You are on page 1of 18

CRV 10 – Controller

Academy Main Trainer Thermal, LATAM

26/02/2020
Map of the presentation

Controller

ACM05U1 CRD10 Boards Communication

Visión general Power Detection Board

I/O Compressor Driver

Power supply EEV Driver

2
1 – ACM05U1 Board

3
ACM05U1 - Overview
Interface ACM05U1

DI 8

DO 9

AI 4

AO 2

NTC 6

485 3

CAN 1

4
ACM05U1 – Inputs/Outputs (1)
DI x 8 DO x 5(Relay) USB

J28 J11
J31 24V input J19
J21
DO x 4(Relay*3
J18 & TRIAC*1)
J38 RS485 (Remote Sensor)

J39 RS485-3(System) J9 PWM x 4

J12 12Vdc +-
J22 RS485-1
J14 RS485-2(Monitor)
J20 CAN
J17 J13 24V Input
J10 J8
J30 J6 J7 J23 J24 J15 J16 J34
J25

Power Detect AI x 4 NTC x 6 AO x 2 NTC x 2,


AI x 1

5
ACM05U1 – Inputs/Outputs (2)
Clogged filter Condensate water Remote General Alarm
Comp.
switch level switch Not Used (humidif.)
Auxiliary ON/OFF
DI power
contactor supply Water UF
Inverter
detect
Remote
Sensor Electric Heater Electric Heater Condensate high
J31 temp. switch
LLSV water level switch

10 DI
Board
J38 RS485 J18
TRIAC

J39 – Condenser fan


RS485
EEV board
Compressor
Driver J12 – 12 Vdc
J18
Digital Output
J14 – RS485
Monitor

Unity Card
J20 – CAN
Condensate pump
J16
J30 0-10 V
J25 – 2 x NTC output
J8 – 1 x NTC J34 – 1x AI
HMI display J23 – 1 x AI analog input analog input 24 V
0-5 V
power input

Compressor
Power detection Return Air T&H sensor
High Pressure Discharge T sensor Evaporator fan 6
board Supply T sensor
transducer
ACM05U1 – Inputs/Outputs
Terminal Pin DI
1、 2 Remote Shutdown Switch
3、 4 Water under floor detect
J19
5、 6 Condensate Water Level Switch
7、 8 Clogged Filters Switch
1、 2 Compressor auxiliary Contactor Switch
J21 3、 4 EL Heat High Temp Switch
5、 6 Condensate High Water Level Switch
7、 8 Customer Input1 Switch(Smoke, Fire)

Terminal Pin DO
1、 2 LLSV (line voltage)
3、 4 EL Heat Output
J28 5、 6 Compressor Control
7、 8 Humidify Control (not present in EMEA units)
9、 10 Common Alarm
DO6 Condensate Water Pump Output
J18 DO7 N/A
DO8 N/A
7
ACM05U1 – Inputs/Outputs
Terminal Pin AI
J8 1、 2 Discharge Temperature
J17 1、 2 Return Temperature 2
1、 2 NONE
J10
3、 4 NONE
1、 2 Supply Temperature1
J25
3、 4 Supply Temperature 2
J34 1~8 HT Board(Return Temperature 1/ Return Humidity 1 )
J23 1~3 Compressor High Pressure

Terminal Pin AO
J15 1、 2 N/A
J16 1、 2 EC Fan Control ( 0~10V )
J18 2 Condenser Fan ( b y the TRIAC, from line voltage )

8
ACM05U1 – Power Supply
Terminal Pin Power Supply
J13 J13 Power Supply (24V)
J31 J31 DI Detect Power Supply (24V)
J30 1~8 AC Power Detector (input power)

J31

J13

J30 9
2 – CRD10 Boards

10
CRD 10 Boards (1) General Alarm
EEV Driver

10 DI
Compressor

Remote T sensor

Compressor Driver Condenser Fan

Unity Card TH Board

Power EC fan
HMI Display
Detector 11
CRD 10 Boards (2) General Alarm

Compressor
p.n. 02520221
EEV Driver
10 DI p.n. 03040087
p.n. 03035588

Remote T sensor
p.n. 277072
Condenser Fan
Motor: p.n. 32030105
Fan Blade: p.n. 32010680

Compressor Driver
PACC
p.n. 03040113
p.n. 03035816

Unity Card TH Board


p.n. IS-UNITY-DP p.n. 03020343

HMI Display Power Detector EC fan


p.n. 02130862 p.n. 03029886 p.n. 32010561 12
CRD 10 Boards – Power Detection Board Install

Control Board Power Detection Board

Support:
50 Hz – 60 Hz
1 phase
230 V

13
CRD 10 Boards – Compressor Driver

CON1 EMI Filter

Terminal Description Type

J2 CON1 Single-phase power input 208/230Vac

J2 485+,485- \

J13 Three-phase AC output, U, V, W \

J13

Compressor Driver -- 230V/1Ph/50/60Hz

14
CRD 10 Boards – EEV Driver
PACC Temperature
RS485

Power Pressure
24 V

KM9

Pt 1000
15
3 – Communication

16
Communication
Terminal Pin Communication
J39 1、 2 RS485-3 (for EEV / VFD / 10DI / Remote Sensor)
J22 1、 2 RS485-1
J14 1、 2 RS485-2 (for SIC or other)
J20 1、 2 CAN 1

J39 RS485-3
J12 12Vdc + -
J22 RS485-1
J14 RS485-2
J20 CAN

17