Professional Documents
Culture Documents
Modeling Time-Varying Harmonics in Electric Power Systems With Wind Farms, Through The Possibility Theory - V.3
Modeling Time-Varying Harmonics in Electric Power Systems With Wind Farms, Through The Possibility Theory - V.3
Received: November 27th, 2013. Received in revised form: April 21th, 2014. Accepted: XXXX.
Abstract
This paper focuses on the analysis of the connection of wind farms to the electric power system and their impact on the harmonic load-flow. A
possibilistic harmonic load-flow methodology, previously developed by the authors, allows for modeling uncertainties related to linear and
nonlinear load variations. On the other hand, it is well known that some types of wind turbines also produce harmonics, in fact, time-varying
harmonics. The purpose of this paper is to present an improvement of the former method, in order to include the uncertainties due to the wind
speed variations as an input related with power generated by the turbines. Simulations to test the proposal are performed in the IEEE 14-bus
standard test system for harmonic analysis, but replacing the generator, at bus two, by a wind farm composed by ten FPC type wind turbines.
Keywords: full power converter, harmonic distortion, possibility distribution, power system, uncertainty, wind turbine.
Resumen
En este trabajo se analiza el impacto de la conexión de parques eólicos, en el flujo de cargas armónicas en un sistema de potencia. Algunos
generadores eólicos producen armónicos debido a la electrónica de potencia que utilizan para su vinculación con la red. Estos armónicos son
variables en el tiempo ya que se relacionan con las variaciones en la velocidad del viento. El propósito de este trabajo es presentar una mejora
a la metodología para el cálculo de incertidumbre en el flujo de cargas armónicas, a través de la teoría de la posibilidad, la cual fue
previamente desarrollada por los autores. La mejora consiste en incluir la incertidumbre debida a las variaciones de la velocidad del viento.
Para probar la metodología, se realizan simulaciones en el sistema de prueba de 14 barras de la IEEE, conectando en la barra dos un parque
eólico compuesto por diez turbinas del tipo FPC.
Palabras clave: convertidor de potencia AC/DC – DC/AC; distorsión armónica, distribución de posibilidad, sistemas de potencia,
incertidumbre, generador eólico.
with c(0)= a(0)/2, c(h) = a( h )2 + b( h )2 and θ (h)=tan-1(a(h)/ b(h)) As above mentioned, harmonics are conceptualized as a
where: h: harmonic component order, c(0): magnitude of the steady-state phenomenon, that is, the waveform to be analyzed
DC component, c(h): peak value of the harmonic component is assumed to be repeated periodically from -∞ to ∞.
In practical situations, however, the voltage and current
(h) and θ (h): phase angle of the harmonic component (h), the
distortion levels as well as their fundamental components are
Fourier coefficients a(0), a(h) and b(h) are given by:
continually changing in time. This is due to the fact that the
2 T /2
a(0) =
T −T / 2
f (t ) dt ,∫ (2) network configuration usually changes and its linear and
nonlinear loads vary all the time; in addition, even if they were
2 T /2 constant their parameters are not usually well-known. All
a( h ) =
T −T / 2 ∫
f (t ) cos(hωt )dt , (3)
these features make harmonic distortion a phenomenon
2 T /2 involving uncertainty.
b( h ) =
T −T / 2 ∫
f (t ) sin(hω t ) dt , (4) Therefore, it is inadequate that the harmonic load-flow
calculation, in a real power system, be performed on a
Figure 1 shows the decomposition of a function f(t) in its
deterministic basis, i.e., assuming that all the relevant
harmonic components. The harmonic spectrum is shown too,
parameters are well known and non-random. In fact, this kind
which is obtained by dividing the peak value of each harmonic
of studies only provides a static and certain image of a varying
component by the peak value of the fundamental component:
and uncertain situation.
c(h)/c(1).
Methodologies based on the probability theory, with
1
100
f(t) different degrees of sophistication, have been developed to
deal with these uncertainties [2]. Practical application of them,
0.8
fundamental however, often has to face the lack of information to describe
harmonic components
50
0.6
harmonic in probabilistic terms the amount and type of medium size and
spectrum small distributed nonlinear loads (NLs), as well as the
0
0.4
composition of linear loads (LLs). This suggests that in many
-50 practical cases, the available information for harmonic load
fifth seventh 0.2 flow can be described better through fuzzy measures like
-100 possibility distributions.
0
0 0.005 0.01 0.015 0.02 0.025 0.03 1 3 5 7 9 11 13 2.4 Effects of harmonics on the network
time (s) harmonic order (h)
Figure 1. Representation of the Fourier series and the harmonic spectrum of a There are several problems related to harmonics, such as:
function f(t). Source: Authors
- Overheating of neutral conductors,
- Overheating of transformers,
2.2 Causes of harmonics in electric power systems - Overloading of capacitors for power factor correction,
- Problems with induction motors,
Linear devices satisfy the superposition principle, i.e.: if - Control failures in electronic devices which detect the
i(t) is the current flowing through it when a voltage v(t) is zero crossing of the voltage wave, and others.
applied, then a current α⋅i(t) will flow if the applied voltage is
α⋅v(t). A non-linear load is a device for which this relationship 3 Modeling the power system components at harmonic
does not hold. Figure 2 illustrates this concept. frequencies
In an ideal linear power system, both voltage and current
waveforms are perfect sine waves. In real power systems, 3.1 Model of Nonlinear Loads
however, there are nonlinear components for which the current
is not a sinusoid, even if a perfect sine voltage were applied. Accurate modeling of nonlinear loads is a difficult issue
This non-sinusoidal current produces voltage drops in other because of their inherent complexity and because some of
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
them are constantly changing their operational modes. In this level to the next. Other connections such as zigzag windings
section, basic models of nonlinear loads from a deterministic are used to mitigate harmonics.
point of view are presented.
In methodologies based on frequency domain analysis, the 3.2.2 Overhead lines and underground cables
common practice is to model nonlinear loads through
harmonic current sources, whose amplitudes and phases For balanced harmonic analysis the models of typical lines
depend on a set of parameters that characterize their harmonic or cables can be further simplified into a single-phase π-
behavior and their operating state. circuit, as shown in Fig. 3, which uses positive and zero
The simplest model assumes that harmonic currents do not sequence data.
depend on the applied voltage waveform, but only on its j
Zljk
k
power frequency component. For example, for thyristor-
controlled rectifiers, expressions like (5) can be used to
compute the amplitude and phase of the harmonic components
Ycj0 Yck0
of the injected currents at node j.
i (jh) = f h (v (1)
j , vdc , idc , β ) (5)
Figure 3. Line model for harmonic analysis. Source: Authors
where, v (1)
j is the power frequency component of the applied
voltage at node j, vdc and idc the voltage and current in the DC In Fig. 3, Zljk comprises a resistance and a series reactance
side of the rectifier, and β the switching angle of the thyristors. connected between nodes j and k of the network. Moreover,
This model could be further simplified if parameter β in admittances Ycj0 and Yck0 represent two capacitors connected
(5) is implicitly expressed as a function of the active (≈vdcidc) between their respective nodes and earth.
and reactive power of the rectifier, Prect and Qrect respectively, The main issues in modeling lines and cables are the
thus the expression (5) becomes: frequency dependence of per-unit length series impedance and
i (jh) = f h (v (1) the long line effects. As a result, the level of detail of their
j , Prect , Qrect ) (6)
models depends on the line length and harmonic order.
More detailed models have been developed for some of the Thus, as a first approximation, it can be considered that the
most important devices based on power electronics; however, series resistance is independent of frequency, and that both the
such models can be used only when the characteristics of the series reactance and the capacitive admittances depend
nonlinear device are well known. This, unfortunately, is not linearly on the frequency.
the most common in the case of real electric power systems. On the other hand, more complex models, especially for
long lines and high frequency harmonics, consider the Skin
3.2 Behavior and Models to Harmonic Frequencies of the effect correction in the series resistance and propagation
Main Elements of an Electric Power System effects by associating several π-circuits in series.
Modeling of electric power system elements over a wide 3.2.3 Aggregate load model: shunt capacitors and loads
range of frequencies is relatively well documented in the
bibliography [3,6]. As in other power system studies, it is only practical to
However, due to the importance of this topic, typical model an aggregate load for which reasonably good estimates
harmonic frequency models representing the elements in of active (MW) and reactive (MVAR) power are usually
common power systems, such as transformers, lines and readily available. However, this information is insufficient to
cables, shunt capacitors and loads, are described in what establish an adequate load model at harmonic frequencies. In
follows. fact, the system harmonic impedance is sensitive to the model
parameters, model topology and the actual load composition.
3.2.1 Transformers In agreement with the aforementioned, the important
components of the load for harmonic analysis are:
The transformer is usually modeled as a lumped ‐ The resistive component (passive loads),
impedance which represents its leakage impedance. Such ‐ The step-down transformer (distribution or service
lumped impedance comprises a series inductance with transformers),
resistance; this is because the frequency dependent effects are ‐ The motor components (motive loads),
not significant for the harmonic frequencies of common ‐ The non-linear loads (exposed at section 3.1), and
interest. However, other complex models include the nonlinear ‐ The shunt capacitors and filters (such as power factor
characteristics of core loss resistance, the winding stray compensation capacitors and so on).
capacitance, the core saturation, the skin effects, etc. Effects of Linear passive loads have a significant effect on system
stray capacitance are usually noticeable only for frequencies frequency response primarily near resonant frequencies. I.e.,
higher than 4 kHz. the resistive component provides damping when the overall
On the other hand, for three-phase transformers the system response is near a parallel resonance (high impedance).
winding connections are important for determining the effect The aggregate load model should include the distribution
of the transformer on zero-sequence harmonic components, or service transformer. At power frequencies the effect of
i.e., delta connections isolate these currents from one voltage distribution transformer impedance is not of concern in the
analysis of the high voltage network, however, at harmonic
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
frequencies the impedance of the transformer is practically an In synchronous generators, the rotating magnetic field
inductance in series with the load. Moreover, it is also established by a harmonic current in the stator rotates at a
important to discriminate the motor components from the speed significantly different from that of the rotor. Therefore,
overall load because the active power absorbed by rotating to harmonic frequencies the impedance approaches the
machines does not exactly correspond to the value of a negative sequence impedance or to the average among sub-
damping resistance. transient direct and quadrature axis impedances [3]:
On the other hand, it is clear that the nonlinear load X d" + X q"
component determines the levels of harmonic currents injected X2 = (7)
to the system. 2
Finally, the shunt capacitors and the stray inductance of the In the case of induction generators, the inductance is
supply system can resonate at or near one of the harmonic represented through the locked rotor reactance.
frequencies. In both cases, the dependency of the resistance on the
Several models to aggregate loads at harmonic frequencies frequency may be important due to the skin effect and the
have been proposed in the bibliography [3,7]. However, load eddy current losses, therefore this dependence may be
representation for harmonic analysis is still an active research considered by increasing the resistance value at the
area. fundamental frequency by h , where h is the harmonic
Section 6 of this paper deals with the fact that most of the order.
magnitude and composition parameters, which are necessary Furthermore, in induction machines the “α” parameter is
to achieve an adequate load model representation, are known considered which relates the rotor resistance R1, with the
with uncertainty in real power systems. In effect, the influence locked rotor resistance, RB, by α = R1/RB, and has a typical
of such uncertain parameters in a general load model is studied value equal to 0.5. On the other hand the slip at harmonic
in [7]. frequency sh is given by (8).
± hω1 − ωr
sh = (8)
3.3 Model of a wind turbine at harmonic frequencies ± hω1
where ωr is the rotor speed and the sign + or – depends on the
There are several types of wind turbines, among which positive or negative sequence of the harmonic order
include: Fixed Speed Induction Generator (FSIG), Doubly Fed considered.
Induction Generator (DFIG) and Full Power Converter (FPC). The models to harmonic frequency for induction and
Each type of system has advantages and disadvantages synchronous generators are shown in Fig. 5.
inherent to the technology used, and pursuing the same goal:
maximum energy transfer from the wind turbine to the grid, at
⎡ (1 − α ) ± h − 1 ⎤
the lowest cost, and ensuring adequate levels of RB ⎢α h + ⎥ hR2
electromagnetic compatibility. However, this paper will only ⎢⎣ sh ⎥⎦
deal with the modeling to harmonic frequency of the wind jhX B jhX 2
turbine FPC type, as they are widely used in wind farms in
Latin America, and also have a characteristic harmonic
spectrum by multiples of the grid frequency [8]. Despite that, (a) (b)
the study may be extended in the future to other turbine Figure 5. Models to harmonic frequency for: (a) induction generators, (b)
models. synchronous generators. Source: Authors
The basic configuration of a wind turbine type FPC is
presented in Fig. 4. The two main components to be modeled 3.3.2 Converter
to harmonic frequency are the generator and the converter.
Electric Utility Grid In an FPC type wind turbine, the electric parameters,
variables with the wind speed, are transformed to grid
parameters by a converter. The commutation valves used in
Coupling the converter are Insulated Gate Bipolar Transistors (IGBT)
Induction or Transformer with anti-parallel diodes. On the side of the generator, the
Turbine Synchronous convert transforms a three-phase AC voltage of variable
Generator
DC link
amplitude and frequency in a constant DC voltage. On the side
of the grid, the converter is responsible for converting this DC
voltage into an AC voltage phase, with constant amplitude and
frequency (exactly like the power grid where the unit is
connected).
Power Converter Using digital signal processors, the vector control is
Wind
Figure 4. Configuration of a FPC type wind turbine. Source: Authors performed in the converter (PWM technology). The control
algorithms are diverse and depend on the manufacturer, but
always looking for the optimum use of turbine-generator. In
3.3.1 Generator Fig. 6 the characteristic curve of wind speed versus generated
power through a commercial generator of 2 MW is shown.
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
2200 intuition, ideology, beliefs, feelings, etc., i.e., options with a
2000
degree of subjectivity, but not of arbitrariness.
Fuzzy sets and possibility theories provide a formal
1800
framework to model vague relationships or concepts, such as,
1600 size, pollution, economics, satisfaction, adequacy, etc.
1400 Definitions for the formal treatment of the fuzzy sets and
1200
possibility distributions can be found in [10], and applications
to the specific problem of harmonic analysis in [11-14].
1000
IWP-100-20MW
800 4.2 The possibilistic harmonic load-flow
600
400
Through the references [11-14], a complete formulation for
calculating the harmonic load-flow, considering uncertainties
200
in the input parameters, has been presented. Such uncertainties
0 are modeled by possibility distributions. Readers are
0 5 10 15 20
encouraged to review such references to achieve a better
Figure 6. Generated power vs. wind speed at a 2 MW turbine-generator of the understanding of the methodology described below.
FPC type. Source: Adapted from www.impsa.com
4.2.1 General formulation for the case of possibilistic
Although a characteristic function of the harmonic independence
behavior of a wind turbine-generator type FPC has not been
fully defined (e.g., similar expressions to those defined in (5) The simpler case not involving possibilistic dependences
and (6) for a converter), there is information, such as that will be considered first. To this purpose, consider the general
presented in Table 1, which relates the harmonic current, iw(h), expression of the harmonic bus voltages, i.e.:
injected by the wind generator, as a percentage of the V = Y−1I (9)
fundamental frequency current, iw(1), (50 or 60 Hz). Note that where the harmonic order has not been identified for
this type of data is normally provided by the manufacturer and notational simplicity.
it is obtained from the electric power quality tests. When harmonic interaction is neglected (harmonic
Thus, using information from Fig. 6 and Table 1, it is penetration approach, [3]) components ik (k = 1…n) of vector I
possible to model the harmonic current that injects a wind do not depend on the harmonic voltages.
turbine-generator according to the wind speed, in this case a On the other hand, the diagonal elements of Y and the
wind generator 2 MVA. injected currents ik, depend on the model of the linear and
nonlinear loads, and on a number of parameters describing
Table 1. their magnitudes and compositions. For the sake of generality,
Characteristic harmonic of a FPC wind generator in this section no hypotheses will be made regarding these
Harmonic
5 7 11 13 17 19 23 25 aspects as the development of a specific model is postponed to
order (h)
the section 4.3.
iw(h)/ iw(1) 0.5 0.54 0.21 0.10 0.13 0.19 0.19 0.02
Source: Authors
However, by assuming that a generic vector
P = ( p1 , p2 , , pn p ) of np parameters completely describes
4 Possibilistic harmonic load-flow the loads of the system, determining accordingly all the
injected currents and the bus admittance matrix in (9), i.e:
4.1 Uncertainty management
V = [ Y( P ) ] I ( P )
−1
(10)
By denoting Z j (P) the jth row of Z(P) = [ Y(P)] , the
−1
Most real-world decisions are made within an environment
in which: goals, constraints, possible actions (solution space)
amplitude of the harmonic voltage at a generic bus j, can be
and consequences are not precisely known. To deal
written as:
quantitatively with imprecision usually techniques and
concepts of probability theory are employed. However, it (
v j (P) = abs Z j (P)I(P) ) (11)
must be considered, that when uncertainty is modeled by using or, using a more general notation:
probability density functions, PDFs, it is implicitly accepted v j ( p1 , p2 , , pn p ) = f j ( p1 , p2 , , pn p ) (12)
that the imprecision of whatever nature can be compared with
randomness, an assumption which may be questionable. I.e., When pk are uncertain parameters described through fuzzy
in many situations, the decision maker cannot measure or numbers Pˆ1 , Pˆ2 , , Pˆn p with independent membership
express an explicit function for all determinant parameters
within a decision process. This is because of various reasons, functions μ Pˆ ( pk ) , k = 1…np, the harmonic voltage vj
k
e.g., incomplete information, insufficient knowledge, lack of becomes a possibilistic variable, expressed by a fuzzy number
or inaccuracy of models, or that the involved cost to acquire Vˆj . Thus:
the lacking information is high regarding the improvement in
results. Therefore, in those situations, it could be advisable to Vˆ j = f j (Pˆ ) (13)
appeal to other types of information, namely: experience,
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
where P̂ is the fuzzy Cartesian product: Pˆ = Pˆ1 × Pˆ2 × × Pˆn p , Now, if the possibility distribution functions μ Pˆ ( pk ) are
k
whose membership function is (see [13]): compatible and all of them are equally reliable, then the
(
μPˆ p1 , ) {
, pn p = min μ Pˆ ( p1 ),
1
, μ Pˆ ( pn p )
np
} (14)
standard fuzzy intersection operator, [11], can validly be
applied to obtain the joint distribution functions, for each
node; i.e.:
Accordingly, the membership function of Vˆj can be
written as: i
{
μPˆ (Pi ) = min μ Pˆ ( p1 ),.., μ Pˆ ( pni ), μ Pˆ
1 ni ni +1
( g1 (Pi ) ) ,...
( ) ( gn (Pi ) )}
(20)
μVˆ (v j ) = max ⎡μ p , , pn p ⎤⎥ (15)
j v j = f j ( p1 , , pn p ⎢ Pˆ 1
)⎣ ⎦ ..., μ Pˆ e
np
⎪
Analogously, the following relationships can be written in ⎨
⎪ pn = g n ( Pi )
terms of the α-cuts (for definition see [10]): ⎩ p e
V j( ) = f j P( )
α α
( ) (17)
On the other hand, from a deterministic viewpoint, the
harmonic voltage at bus j is, in general, a function of
(α ) (α ) parameters pk, with k = 1…np.
with P( ) = P1 × P2 × × Pn( ) .
α α
np (
⎡ min f p ,.., p , max f p ,.., p ⎤ (18)
⎢ p1∈P1(α ) j 1 p1∈P1( )
α j 1 np
⎥ ) ( ) ⎧ f j ( P )=v j
⎪
⎡
⎣ 1 n p
{ ⎤
pos(v j ) = max ⎢ min μ Pˆ ( p1 ),..., μ Pˆ pn p ⎥ (23)
⎦
( )}
⎢ ⎥ ⎪ pni +1 = g1 ( Pi )
⎨
⎢ pn p ∈Pn(pα ) pn p ∈Pn( )
α
⎥ ⎪
⎣ p ⎦ ⎪⎩ pn p = g ne ( Pi )
and can be determined solving two optimization problems
which is a direct generalization of equation (16) above.
(minimization and maximization respectively).
Similarly, the α-cuts of Vˆj are the intervals:
4.2.2 General Formulation for the case of possibilistic
V j( ) = ⎡⎢ v j( ) , v j( ) ⎤⎥ =
α α α
dependence ⎣ ⎦
⎡ ⎤ (24)
A more general situation, whenever the possibilistic
dependences to be modeled are of the type due to a well-
( )
⎢ min(α ) f j p1 ,.., pn p , max(α ) f j p1 ,.., pn p ⎥
⎢⎣( P )∈P ( P )∈P ⎥⎦
( )
defined physical connection among fuzzy variables whose and can be determined solving the following optimization
possibility distribution functions have been determined problems:
independently, is analyzed in what follows.
In this general case the uncertain variables are a set of np
α
⎣ (
v j( ) = min ⎡⎢ f j p1 ,.., pn p ⎤⎥
⎦ )
parameters ( p1 , p2 , , pn p ) , with possibility distribution (25)
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
4.2.3 Possibilistic harmonic load-flow algorithm Several studies suggest the electric circuit shown in Fig. 8,
Inputs: i) Network topology; ii) Certain network parameters; iii) [7], as a suitable model for harmonic load-flow calculation;
Possibility distributions of uncertain parameters: μ P̂ ; iv) Required where each branch represents the sum of loads with similar
k
characteristics. This model also allows the inclusion of the
bus voltages: busj , j=1…nb, (nb: number of buses); v) Required
harmonic orders: hm , m=1…nh; (nh: number of harmonic
wind generator as an RL branch and a harmonic current
frequencies); vi) Required α-cuts: αk , kα=1…nα , (α1=1,…, αnα=0 source.
bus i
and nα: number of α-cuts)
Rp(h)
Xm(h) Rm(h)
Z(h)filters
j = 1 ; m = 1 ; kα = 1
Xpfc(h) i(h)
Xp(h)
hm
busj
Figure 8. General model of the aggregated load at a node of the PS. Source:
αk Authors
(h)
Compute the lower and upper limits of αk-cut where X pfc models capacitors for power factor correction.
( k
α ,hm )
Vbus
j
by solving (25) and (26) Rm(h) and X m( h ) model rotating machinery. R(ph) and
( k α ,hm ) ( k α ,hm ) X (ph) model passive loads and small engines. i(h) models
Store: vbus and vbus
j j
kα =kα+1 harmonic currents injected by nonlinear devices (rectifiers,
m= m+1, no inverters, wind turbines etc.); and filters model the RLC
kα =1, kα=nα circuits installed to filter harmonics.
yes j=j+1,
j =1
Store: Vˆbus
( hm ) kα =1 4.3.2 Fuzzy parameters
j
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
These model parameters, together the appropriate article, in which generator at bus two is replaced by ten FPC-
expressions, allow to compute the parameters of the circuit in type wind generators, each one of 2 MW.
Fig. 8. 1 1 1 1
α
4.3.3 Relationships between the model parameters and the 0.5 0.5 0.5 0.5
aggregated load parameters
0 0 0 0
For each harmonic frequency, nonlinear loads are 0.02 0.03 0.04 0.04 0.05 0.06 0.02 0.03 0.04 0.01 0.02 0.03
represented by current sources at their respective nodes, and bus 2 bus 3 bus 5 bus 7
link the model parameters by means of expressions as (5) and 1 1 1 1
(6). In addition, the model for the harmonic current injected by
α
a wind turbine corresponds to that presented in Section 3.3.
0.5 0.5 0.5 0.5
Regarding linear loads, detailed expressions which relate
the model parameters with the elements of the aggregate
circuit of Fig. 8, are presented in the Appendix (Section 8) of 0 0 0 0
0.01 0.025 0.04 0.01 0.025 0.04 0.01 0.025 0.04 0.01 0.025 0.04
reference [13]. bus 9 bus 10 bus 12 bus 14
5 Case study Figure 10. Per unit 5th order harmonic voltage magnitude at buses 2, 3, 5, 7, 9,
10, 12 and 14. Dotted lines indicate the Possibility functions obtained in [13];
i.e. case i. Continuous lines indicate the Possibility functions obtained in case
5.1 Description of the electric power system ii, i.e., by considering the wind farm at bus 2, and assessing the influence of
the variability of the wind speed between the interval [5 mps – 20 mps].
The test system is presented in Fig. 9. Main parameters of Source: Authors
the power system are summarized in [15]. Furthermore, in Fig.
5.3 Discussion
7 of reference [13], the values of the uncertain parameters to
model aggregated harmonic loads and sources are presented.
From results presented in Fig. 10, it can be concluded that
I.e. these uncertain parameters are modeled through triangular
the wind farm connection impacts over the 5th harmonic
possibility distributions, and the values reported in [11,13] are
voltage magnitudes at all buses of the power system. In
the same employed for this case study. The only difference is
particular, in most of the buses, there is a decrease in
that a 20 MW wind farm of ten generators, each one of 2 MW,
the harmonic distortion, surely due to phasorial cancellation
is included at the generation bus 2. Moreover, it is assumed
between the harmonic currents flowing through the network.
that wind speed is known with uncertainty, and that it can vary
However, this situation is different at bus 3, where the
between 5 mps and 20 mps. Under other wind speed
harmonic voltage distortion increases considerably and
conditions, the generators are turned off, due to security
reaches levels that can be intolerable from the electromagnetic
reasons.
compatibility point of view.
It can also be noted that obtained possibility distributions, in
b-13 b-14
the case ii, are trapezoidal. This is the result of modeling the
uncertainty related to the wind speed as an interval, unlike the
b-11 b-10
other uncertain parameters which are modeled with triangular
b-12 possibility distributions. It is therefore concluded that involve
G uncertainty in the wind speed; i.e., an input parameter, has a
b-1 b-6 b-9 considerable effect on the uncertainties associated with the
b-7 harmonic voltage magnitudes, i.e., the outputs of the
G possibilistic harmonic load-flow.
b-5 b-4
b-8 ↑
Harmonic
6 Conclusions
source
This work has focused on including the wind-turbine FPC
b-2 b-3 type within the methodology for calculating the possibilistic
WF Wind Harmonic harmonic load-flow. The methodology is able to consider the
Farm source ↑ uncertainties due to the deficiency of information regarding
Figure 9. IEEE 14-bus standard test system for harmonic analysis. Source: harmonic sources and the magnitude and composition of linear
Authors loads; i.e., wind turbines, nonlinear devices, and conventional
loads.
5.2 Results The Possibility Theory has been selected to model
uncertainty, because it seems to be an interesting alternative
The aim of simulation is to compare the results obtained in for situations where the information is too vague to define
both cases: i) the case in which the generator at bus 2 reliable probability distributions; a common situation in the
corresponds to a synchronous machine that does not inject context of harmonic studies.
harmonics into the network (this case corresponds with that The possibilistic harmonic load-flow has shown flexibility
reported in reference [13]), and ii) the proposed case in this allowing include wind farms as harmonic sources. In fact, the
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353
reformulated method has been proven in the IEEE 14-bus [13] Romero, A. A., Zini, H. C., Rattá, G. and Dib, R. Harmonic load-flow
approach based on the possibility theory. Generation, Transmission &
standard test system for harmonic analysis. Distribution, IET, 5 (4), pp. 393-404, 2011.
In order to evaluate the performance of the proposal, a
comparison with previously published simulations, in which [14] Romero, A. A., Zini, H. C., Rattá, G. and Dib, R. A fuzzy number based
wind farms were not considered, was performed in this article. methodology for harmonic load-flow calculation, considering uncertainties.
Latin American Applied Research, 38, pp. 205-212, 2008.
Obtained results show that it involve uncertainty in the wind
speed has a considerable effect on the uncertainties associated [15] IEEE Task force on harmonics modeling and simulation. Test Systems for
with the computed harmonic voltage magnitudes, therefore Harmonics Modeling and Simulation. IEEE Transactions on Power Delivery,
this uncertainty must be considered when harmonic studies 14, pp. 579-585, 1999.
must be developed.
It is hoped that the methodology developed contributes to
A. A. Romero-Quete was born in Colombia in 1978. He received the
the solution of real problems related with harmonics in electric Electrical Engineer degree in 2002, at the “Universidad Nacional de Colombia
power systems. For example, problems such as decision (UNC)” and his Ph.D. at the “Instituto de Energía Eléctrica, Universidad
making under uncertainty, harmonic filter design, harmonic Nacional de San Juan” (IEE-UNSJ) in 2009. He had been working and
filters and capacitors location, analysis of the impact of the researching as high voltage test technique engineer at “Laboratorio de
Ensayos Eléctricos Industiales, Fabio Chaparro, UNC” until 2003, when, he
connection wind farms, among others. was awarded with a scholarship from the German Academic Exchange
In future work, research efforts must be conducted for the Service (Deutscher Akademischer AustauschDienst - DAAD) to conduct
development of harmonic models for other types of wind Ph.D. studies at IEE-UNSJ. Currently, Andrés Romero is researcher of the
turbines, e.g., DFIG type wind turbines, and their inclusion in Consejo Nacional de Investigaciones Científicas y Técnicas, CONICET, at the
IEE-UNSJ. His research interests are asset management, power quality, and
the possibilistic harmonic load-flow method. high voltage test techniques. Email: aromero@iee.unsj.edu.ar
[7] Romero, A. -A., Zini, H. -C., Ratta, G., Dib, R., A novel fuzzy number G. Rattá, was born in Italy in 1950. He received his Electromechanical
based method to model aggregate loads for harmonic load-flow calculation, Engineer degree from Universidad Nacional de Cuyo-Argentina in 1974.
Transmission and Distribution Conference and Exposition: Latin America, Since 1997 he has been director of the IEE-UNSJ, Argentina. Prof. Rattá is
2008 IEEE/PES , pp. 1-8, 13-15, 2008. currently an Assistant Professor in the UNSJ. He is also member of the
Commission of Postgraduate Evaluation. His research interests include
[8] Baroudi, J. A., Dinavahi, V. and Knight, A. M. A Review of Power transient behavior of power system components and power quality. Email:
Converter Topologies for Wind Generators. Renewable Energy, Elsevier, 32, ratta@iee.unsj.edu.ar
(14), pp. 2369-2385, 2007.
[11] Romero, A. A., Zini, H. C., and Rattá, G. Modelling input parameter
interactions in the possibilistic harmonic load flow. Generation, Transmission
& Distribution, IET , 6 (6), pp. 528-538, 2012.
[12] Romero, A. A., Zini, H.C. and Rattá, G. An Overview of Approaches for
Modelling Uncertainty in Harmonic Load-flow. Ingeniería e Investigación,
31 (2), pp. 18-26, 2011.
Dyna, year 83, no. 183, pp. 1-1. Medellín, February, 2014. ISSN 0012-7353