The Differences In UL142 Fuel Tank Construction


By Pete Torres, Pro Power Solutions

During a preliminary design meeting for an indoor diesel set, a consulting engineer asked, “When we specify the
diesel generator’s tank to be supplied as a “UL 142 Base Tank”, what tank construction will be submitted?

Given today’s competitive market, open bid projects are quoted with a minimum bill of materials that meet the project’s plans
and specifications, all in order to be the low bidder to win the project. If a specification only references that the tank be
classified as UL142, design options can be submitted that are low in cost, but may not meet code approval for both indoor and
outdoor applications.

There are five basic types of Generator-Base Tank designs that can be Underwriters Laboratory (UL) Listed as "Special
Purpose Flammable Liquid Tanks". The basic “standard” for these tank designs is an Underwriters “UL-142 Steel Aboveground
Tanks for Flammable and Combustible Liquids” listing. Tank designs are known by various industry slang names, and in some
cases the same name is applied to several different types of tank. This has been very confusing and misleading. The five
different tank designs are in the following UL categories:

1. single wall tank


2. open-top diked tank
3. closed-top diked tank
4. secondary-containment generator tank
5. protected secondary tank (UL 2085)

Any of the following options may be submitted by a “low bidder” if the tank’s requirement is only UL142:

Open-Top Diked

This is a "double wall" tank, and the side rails of the dike (or rupture basin) have been
designed to support the weight of the generator set. The inner tank is attached to the dike and
the dike is open to the atmosphere. This type tank offers little protection against falling debris
or precipitation from entering the containment basin.

This tank has been traditionally installed indoors and out of the weather; however, current
venting code issues for indoor applications, if enforced, would likely prohibit the local
jurisdiction having authority (LJHA) from awarding approval.

Closed-Top Diked

This is a "double wall" tank, and the side rails of the dike have been designed to support the
weight of the generator set. The inner tank is attached to the dike and the dike is covered
with one end open to the atmosphere. The cover for the dike is vented at one end to keep
rain and debris from entering the dike. When this tank is UL Listed, it will include an
emergency vent connection on the inner tank only.

This application is typically acceptable by LJHA’s for outdoor use; however, there is no true
connection to pipe the normal vent to the exterior of a building for an indoor application. Also

1 of 2 08/02/2013 11:14 AM
UL142 Fuel Tank Construction http://propowersolutions.com/power-insider/0410ConstDiff.html

if the local codes require the vents to be extended above the generator enclosure, there is
no way to extend the normal vent.

Secondary Containment

The Secondary Containment (Double Wall) Generator Base Tank is a true double wall
constructed tank, the rails of the outer tank have been designed to support the weight of the
generator set. This is the only form of generator base tank recognized by Underwriters
Laboratories as a "double wall". Both the inner tank and outer tank must be pressure tested
to 3 psi. When this tank is UL Listed, it will include an emergency vent connection on the
inner and outer tank.

If the application is an indoor generator and skid tank, then a Secondary Containment tank
should be specified so both the normal and emergency vents can be piped and extended to
the exterior of the room.

All tanks manufactured by Generac Industrial Power are UL 142 Secondary Containment tanks suitable for use both
indoors and outdoors!