Grid Automation
Recloser Protection and Control RER615
IEC 60870-5-101/104 Point List Manual
Document ID: 1MRS757824
Issued: 2015-03-06
Revision: C
Product version: 1.1
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................6
Related documentation..................................................................7
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................7
Functions, codes and symbols......................................................8
Section 4 Glossary.........................................................................67
Section 1 Introduction
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
Maintenance
Engineering
Planning &
Installation
Operation
purchase
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application Engineering Guide
Communication protocol manual
IEC 61850 Engineering guide
Point list manual
GUID-7414985D-2433-46E4-B77B-CCE64F6FC8D0 V1 EN
Figure 1: The intended use of documents during the product life cycle
1.4.1 Symbols
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• The example figures illustrate the IEC display variant.
• Menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
2.1 Overview
This document describes the IEC 60870-5-101/IEC 60870-5-104 data points and
structures available in the IED. The point lists describe a superset of all data
available through the standard configuration/s. The tables show the default point
definitions. All these data can be freely remapped in which case PCM600 can
provide an updated point list export of the new outlook.
1) All directional protection functions can also be used in the non-directional mode
2) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration
3) Only one can be ordered as an option at a time with OC or directional OC
4) Can be ordered as an option when OC is also chosen
5) Io selectable by parameter, Io measured by default
6) Can be ordered as an option when OC or directional OC is also chosen
7) Uo calculated is always used
8) One of the three can be ordered as an option when directional OC and directional EF are chosen: Admittance based EF, Wattmetric
based EF or Harmonics based EF
9) Uo calculated is always used with the first instance
10) UoB calculated is always used with the second instance
11) Voltage group B is always used with the third instance
12) Voltage group B is always used with the second instance
2.3 Indications
2.4 Measurands
For measurand values, the object type code also reflects which value coding
variation the object has as default.
36 M_ME_TF_1 2)3)
21 Measurand, 9 M_ME_NA_1 10 M_ME_TA_1 1)2)
normalized
34 M_ME_TD_1
2)3)
2.6 Controls
The internal object types appear in the protocol as standard IEC 60870-5-101/104
ASDU data types.
3.1 Overview
This section and the documents listed below provide complete information on how
to communicate with a RER615 via the IEC 60870-5-101 protocol.
Please note that the IEC 60870-5-104 protocol support shares application level
feature of the IEC 60870-5-101 implementation defined in this section.
The pages in this section have been extracted from the 60870-5-101 © IEC: 2003,
Section 8.
This companion standard presents sets of parameters and alternatives from which
subsets have to be selected to implement particular telecontrol systems. Certain
parameter values, such as the number of octets in the COMMON ADDRESS of
ASDUs represent mutually exclusive alternatives. This means that only one value
of the defined parameters is admitted per system. Other parameters, such as the
listed set of different process information in command and in monitor direction
allow the specification of the complete set or subsets, as appropriate for given
applications. This Clause summarizes the parameters of the previous Clauses to
facilitate a suitable selection for a specific application. If a system is composed of
equipment stemming from different manufacturers it is necessary that all partners
agree on the selected parameters.
System definition
(Network-specific parameter, all configurations that are used are to be marked with
“X”.)
(Network-specific parameter, all configurations and data rates that are used are to
be marked with “X”.)
(Network-specific parameter, mark all used options with an “X“. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is
implemented for unbalanced transmission, indicate the Type ID and COT of all
messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time-out interval are used
exclusively in this companion standard.
Two octets
Structured
Unstructured
Frame length
When using an unbalanced link layer, the following ASDU types are returned in
class 2 messages (low priority) with the indicated causes of transmission:
Mode 1 (Least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
Three octets
Cause of transmission
(Station-specific parameter, mark each Type ID with an “X“ if it is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
<14> := Measured value, short floating point value with time tag M_ME_TC_1
<18>:= Packed start events of protection equipment with time tag M_EP_TB_1
<19>:= Packed output circuit information of protection equipment with time tag M_EP_TC_1
<34>:= Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
<35>:= Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
<36>:= Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
<39>:= Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
<40>:= Packed output circuit information of protection equipment with time tag M_EP_TF_1
CP56Time2a
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17> or of
the set <30...40> are used.
(Station-specific parameter, mark each Type ID with an “X“ if it is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
(Station-specific parameter, mark each Type ID with an “X“ if it is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
(Station-specific parameter, mark each Type ID with an “X“ if it is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
File transfer
(Station-specific parameter, mark each Type ID with an “X“ if it is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
<122>:= Call directory, select file, call file, call section F_SC_NA_1
(Station-specific parameters)
Activation termination
Request or requested
Background scan
Periodic, cyclic
Spontaneous
Deactivation
File transfer
Activation
Initialized
20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<1> M_SP_NA_1 X X X
<2> M_SP_TA_1 X X
<3> M_DP_NA_1 X X X
<4> M_DP_TA_1 X X
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1 X X
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1 X X
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1 X X
<15> M_IT_NA_1 X
<16> M_IT_TA_1 X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X X X
<30> M_SP_TB_1 X X X X
<31> M_DP_TB_1 X X X X
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1 X X
<35> M_ME_TE_1 X X
<36> M_ME_TF_1 X X
<37> M_IT_TB_1 X X
Table continues on next page
Activation termination
Request or requested
Background scan
Periodic, cyclic
Spontaneous
Deactivation
File transfer
Activation
Initialized
20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X X
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<70> M_EI_NA_1*
<100> C_IC_NA_1 X X X X X X X X X
<101> C_CI_NA_1 X X X X X X X
<102> C_RD_NA_1
<103> C_CS_NA_1 X X X X X X X
<104> C_TS_NA_1
<105> C_RP_NA_1
<106> C_CD_NA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
Table continues on next page
Activation termination
Background scan
Periodic, cyclic
Spontaneous
Deactivation
File transfer
Activation
Initialized 20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<125> F_SG_NA_1
<126> F_DR_TA_1*
* Blank or X only
Station initialization
Remote initialization
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Read procedure
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Read procedure
Spontaneous transmission
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Spontaneous transmission
(Station-specific parameter, mark each information type with an “X“ where both a
Type ID without time and a corresponding Type ID with time are issued in
response to a single spontaneous change of a monitored object.)
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1 (if defined for a specific project)
Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and M_ME_TF_1
Station interrogation
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
global
group 5 group 11
group 6 group 12
Information object addresses assigned to each group must be shown in a separate table.
Clock synchronization
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Clock synchronization
Command transmission
(Object-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
No additional definition
Persistent output
Counter read
Counter reset
Parameter loading
(Object-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Threshold value
Smoothing factor
Parameter activation
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Test procedure
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Test procedure
File transfer
Transparent file
Transparent file
Background scan
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Background scan
(Station-specific parameter, mark with an “X“ if the function is only used in the
standard direction, “R“ if only used in the reverse direction, and “B“ if used in both
directions.)
Section 4 Glossary
www.abb.com/substationautomation