Professional Documents
Culture Documents
Vacuum Generator
Circuit-Breaker for
Synchronous Condenser
Applications
Topic Presenter
Installed fleet
(%) ~ 85 % ~ 10 % ~5%
Page 3 Unrestricted | © Siemens 2023 | Expert Workshop Series | 2023-01-31
Utility Applications
Opportunities for Synchronous Condenser
Challenges Benefits
• Reduction of nuclear and fossil power is • Increased controlled reactive power in the grid
causing stability problems in the HV grid (reduction of short- • Increased short-circuit capacity in the grid
circuit cower and voltage / frequency stability) • Stability of grid voltage / frequency
• Increase of renewable energy (means stress to power grid) • Ability to settle grid system incidents
• International transit trade of electricity (causes additional • Increased load fow capacity
stress to transmission network)
Problems Reference: Deecke, Kawecki – Usage of Existing Power
Plants as Synchronous Condenser, Siemens AG, 2015
• Lack of short-circuit power in the grid DOI: 10.15199/48.2015.10.12
short-circuit current →
Interaction between
Asymmetrical
•
generator and system
• No generally valid short-
circuit characteristics
Time →
Current →
Asymmetry →
Isolated star point
• symmetrical three-phase fault
• at voltage maximum
(maximum arcing time)
Aim: worst-case scenarios
• maximum mechanical stress Time →
(maximum peak current) I''k Initial short-circuit current (RMS) tpro Protection (relay) time
ip Short-circuit peak current topen Opening time (mechanical)
• maximum thermal stress isc Transient short-circuit current tcp Contact parting time
(maximum arcing time) Isym Symmetrical breaking current (RMS)
Idc Direct breaking current (RMS)
Iasym Asymmetrical breaking current (RMS) DC% Degree of asymmetry
• at voltage maximum
symmetrical phase (without asymmetry)
maximum asymmetrical opposite phases
Aim: worst-case scenarios
• maximum mechanical stress
(maximum peak current)
tcp
isc
Idc
Limitations Excitation
• Overexcitation: rotor field current > 100%
• Stator: armature current reactive power > 0 %
• Rotor: field winding current (excitation) • Underexcitation: rotor field current < 100 %
• Operation: stator end heating / rotor angle safety reactive power < 0 %
I1∙jXd
Motor mode
U1
U1
Up
Up
ϑ
ϑ
φ φ I1
I1
overexcited underexcited
I1∙jXd
I1∙R
I1∙jXd
I1∙R
U1
Up Generator mode Up
U1
ϑ
ϑ
φ
I1
Page 12 Unrestricted | © Siemens 2023 | Expert Workshop Series | 2023-01-31 I1 φ
Operation of generators
Underexcitation / Overexcitation: capability curve
Limitations
• Synchronous Generator:
Stator limitation
Rotor limitation
Synchronous Condenser:
Stator limitation
Power capability
• Enhanced reactive power
capability for SynCon
Operation regime
• SynGen: (0.8 lead…0.8 lag)|pf. Reference: Siemens Energy SGen5/6-100A Series
SynCon: ≈ 150 MVA (Apparent Power)
• SynCon: (0…0.2 lead)|pf. SynGen: ≈ 155 MVA (Apparent Power)
(0.2 lag…0)|pf. (Turbogenerator)
OP / Max [%]
60 80
40 70
Operation 20 60
U1
Highest asymmetry Up
U1
Up
ϑ
ϑ
φ φ I1
I1
overexcited underexcited
I1∙jXd
I1∙R
I1∙jXd
I1∙R
ϑ
ϑ
φ
I1
I1 φ
250 250
200
δ0 = 90° 200
δ0 = 180°
150 150
0 0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-50 -50
-100 -100
-150 -150
-200 -200
-250 -250
Phase R Phase S Phase T Phase R Phase S Phase T
Inertia
Parameter
• SynGen:
xd >...>>
usually connected to x'd >…>>
G
turbine delivering G
Q x''d >…>>
GCB BUSMV GSUT BUSHV
significant Inertia xq >…>>
• SynCon: x'q >…>>
x''q >…>>
SynGen
SynCon
might be connected to
G T'd >…≈
flywheel increasing the G
Q
GCB BUSMV GSUT BUSHV T''d >…≈
inertia at rotor shaft
T'q >…≈
Reactances
T''q >…≈
• Generally lower reactances Ta >…≈
Reference: Siemens Energy SGen5/6-100A Series
of SynCon lead to significantly SynCon: ≈ 150 MVA (Apparent Power) cosφ >>
higher short-circuit currents SynGen: ≈ 155 MVA (Apparent Power) J/H ?
Inertia
rated: ≈ 5.500 kgm² (Rotor only)
• Most significant influence on
Out-of-Phase faults due to
false synchronization
• Marginal impact on
generator-source faults
• Impact of inertia:
low: » − 50 %
rated: ≈ 5.500 kgm² (Rotor only)
high: » + 50 %
Inertia
rated: ≈ 5.500 kgm² (Rotor only)
• Most significant influence on
Out-of-Phase faults due to
false synchronization
• Marginal impact on
generator-source faults
• Impact of inertia:
low: » − 50 %
rated: ≈ 5.500 kgm² (Rotor only)
high: » + 50 %
• System parameters
Impedance ratios:
Grid: 10 » + / − 50 %
Transformer: 45 » + / − 50 %
Short-circuit capability:
Grid: 30 kA » + / − 50 %
High voltage level:
Grid: 400 kV » − / + √
Nonnendammallee 104
13629 Berlin
Germany
© Siemens 2023
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or performance
features which may not always specifically reflect those described, or which
may undergo modification in the course of further development of the
products. The requested performance features are binding only when they
are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens, its
affiliated companies or other companies whose use by third parties for their
own purposes could violate the rights of the respective owner.