Setup manual for electro hydraulic proportional controls for axial piston pumps, PV family
Contents
1. Table of available electro hydraulical controls ...................................................................3
2. Proportional displacement control, code …FDV (old: FPV) ................................................3
3. Proportional displacement control with pressure compensation,
codes ...UDR, ...UDK (old: UPR, UPK) .............................................................................6
4. Proportional displacement control with closed loop pressure control,
code ...UDM (old: UPM) .................................................................................................8
5. Preload valve for proportional controlled pumps, code PVAPVV........................................ 10
Table 1: Main dimensions - preload manifold ................................................................. 11
6. External pilot pressure supply ....................................................................................... 12
7. Quick pressure relief with quick unload valve, code PVAPSE* in
combination with controls codes ...UDS resp. UDQ ........................................................ 13
8. Preload and quick unload manifold PVAPVE* in combination with compensator codes
...UDP resp. ...UDF ...................................................................................................... 14
Table 3: Main dimensions of the preload and quick unload manifold ................................. 15
9.1 Basic adjustment of CIP sensor .................................................................................... 16
9.2 Basic adjustment LVDT ................................................................................................18
9.3 Basic adjustment control valves .................................................................................... 19
10. Connecting diagram for proportional displacement control; Code ...FDV. .........................20
11. Connecting diagram for p/Q-control; Codes ..UDR, ...UDK, ...UDM, ...UDS, ...UDQ, ...
UDP and ...UDF. ..................................................................................................................... 21
12. Cables and connections .................................................................................................22
13. Trouble shooting guide ...................................................................................................24
Notes:
The compensator / control ordering codes shown represent the last three digits in the
pump ordering code (di-gits 13 to 15).
displacement
pressure p1
FDV - Function
Solenoid A Solenoid current,
Solenoid B
Displacement
control valve
U
S
pA
S T
Figure 2: Circuit diagram...FDV control
The control valve contains a control spool, to minimum displacement. This requires a pump
which is moved by two proportional solenoids. outlet pressure p1 of at least 15 bar.
The valves hydraulic neutral point is given by
the electronic control module. According to If this pressure cannot be maintained, special
the area ratio of the servo piston, the control arrangements for a proper displacement control
pressure pA is approximately 25 % of the pump are required (please refer to chapter 4). Without
outlet pressure p1. an appropriate load pressure the pump will stay
Solenoid A is driven by the electronic module for at full displacement.
a flow command of 100 %. The spool connects
thereby port A with the pump housing (Port T). The ordering code for a single control valve is:
The oil out of the large piston area drains off, PVCMD1FB*** the first * indicates the mounting
the pump is swashing to maximum displace- option ( with interface plate / elbow manifold ).
ment. Solenoid B is activated in case of 0 % flow The two * at the end indicate seal option and
command. The pump outlet pressure p1 on the screws option (For details please see the com-
large servo piston area downstrokes the pump pensator spare parts list PVI-PVC).
Circuit diagram
displacement cmd. (Qcmd) 0... +10 V
or 4...20 mA 10 12 V DC 3 18...30 V
power supply
connect to terminal 11, 0 V 9 5V DC 4 0
17 solenoid p-valve
(pressure pilot valve)
19
12 10 V reference output
Displacement control WQ Wp
Code PVCMD1FBU** Pressure compensator
XQ Xp Stage, Code PVCM*U2**
IP
I Q:A I Q:B
BP
M
P T A P T BD2 PP A
P
WV
T
MP1 P P A T
P A T
pA Proportional pressure pilot
U
S valve, Code PVACRE***K**
(not included with code ...UDR)
S T
XQ = signal, displacement
IQ:A = solenoid current A, displacement control valve
IQ:B = solenoid current B, displacement control valve
IP = solenoid current, pressure pilot Valve
WQ = command, displacement
WP = command, pressure
Pressure compensator,
Code PVCM*U2**
Displacement control valve WQ WP Pressure sensor
Code PVCMD1FBU**
SCP01-600-24-06
XQ XP PVACMS*
IP
IQ:A IQ:B
U
BP P
P T A P T BD2 PP A
P
WV
T
MP1 P P A T
P A T
Proportional pressure valve,
U
S
Code PVACRE***K**
S T
XQ = signal, displacement
IQ:A = solenoid current A, displacement control valve
IQ:B = solenoid current B, displacement control valve
XP = signal, pressure
IP = solenoid current, pressure pilot Valve
WQ = command, displacement
WP = command, pressure
preload valve, WQ WP
Code PVAPVV*
XQ XP
IP
Mp1 IQ:A IQ:B
T
pP
BP
M
P T A P T BD2 PP A
p2
P
WV
Mp1
T
P A T
P A T
MP1
U
S
S T
XQ = signal, displacement
IQ:A = solenoid current A, displacement control valve
IQ:B = solenoid current B, displacement control valve
XP = signal, pressure sensor
IP = solenoid current, pressure pilot Valve
WQ = command, displacement
WP = command, pressure
Figure 8: Hydraulic circuit of a pump with ...UDK with preload valve control
Figure 9 shows the preload manifold for direct Input and output are designed as flange ports
mounting to the pressure port of the pump. It according to ISO 6162 and fit direct to the ac-
takes screws with the length L to mount it to the cording PV frame size. Table 1 shows the main
pump. L includes the length screwed into the dimensions.
pump end cover.
Gage port p1, G1/4“
Drain port L, (preloaded pressure,
G1/4“ covered)
flanged ports
ISO 6162: DN, PN;
fits to PV frame size
BG; threads: M
check valves M
Bp
T BD2 A
P M
WV
P T P A A P T
U
s
Mp1
IQ:A IP
XQ XP
S T WQ WP
Figure 10: Hydraulic circuit of a pump with external pilot pressure supply
DP2 PP
9 bar
M
DP1 P T A P T BD2 PP A
T
P
WV
P
T
P A T
P A T
MP1
U
s
S T
Figure 11: Hydraulic circuit of the ...UDS control with quick unload valve
8. Preload and quick unload manifold PVAPVE* in combination with compensator codes
...UDP resp. ...UDF
The pump accessory manifold code PVAPVE* hose to the control ports of this manifold. The
combines preload and quick unload function. hydraulic circuit diagram in figure 12 display this.
This manifold is flanged direct to the pressure Both functions are built into one manifold. Figure
port of a PV pump. For functional description 13 shows this manifold and table 3 lists the main
see the last chapters. dimensions.
To ensure a correct function under all working The dimension L indicates the total length of the
conditions and to control immediately the load mounting bolts and includes the length screwed
pressure, the control pressure has to be taken into the pump end cover.
after the preload valve. The hydraulic connections between manifold
Sensing area of the control spool and spring and pump compensator (ps and pp) are not
chamber are both to be connected by pipe or included in the pump shipment.
VE
Mpp pre-load and quick unload manifold,
code: PVAPVE*
pP
DP2 WQ WP
XQ XP
4 bar IP
DP1 IQ:A IQ:B
pS
T pS
pP
1.0
M
p2 P T A P T BD2 PP A
Mp2 P
WV
Mp1
T
P P A T
p1 P A T
pM
US
S T
Figure 12: Hydraulic circuit of the ...UDP control with pre-load and quick unload manifold
Alternative
outlet port P2,
thread G2
Also available in
US-version ( UNC
threads and UNF
ports) and with
ports according to
ISO 6149 Port p1,G1/4“,
preloaded
pressure (covered)
Gage port MpS, system
pressure, G1/4“ Port p system Port pP, pilot Gage port MpP,
pressure, G1/4“ pressure, G1/4“ pilot pressure, G1/4“
Figure 13 Preload and quick unload manifold
use 32 mm key
(max. 40 Nm)
Sensor
Teach Process
1. Solenoid to be connected according to chap- 4. At running pump, the nominal value for dis-
ter 9 and 10 to the electronic control module placement [WQ] is to be set to 0 %
2. To teach the sensor switch to controller 5. Test rig must be set to a pressure = 25 bar.
option TYPE = S in the ProPVplus software. All other connections / valves in the hydraulic
This means that the sensor signal is not circuit have to be closed.
considered. 6. Push button on teach adapter for 3 sec-
3. Connect teach adapter (RK-PV000CIP- onds → LED on sensor flashes one time per
TEACH47) with CIP sensor. second.
Figure 14:
Hydraulic sheme
for pump in 0 %
displacement
7. Push button on teach adapter for 1 second 8. Set the nominal value for the pump displace-
→ 0 % displacement value is defined [4 mA], ment to 100 % so that the pump is in max
LED on sensor flashes 4 times per second displacement. The displacement of the
pump can be checked with the help of a flow
Attention: After teaching 0 % displacement measuring device. The maximum displace-
value the sensor is given an undefined signal ment is reached, if the displacement / flow
between 4 and 20 mA. does not further increase, even when the
input command is still raised.
9. Push button on teach adapter for 1 second → Attention: The teach process needs to be fin-
100 % displacement value is defined [20 mA], ished within 2 minutes. Otherwise the sensor will
LED on sensor emits a permanent light signal. reset to the previous setting.
10. Disconnect teach-adapter and sensor and
reconnect sensor with electronic control Note: If the teach button is pressed for 8 sec-
module. onds, all settings are deleted, and the sensor is
reset to the factory settings.
9.2 Basic adjustment LVDT At running pump the command for the displace-
ment is to be set to 0 and the pressure relief valve
The inductive position transducer for displace- of the circuit / test rig has to be set to a pressure
ment feedback (LVDT) and the compensator > 25 bar. All other connections / valves in the
valves are factory preset and the settings are hydraulic circuit are to be closed.
secured. New or readjustment is only neces- The pump then will down stroke to deadhead
sary after repair. at the minimum pump compensating pressure
LVDT for displacement feedback: (10 ± 2 bar). By setting the zero adjustment
Prior to a basic setting the adjustment of the potentiometer (see figure 17) at the LVDT the
armature length is to be checked / readjusted diagnosis output of the control module is to
(see figure 16). The exact dimension for this be set to 0 V, as the actual displacement is the
setting is given in table 4: minimum displacement that can be controlled.
After adjustment the potentiometer must be
Table 4: setting dimensions LVDT core sealed again.
Size Size Serie 45
1 PV016-028 73.5 MAX-adjustment:
2 PV032-046 73.5 Next the command for the displacement is to
3 PV063-092 75.0 be increased, until the maximum displace-
ment of the pump is reached. That can either
4 PV140-180 75.0 be monitored by using the diagnosis output or
5 PV270 75.0 a flow meter at the pump outlet. The maximum
6 PV360 75.0 displacement is reached, if the displacement /
flow does not further increase, even when the
input command is still raised.
Zero adjustment:
Next the zero adjustment of the LVDT is to be
checked. The LVDT and the solenoid of the
displacement control valve are to be connected
according to chapter 9 to the electronic control Figure 17: Iinductive positon transducer (LVDT),
module. outside view
If the actual value gets 10V before the pump is full The factory setting for the differential pressure
stroked, the LVDT parameter need to be reset. is 15 ± 1 bar. For re-adjustment two pressure
If the actual value is below 10V and the pump is gages / transducers are required. The differ-
already full stroked, the LVDT parameter need ential pressure to be adjusted is the difference
to be reset as well. between the two pressures on both sides of
the control spool of the pressure compensator
9.3 Basic adjustment control valves stage in a control situation. For compensator
codes ...UDP and UDF (old: UPP and UPF) this
See also Installation and Start-Up Manual is the difference between the pressure pF on
for the digital control module PQDXXA-Z10. the sensing side and the pilot pressure pR (see
Caution: the proportional displacement con- figure 12).
trol, code ...FDV (old: FPV) does not include For all other codes it is the difference between
a pressure compensation. Therefore the pump outlet pressure p1 and pilot pressure pR.
hydraulic circuit needs to be protected with The leads to a minimum compensation pres-
a pressure relief valve (safety valve). This sure of 15 bar at completely unloaded spring
valve has to be layed out for full pump flow. chamber.
The remote pressure compensation stage of
the p-Q-controls codes ...UDR, ...UDK, ...UDM,
...UDS, ...UDP und ...UDF (old: ...UPR, ...UPK,
...UPM, ...UPS, ... UPQ, ...UPP and UPF), refered
chapters 2 to 7, is adjusted as follows.
31 18
PWM solenoid A Q-valve
(displacement control valve)
13 20
14 21 solenoid B Q-valve
(displacement control valve)
0V 11 23
17
19
12 10 V reference output
16
Cable 3a Cable 3b
Solenoid A Solenoid B
MP1 P P A T
P A T
U
Cable 1 S
CIP/
LVDT
flow Q
S T
flow
pressure p
11. Connecting diagram for p/Q-control; Codes ..UDR, ...UDK, ...UDM, ...UDS, ...UDQ,
... UDP and ...UDF.
Base parameter sets for UD* are available with module firmware PQDXXA-Z10-r03
and higher. (cable details see chapter 12)
displacement cmd. (Qcmd) 0... +10 V
or 4...20 mA 10 12 V DC 3 18...30 V
power supply
connect to terminal 11, 0 V 9 5V DC 4 0
displacement transducer 6 22
LVDT = 0...+10 V or CIP = 4...20 mA 18...30 V
power supply
horse power 0... +10 V 29 24 0
command (Lcmd) 0
31 PWM 18
solenoid A Q-valve
pressure command, (pcmd) 0... +10 V (displacement control valve)
or 4...20 mA 13 20
pressure transducer 0... +10 V 14 21
or 4...20 mA solenoid B Q-valve
(displacement control valve)
0V 11 23
17 solenoid p-valve
(pressure pilot valve)
19
12 10 V reference output
Cable 2
pressure sensor
Pressure compensator Pressure sensor
stage, code PVCM*U2** PVACMS, SCP01-600-24-06
(with quick unload (for closed loop Cable 3b
Displacement control manifold: code PVCM*US**, pressure control and Q-valve
stage with preload and quick horse power) solenoid B
Code PVCMD1FBU** unload manifold: code
PVCM*UP**
Cable 3a
Q-valve
Cable 4
solenoid A
U
p-valve
P
BP
M
P T A P T BD2 PP A
P
WV
T
MP1 P
Cable 1 P A T
CIP / P A T
Proportional pressure pilotvalve
LVDT code PVACRE***K**
U
Q
S
UQ
UP
S T
Teach-in
Pin 9
cable:cable: 4 x 0,54mm²,
x 0,5 shielded,
mm², shielded,
max. 50 max. 50 m long
m long
connector:
connector: CIP: round
CIP: round typex M12
type M12 x 1; 4-pin
1; 4-pin
LVDT:LVDT:
roundround typexM12
type M12 x 1; 5-pin
1; 5-pin
angledangled
versionversion
protection
protection class
class IP IP 65 for voltages uop to 250 V
65 for
voltages up to 250 V
Alternative: shielded cable with molded Notice: To protect the sensor, a cable strain
connector; in different length and variations. relief should be provided on the system side.
Cable 4 to proportional pressure pilot valve solenoid (not for compensator code ...FDV,
...UDR, ...UDP, ...UDS [old: ...FPV, ...UPR, ...UPP, ...UPS])