400
U = 400 V /
∆U = 3 % /
T ± + 30 oC /
300 in air,
Imax = 250 A 70 mm2 laid along a surface!
Imax = 202 A 50 mm2
200
Imax = 162 A 35 mm2
Imax = 99 A 16 mm2
100
90
80 Imax = 74 A 10 mm2
70
60 Imax = 53 A 6 mm2
50
Imax = 41 A 4.0 mm2
40
20
IN
[A]
10
9
8
7
6
5
1
10 20 30 40 50 60 70 80 90100 L [m] 200 300 400 500
Example:
a) IN = 68 A, 1 x 16 mm2 , ∆U ± 3 % o L ± 105 m! b) IN = 68 A, 1 x 25 mm2 , ∆U ± 3 % o L ± 165 m!
IN = motor current resulting from actual voltage
For supply voltages other than 400 V, the cable lengths must be calculated as follows, for ex. ...
U1 = 400 V, L1 = 105 m, U2 = 500 V o L2 = (U2 : U1) x L1, L2 = (500 V : 400 V) x 105 m = 131.3 m!
For parallel cables the value is doubled to obtain the permissible length.
79
50 Hz Accessories
200
Imax = 171 A 16 mm2
30
20
IN
[A]
10
9
8
7
6
5
1
10 20 30 40 50 60 70 80 90100 L [m] 200 300 400 500
Example:
a) IN = 27 A, 2 x 6 mm2, ∆U ± 3 % o L ± 145 m! b) IN = 27 A, 2 x 10 mm2 , ∆U ± 3 % o L ± 235 m!
IN = motor current resulting from actual voltage
For supply voltages other than 400 V, the cable lengths must be calculated as follows, for ex. ...
U1 = 400 V, L1 = 145 m, U2 = 500 V, o L2 = (U2 : U1) x L1, L2 = (500 V : 400 V) x 145 m = 181.3 m!