Professional Documents
Culture Documents
Switchgear and Protection Net
Switchgear and Protection Net
Electrical Faults
Open circuit faults are also called as series faults. These are
unsymmetrical or unbalanced type of faults except three phase open
fault.
Thus, single and two phase open conditions can produce the
unbalance of the power system voltages and currents that causes great
damage to the equipments.
Causes
Broken conductor and malfunctioning of circuit breaker in one or
more phases.
Effects
These are the most common and severe kind of faults, resulting in the
flow of abnormal high currents through the equipment or transmission
lines. If these faults are allowed to persist even for a short period, it
leads to the extensive damage to the equipment.
Short circuit faults are also called as shunt faults. These faults are
caused due to the insulation failure between phase conductors or
between earth and phase conductors or both.
The various possible short circuit fault conditions include three phase
to earth, three phase clear of earth, phase to phase, single phase to
earth, two phase to earth and phase to phase plus single phase to earth
as shown in figure.
The three phase fault clear of earth and three phase fault to earth are
balanced or symmetrical short circuit faults while other remaining
faults are unsymmetrical faults.
Causes
These may be due to internal or external effects
Symmetrical Faults
A symmetrical fault gives rise to symmetrical fault currents that are
displaced with 1200 each other. Symmetrical fault is also called as
balanced fault. This fault occurs when all the three phases are
simultaneously short circuited.
These faults rarely occur in practice as compared with unsymmetrical
faults. Two kinds of symmetrical faults include line to line to line (L-
L-L) and line to line to line to ground (L-L-L-G) as shown in figure
below.
Unsymmetrical Faults
The most common faults that occur in the power system network are
unsymmetrical faults. This kind of fault gives rise to unsymmetrical
fault currents (having different magnitudes with unequal phase
displacement). These faults are also called as unbalanced faults as it
causes unbalanced currents in the system.
Up to the above discussion, unsymmetrical faults include both open
circuit faults (single and two phase open condition) and short circuit
faults (excluding L-L-L-G and L-L-L).
A line to line fault occur when a live conductor get in contact with
other live conductor. Heavy winds are the major cause for this fault
during which swinging of overhead conductors may touch together.
These are less severe faults and its occurrence range may be between
15-20%.
In double line to ground faults, two lines come into the contact with
each other as well as with ground. These are severe faults and the
occurrence these faults is about 10% when compared with total
system faults.
"A current limiting reactor, also called a series reactor, is a coil which
has high inductive reactance as compared to its resistance."
These reactors are used to limit the short circuit current and the effect
of resulting voltage disturbances during fault conditions. The short
circuit currents depend upon the generating capacity, voltage at the
fault point and the total reactance between the generators and the fault
point.
The short circuit current can be kept within safe limits by increasing
the reactance between the source and the fault. Thus, there is a need
of providing a protective reactor. By including a reactor or few
reactors at strategic locations, the short circuit currents at different
points in the power system can be reduced.
Drawbacks of Reactors:
The main drawbacks of a reactor are:
1. The total percentage reactance of the system is increased, thus
causing an increase in the reactive voltage drop.
2. The power factor is decreased.
The tie-bar system is better and more flexible than the ring system. In
this system, the generators are connected to the common bus-bar (tie-
bar) through the reactors but the feeders are fed from the generator
side of the reactors
In the ring system the short circuit current due to a fault on any bus
bar section, is fed from the generators connected to other sections
through one reactor, whereas in the tie-bar system the current flows
through two reactors in series. Therefore this system requires only
half the reactance compared to the ring system.
In the tie-bar system, the short circuit MVA or the short circuit
current is independent of the number of bus-bar sections. Thus, extra
generators may be added to the system without addition of extra
circuit breakers or without increasing the existing reactance.
Important Elements for Power System Protection
Switchgear
Consists of mainly bulk oil circuit breaker, minimum oil circuit
breaker, SF6 circuit breaker, air blast circuit breaker and vacuum
circuit breaker etc. Different operating mechanisms such as solenoid,
spring, pneumatic, hydraulic etc. are employed in the circuit breaker.
Circuit breaker is the main part of protection system in power system
and it automatically isolate the faulty portion of the system by
opening its contacts.
Protective Gear
Consists of mainly power system protection relays like current relays,
voltage relays, impedance relays, power relays, frequency relays, etc.
based on operating parameter, definite time relays, inverse time
relays, stepped relays etc. as per operating characteristic, logic wise
such as differential relays, over fluxing relays etc. During fault the
protection relay gives trip signal to the associated circuit breaker for
opening its contacts.
Station Battery
All the circuit breakers of electrical power system are DC (Direct
Current) operated. Because DC power can be stored in battery and if
situation comes when total failure of incoming power occurs, still the
circuit breakers can be operated for restoring the situation by the
power of storage station battery. Hence, the battery is another
essential item of the power system. Some time it is referred as the
heart of the electrical substation. An electrical substation battery or
simply a station battery containing a number of cells accumulate
energy during the period of availability of AC supply and discharge at
the time when relays operate so that relevant circuit breaker is tripped
at the time failure of incoming AC power.
Back-up protection
As shown in below fig, each line associated with over current relay
that protect the lines from faults. So, if a fault happens on any line, it
will be cleared by its relay and circuit breaker.
The service record of primary relaying is very high with well over
90% of all operations being correct.
But this is not always the case, sometimes faults are not illuminated
by the primary or main protection system i.e. circuit breaker and relay
system because of trouble within the relays, circuit breakers or wiring
system in different conditions.
Secondary Protection
Relay Back-up
Same breaker is used by both main and back-up protection, but the
protective systems are different. Separate trip coils may be provided
for the same breaker.
Breaker Back-up
Different breakers are provided for main and back-up protection,
both the breakers being in the same station
Remote back-up
The main and back-up protections provided at different stations and
are completely independent.