FAN COILS

ACCESSORY ELECTRIC HEATERS

WIRING DIAGRAMS
FIELD INSTALLED FE4A
FIG. FB4C FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL
HEATER MODEL FE5A
1 KFCEH0401N03 18,24 001 19,25 18,24 18,19,24,25 328613--- 101
1 KFCEH0501N05 18--- 60 002--- 006 001--- 002 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
1 KFCEH0801N08 18--- 60 002--- 006 001--- 003 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
1 KFCEH0901N10 18--- 60 002--- 006 001--- 004 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
5 KFCEH1601315 42--- 60 002--- 006 001--- 004 002--- 006 43--- 61 18--- 60 18--- 61 19--- 61 328614--- 101
6 KFCEH2001318 42--- 60 003--- 006 001--- 004 002--- 006 43--- 61 42--- 60 42--- 61 37--- 61 328615--- 101
1 KFCEH2401C05 18--- 60 002--- 006 001--- 002 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
1 KFCEH2501C08 18--- 60 002--- 006 001--- 003 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
1 KFCEH2601C10 18--- 60 002--- 006 001--- 004 002--- 006 19--- 61 18--- 60 18--- 61 19--- 61 328613--- 101
2 KFCEH2901N09 36--- 60 002--- 006 003--- 004 002--- 006 37--- 61 36--- 60 36--- 60 31--- 61 328606--- 101
3 KFCEH3001F15 24--- 60 002--- 006 001--- 004 002--- 006 25--- 61 24--- 60 24--- 61 19--- 61 328605--- 101
3 KFCEH3101C15 24--- 60 002--- 006 001--- 004 002--- 006 25--- 61 24--- 60 24--- 61 19--- 61 328605--- 101
4 KFCEH3201F20 30--- 60 002--- 006 002--- 004 002--- 006 31--- 61 30--- 60 30--- 61 19--- 61 328604--- 101
4 KFCEH3301C20 30--- 60 002--- 006 002--- 004 002--- 006 31--- 61 30--- 60 30--- 61 19--- 61 328604--- 101
328602--- 101,
7,8 KFCEH3401F24 48,60 004--- 006 003--- 004 005--- 006 49--- 61 48--- 60 48--- 61 49--- 61
328603--- 101
328602--- 101,
7,8 KFCEH3501F30 48,60 004--- 006 003--- 004 005--- 006 49--- 61 48--- 60 48--- 61 49--- 61
328603--- 101

FIELD INSTALLED
FIG. FY5B LABEL
HEATER MODEL
9 MKFCEH0501N05 18,24 328205--- 101
9 MKFCEH0801N08 18,30 328205--- 101
9 MKFCEH0901N10 24--- 48 328205--- 101
10 MKFCEH3001F15 36--- 60 328206--- 101

FAN COIL WITH RBC X ---13 MOTOR

FIELD INSTALLED
FIG. FB4C FX4D LABEL
HEATER MODEL
11 MKFCEH0501N05 18,24 19,25 335975--- 101
11 MKFCEH0801N08 18,30 31 335975--- 101
11 MKFCEH0901N10 24--- 48 37--- 61 335975--- 101
12 MKFCEH3001F15 36--- 60 61 336923--- 101
FAN COIL WITH BROAD OCEAN DIGI---MOTOR

FIELD INSTALLED
FIG. FB4C FX4D LABEL
HEATER MODEL
13 MKFCEH0501N05 24 --- 337518--- 101
13 MKFCEH0801N08 18,30 31 337518--- 101
13 MKFCEH0901N10 24--- 36 37--- 49 337518--- 101
14 MKFCEH3001F15 36 --- 338001--- 101

FAN COIL WITH COOLING ONLY CONTROL

FIG. MODEL SIZE LABEL


15 FV4C 002--- 006 326014--- 101
16 FE4A/FE5A 002--- 006 333107--- 101
17 FY5B/PF4MNA 18--- 60 328964--- 101
17 FH4C 001--- 004 328964--- 101
18 FB4C/FX4D (RBC) 18--- 61 336228--- 101
18 PF4MNA/B 19,25,31,37,43,49,61 336228--- 101
19 FB4C/FX4D (BOM) 18--- 61 337519--- 101

FIG. HEATER MODEL FF1E LABEL


20 KFDEH0801D05 18,24,30,36 324494--- 101
20 KFDEH0901D75 18,24,30,36 324494--- 101
20 KFDEH1001D11 18,24,30,36 324494--- 101
20 MKFDEH0801D05 18,24,30,36 324494--- 101
20 MKFDEH0901D75 18,24,30,36 324494--- 101
20 MKFDEH1001D11 18,24,30,36 324494--- 101
21 KFEEH0101D05 19,25,31,37 335826--- 101
21 KFEEH0201D75 19,25,31,37 335826--- 101
21 KFEEH0301D11 19,25,31,37 335826--- 101

2
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 1.7 COMPONENT ARRANGEMENT

FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR2
FOR VOLTS & HERTZ
SEE NOTE #1 LS1 LS2

OR OR OR OR L2
L1 L1 L2

DISC

DISC
CB CB RELAY 1
6 2
GND L2 L1
CB 8 4
LS2 HTR2 BLK 1 0
YEL BLK 60A 60A
8 6 REC
YEL RELAY 1 BLK RELAY 1
LS1 HTR1 BLK 22 VDC COIL
4 2
LEGEND
BLU REC CB CIRCUIT BREAKER
YEL FU LINE FUSE
BLK ORN VIO PLUG 2
GND EQUIPMENT GROUND
9 11 7 3 2
HTR HEATER
REC RECTIFIER
NOTES: TDR TIME DELAY RECITFIER
1. Use Copper Wire (75ºc Min) Only Between Disconnect Switch And Unit. FIELD POWER WIRING
2. To Be Wired In Accordance With Nec And Local Codes.
MARKED TERMINAL
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, Use The Same Or
PLUG AND RECEPTACLE
Equivalent Type Wire.
4. Use 60 Amp class K Fuses Only, For Replacement.
LABEL ( 3 ) 328613-101 REV. B

Fig. 1 -- 328613--101
A07001

SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 5.1 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC
HTR1 HTR3 HTR2
FOR VOLTS & HERTZ
LS1 LS3 LS2
GND SEE NOTE #1
BLU
L1 L3 L2 RELAY 1 RELAY 2
HTR1 BLK RELAY 2 BLK 6 2 6 2
YEL LS1
4 2
YEL BLU
BLU 8 4
RELAY 2 8 4
LS2 HTR2 BLU
8 6 1 0 1 0
YEL RELAY 1 REC REC
LS3 HTR3 BLK
BLU 2 RELAY 2
4 22 VDC COILFOR 3 PHASE WIRING
Denotes wire to be moved for 3 phase
YEL RELAY 1 conversion. Dashed wire (- - -) indicates
BLU 22 VDC COIL REC
wiring after conversion.
BLK 1. Disconnect BLUE wire from limit switch
IDR REC RED BRN 3(LS3), cut, strip, and connect to field wire L3.
YEL BLU BLK 2. Disconnect YELLOW wire from LS1 and
ORN ORN ORN VIO connect to LS3.
PLUG 2
3. Disconnect BLUE wire from relay 2 terminal
9 11 7 5 8 3 2 1 4
2 and connect to LS1.
NOTES: LEGEND
1. Use Copper Wire (75ºc Min) Only Between Disconnect Switch
And Unit. GND EQUIPMENT GROUND REC RECITFIER
2. To Be Wired In Accordance With Nec And Local Codes. HTR HEATER FIELD POWER WIRING
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, IDR IDENTIFIER RESISTOR MARKED TERMINAL
Use The Same Or Equivalent Type Wire. PLUG AND RECEPTACLE
4. Use 60 Amp class K Fuses Only, For Replacement.
LABEL (3) 328606-101 REV. B

Fig. 2 -- 328606--101

A07002

3
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 3.4 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC
FOR VOLTS & HERTZ HTR1 HTR3 HTR2
SEE NOTE #1
LS1 LS3 LS2
L1 L3 L1 L3 GND L4 L2 L4 L2

FU1

FU3
CB1 CB2

FU2
CB2 CB1

FU4
INTERNAL PROTECTION RELAY 1
MAY BE EITHER FUSES OR
CIRCUIT BREAKERS L4 L3 L2 L1 6 2
CB1 CB2
HTR2 RELAY 2
LS2 60A 60A 60A 60A
YEL BLK 4 2 BLK 8 4
L4 FU4
YEL LS1 HTR1 RELAY 2 L2 FU2 1 0
BLK 8 6 BLK REC
L1 FU1
YEL RELAY 1 L3 FU3 RELAY 2
HTR3
LS3
BLK 4 2 BLK 6 2
BLU RELAY 2
BLK RELAY 1 22 VDC COIL
22 VDC COIL 8 4
IDR TDR 1 0
YEL BLU BLK REC TDR
PLUG 2 GRY GRY ORN VIO RED BRN
LEGEND
9 11 7 5 8 3 2 6 4 CB CIRCUIT BREAKER
NOTES: FU LINE FUSE
REC RECITFIER GND EQUIPMENT GROUND
1. Use Copper Wire (75°c Min) Only Between Disconnect Switch
TDR TIME DELAY RECITFIER HTR HEATER
And Unit.
2. To Be Wired In Accordance With Nec And Local Codes. FIELD POWER WIRING IDR IDENTIFIER RESISTOR
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, MARKED TERMINAL
Use The Same Or Equivalent Type Wire. PLUG AND RECEPTACLE
4. Use 60 Amp Class K Fuses Only, For Replacement. LABEL (3) 328605-101 REV. B

Fig. 3 -- 328605--101
A07003

SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 5.1 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR3 HTR2
FOR VOLTS & HERTZ
SEE NOTE #1 LS1 LS 3 LS2
& 4
L1 L3 L1 L3 GND L4 L2 L4 L2

HTR4
FU1

FU3

CB1 CB2
FU2

CB2 CB1
FU4

INTERNAL PROTECTION
MAY BE EITHER FUSES OR
CIRCUIT BREAKERS
RELAY 3 L4 L3 L2 L1 RELAY 2
YEL LS3 HTR3 BLK BLK
4 2 CB1 CB2 6 2
YEL RELAY 2 60A 60A 60A 60A
YEL LS2 HTR2 BLK BLK
4 2 RELAY 2 L4 FU4
YEL 8 4
LS1 HTR1 BLK RELAY 2 22 VDC COIL L2 FU2
BLK 1 0
8 6 L1 FU1
RELAY 1 TDR
YEL LS4 HTR4 BLK BLK TDR L3 FU3
4 2 RELAY 1 RELAY 3
YEL RELAY 3
BLU RELAY 1 22 VDC COIL 6 2 6 2
BLK 22 VDC COIL RED BRN
IDR REC 8 4 8 4
REC 1 0 1 0
YEL BLU BLK GRY BRN
PLUG 2 BLU BLU ORN VIO REC REC
9 11 7 5 8 3 2 6 1 4 LEGEND
NOTES: IDR IDENTIFIER RESISTOR CB CIRCUIT BREAKER
1. Use Copper Wire (75°c Min) Only Between Disconnect Switch REC RECITFIER FU LINE FUSE
And Unit. TDR TIME DELAY RECITFIER GND EQUIPMENT GROUND
2. To Be Wired In Accordance With Nec And Local Codes.
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, FIELD POWER WIRING HVTB HIGH VOLTAGE
Use The Same Or Equivalent Type Wire. MARKED TERMINAL TERM. BLOCK
4. 1 Phase Heaters Are Shown Wired For Single Supply Circuit. PLUG AND RECEPTACLE HTR HEATER
5. Use 60 Amp Class K Fuses Only, For Replacement.
LABEL (3) 328604-101 REV. A

Fig. 4 -- 328604--101
A07004

4
SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 3.4 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC
FOR VOLTS & HERTZ HTR1 HTR3 HTR2
SEE NOTE #1
GND LS1 LS3 LS2
L1 L3 L2
BLU
HTR3 BLK RELAY 2
YEL LS3 BLK RELAY 1 RELAY 2
8 6
BLK 6 2 6 2
BLU
HTR2 BLK RELAY 2
LS2 BLU
4 2 8 4 8 4
YEL RELAY 1
LS1 HTR1 BLK BLK 1 0 1 0
4 2 REC TDR
RELAY 2
BLU 22 VDC COIL LEGEND
BLK GND EQUIPMENT GROUND
RELAY 1
22 VDC COIL TDR HTR HEATER
REC RECITIFIER
TDR TIME DELAY RECITIFIER
REC RED BRN FIELD POWER WIRING
YEL BLU BLK ORN VIO
PLUG 2 MARKED TERMINAL
9 11 7 3 2 6 4 PLUG AND RECEPTACLE

NOTES:
1. Use Copper Wire (75ºc Min) Only Between Disconnect Switch And Unit.
2. To Be Wired In Accordance With Nec And Local Codes.
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, Use The Same Or Equivalent Type Wire.
4. Use 60 Amp class K Fuses Only, For Replacement.
LABEL ( 3 ) 328614-101 REV. B

Fig. 5 -- 328614--101
A07005

SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 5.1 COMPONENT ARRANGEMENT

FIELD POWER WIRING SEE RATING PLATE HTR1 HTR4 HTR3 HTR2
DISCONNECT PER NEC
HVTB FOR VOLTS & HERTZ
GND SEE NOTE #1 LS 1 LS 4 LS 2
& 6 & 3 & 5

L1 BLU
L3 L2 HTR6 HTR5
YEL LS6 HTR6 BLU BLU BLK RELAY 2
YEL 8 6 6 2

YEL LS5 HTR5 BLK RELAY 3 BLK


4 2 8 4
HTR4 BLK
1 0
BLU LS4 BLK RELAY 2 TDR
8 6 22 VDC COIL RELAY 1 RELAY 3
RELAY 2
YEL LS3 HTR3 BLU BLU 6 2 6 2
4 2 TDR
YEL LS2 HTR2 BLK BLK RELAY 3 8 4 8 4
8 6 RELAY 1 22 VDC COIL
22 VDC COIL
RED BRN 1 0 1 0
RELAY 1 REC TDR
BLU LS1 HTR1 BLK BLK TDR
4 2 LEGEND
REC
YEL GRY BRN GND EQUIPMENT GROUND
BLU BLK ORN VIO
PLUG 2 HVTB HIGH VOLTAGE
9 11 7 3 2 6 1 4 TERM. BLOCK
NOTES: HTR HEATER
1. Use Copper Wire (75ºc Min) Only Between Disconnect Switch And Unit. REC RECITFIER
TDR TIME DELAY RECITFIER
2. To Be Wired In Accordance With Nec And Local Codes.
FIELD POWER WIRING
3. If Any Of The Original Wire, As Supplied, Must Be Replaced,
MARKED TERMINAL
Use The Same Or Equivalent Type Wire. PLUG AND RECEPTACLE
4. 1 Phase Heaters Are Shown Wired For Single Supply Circuit.
5. Use 60 Amp Class K Fuses Only, For Replacement. LABEL ( 3 ) 328615-101 REV. A

Fig. 6 -- 328615--101
A07006

5
30KW 1PH SCHEMATIC DIAGRAM HEATER VA: 5.1 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR4 HTR3 HTR2
HVTB FOR VOLTS & HERTZ
GND LS 1 LS 4
SEE NOTE #1 LS 2
& 6 & 3 & 5
L1 L2

YEL HTR 6 BLK HTR6 HTR5


YEL LS 6 BLK BLK
FU5 8 6 FU6 HVTB
HTR 5 RELAY 3 L5 FU5 RELAY 2
YEL LS 5 BLK L3 FU3
4 2 BLK 6 2
L1 FU1
YEL HTR 4 L1 L2 L3
YEL LS 4 BLK BLK FU4 BLK L6 FU6
FU3 8 6 8 4
RELAY 2 L4 FU4
YEL LS 3
HTR 3
BLK
RELAY 2
22 VDC COIL L2 FU2 1 0
4 2 BLK TDR
YEL
RELAY 1 RELAY 3
YEL LS 2 HTR 2 BLK BLK FU2 BLK TDR
FU1 8 6 6 2 6 2
RELAY 3
RELAY 1 RELAY 1
YEL LS 1 HTR 1 BLK 22 VDC COIL
4 2 BLK 22 VDC COIL 8 4 8 4
YEL RED BRN
BLU 1 0 1 0
BLK TDR
REC REC TDR
YEL BLU BLK
WHT or PNK IDR WHT or PNK ORN BRN
PLUG 2
VIO GRY LEGEND
9 11 7 5 8 3 2 6 1 4 CB CIRCUIT BREAKER
FU LINE FUSE
NOTES: REC RECITFIER GND EQUIPMENT GROUND
1. Use Copper Wire (75º c Min) Only Between Disconnect Switch And Unit. TDR TIME DELAY RECITFIER HVTB HIGH VOLTAGE
2. To Be Wired In Accordance With NEC And Local Codes. TERM. BLOCK
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, Use The FIELD POWER WIRING
HTR HEATER
Same Or Equivalent Type Wire. MARKED TERMINAL
IDR IDENTIFIER RESISTOR
4. 1 Phase Heaters Are Shown Wired For Single Supply circuit. PLUG AND RECEPTACLE
5. Use 60 Amp Class K Fuses Only, For Replacement.
LABEL (3) - 1 PHASE 328603-101 REV. A

Fig. 7 -- 328603--101
A07007

SCHEMATIC DIAGRAM SINGLE SUPPLY CIRCUIT HEATER VA: 5.1 COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR4 HTR3 HTR2
HVTB FOR VOLTS & HERTZ
GND
SEE NOTE #1 LS 1 LS 4 LS 2
& 6 & 3 & 5
L1 YEL BLK L2
L3

YEL LS6 HTR6 BLK BLK HTR6 HTR5


FU5 8 6 FU6
HVTB
L5 FU5
YEL LS5 HTR5 BLK RELAY 3 BLK RELAY 2
2 L3 FU3
4 6 2
L1 FU1
HTR4 BLK BLK BLK L1 L2 L3
YEL LS4 L6 FU6
FU3 8 6 FU4
RELAY 2 L4 FU4 8 4
RELAY 2 22 VDC COIL L2 FU2
YEL LS3 HTR3 BLK BLK 1 0
4 2 TDR
YEL LS2 HTR2 BLK BLK BLK TDR RELAY 1 RELAY 3
YEL 8 6 FU2
FU1 RELAY 3 6 2 6 2
RELAY 1 RELAY 1 22 VDC COIL
YEL LS1 HTR1 BLK BLK 22 VDC COIL RED
BRN
4 2
TDR 8 4 8 4

YEL REC BRN 1 0 1 0


BLU BLK GRY TDR
PLUG 2 WHT or PNK IDR WHT or PNK ORN VIO REC

9 11 7 5 8 3 2 6 1 4 LEGEND
NOTES: FU LINE FUSE
REC RECITFIER GND EQUIPMENT GROUND
1. Use Copper Wire (75°c Min) Only Between Disconnect Switch
And Unit. TDR TIME DELAY RECITFIER HVTB HIGH VOLTAGE
2. To Be Wired In Accordance With Nec And Local Codes. FIELD POWER WIRING TERM. BLOCK
3. If Any Of The Original Wire, As Supplied, Must Be Replaced, MARKED TERMINAL
Use The Same Or Equivalent Type Wire. HTR HEATER
4. 1 Phase Heaters Are Shown Wired For Single Supply Circuit. PLUG AND RECEPTACLE IDR IDENTIFIER RESISTOR
5. Use 60 Amp Class K Fuses Only, For Replacement.
LABEL (3) - 3 PHASE 328602-101 REV. A

A07038
Fig. 8 -- 328602--101

6
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
BLOWER MOTOR
ROTATION ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE

SCHEMATIC DIAGRAM COMPONENT ARRANGEMENT

FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR2
FOR VOLTS & HERTZ
SEE NOTE #1 LS1 LS2
R1
OR OR OR OR
SYSTEM TRANSFORMER: 40.0VA
L1 L2 L2
L1 FAN COIL/HEATER: 8.4VA

DISC

DISC
REMAINING VA AVAILABLE: 31.6VA
CB CB

GND RELAY 1 COM


YEL BLK RED

TRAN
LS2 HTR2 6 2 24 V
BLK 208 V
8 6
BRN 230 V
YEL RELAY 1 BLK
LS1 HTR1 BLK 8 4
4 2
1 0
BLU REC
BLK RELAY 1
DIE CUT DIE CUT
.50" 1" X 1/2" 22 VDC COIL 1" X 1/2" .50"
AS SHOWN AS SHOWN
GND
YEL REC
BLU BLK
ORN VIO L2 L1

R G T C C C
PLUG CB2
9 11 7 3 2 6 1 4
9 11 7 3 2 60A 60A
6 1 4
RECP BRN F
BLU BLK

NC
R G T C C C

SPT NC PCB NO
FR
W2

W3
E
NO SPT
FR
F RED-LOW BRN
BLU-MED FM
BRN
WHT

VIO
PCB BLU BLK-HI CAP

GRY
GND YEL-COM
BRN
RED

BLK GRN/YEL-GND
YEL SEE NOTE #5
RED

208 V 230 V FAN MOTOR THERMALLY PROTECTED


COM C
W2 G LEGEND
R WHT CB CIRCUIT BREAKER HTR HEATER
COM CAP CAPACITOR LS LIMIT SWITCH
BRN

BRN BRN RED BARRIER SEE NOTE #7


COM COMMON LOW MARKED
TRAN VOLTAGE TERMINAL
YEL BRN INDOOR OUTDOOR
HI BLK THERMOSTAT UNIT F FUSE PLUG AND
FM FM FAN MOTOR RECEPTACLE
MED BLU FIELD POWER PRINTED CIRCUIT
PCB BOARD
GRN/YEL WIRING
LO RED GND FR PCB FAN RELAY REC RECTIFIER
LINE FUSE R RELAY
FU
EQUIPMENT TRAN TRANSFORMER
NOTES: GND GROUND UNMARKED
1. Use copper wire (75*C min.) only between disconnect switch and unit. SPT FAN SPEED TAP TERMINAL
2. To be wired in accordance with N.E.C. and local codes. LOCATION
3. If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
MINIMUM MOTOR SPEED SELECTION
4. Replace low voltage fuse with no greater than 5 amp fuse.
FAN COIL SIZE 018 024 030 036 042 048 060 070
5. (3) speed motor shown. Optional (2) speed motor uses HI (BLK) and LOW (BLU or RED).
6. Smaller heaters will have fewer components. MOTOR SPEED ONE HTR LO LO LO LO -- -- -- --
7. Connect R to R, G to G, etc., see outdoor instruction for details. 328205-101 REV. A MOTOR SPEED TWO HTR LO LO LO LO LO LO LO LO

Fig. 9 -- 328205--101
A07008

7
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
BLOWER MOTOR
ROTATION ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE

SCHEMATIC DIAGRAM COMPONENT ARRANGEMENT

FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC


FOR VOLTS & HERTZ HTR1 HTR3 HTR2
SEE NOTE #1 LS1 LS3 LS2
R1 R2
GND
L1 L3 L1 L3 L4 L2 L4 L2 SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 11.8VA
INTERNAL PROTECTION REMAINING VA AVAILABLE: 28.2VA
CB1 CB2 MAY BE EITHER FUSES OR CB2 CB1

FU2
FU3
FU1

FU4
CIRCUIT BREAKERS
COM
RED

TRAN
L4 L3 L2 L1
RELAY 2 CB1 CB2 24 V 208 V
YEL LS2 HTR2 BLK BLK
4 2 60A 60A 60A 60A BRN 230 V
YEL
RELAY 2
YEL LS1 HTR1 BLK BLK
8 6
LS3 HTR3 BLK RELAY 1
BLK RELAY 1
4 2
DIE CUT YEL 6 2 DIE CUT
BLU BLK RELAY 1 RELAY 2
1" X 1/2" 22 VDC COIL GND 1" X 1/2"
.50" 22 VDC COIL .50"
AS SHOWN 8 4 AS SHOWN
REC TDR 1 0
REC
ORN VIO

R G T C C C
YEL BLU BLK RED BRN RELAY 2
PLUG
9 11 7 3 2 4 6 2
6 1
9 11 7 3 2 6 1 4
RECP 8 4
BRN F
1 0
BLU BLK TDR

NC
L4 FU4
R G T C C C

SPT NC L2 FU2 PCB NO


L1 FU1 FR
L3
W2

W3
FU3
E
NO SPT
FR
F RED-LOW BRN
FM
BLU-MED
WHT

VIO

PCB BRN
BLU

GRY

GND BLK-HI CAP


YEL-COM
BRN
RED

BLK
GRN/YEL-GND
YEL
RED

208 V SEE NOTE #6 FAN MOTOR THERMALLY PROTECTED


COM 230 V
C
R WHT W2 G
LEGEND
COM
BRN

BRN BRN RED BARRIER SEE NOTE #7 CB CIRCUIT BREAKER HTR HEATER
TRAN CAP CAPACITOR LS LIMIT SWITCH
YEL BRN INDOOR OUTDOOR COMMON LOW MARKED
COM TERMINAL
HI BLK THERMOSTAT UNIT VOLTAGE
F FUSE PLUG AND
MED FM RECEPTACLE
BLU FM FAN MOTOR
GRN/YEL FIELD POWER PCB PRINTED CIRCUIT
LO RED GND BOARD
WIRING REC RECTIFIER
FR PCB FAN RELAY R RELAY
NOTES: LINE FUSE
FU TRAN TRANSFORMER
1. Use copper wire (75*C min.) only between disconnect switch and unit. EQUIPMENT UNMARKED
2. To be wired in accordance with N.E.C. and local codes. GND GROUND TERMINAL
3. If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire. SPT FAN SPEED TAP TDR TIME DELAY
4. Replace low voltage fuse with no greater than 5 amp fuse. LOCATION RECTIFIER
5. Use 60 amp class K fuses only, for replacement.
6. (3) speed motor shown. Optional (2) speed motor uses HI (BLK) and LOW (BLU or RED). MINIMUM MOTOR SPEED SELECTION
7. Connect R to R, G to G, etc., see outdoor instruction for details. FAN COIL SIZE 018 024 030 036 042 048 060 070
8. If wire crimp is removed an emergency heat relay is required. (See outdoor-thermostat instructions).
328206-101 REV. A MOTOR SPEED AT 15 KW -- MED LO LO LO LO LO LO

Fig. 10 -- 328206--101
A07009

8
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
BLOWER MOTOR
ROTATION ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE

SCHEMATIC DIAGRAM COMPONENT ARRANGEMENT

FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC HTR1 HTR2
FOR VOLTS & HERTZ
SEE NOTE #1 LS1 LS2
R1
OR OR OR OR
SYSTEM TRANSFORMER: 40.0VA
L1 L2 L2
L1 FAN COIL/HEATER: 8.4VA

DISC

DISC
REMAINING VA AVAILABLE: 31.6VA
CB CB

GND RELAY 1 COM


YEL BLK RED

TRAN
LS2 HTR2 6 2 24 V
BLK 208 V
8 6
BRN 230 V
YEL RELAY 1 BLK
LS1 HTR1 BLK 8 4
4 2
1 0
BLU REC
BLK RELAY 1
DIE CUT DIE CUT
1" X 1/2" 22 VDC COIL 1" X 1/2"
.50" .50"
AS SHOWN AS SHOWN
GND
YEL REC
BLU BLK
ORN VIO L2 L1
PLUG CB2 PLUG 1
9 11 7 4 3 2 6 1

1
9 11 7 3 2 60A 60A
4 6 1
RECP F

W3
WHT

W2

6
BRN

BLU
VIO
WHT
BLU RESISTOR PCB

GRY
SPT
YEL
FUSE
BRN

RED

BRN - C
208 V WHT BLK - L
230 V

FM
COM

RED

C R W G YEL - N BLU - 2
GND
THERMOSTAT GRN/YEL - GND
EL CONNECTION
N/Y TRAN
GR BRN
SPEED TAP LEGEND
SELECTION
SEE NOTE #5
GRN/YEL
WHT
BLU

1 LOW CB CIRCUIT BREAKER HTR HEATER


BRN

YEL
BLK

LS LIMIT SWITCH
2 MEDIUM
COM COMMON LOW MARKED
3 HIGH VOLTAGE TERMINAL
1 2 3 4 5 C L G N 4 NOT USED F FUSE PLUG AND
Speed Tap Power FM FAN MOTOR RECEPTACLE
Connections Connections 5 NOT USED FIELD POWER PRINTED CIRCUIT
WIRING PCB BOARD
Motor Connections
REC RECTIFIER
LINE FUSE R RELAY
NOTES: 1. Use copper wire (75ºC min.) only between disconnect switch and unit. FU EQUIPMENT TRAN TRANSFORMER
2. To be wired in accordance with N.E.C. and local codes. GND GROUND UNMARKED
3. If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
4. Replace low voltage fuse with no greater than 5 amp fuse. SPT FAN SPEED TAP TERMINAL
LOCATION
5. To change speed tap, move blue wire to desired terminal.
6. Smaller heaters will have fewer components.
7. Connect R to R, G to G, etc., see outdoor instruction for details. 335975-101 REV. A

Fig. 11 -- 335975--101
A12359

9
Fig. 12 -- 336923--101
A12360

10
A12361
Fig. 13 -- 337518--101

11
A12362
Fig. 14 -- 338001--101

12
A07029
Fig. 15 -- 326014--101

13
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING CAUTION: AT TENTION:
BLOWER MOTOR NOT SUITABLE FOR USE NE CONVIENT PAS A UX
ROTATION ON SYSTEMS EXCEEDING INSTALLATIONS DE PLUS DE
150V TO GROUND 150 V A L A TERRE
COOLING CONTROL ONLY COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC COM RED
FOR VOLTS & HERTZ 24 V
208 V TRAN
SEE NOTE #1 230 V BRN
L2
L1 GND PCB
YEL BLK
PLUG 2 STATUS
9 11 7 3 2 6 1 4 GND
COMM
9 11 7 8 5 3 2 6 1 4
RECP 2 RED ECM
BLK BLU BRN
YEL BLU BRN
VIO RED

COM RED
PCB MOTOR
TRAN
24 V

SYSTEM COMM.
SEC2 SEC1 SYSTEM TRANSFORMER: 40.0 VA

OAT A B C D
YEL 230 V
BRN F FAN COIL: 4.0 VA
BLK U REMAINING VA AVAILABLE: 36.0 VA
PLUG 5 S
E
PLUG 3 BRN 5 NOTES:
RED 4 1. Use Copper Wire (75ºC Min) Only Between
1 2 3 4 5
VIO 3 Disconnect Switch And Unit.

NON-COMMUNICATING
GRN/YEL BLU 2 2. To Be Wired In Accordance With N.E.C.
GND BLU 1 HUM C O Y W G R And Local Codes.

OUTDOOR UNIT
PLUG 1 3. If Any Of The Original Wire, As Supplied,
RECP 4
RECP 3

Must Be Replaced, Use The Same Or


YEL BLU 4 3 2 1
CL5 Equivalent Type Wire.
OPN 4. Replace Low Voltage Fuse With No
ECM
BLU
YEL

1 2 3 4 COM Greater Than 5 Amp Fuse.


RED
GRN

5. For Use With Communicating Thermostat


Only, Connect A To A, B To B, Etc.
RED GRN 6. Communicating Outdoor Units Connect
A To A, B To B, Etc.
7. Non - Communicating Outdoor Units
TROUBLE SHOOTING INFORMATION: Connect R To R, Y To Y, Etc.
MOTOR LED MOTOR FAULT / ACTION LEGEND
F
OFF NOT RUNNING NONE - CHECK STATUS LED
FIELD POWER WIRING
OFF RUNNING MOTOR
MARKED TERMINAL
ON (FLASHING) NOT RUNNING MOTOR / HARNESS
PLUG AND RECEPTACLE
ON (FLASHING) RUNNING NONE
COM COMMON
GND EQUIPMENT GROUND
STATUS LED FAULT / ACTION
ECM FAN MOTOR
ON NONE - STANDBY MODE
OAT OUTDOOR AIR THERMISTOR
OFF NO LOW VOLTAGE OR CONTROL - CHECK POWER AND FUSE
PCB PRINTED CIRCUIT BOARD
16 NO SYSTEM COMMUNICATIONS - CHECK WIRING
RECP RECEPTACLE
OTHER REFER TO SERVICE SCREENS ON USER INTERFACE OR THE
TRAN TRANSFORMER
FAN COIL TROUBLESHOOTING GUIDE
333107-101 REV. B
A12363
Fig. 16 -- 333107--101

14
NOTES
1. Use Copper Wire (75ºC Min) Only
Between Disconnect Switch And Unit.
2. To Be Wired In Accordance With NEC
And Local Codes.
3. If Any Of The Original Wire, As
Supplied, Must Be Replaced, Use The
Same Or Equivalent Type Wire.
4. Replace Low Voltage Fuse With No
Greater Than 5 Amp Fuse.
5. (3) Speed Motor Shown Optional (2)
Speed Motor Uses HI (BLK) And LOW
(BLUE or RED).
6. Connect R To R, G To G, Etc. See
Outdoor Instruction For Details. 328964-101 REV. A
A07027
Fig. 17 -- 328964--101

15
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
BLOWER MOTOR
ROTATION

COOLING CONTROL ONLY


COMPONENT ARRANGEMENT
FIELD POWER WIRING SEE RATING PLATE DISCONNECT PER NEC
FOR VOLTS & HERTZ
SEE NOTE #1 COM
L1 GND L2 24 V
208 V TRAN
BLK
YEL 230 V
PLUG
9 11 7 4 3 2 6 1 SYSTEM TRANSFORMER: 40.0 VA
9 11 7 4 3 2 6 1 FAN COIL: 5.0 VA
RECP REMAINING VA AVAILABLE: 35.0 VA

W3
W2
WHT

E
BRN

BLU
WHT

VIO
BLU GND
RESISTOR

GRY
YEL
FUSE

BRN

RED
BRN - C
WHT
208 V BLK - L FM
230 V

BLU - 2
COM

RED

C R W G YEL - N
WH
THERMOSTAT GRN/YEL - GND T-4
EL CONNECTION
RN/Y TRAN
G BRN

SPEED TAP LEGEND


GRN/YEL
WHT
BLU

SELECTION
SEE NOTE #6
BRN

YEL
BLK

1 LOW C COMMON
C L G N
2 MEDIUM F LOW VOLTAGE FUSE
1 2 3 4 5
Speed Tap Power
3 HIGH FM FAN MOTOR
Connections Connections 4 ELEC HEAT
Motor Connections GND EQUIPMENT GROUND
5 SEE NOTE 7
RECP RECEPTACLE
NOTES
SPT FAN SPEED TAP LOCATION
1. Use Copper Wire (75ºC Min) Only Between Disconnect Switch And
Unit. TRAN TRANSFORMER
2. To Be Wired In Accordance With NEC And Local Codes. UNMARKED TERMINAL
3. If Any Of The Original Wire, As Supplied, Must Be Replaced. Use FIELD POWER WIRING
The Same Or Equivalent Type Wire.
4. Replace Low Voltage Fuse With No Greater Than 5 Amp Fuse. MARKED TERMINAL
5. Connect R To R, G To G, Etc. See Outdoor Instruction For Details. PLUG AND RECEPTACLE
6. To change speed tap, move blue wire to desired terminal.
7. See airflow tables for tap usage. 336228-101 REV. A

A12364
Fig. 18 -- 336228--101

16
A12365
Fig. 19 -- 337519--101

17
SCHEMATIC DIAGRAM CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
SEE RATING PLATE FOR VOLTS & HERTZ ATTENTION:
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150 V A LA TERRE
FIELD POWER WIRING
COOLING CONTROLS
COMPONENT ARRANGEMENT
ELECTRIC HEAT

L1 L1 SEE NOTE #1
L2 L2
DISCONNECT PER NEC LS LS

SEE NOTE #8
HTR HTR
SEE NOTE #8

SYSTEM TRANSFORMER 40.0 VA


DISC

DISC

DISC
FAN COIL/HEATER: 8.4 VA

DISC
GND
REMAINING VA AVAILABLE: 31.6VA
SEE NOTE #6 COM
YEL YEL RELAY 1 RED

TRAN
BLK
8 6 24V 208V
LS2 HTR2 BLK
BLK 2
8 6 4 BRN 230V
YEL RELAY 1 BLK 1
LS1 HTR1 BLK
4 2 REC C
T1 F
R
YEL BLU G
BLK RELAY 1
22 VDC COIL L2 L1
NC
DISC PC8 NO
BLU REC 60A 60A FR
BLK BLK GND SPT
VIO
SPT ORN RED- LOW
NC BRN
G GRY FM CAP
NO R RED BRN
YEL FR GND BLK-HI
F
YEL PCB T1 ORN GRN/YEL-GND YEL-COM
BLK

C GRY
RED SEE NOTE #5
YEL VIO
BRN FAN MOTOR THERMALLY PROTECTED
CAP COM 208V 230V
COM LEGEND
BRN BRN C R W G CAP CAPACITOR
YEL RED COM COMMON
HI BLK DISC DISCONNECT
FM TRAN BARRIER SEE NOTE#7
F FUSE
BRN
LO RED GRN/YEL INDOOR OUTDOOR FM FAN MOTOR
GND THERMOSTAT UNIT FIELD POWER WIRING
NOTES FR PCB FAN RELAY
GND EQUIPMENT GROUND
1. Use copper wire (75oc min) only between disconnect switch and unit HTR HEATER
2. To be wired in accordance with nec and local codes.
LS LIMIT SWITCH
3. If any of the original wire, as supplied, must be replaced, use the same
or equivalent type wire. MARKED TERMINAL
4. Replace low voltage fuse with no greater than 5 AMP fuse. PLUG AND RECEPTACLE
5. (2) Speed Motor uses HI (BLK) and LOW (RED). PCB PRINTED CIRCUIT BOARD
6. Smaller heaters will have fewer components. REC RECTIFIER
7. Connect R to R, G to G, etc.., see outdoor instructions for details. SPT FAN SPEED TAP LOCATION
8. Cooling controls wiring not used with electric heaters. TRAN TRANSFORMER
UNMARKED TERMIINAL
This compartment must be closed except MINIMUM MOTOR SPEED SELECTION
when servicing FAN COIL SIZE 018 024 030
MOTOR SPEED ONE HTR LO LO LO
ROTATION
324494-101 REV.A MOTOR SPEED TWO HTR LO LO LO

Fig. 20 -- 324494--101

A00163

18
A09212
Fig. 21 -- 335826--101

19
Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 08/12 Catalog No: WD---FANCOIL---01