Professional Documents
Culture Documents
Tenaris Tamsa's Ladle Furnace Electrode Consumption Reduction
Tenaris Tamsa's Ladle Furnace Electrode Consumption Reduction
INTRODUCTION
LF1 Operations
Due to steelshop lay out, LF1 needs to erogate more energy than LF2: it is the first station that receives steel tapped from
electric arc furnace, almost all ferroalloys are added there, and it is the previous station to vacuum degassing process (40-50%
of production), which produces an important temperature loss that is compensated by rising exit temperature at LF1. In figure
1 is presented a diagram that outlines LF1 operations, an important aspect that will be explained to be relevant for this work is
that heating periods were performed any time regardless argon flow level.
Electrical Operation.
LF1 works with a 20MVA transformer with 17 taps. From user HMI is possible to change only tap, current is already configured
by an impedance set point.
First trials
It was planned to test 4 more taps than normal operation (up to Tap 12). First trials aimed to determine possibility to work with
each of the selected taps by heating for about 5-10 minutes periods with strong argon flow, since it is the most flexible condition
in terms of operative needs (heating whenever needed regardless argon flow).
After some short tests it was determined that it is possible to work with high argon flow up to Tap 10, since Tap 11 already
showed a significant impact on arc stability as it can be observed in figure 4 and 5. In the same figure the highlighted area
corresponds to Tap 11 operation with low argon (weak stirring), which indicates that it is possible to work above tap 10 if
Argon flow is limited, presenting even a better performance on arc stability than observed on Tap 8 with strong stirring.
Figure 4. Impedance behavior with tap 8 to 11. Highlighted operation with low argon stirring (1)
Figure 5. Power behavior with tap 8 to 11. Highlighted operation with low argon stirring (1)
Benefit was calculated in % of reduction, considering that constants remain the same. This is shown in Table I:
From first trials, it was proposed to perform more tests using TAP 12 to obtain at least 23% of electrode saving. Since arc
instability does not allow using strong stirring with this TAP, it is also necessary to determine if it is feasible to restrict heating
periods using low argon flow only.
TAP 12 trials
Next stage trials had the following objectives:
• Characterize heating rate using tap 8 during initial period, weak and strong stirring (previous practice), and tap 12
with low argon flow (proposed new practice).
• Characterize roof cooling water temperature behavior with Tap 8 and Tap 12.
• Verify if eliminating initial period heating could have an impact on desulphurization (since one critical condition to
remove Sulphur is temperature).
72 heating periods with Tap 8 and Tap 12 were followed, taking notes of initial and final temperature, power on, additions
made during heating, argon flow and whether it corresponded to an initial period or not.
Heating rate
In figure 6 it is possible to observe heating rate in °C per minute corresponding to each test scenario (Energy loss due to
additions was considered):
Initial desulphurization:
To determine if initial desulphurization could be affected, a short test was performed by comparing Sulphur values (average
and Standard deviation) after initial high stirring periods without heating against average initial Sulphur from previous month
(normal operation), observing no impact on eliminating heating at this period since sulfur values are even lower, see figure 8:
RESULTS
After characterizing Tap 12 operation, practice was modified to perform a long test and validate electrode consumption. The
following conditions were established:
• Perform initial 5 minutes high stirring period without heating.
• Heating periods using TAP 12 instead of TAP 8
• Use only low argon stirring during power on to favor stable arc operation and avoid arcing.
Results were observed from the first month of implementation, and after 6 months of being implemented it could be
concluded:
• 30% of electrode consumption from LF1 was reduced, from a typical value of 0.30 to 0.20 Kgs/MT (see figure 9)
and it is maintained up to the date this manuscript was written (11 months).
• From the moment the new practice was implemented, no roof water leak due to arcing has been identified.
ACKNOWLEDGEMENTS
We thank to all personnel of operations and technology department from Tenaris Tamsa’s steelshop for the provided support
to reach the objectives. We also would like to thank Tenaris Tamsa for the opportunity to participate in this project and to all
that provided valuable feedback on an earlier version of the manuscript.
Special thanks to Jackson Kuntze and Enrique Garza from SDK for their valuable support and analysis during first trials.
REFERENCES
1. Jackson Kuntze / Enrique Garza, SDK TAMSA Visit Report, March 2018.