Installation and
operating manual
Table of Content
1 About this manual 5
1.3 Scope 6
3 Product features 17
4 Installation 23
4.4 Connections 26
4.5 Tools 26
2 SOFAR 1100...3300TL-G3
TABLE OF CONTENT
5 Electrical connections 33
8 Troubleshooting handling 69
8.1 Troubleshooting 69
SOFAR 1100...3300TL-G3 3
TABLE OF CONTENT
8.2 Maintenance 79
9 Technical data 80
4 SOFAR 1100...3300TL-G3
ABOUT THIS MANUAL
SOFAR 1100...3300TL-G3 5
ABOUT THIS MANUAL
1.3 Scope
6 SOFAR 1100...3300TL-G3
ABOUT THIS MANUAL
DANGER
Non-observance will result in death or serious injury.
• Follow the warnings in order to prevent death or serious
injury!
WARNING
Non-observance may result in death or serious injury.
• Follow the warnings in order to prevent serious injury!
CAUTION
Non-observance may result in minor injury.
• Follow the warnings in order to prevent injury!
ATTENTION
Non-observance may result in property damage!
• Follow the warnings in order to prevent damage to or
destruction of the product.
NOTE
• Provides tips essential to the optimal operation of the
product.
SOFAR 1100...3300TL-G3 7
BASIC SAFETY INFORMATION
8 SOFAR 1100...3300TL-G3
BASIC SAFETY INFORMATION
DC switch in the Array junction box. Not doing this may result in
serious injury.
SOFAR 1100...3300TL-G3 9
BASIC SAFETY INFORMATION
The labels must NOT be concealed by items and foreign objects (rags,
boxes, devices, etc.); they must be regularly cleaned and kept clearly
visible at all times.
10 SOFAR 1100...3300TL-G3
BASIC SAFETY INFORMATION
DANGER
Dangerous DC voltage
• Before establishing the electrical connection, cover the PV
modules using opaque material or disconnect the PV
generator from the inverter. Solar radiation will cause
dangerous voltage to be generated by the PV generator!
DANGER
Danger through electric shock!
• All installations and electrical connections may only be
carried out by trained electricians!
IMPORTANT
Authorisation for grid feed-in
• Obtain authorisation from the local power grid operator
before connecting the inverter to the public power grid.
NOTE
Voiding of guarantee
• Do not open the inverter or remove any of the labels.
Otherwise, SOFARSOLAR shall assume no guarantee.
SOFAR 1100...3300TL-G3 11
BASIC SAFETY INFORMATION
2.1.6 Operation
DANGER
Electric shock
• Contact with the electrical grid or the device’s terminals may
result in an electric shock or fire!
• Do not touch the terminal or the conductor which is
connected to the electrical grid.
• Follow all instructions and observe all safety documents that
refer to the grid connection.
CAUTION
Burning due to hot housing
• While the inverter is being operated, several internal
components will become very hot.
• Please wear protective gloves!
• Keep children away from the device!
12 SOFAR 1100...3300TL-G3
BASIC SAFETY INFORMATION
DANGER
Dangerous voltage!
• Before carrying out any repair work, first switch off the AC
circuit breaker between the inverter and power grid, and then
the DC switch.
• After switching off the AC circuit breaker and the DC switch,
wait a minimum of 5 minutes before starting any
maintenance or repair work.
IMPORTANT
Unauthorised repairs!
• Following the elimination of any faults, the inverter should
be fully functional once more. Should any repairs be
required, please contact a local authorised service centre.
• The internal components of the inverter must NOT be
opened without the relevant authorisation. Shenzhen
SOFARSOLAR Co., Ltd. assumes no responsibility for any
resulting losses or defects.
CAUTION
SOFAR 1100...3300TL-G3 13
BASIC SAFETY INFORMATION
ATTENTION
Implement earthing!
• The PV generator must be earthed in accordance with the
requirements of the local power grid operator!
• For reasons of personal safety, we recommend that all PV
module frames and inverters of the PV system are reliably
earthed.
WARNING
Damage due to overvoltage
• Ensure that the input voltage does not exceed the maximum
permissible voltage. Overvoltage may cause long-term
damage to the inverter, as well as other damage that is not
covered by the warranty!
14 SOFAR 1100...3300TL-G3
BASIC SAFETY INFORMATION
Symbol Description
Earthing point
SOFAR 1100...3300TL-G3 15
BASIC SAFETY INFORMATION
Symbol Description
16 SOFAR 1100...3300TL-G3
PRODUCT FEATURES
3 Product features
This chapter describes the product features, dimensions and
efficiency levels.
SOFAR 1100...3300TL-G3 17
PRODUCT FEATURES
18 SOFAR 1100...3300TL-G3
PRODUCT FEATURES
SOFAR 1100...3300TL-G3 19
PRODUCT FEATURES
3.3.1 Functions
The inverter can limit the active power fed into the grid to a specific
value (as a percentage of the rated output).
20 SOFAR 1100...3300TL-G3
PRODUCT FEATURES
If the grid frequency is higher than the limit value, the inverter will
reduce the output power; this is required to ensure stability of the
grid.
E Data transfer
The inverter (or a group of inverters) can be monitored remotely via
the RS485 communication bus or via WiFi/GPRS.
F Software update
The device supports local updates via USB stick and remote updates
via WiFi/GPRS.
AC grid relais
AC Output
AC EMC filter
DC/AC Inverter
DC Switch
DC Input
DC/DC Booster
DC EMC filter
1A + L1
1A - N
1
PE
MPPT
SOFAR 1100...3300TL-G3 21
PRODUCT FEATURES
22 SOFAR 1100...3300TL-G3
INSTALLATION
4 Installation
DANGER
Fire hazard
• Do NOT install the inverter on flammable material.
• Do NOT install the inverter in an area in which flammable or
explosive material is stored.
CAUTION
Burning hazard
• Do NOT install the inverter in places where it can be
accidentally touched. The housing and heat sink may become
very hot while the inverter is being operated.
IMPORTANT
Weight of the device
• Take into account the weight of the inverter when
transporting and moving it.
• Choose a suitable installation location and -surface.
• Commission a minimum of two persons with the
installation of the inverter.
• Do not set down the inverter upside-down.
SOFAR 1100...3300TL-G3 23
INSTALLATION
After unpacking the inverter, check that the delivery items are both
intact and complete. In the event of any damage or missing
components, contact the wholesaler.
24 SOFAR 1100...3300TL-G3
INSTALLATION
02 Wall bracket 1
07 M5 hexagon screws 2
08 Dowel 3
09 M5 washer 5
10 Spring washer 5
11 Self-tapping screw 3
12 Manual 1
13 Warranty card 1
16 AC output terminal 1
SOFAR 1100...3300TL-G3 25
INSTALLATION
4.4 Connections
CAUTION
Damage during transportation
• Please check the product packaging and connections
carefully prior to installation.
*Note: Insert the screw into the hole on the DC switch to lock the
switch. Remove the screw prior to the switch.
4.5 Tools
Prepare the tools required for the installation and the electrical
connection.
26 SOFAR 1100...3300TL-G3
INSTALLATION
02 Screwdriver Wiring
SOFAR 1100...3300TL-G3 27
INSTALLATION
28 SOFAR 1100...3300TL-G3
INSTALLATION
30
cm
30 cm 30 cm
50
cm
SOFAR 1100...3300TL-G3 29
INSTALLATION
10 cm
100 cm
20 cm 30
cm
30 SOFAR 1100...3300TL-G3
INSTALLATION
ATTENTION
Mechanical damage
• In order to prevent injuries and damage to the device,
ensure that the inverter is kept balanced while it is being
moved - it is very heavy.
• Do not place the inverter on its connections, as these are
not designed to bear its weight. Place the inverter
horizontally on the ground.
• When you place the inverter on the ground, place foamed
material or paper underneath it in order to protect its
housing.
SOFAR 1100...3300TL-G3 31
INSTALLATION
1 Hold the wall bracket in the desired place and mark the three
holes. Put the wall bracket aside and drill the holes.
3. Fasten the rear panel to the wall using the three screws.
3 Place the inverter in the wall bracket. Secure the inverter to the
wall bracket using a M5 hexagon screw.
4 You can secure the inverter to the wall bracket using a lock.
32 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
5 Electrical connections
DANGER
Electrical voltage at the DC connections
• Ensure that the DC switch is OFF before establishing the
electrical connection. The reason is that the electrical charge
remains in the capacitor after the DC switch has been
switched off. Therefore, at least 5 minutes must lapse before
the capacitor has been electrically discharged.
DANGER
Electrical voltage
• PV modules generate electrical energy when exposed to
sunlight, and this may present an electrical shock hazard.
Therefore, cover the PV modules with an opaque sheet
before connecting to the DC input power cable.
ATTENTION
Qualification
• The installation and maintenance of the inverter must be
carried out by an electrician.
SOFAR 1100...3300TL-G3 33
ELECTRICAL CONNECTIONS
Interface DVC
DC input DVCC
AC output DVCC
CT interface DVCA
34 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
1. Connect PE cable
ATTENTION
Pole earthing not permissible!
• As the inverter is transformerless, the plus and minus poles
of the PV generator must NOT be earthed. Otherwise, the
inverter will malfunction. In the PV system, not all live metal
parts (e.g. PV module frames, PV frame, generator
connection box housing, inverter housing) require earthing.
Procedure
1. Remove the insulation of the cable. For outside use, cables of ≥
4mm² are recommended for earthing).
SOFAR 1100...3300TL-G3 35
ELECTRICAL CONNECTIONS
3. Install the crimped ring terminal and the washer with the M5
screw and tighten these with a torque of 3 Nm using an Allen
key:
③ Threaded hole
36 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
SOFAR 1100...3300TL-G3 37
ELECTRICAL CONNECTIONS
CAUTION
Danger of reverse polarity!
• Ensure that the polarity is correct before plugging into the DC
connections!
① Locking
Note: Insert the protective caps into the unused DC connections.
38 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
CAUTION
Danger of DC arcing
• Before removing the plus and minus connector, ensure that
the DC switch has been set to OFF.
In order to remove the plus and minus connection from the inverter,
insert a removal key into the locking and press on the key with the
adequate force as shown in the following illustration:
CAUTION
AC connection
• Each inverter must have its own circuit breaker.
• Do not connect any consumers between the inverter and
circuit breaker!
• The AC disconnecting device must be easily accessible.
SOFAR 1100...3300TL-G3 39
ELECTRICAL CONNECTIONS
NOTE
• The inverter SOFAR 1100...3300TL-G3 has a built-in AFI
(univ. sensitive residual current protection). If an external
AFI is required, we recommend an AFI type A featuring a
residual current of 100 mA or higher.
• Please follow the national rules and regulations for the
installation of external relais or circuit breakers!
Dimensioning
The AC output cables are three-wire cables for outdoor areas. To
simplify the installation process, use flexible cables. The
recommended cable specifications are listed in the following table.
TV
1100TL-G3
1600TL-G3
2200TL-G3
2700TL-G3
3000TL-G3
3300TL-G3
Model
AC 16 A / 16 A / 25 A / 25 A / 25 A / 25 A /
disconnector 400 V 400 V 400 V 400 V 400 V 400 V
40 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
AC connector type
The inverter is equipped with two types of IP66 AC connector (type I
connector or type II connector):
SOFAR 1100...3300TL-G3 41
ELECTRICAL CONNECTIONS
Connector type A B
Type I 30 … 50 mm 6 … 8 mm
Type II 15 … 25 mm 6 … 8 mm
42 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
Type I
Type II
Type I
SOFAR 1100...3300TL-G3 43
ELECTRICAL CONNECTIONS
Type II
Connection Cable
L Phase (brown)
3. Assemble the connector housing and screw the cable gland tight.
Type I
44 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
Type II
CAUTION
Electrical voltage
• Ensure that the grid has been switched off before removing
the AC connector.
SOFAR 1100...3300TL-G3 45
ELECTRICAL CONNECTIONS
NOTE
• The RS485 line may not be any longer than 1000 m
• Assign each inverter its own modbus address (1 to 31) via
the LCD display
When you have installed the stick logger, the inverters can directly
upload your operating, energy and alarm data in the SolarMAN
monitoring portal.
46 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
NOTE
• In order to use the stick logger, the inverters must have the
modbus address 1
Carry out the following steps in order to configure the WiFi stick:
SOFAR 1100...3300TL-G3 47
ELECTRICAL CONNECTIONS
48 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
Configuration steps
1 After starting the app, register as a new user or enter the current
SOLARMAN access data.
5 Press the button on the WiFi stick for 1 second to activate the
WPS mode of the stick so that the smartphone can be connected
to the WiFi stick.
SOFAR 1100...3300TL-G3 49
ELECTRICAL CONNECTIONS
6 Now, select your local WiFi network for Internet access and enter
your WiFi password.
The LEDs on the WiFi stick provide information regarding the status:
Reset button
Keystroke Description
50 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
Keystroke Description
5 sec. Restart
1 Open the app and call up the Bluetooth Tools menu item
2 Identify the WiFi stick with the serial number and select it.
SOFAR 1100...3300TL-G3 51
ELECTRICAL CONNECTIONS
6 You can check the status via the “Logger Status” and “Read”
menu item. Depending on the grid operator, wait several minutes
until the connection has been established and the status is
normal:
52 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
The wiring methods for RS485 and the current sensor (CT) are
identical:
2. Release the waterproof cable gland and remove the plug of the
waterproof connector;
SOFAR 1100...3300TL-G3 53
ELECTRICAL CONNECTIONS
3. Select a suitable cable and strip it approx. 6 mm. Guide the cable
through the cable gland and the waterproof cover, connect the
wires and tighten the screws of the terminal using a slot head
screwdriver.
Cable assignments
Connection
54 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
The function of the logic interface must be set on the LCD display;
please observe the operating steps in section 6.3.
SOFAR 1100...3300TL-G3 55
ELECTRICAL CONNECTIONS
2 Orange DRM2/6
4 Blue DRM4/8
6 Green DRM0
56 SOFAR 1100...3300TL-G3
ELECTRICAL CONNECTIONS
1 0 0 1 0% 1
0 1 0 0 30% 1
0 0 1 0 60% 1
0 0 0 0 100% 1
SOFAR 1100...3300TL-G3 57
ELECTRICAL CONNECTIONS
1 0% < 5 seconds 1
0 100% / 1
58 SOFAR 1100...3300TL-G3
COMMISSIONING THE INVERTER
ATTENTION
Check the voltage range
• Ensure that the DC and AC voltages are within the permissible range
of the inverter.
NOTE
• Different distribution network operators in various countries have
differing requirements for the grid connection of grid-coupled PV
inverters.
• Ensure that you have selected the correct country code according
to regional authority requirements, and consult a qualified
electrician or employees of electrical safety authorities.
• SOFARSOLAR is not responsible for the consequences of selecting
the incorrect country code.
• The selected country code influences the device grid monitoring.
The inverter continuously checks the set limits and, if required,
disconnects the device from the grid.
SOFAR 1100...3300TL-G3 59
OPERATION OF THE DEVICE
Button
Hold the button down to bring up the next menu level or to confirm
the selection ("Enter" button)
LEDs
RUN (green) illuminates: “Normal” state
60 SOFAR 1100...3300TL-G3
OPERATION OF THE DEVICE
The following table displays the various statuses and their meanings:
Status Description
SOFAR 1100...3300TL-G3 61
OPERATION OF THE DEVICE
Main menu
“Settings” menu
62 SOFAR 1100...3300TL-G3
OPERATION OF THE DEVICE
SOFAR 1100...3300TL-G3 63
OPERATION OF THE DEVICE
64 SOFAR 1100...3300TL-G3
OPERATION OF THE DEVICE
Password
SOFAR 1100...3300TL-G3 65
OPERATION OF THE DEVICE
2. Event list
66 SOFAR 1100...3300TL-G3
OPERATION OF THE DEVICE
Display time
Displays the current system time.
Firmware update
The user can update the software via the USB flash drive.
SOFARSOLAR will provide the firmware update when it is required.
4. Unzip the file and copy the original file to a USB stick. Attention:
The firmware update file must be in the “firmware” subfolder!
5. Insert the USB flash drive into the USB interface of the inverter.
8. The system will then successively update the main DSP, auxiliary
DSP and ARM processors. Pay attention to the displays.
SOFAR 1100...3300TL-G3 67
OPERATION OF THE DEVICE
10. After the update is complete, switch the DC switch off and wait
until the LCD screen goes out
13. You can check the current software version in item “3. Software
version” of the SystemInfo menu.
68 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
8 Troubleshooting handling
8.1 Troubleshooting
This section contains information and procedures pertaining to the
remedying of potential problems with the inverter.
• Are the input connections, output connections and the wiring all in
good condition?
SOFAR 1100...3300TL-G3 69
TROUBLESHOOTING HANDLING
NOTE
• In the case of devices equipped with a stick logger, the
alarm information can be viewed on the monitoring portal
and retrieved via the smartphone app.
70 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
05 PVUVP The input voltage is too Check whether too few PV modules
low have been switched in series and
correct this if required. The inverter
automatically returns to its normal
operating state.
SOFAR 1100...3300TL-G3 71
TROUBLESHOOTING HANDLING
14 HwBoostOCP The input current is too Check whether the input current is
high and has triggered the higher than the maximum
hardware protection permissible input current of the
inverter. Check the input cables. If
both are correct, please contact the
technical support department.
72 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
GFCIDeviceF
20 GFCI measurement error
ault
HwAuxPower
22 Auxiliary voltage error
Fault
26 BusOVP The bus voltage is too high ID26-ID27 are internal errors of the
inverter. Switch the DC switch OFF,
27 VbusUnbalan The bus voltage is not
wait 5 minutes and then switch the
balanced
DC switch ON. Check whether the
error has been rectified. If not,
please contact the technical
support department.
SOFAR 1100...3300TL-G3 73
TROUBLESHOOTING HANDLING
28 DciOCP The DC current is too high Check the setting of the MPPT
input mode (parallel
mode/independent mode) of the
inverter and correct if required.
29 SwOCPInstan The grid current is too Internal inverter error, switch the
high DC switch OFF, wait 5 minutes and
then switch the DC switch ON.
Check whether the error has been
rectified. If not, please contact the
technical support department.
30 SwBOCPInst The input current is too Check whether the input current is
ant high higher than the maximum
permissible input current of the
inverter, then check the input
cables. If both are correct, please
contact the technical support
department.
50 ConsistentFa The sample value of the DC switch ON. Check whether the
consistent
74 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
SOFAR 1100...3300TL-G3 75
TROUBLESHOOTING HANDLING
76 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
81 OverTempDe The inverter has derated Ensure that the installation position
rating itself due to the and method both comply with the
temperature being too necessary requirements of this
high user manual. Check whether the
ambient temperature at the
installation location exceeds the
upper limit value. If so, improve the
ventilation in order to reduce the
temperature.
83 RemoteDerat The inverter has derated The inverter logs ID83 when the
ing itself through the remote remote power is reduced. Check
control the wiring of the remote control
input and output signal connection
on the communication board
SOFAR 1100...3300TL-G3 77
TROUBLESHOOTING HANDLING
84 RemoteOff The inverter was switched The inverter logs ID84 in the event
off through the remote of a remote switch-off. Check the
control wiring of the remote control input
and output signal connection on
the communication board
94 Softwareversi The the control board and Contact the technical support
onisnotconsis communications board department in order to upgrade the
tent software is not consistent software.
95 Communicati The EEPROM of the ID95 ... ID96 are internal errors of
onboardEEPR communications board is the inverter. Switch the DC switch
OMfault faulty OFF, wait 5 minutes and then
switch the DC switch ON. Check
96 RTCclockchip The RTC clock chip is
whether the error has been
anomaly faulty
rectified. If not, please contact the
technical support department.
78 SOFAR 1100...3300TL-G3
TROUBLESHOOTING HANDLING
8.2 Maintenance
Inverters do not generally require daily or routine maintenance. Before
carrying out cleaning, ensure that the DC switch and AC circuit breaker
between the inverter and power grid have been switched off. Wait at least
5 minutes before carrying out cleaning.
SOFAR 1100...3300TL-G3 79
TECHNICAL DATA
9 Technical data
Datasheet 1100TL-G3 1600TL-G3 2200TL-G3 2700TL-G3 3000TL-G3 3300TL-G3
Input (DC)
Full power MPPT voltage range (V) 110-450 150-450 200-450 250-500 275-500 300-500
Output (AC)
THDi < 3%
Efficiency
Protection
80 SOFAR 1100...3300TL-G3
TECHNICAL DATA
DC switch Yes
Communication
General
Topology Transformerless
Noise < 25 dB
DC switch Optional
Cooling Natural
Display LCD+LED
Standard
Safety standards IEC 62116, IEC 61727, IEC 61683, IEC 60068 (1,2,14,30), IEC 62109-1 / 2
SOFAR 1100...3300TL-G3 81