts. This dual conduction work. Examples include cutters of
minimizing harmonic distortion and produces a phase-to-phase short cir- contour milling machines and the
maximizing input power factor. cuit, turning expensive drives into arm of a robot.
Benefits and features include: smoke generators. Two of the most common types of
• Bidirectional power flow to and To avoid this problem, connect the these special positioning drives in-
from the ac power line. reverse-rectifier to a higher voltage clude servo and step.
• Controllable input power factor. source (usually a transformer with a Servo — A servo positioning drive
• Lowest ac line harmonics. higher secondary voltage). receives signals from a controller —
• Ability to create higher motor out- Regenerative PWM inverters with computer numerical control (CNC),
put voltages than the input voltage. S-6R rectifiers offer: programmable logic controller (PLC),
• Adaptable to common dc bus • Reliable SCR power semiconduc- or computer — that tells the drive the
designs. tors. direction, speed, and time to move a
• Power-dip ride-through when • Reverse six-pulse power circuit part from Location A to Location B.
line voltage sags. that is adaptable to common-bus Plus, a sensor continuously deter-
Bi-directional transistor recti- applications. mines the exact position of the part,

1997 Power Transmission Design A49


and sends this information to the con-
troller. The controller then deter-
mines the difference between the in-
Cleaning up power-line pollution
tended position at any given time and
the actual position. Using this error Until recently, power line pollution formers, and electronic equipment.
signal, the controller corrects the — voltage and current harmonics — There are three approaches to meet
power to the drive motor to maintain caused few problems and was often ig- the limits of current and voltage distor-
the needed position-time relation- nored. However, the increasing use of tion as specified in IEEE Std. 519-1992:
ship. Thus, the drive is controlling po- nonlinear-load devices — the causes Drive filters. A specific filter for
sition, because it is using a position each drive traps
feedback loop. and eliminates
Offering extremely fast response unwanted har-
Main
and precise control, some servos ac- transformer monics as close
DC adjustable-
celerate from standstill to 1000 rpm speed drive to the source as
in a few milliseconds. Most servos are controller 500-hp possible so they
PCC
built with at least two feedback loops do not affect
— speed (or current) and position. DC other equip-
motor
Speed feedback can be supplied by ment, Figure E.
a tachometer-generator (tach). An en- Filter 500-hp An alterna-
coder, or similar sensor, can give posi- tive, less-costly
tion feedback. In other drives, one de- DC approach uses
motor
vice—usually an encoder—supplies one filter to re-
both speed and position feedback sig- Filter 200-hp duce the har-
nals. (These sensors are described in monics of a
DC
detail in the Controls and Sensors De- motor group. Such a
partment of this Handbook.) In some filter is con-
Filter 200-hp
designs, the position feedback is con- nected at the
nected to the system controller; and in DC point of common
others, it feeds to the drive controller. motor coupling (PCC)
Many multiaxis drive controllers Filter or inboard of the
include system control functions plus Other plant main
a power supply and several servo loads transformer.
power amplifiers in one unit. The group filter
For many years, dc was the only Figure E — Filter at each drive eliminates enables drives within that group to af-
type of high-response servo drive unwanted harmonics at the source. This fect the operation of other drives
available. However, microprocessors filter placement reduces the chance of the within the same group. For example,
harmonics produced by one drive from
and significant developments in harmonics produced by one drive may
affecting the operation of another device.
power transistors and magnets have cause erratic operation of another
made several alternatives available. drive or other electronic devices.
Conventional dc—For some, the of power-line pollution — makes re- If a filter is required and if electric
motor follows the general design of ducing harmonics now a necessity. costs require adding power-factor cor-
conventional dc motors. However, ser- Examples of nonlinear-load devices recting capacitors, plan both at the
vomotors have low armature inertia include ac and dc adjustable-speed same time, because part of the filter
and offer extremely fast response (ac- drives, static uninterruptable power design may require capacitors. Also,
celeration of 4,000 radians/sec2). supplies, programmable controllers, be sure that the filter design does not
Printed-circuit or disc armature de- rectifiers, switching-type power sup- produce a system resonance.
signs, operate above 4,000 rpm and plies, static lighting ballasts, comput- Simulating 12-pulse systems.
offer acceleration rates of 15,000 radi- ers, and x-ray devices. Individual drive transformers con-
ans/sec2. Power-line pollution can cause such nected delta-wye for half the load and
Servo power amplifiers usually have problems as power factor reduction, other transformers connected in
power transistors to produce a pulse- power system overloading, system res- delta-delta can produce a combined
width-modulated (PWM) dc output. onance, and failure of motors, trans- harmonic content that approaches the
This design offers faster response and
better commutation between the than about 20 hp. able this type of drive to offer re-
brushes and commutators than offered AC vector — Built with high-re- sponse equal to or better than dc
by power units with SCR designs. sponse, two-phase or three-phase ac units. Plus, these ac systems have no
Brushless dc (BLDC) — Consid- induction or permanent-magnet syn- maintenance problems associated
ered both an ac and a dc design, the chronous motors, these ac servos also with dc brushes and commutators.
BLDC servo is discussed previously in operate on adjustable frequency to ob- AC vector servos are increasingly the
this department under “Brushless tain adjustable speed. The capabili- servo of choice for applications requir-
dc.” Nowadays, the BLDC servo is the ties of these servo drives are con- ing more than about 20 hp. For more in-
most frequently installed type of stantly increasing. Recent advances formation on ac vector drives, see the
servo, especially for those rated less made possible by microprocessors en- previous department Vector under the

A50 1997 Power Transmission Design


Main Main
transformer transformer
6-pulse
Delta Wye SCR drive
PCC
PCC 500-hp
50 % I
DC
motor I DC
Load share motor

500-hp 50 % I

DC
motor 6-pulse
Other
loads SCR drive

200-hp
Figure G — Common two-transformer configuration for reducing
DC harmonics produced by high horsepower six-pulse drive.
motor

200-hp
Main
DC transformer 6-pulse
SCR drive
motor

Other PCC
loads 50 % I I DC
Load share
motor
Figure F — By connecting half the load to transformers
connected delta-wye and the other half to transformers with 50 % I
delta-delta configuation, the resulting harmonics approach those
6-pulse
produced by 12-pulse drives.
Other SCR drive
loads
content of a 12-pulse drive, Figure F.
This method reduces harmonics at • Two separate Figure H — Improvement on the configuration in Figure 3. In this
the PCC, if the sum of delta-wye loads isolation trans- single-transformer scheme, the harmonics are reduced in the
primary on the transformer rather than at the PCC.
equals the delta-delta loads. formers, one con-
This transformer configuration can nected delta-wye
be cost-effective if present drive-isola- and the second delta-delta. seen by any other loads connected to
tion transformers have the same pri- • A single transformer with two the plant main transformer.
mary and secondary voltages, and the secondaries. In this case, the primary With the alternate arrangement,
secondary is reconnectable to a delta is in delta and one secondary is in wye harmonic reduction takes place in the
configuration and maintains the and the second is in delta. transformer primary. Also, installed
proper output voltage. In the first method, should either of cost is lower, because the single trans-
Dedicated 12-pulse system. For the two transformers fail, replace- former requires only one set of trans-
larger drives (over 500 hp) consider ment is relatively easy, because both former primary protection. But, be-
creating a dedicated 12-pulse system are standard model number items, cause the transformer has two
from two six-pulse drives that have Figure G. However, the installed cost secondary windings — one delta, the
load-sharing capability or buying a 12- of this system is higher, because two other wye — if something should hap-
pulse drive. The resultant harmonics sets of transformer primary protec- pen to the transformer, repair or re-
remain fairly constant. This approach tion are required. Also, harmonic re- placement would take time.
will reduce the amount of required fil- duction takes place at the PCC, Fig- Excerpted from an article by
tering and its associated cost. ure H, so the original harmonics Theodore J. Bryda, Consultant, in the
There are two basic configurations: caused by each six-pulse drive will be April 1995 issue of PTD.

heading “Types of regulators.” set, the drive also determines the rate cussed in the Motor Product Depart-
Step-motor drive — Unlike a of these pulses and hence the speed ment of this Handbook.)
closed-loop servo drive that requires a during the transition. Step drives can be used with posi-
position feedback signal, a step-motor These logic control devices offer tion feedback for increased accuracy,
drive usually operates open-loop. The complex programming capabilities, because these motors can get out of
drive control pulses the motor with a and the ability to step motors in frac- step during unusual load conditions.
specific number of pulses to achieve tions of a step for greatly improved Servo-step trade-offs — Deciding
the desired position change. In addi- resolution and repeatability. Some of- which precision motion control sys-
tion to determining the number of fer better than 65 arc sec/rev un- tem to select is usually not clear cut.
pulses required for a specific move loaded. (Step-motor details are dis- Major factors include torque-speed

1997 Power Transmission Design A51


capabilities, especially at the lower adj u s t a b l e - d i a m e -
speeds; operating speed range; re- t e r sheaves. As the di-
sponse; maximum torque; repeatabil- ameter of one sheave in-
ity; space constraints; and cost. creases, the other
decreases—maintaining
nearly constant belt or
MECHANICAL chain length—and ad-
ADJUSTABLE-SPEED DRIVES justs the ratio of the in-
put-to-output sheave di-
Two basic types of construction ameters, Figure 15. These
comprise mechanical adjustable- units offer ratios from 2:1
speed drives — belt or chain, and trac- to the more common 6:1,
tion. Although electrical adjustable- with some small-power
speed drives have replaced units capable of 16:1.
mechanical units in some applica- Many different types
tions, design and specifying engineers of operating mechanisms Figure 15 — Basic concept of belt-type
still favor mechanical designs for and belts or chains are used for this mechanical adjustable-speed drive.
many applications. The major rea- design. One of the simplest mecha-
sons: simplicity, ease of maintenance, nisms involves sliding the drive motor and the resultant output speed. These
desirable operating characteristics, to change the center distance between units are available with hand wheels
and cost. sheaves. One or both sheaves are and automatic powered devices to
spring loaded. As the motor moves, turn the drive control screw and move
the spring keeps nearly constant belt the motor.
Belt and chain drives tension by changing sheave diameter. This same principle, with added so-
The drive is based on the principle of This action changes the sheave ratio phistication, is supplied in packaged

The best small-motor drive: ac or dc?


for single or three-phase power for
Advances in technology are en- enclosed, nonventilated (TENV) dc low-horsepower applications. Some,
hancing the capabilities and lower- motor is often selected for low-speed when operating from single-phase
ing the costs of adjustable-speed ac application. It is common to oversize power, require derating the output
and dc controllers. Here’s a look at the ac motor or add a separately pow- current by about 50%. Other ac
some of the tradeoffs for these two ered blower. However, oversizing a drives incorporate an oversized dc
types of drives rated to 5 hp. motor may require selecting a larger bus capacitor to filter the higher cur-
Cost. General-purpose dc pack- drive controller. rent ripple to allow for single-phase
ages are still less expensive than ac High-efficiency ac motors can usu- operation without derating. But re-
controllers due to their lower level of ally operate over a 6:1 speed range, member, the output of an ac drive is
component complexity and fewer and dc over at least 20:1 without us- always three phase, regardless of in-
power controlling devices. An ac ing a speed feedback device. put power supply.
drive has a rectifier section to convert Power factor. A dc drive with its Running multiple motors. With
ac to dc, and an inverter section to in- SCR section has a power factor that dc drives, it is one controller per mo-
vert dc to controlled ac. By contrast, a decreases at light loads and low tor. AC drives can run multiple mo-
low-cost dc controller uses SCRs to speeds, its measurable range is tors as long as they all run at the
rectify and control the power. about 20% to 95%. An ac drive with a same speed.
Customization. An ac controller is fixed-diode converter section has a Rapid stopping. Bringing a mo-
usually a digital device. Its on-board displacement power factor of 95%, tor and load to a quick stop tends to
microprocessor, EPROM (electrically regardless of load or speed. turn the motor into a generator,
programmable read only memory), Increasing speed. DC motor which means the regenerative energy
and ASIC (application specific inte- speed is proportional to applied ar- developed must be dumped usually
grated circuit) are easier to customize mature voltage. AC motor speed is a into a dynamic-braking resistor bank
to application requirements. function of applied frequency and or back to the ac line. Dc drives (even
Speed regulation. With simple voltage from the ac drive, which is small, single-phase units) are avail-
slip compensation (similar to IR com- typically capable of 400 Hz operation able to regenerate back to the line.
pensation on a dc drive), an ac pack- (12,000 rpm on a 4-pole motor). An ac drive requires an additional
age is capable of 1% speed regulation Check with the motor manufacturer transistor and logic to monitor the dc
based on a standard NEMA Design B when operating above nameplate bus-voltage level to turn the transis-
squirrel cage induction motor. speed, regardless of whether it’s an tor on at the proper point to dump the
Speed range. Speed range is a ac or dc motor. regenerative energy into an external
function of the motor’s ability to dis- Single-phase. Single-phase dc dynamic-braking resistor.
sipate heat, to operate without cog- drives are designed and rated for op- Excerpted from an article by
ging at low speeds, and to avoid fly- erating from a single-phase power Saftronics Inc. in the April, 1996 is-
ing apart at high speeds. A totally source. Many ac drives are designed sue of PTD.

A52 1997 Power Transmission Design


pressure at various Traction drives
speeds, belt strength,
and belt centrifugal Direct mechanical contact of
force. smooth surfaces characterizes trac-
Several types of belts tion drives. These units operate on
optimize the drive for the principle that smooth surfaces
the application. Rubber transmit torque without pulsation,
belts, among the most and that speed can be adjusted by ad-
frequently used, in- justing the ratio of input-to-output
clude standard V-belts contact diameters, Figure 17.
for applications requir- Other traction drives require a spe-
ing up to 2:1 speed ad- cial lubricant that, in effect, hardens
justment. Also, wide- under high pressure, such as that cre-
thin industrial rubber ated between metal surfaces in heavy
belts are designed for contact.
up to 8:1 adjustable- Traction drives are manufactured
speed applications. with speed ratios from 5:1 to special
Figure 16 — Typical output torque and Wood block belts are units with 25:1. Power ratings vary
power vs. speed curve for belt-type still used for high torque, low-speed ap- from fractional to about 100 hp. ■
adjustable-speed drive. plications (below about 1,200 rpm). This
design has a set of
drives. Most of these units include an wood blocks bolted
electric motor, adjustable-speed sec- to a thick composi-
tion, and geared reducer. The speed tion belt.
adjustment method can be a hand Metal chains
wheel or an air or electric motor for provide no-slip con-
remote control. nection between
Complex belt and sheave charac- input and output.
teristics affect the torque and power These units offer several other advan- Figure 17 — Common design of metal-to-
that belt drives can transmit, Figure tages: life of 10,000 hr, small size, and metal traction drive. A hardened ring on the
16. The major factors include sheave easy chain replacement. output shaft disc rides on the driving cone.

1997 Power Transmission Design A53

You might also like