KVF / KVI

KVIF/1908/UK
Capture Jet™ hood
With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

© Halton
KVF

New design
Halton Skyline LED
Culinary light inside

KVI

ALLIED MEMBER

LISTED

KVF/I hoods are particularly suitable for LEED(1) projects and • Quick and easy commissioning. Hoods delivered “ready
can be used in all closed, open or show kitchens (hotels, to install”, with all accessories included, such as light
hospitals, gastronomic restaurants, central kitchens, etc). fitting, T.A.B.™ taps and balancing dampers for quick
KVF/I hoods have the latest generation of patented Capture balancing on-site.
Jet™ technology. KVF hoods are equipped with a low-velocity • Sturdier and easier to clean: Less parts and less joints.
makeup air system built into the front face. Stainless steel construction.
• HACCP(2) certified.
(1) Leadership in Energy and Environmental Design
• Considerable energy savings: 30 to 40% less exhaust
(2) Hazard Analysis Critical Control Point
airflow rates due to Capture Jet™ technology.
• Savings on maintenance and enhanced safety: Highly-
efficient KSA cyclonic filters (UL, NSF and LPS 1263
certified). Prevents build-up of grease deposits which
constitute a serious hygiene and fire hazard. Lower
ductwork cleaning costs.

• KVF - Better capture and comfort thanks to a low-


velocity diffuser built into the front (make up air without
draughts).
• Halton Skyline LED culinary light provides the best visual
comfort while contributing to further improve the safety
and the energy savings.
• Performance tested independently in accordance with
the ASTM 1704 standard. Exhaust airflow rates
calculated on the base of this performance and the
calculation of cooking appliances’ heat loads.

1
Description of the main technologies

KVIF/1908/UK
© Halton
KVF

New design
Halton Skyline LED
Culinary light inside

KVI

Capture Jet™ technology Cyclonic filter (KSA) Halton Skyline (HCL)


Up to 40% reduction 95% efficient on 10 µm and above Kitchen specific and LED based
in airflow rates particles Culinary Light

Integrated makeup air Testing & Balancing (T.A.B.™)


Better smoke capture and comfort Quick airflow rates measurement
(KVF)

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

2
KVIF/1908/UK
Capture Jet™
technology

© Halton
ENERGY EFFICIENCY
30 to 40% reduction in exhaust airflow rates.

INDOOR ENVIRONMENT QUALITY (IEQ)


The capture efficiency combined with reduced airflow rates
improve the working conditions.

SAFETY
Cooking vapours are not dispersed and food safety is
improved.

All hoods fitted with the constantly evolving Capture Jet™ WITH Capture Jets WITHOUT Capture Jets

technology (patented) bring about a 30 to 40% reduction


of exhaust airflow rates compared to classic hoods.

The latest generation of the Capture Jet™ technology


rests on the association of two sets of nozzles supplied
with an extremely low supply air volume (a maximum of
30 m³/h/ml of hood). These nozzles fit to the lower part of
the hood front as well as the sides, so as to literally
encircle the covered cooking areas.
Digital simulation on the efficiency of the Capture Jets thanks to the
- The horizontal nozzles increase the driving speed to the association of two sets of nozzles
lower part of the hood front thanks to the Venturi effect.
They therefore push vapours back towards the filters. It is possible to bring the reduction of exhaust
- The vertical nozzles form a curtain of air that increases airflows to 64% by combining Capture Jet™ and
the hoods’ containment volume, protects the capture M.A.R.V.E.L technologies.
zone from draughts and considerably minimises the
dispersal of vapours. Thanks to these vertical nozzles, a
hood installed at a height of 2 metres is as efficient as if
it was installed at a height of 1.85 m or 1.90 m.

1 Schlieren tests on a hood WITH and WITHOUT Capture Jets


WITH Capture Jets WITHOUT Capture Jets
3600 m³/h 3600 m³/h 6000 m³/h

The Schlieren system shows the convective All vapours released by the With this same rate of The airflow of a hood without
flows of cooking appliances so that the hoods’ appliances are captured and 3600 m³/h, a traditional hood Capture Jets must be 6000
capture efficiency can be reliably and objectively evacuated at a rate of without Capture Jets is m³/h in order to be considered
measured. 3600 m³/h. inefficient. efficient.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

3
KVIF/1908/UK
Highly-efficient KSA
cyclonic filters

© Halton
ENERGY EFFICIENCY
Reduces the energy used by fans, by minimising loss of
pressure.

SAFETY
95% efficiency on 10 µm particles minimises build-up of
grease deposits and improves fire safety and food safety.

KSA cyclonic filters are composed of vertical honeycomb


sections. Opening only at the top and bottom, they are
designed to force the air to swirl inside. The centrifugal
effect is significant and, above all, continuous – especially
in comparison to the action of traditional filters. Particles
are thus thrown against the honeycomb walls with much
higher force. KSA filters are 95% efficient on 10 µm
particles.

• Improved hygiene and fire safety thanks to less grease


deposits in the exhaust plenums and ducts.
• Lower maintenance costs due to lower cleaning Schlieren tests on a KSA filter

frequency.
• Improved noise levels thanks to limited pressure loss. 100

• A must for the use of UV-C Capture Ray™ technology. 90

• Unbeatable Efficiency/Pressure loss ratio. 80


Efficeincy [%] @ 690 m3/h & 120 Pa

70

60

KSA filters are accredited by the UL (Underwriter 50

Laboratories) as flame-retardant and have NSF (National 40

Sanitation Foundation) Hygienic and safety approval. They 30

20
are fitted on all hoods and ventilated ceilings. 10

0
1 2 3 4 5 6 7 8 9 10
Particle size [µm]

Tests carried out by VTT according to VDI 2052 (part 1) “Ventilation Equipment
for kitchens. Determination of Capture Efficiency of Aerosol Separators
in Kitchen Exhaust”

100

90

80
Efficeincy [%] @ 690 m3/h & 120 Pa

70

60

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Particle size [µm]

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

4
KVIF/1908/UK
Culinary and Human
Centric Light

© Halton
(Halton Skyline)
INDOOR ENVIRONMENT QUALITY (IEQ)
Close to sunlight render and increased lighting levels for a
better colour and texture render. Ideal working conditions.

SAFETY
The sensible areas of the kitchen benefit from a better light
for a better safety and quality control.

ECONOMIC ADVANTAGE
Drastic energy savings leading to reduced payback times.

The impact of lighting in professional kitchens has often safety of the staff and hygiene of the kitchen.
been regulated to simply satisfying illumination levels Halton Skyline is the first LED based lighting technology
without regard for personnel wellbeing. specifically developed for professional kitchens.
The link between good lighting, better working conditions Everyone agrees the light it provides is simply the
and productivity, is now widely recognized. However, closest possible to natural light.
what often occurs when a kitchen benefits from excellent
lighting levels, the staff is dazzled from reflected light.
When dazzling does not occur, the kitchen typically suffers
from a lack of illumination that is more harmful for the

T5 tubes Halton Skyline • Halton Skyline remarkably respects the food colour and
texture from raw ingredients to plated presentation. The
two spot models developed for Halton Skyline have
respectively a CRI of 83 (@4000K) and 95 (@2800K).

• Halton Skyline provides the best visual comfort, without


alteration over time and without dazzling the staff, thus
also playing an active role in the kitchen safety. Among
others, Halton Skyline’s shielding angle is up to two
times higher than DIN EN 12464-1(1) demand.

• Halton Skyline’s Human Centric version is a biodynamic


lighting centered on users needs. It creates daylight-
similar sequences depending on the kitchen activity,
further improving their working conditions and
Wellbeing. You would think you were outside!

• A state of the art lighting technology that, at its core,


saves significantly on energy and maintenance. With a
luminous efficacy of 120 lm/W, Halton Skyline
consumes up to 2,8 times less than fluorescent tubes.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

5
KVIF/1908/UK
Integrated low velocity
makeup air

© Halton
ENERGY EFFICIENCY
Contributes to the exhaust airflow rates reduction achieved
thanks to the Capture Jet™ technology.

INDOOR ENVIRONMENT QUALITY (IEQ)


Better working conditions and productivity thanks to a better
air quality, a draughts reduction, lower noise levels and a
positive impact on the perceived temperature.

Draughts have to be declared public enemy Low velocity makeup air from ceiling enhances both
number one. the kitchen ventilation efficiency and the comfort.
The heat and smoke generated by the cooking appliances
are extremely dispersible. When they rise up toward a
hood or a ventilated ceiling, they are left to their own and
are hence very sensitive to draughts. At a point that the
air displacement generated by one people walking close
by is high enough to disperse them as shown below on a
Schlieren test made on a hood which is not equipped with
the Capture Jet™ technology.

Hood Hood
°C

It enables the kitchen air to be renewed on the principle


1 2 of air displacement. Fresh air naturally drops to low level
In situation of total Capture, a “user” goes along s standard hood at a and fills the working area from that level. The absence of
normal pace (1). The draught generated is enough to disperse the thermal flow turbulences prevents this fresh air from mixing with
plumes and cause spillages (2).
convective flows from the cooking equipment.
“Mixing” diffusers are inadvisable. In addition, a comfort limit naturally appears in the
In narrow spaces like professional kitchens, mixing kitchen’s environment through stratification. Below this
diffusers indeed inevitably generate even stronger limit height i.e. above head level, air quality is optimal.
draughts, harmful for the staff comfort and for the
Low velocity makeup air from ceiling allows not only to
efficiency of hoods and ventilated ceilings.
improve the air quality inside the kitchen but also to
Ceiling diffusers improve the Capture and Containment efficiency of the
Hood Capture Jet™ hoods and ventilated ceilings. It leads to
energy savings thanks to a reduction of the exhaust
airflow rates.
Convective flows

Cooking bloc

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

6
Recommended combinations

KVIF/1908/UK
© Halton
M.A.R.V.E.L. Demand Controlled
Ventilation (MRV)

ENERGY EFFICIENCY
Up to 64% reduction in exhaust airflow rates in association with Capture Jets.
Reduces drastically the cooling/heating energy consumption and the energy use
of supply and extract fans.

INDOOR ENVIRONMENT QUALITY (IEQ)


Reduces noise and draughts through constantly modulating air flows to the
correct level to evacuate all vapours.

Built-in Fire Suppression


System (FSS)

SAFETY
The kitchen and the rest of the building are protected by fires being extinguished
at source. Plenums and exhaust connections are also protected from the spread
of fire.

ECONOMIC ADVANTAGE
Integration of the system in the factory to provide better respect for products and
to optimise costs.

Monitoring system of
duct networks (KGS)

SAFETY
Efficient and cost-effective prevention tool for hygiene and fire safety due to the
assessment of grease build-up in the ductwork.

ECONOMIC ADVANTAGE
Allows for cleaning of ducts only when really necessary and not in a programmed
and often unnecessary way. Maximum safety at minimum cost.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

7
Technical descriptions

KVIF/1908/UK
KVF KVI

© Halton
2 4 3 10 2 3 8

11
9
1

8 7

7 6 5 6 5 4

CODE DESCRIPTION CODE DESCRIPTION


1 Outer casing – visible parts in stainless steel AISI 304 7 Grease collection tray or drain tap
2 Exhaust air connection and adjustment damper 8 Personal supply air nozzles
3 Supply air connection and adjustment damper (type MSM) 9 Capture Jet™ fan
4 Halton Skyline LED light fitting 10 Option Capture Jet™ fan air inlet plenum
5 Capture Jet™ nozzles 11 Perforated front face
6 KSA cyclonic grease filters
2 5 4 3

9
STANDALONE HOOD AND ASSEMBLY OF MODULAR SECTIONS

10

8 7 6
KVF
Standalone

One open end

Two open ends

KVF assembly
One open end

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

8
KVIF/1908/UK
© Halton
KVI
Standalone

One open end

Two open ends

KVI assembly
One open end

QUICK SELECTION DATA

L (section L1 (active Recommended Exhaust air volume* Recommended Capture Jet air volume
length) length) make up air volume (with width = 1300)
l/s m 3/h H = 555 H = 400 l/s m 3/h
1600 1500 420 … 654 1515 … 2358 27 97
2100 2000 560 … 872 2020 ... 3144 200 l/s or 720 m 3/h 157 l/s or 565 m 3/h 31 112
per linear meter per linear meter
2600 2500 700 … 1090 2525 … 3930 35 127
of section of section
5100 5000 1400 … 2180 5050 … 7860 56 202
MSM 100% open MSM 100% open
7600 7500 2100 … 3270 7575 … 11790 DPst = 48 to 52 Pa DPst = 45 to 70 Pa 77 277
10100 10000 2800 … 4360 10100 … 15720 98 352
* Minimum at a T.A.B.TM reading of 59 Pa (505 m3/h or 140 l/s per filter)... maximum at a T.A.B.TM reading of 144 Pa (786 m3/h or 218 l/s per filter)

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

9
KVIF/1908/UK
KVF KVI

© Halton
555
555

555
1200..1900
1200..1900 1200..1900

400

555
400

400
555

555
400
400
400

400
400

400
250

50
205 250
50

205 250

N
O

N
N

M
315

M
M
P

315 170 315

L1 = 1000..3000
= 1100..3100
L1 = 1000..3000

L1 =L 1000..3000
L = 1100..3100

250 250
Q*
Q*

L1/2

M
P

P
M

M
N
N

N
O

450 450
205 205
50

450 205
50

DIMENSIONS WEIGHT (KVF, h=555 mm, kg)


Exhaust Supply Light
L/B 1100 1300 1500 1700 1900
1 Ø315 2 Ø315 3 Ø315 2Ø250 4 Ø250
L M N M, N O P Q 1100 86 91 97 107 113
1600 L1/2 325 - 450 - 720 1600 114 119 125 136 141
2100 L1/2 450 - 450 500 1320 2100 141 147 152 164 170
2600 - 450 L1/2, 450 450 500 1320 2600 169 174 180 193 199
3100 - 450 L1/2, 450 - 500 1320 3100 196 202 207 222 228

- A bove 3000 mm active, hoods are an assembly of separate sections to


make transportation and site handling easier.
- Number of exhaust and supply connections to be determined based on the
sections length and on the calculation of the exhaust airflow rates depending on
the cooking appliances.
- Other air supply possibilities of the Capture Jet fan and on request.
- Other connection configurations for exhaust and supply on request.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

10
Technical descriptions (KVF/I-M)

KVIF/1908/UK
KVF-M KVI-M

© Halton
10 3 4 2 4 10 3 3 2 3

8 8

11
9 9
11
1

6 6
1

8 5 7 7 4 6 5

CODE DESCRIPTION CODE DESCRIPTION


1 Outer casing – visible parts in stainless steel AISI 304 7 Grease collection tray or drain tap
2 Exhaust air connection and adjustment damper 8 Personal supply air nozzles
3 Supply air connection and adjustment damper (type MSM) 9 Capture Jet™ fan
4 Halton Skyline LED light fitting 10 Option Capture Jet™ fan air inlet plenum
5 Capture Jet™ nozzles 11 Perforated front face
6 KSA grease filter

STANDALONE HOOD AND ASSEMBLY OF MODULAR SECTIONS

3 5 2 5

11 11
10 3 4 2 4 10 3
KVF-M
Standalone

9 9
1
11
7

8 6 8 7
6
1
One open end
8 5 7 6

Two open ends

KVF-M assembly
One open end

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

11
KVIF/1908/UK
© Halton
KVI-M
Standalone

One open end

Two open ends

KVI-M assembly
One open end

QUICK SELECTION DATA

L (section L1 (active Recommended Exhaust air volume* Recommended Capture Jet air volume
length) length) make up air volume (with width = 1700)
l/s m 3/h H = 555 H = 400 l/s m 3/h
1600 1500 840 … 1308 3030 … 4716 200 l/s or 720 m 3/h 157 l/s or 565 m 3/h 44 158
2100 2000 1120 … 1744 4040 ... 6288 per linear meter per linear meter 52 188
2600 2500 1400 … 2180 5050 … 7860 of front face of front face 61 218
5100 5000 2800 … 4360 10100 … 15720 MSM 100% open MSM 100% open 102 368
DPst = 48 to 52 Pa DPst = 45 to 70 Pa
7600 7500 4200 … 6540 15150 … 23580 144 518
10100 10000 5600 … 8720 20200 … 31440 186 668
* Minimum at a T.A.B. TM reading of 50 Pa (505 m 3/h or 140 l/s per filter)... maximum at a T.A.B. TM reading of 120 Pa (786 m 3/h or 218 l/s per filter)

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

12
KVIF/1908/UK
KVF-M KVI-M

© Halton
555
555

555
W = 1700*..2800 WW
= 1700*..2800
= 1700*..2800

400
400

400
W = 1700*..2800 WW
= 1700*..2800
= 1700*..2800

205 205 2
50

50
O

O
N

N
N
M

M
M
P

P
170
L = 1100..3100

L = 1100..3100
L1 = 1000..3000
L1 = 1000..3000

L1 = 1000..3000
Q

Q
Q
O

O
N

N
P

P
455 175 455
455 175
175
50

50
* Light in the supply plenum from 1700 to 2100 mm

DIMENSIONS WEIGHT (KVF-M, h=555 mm, kg)


Exhaust Supply Light
L/B 1700 1900 2100 2200 2400 2600 2800
1 Ø315 2 Ø315 3 Ø315 2Ø250 4 Ø250
L M N M, N O P Q 1100 149 154 159 164 169 174 179
1600 L1/2 325 - 450 - 720 1600 200 205 210 215 220 225 230
2100 L1/2 450 - 450 500 1320 2100 251 256 261 266 271 276 281
2600 - 450 L1/2, 450 450 500 1320 2600 302 307 312 317 322 327 332
3100 - 450 L1/2, 450 - 500 1320 3100 353 358 363 368 373 378 383

- Number of exhaust and supply connections to be determined based on the


sections length and on the calculation of the exhaust airflow rates depend-
ing on the cooking appliances.
- Other air supply possibilities of the Capture Jet fan and on request.
- Other connection configurations for exhaust and supply on request.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

13
DPst DPst

KVIF/1908/UK
EXHAUST Pressure drop, sound data and airflow measurement

DPst = Exhaust section static pressure loss


DPTAB
DPTAB

© Halton
DPTAB = T.A.B. TM
pressure for airflow rate measurement
30,70,100 = Damper opening in %

Exhaust plenum
H=555 DPstst
DP DPst

DPTAB DPTAB
DPTAB

SECTION -1000 SECTION -1500

Section 1000 Static pressure loss and sound data Section 1500 Static pressure loss and sound data
DPst 30 30
300 300
70 70
DPst DPst
200 100 200 100

140 DPTAB 140


DPTAB 55 DPTAB
100 100 55

50
50
∆Pst ∆Pst
[Pa] [Pa]
50 45 50
45

40 LpA dB(A) 40
30 30
DPst LpA dB(A)
35
20 20 35

30
30
DPTAB 437 655
10 qv [l/s] 10 qv [l/s]
25 200 300 500
100 200 300 500
qv [m3/h] qv [m3/h]
500 1000 1572 1000 2000 2358
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

SECTION -2000 SECTION -2500


Section 2000 Static pressure loss and sound data Section 2500 Static pressure loss and sound data
30 30
300 300
70 70

200 100 200 100

140 140

100 100
55 55

∆Pst ∆Pst
50 50
[Pa] [Pa]
50 50
45 45

30 30
LpA dB(A)
40 40
LpA dB(A)
20 20
35 35

30 873 30 1092
10 qv [l/s] 10 qv [l/s]
200 300 500 1000 300 500 1000
3144 qv [m3/h] qv [m3/h]
1000 2000 3000 2000 3000 3930
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

14
KVIF/1908/UK
SECTION -3000
Section 3000 Static pressure loss and sound data
30
300
70

© Halton
200 100

140

100

55

∆Pst
[Pa] 50
50

45
30
LpA dB(A)
40
20
35

1310
10 qv [l/s]
500 1000
4716 qv [m3/h]
2000 3000 5000
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Exhaust airflow rate measurement with T.A.B.TM ports


Recommended pressure T.A.B.TM 50-120 Pa
200

00

00

00
00

00

20

25

30
10

15

Maximum
120 Value
Recommended
A)
KS

100
(1

DPTAB
m
0m

[Pa]
50

50

30 qv [l/s]
100 120 160 200 218 300 400 437 500 600 655 800 873 1092 1310 1600
qv [m3/h]
400 500 600 786 1000 1572 2000 2358 3144 3930 4716

Exhaust airflow rate measurement using k factors


KSA (Number of filters) k factor [m 3/h] k factor [l/s] With the T.A.B.TM pressure measurement, it is also possible
1 71,8 19,9 to check the exhaust airflow with the following formula:
2 143,5 39,9
qe = k x ÏwDPTAB [Pa]
3 215,2 59,8
4 287,0 79,7
5 358,8 99,7
6 430,5 119,6
" w.g. Pa
0.8 200
00

00

00
00

00

20

25

30
10

15

KVF/I
m

0.5 120 Capture Jet™ hood


m

Dp With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible
00

TAB 0.4 100


5
on

15
ti
ec
DPTAB

KVIF/1908/UK
EXHAUST Pressure drop, sound data and airflow measurement

Exhaust plenum
H=400

© Halton
DPst
DPst = Exhaust static pressure loss
DPTAB = T.A.B.TM pressure for airflow rate
DPTAB measurement
30,70,100 = Damper opening in %

Section 1000 Static pressure loss and sound data Section 1500 Static pressure loss and sound data
30 30
300 300 70
70 100
100 200
200
170 170

55 55
100 100

50 50

∆Pst ∆Pst
[Pa] 50 45 [Pa] 50 45

40 30 40
30

LpA dB(A) LpA dB(A)


20 35 20 35

30
437 655
10 qv [l/s] 10 qv [l/s]
100 200 300 500 200 300 500
qv [m3/h] qv [m3/h]
500 1000 1572 1000 2000 2358

∆Lr = 4 dB MAXIMUM AIRFLOW


RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Section 2000 Static pressure loss and sound data Section 2500 Static pressure loss and sound data
30 30
300 300
70
70 100
100
200 200
170 170

55

100 55 100 55

50 50
∆Pst ∆Pst
[Pa] 50 [Pa] 50
45 45

30 30
40 40
LpA dB(A) LpA dB(A)
20 20
35 35

30 873 10 1092
10 qv [l/s] qv [l/s]
200 300 500 300 500 1000
31441000
qv [m3/h] qv [m3/h]
1000 2000 3000 2000 3000 3930
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

16
KVIF/1908/UK
Section 3000 Static pressure loss and sound data
30
300
70
100

© Halton
200
170

55
100
55

∆Pst 50
[Pa] 50
45
30
40
LpA dB(A)
20
35

1310
10 qv [l/s]
500 1000 4716
qv [m3/h]
2000 3000 5000
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Exhaust airflow rate measurement with T.A.B.TM ports


Recommended pressure T.A.B.TM 50-120 Pa
200

00

00

00
00

00

20

25

30
10

15

Maximum
120 Value
Recommended
A)
KS

100
(1

DPTAB
m
0m

[Pa]
50

50

30 qv [l/s]
100 120 160 200 218 300 400 437 500 600 655 800 873 1092 1310 1600
qv [m3/h]
400 500 600 786 1000 1572 2000 2358 3144 3930 4716

Exhaust airflow rate measurement using k factors


KSA (Number of filters) k factor [m 3/h] k factor [l/s] With the T.A.B.TM pressure measurement, it is also
1 71,8 19,9 possible to check the exhaust airflow with the following
2 143,5 39,9
formula:
3 215,2 59,8
4 287,0 79,7 qe = k x ÏwDPTAB [Pa]
5 358,8 99,7
6 430,5 119,6

" w.g. Pa
0.8 200
0

00

00
00

00

0
20

25

30
10

15

KVF/I
mm

0.5 120 Capture Jet™ hood


Dp With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible
00

TAB 0.4 100


n5

17
tio
ec
KVIF/1908/UK
SUPPLY Pressure drop, sound data and airflow measurement

Supply plenum

© Halton
H=555
DPst DPst

DPst = Supply static pressure loss


DPTAB = T.A.B.TM pressure for airflow rate
DPTAB measurement DPTAB
10,50,100 = MSM module opening in %

DPst DPst
Section 1000 Static pressure loss and sound data Section 1500 Static pressure loss and sound data
10 50 10 50
300 300

DPTAB DPTAB
200 100 200 100

100 100 55
55
∆Pst ∆Pst
[Pa] 50 [Pa] 50

52 DPst 52 DPst
45 45

40 LpA dB(A) 40 LpA dB(A)


30 30
DPTAB DPTAB
35
200 35 300
20 qv [l/s] 20 qv [l/s]
100 200 300 200 300 500
qv [m3/h] qv [m3/h]
300 500 720 1000 500 1000 2000
1080
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Section 2000 Static pressure loss and sound data Section 2500 Static pressure loss and sound data
10 50 10 50
300 300

200 100 200 100

100 100
55
∆Pst ∆Pst 55
[Pa] [Pa]
50
50
52 48
45
45 LpA dB(A)
LpA dB(A)
30 30
40
40

35 500
20 qv [l/s] 20 qv [l/s]
200 300 400 500 300 1000
1800
qv [m3/h] qv [m3/h]
1000 1440 2000 1000 2000 3000
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

18
KVIF/1908/UK
Section 3000 Static pressure loss and sound data
300
10

© Halton
50
200
100

100

∆Pst
55
[Pa]

50
47
45

40 LpA dB(A)
30

35 600
20 qv [l/s]
300 500 1000
2160
qv [m3/h]
1000 2000 3000
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Supply airflow rate measurement with T.A.B.TM ports


Recommended pressure T.A.B.TM 35 Pa
100

00 00 00 00 00 00 00
50 10 15 20 25 30 40 50
Maximum
35 Value
30
Recommended
∆PTAB
[Pa] 20

10

5 qv [l/s]
100 120 140 160 180 200 300 400 500 600 700 800 1000 1200

qv [m3/h]
400 500 600 700 1000 1500 2000 3000 4000 5000
720 1080 1440 1800 2160 2880 3600

Supply airflow rate measurement using k factors Supply airflow rate measurement using MSM
With the T.A.B. TM
pressure measurement, it is also The supply airflow is balanced with MSM modules
cfm
possible to check
250 the
300supply airflow
400 with
500 the following
600 700 installed
1000 on each
1500 supply connection.
2000 2500 Therefore, it is
2900

formula: qs = k x ÏwDPTAB [Pa] also possible to check the supply airflow by adding up
the airflow of each MSM using the following formula.
L1 (Length of section) mm k factor [m 3/h] k factor [l/s]

1000 121,7 33,8 qs [l/s] = 51 x ÏwDPm [Pa]


1500 182,6 50,7
2000 243,4 67,6 qs [m3/h] = 183,6 x ÏwDPm [Pa]
2500 304,2 84,5
3000 365,1 101,4

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

19
DPst DPst

DPst

KVIF/1908/UK
SUPPLY Pressure drop, sound data and airflow
DPTAB
measurement DPTAB

DPTAB
DPst = Supply static pressure loss

© Halton
DPTAB = T.A.B.TM pressure for airflow rate measurement
10,50,100 = Damper opening in %

Supply plenum
H=400 DPst DPst DPst

DPTAB DPTAB
DPTAB

Section 1000 Static pressure loss and sound data Section 1500 Static pressure loss and sound data
10 10
200 200
DPst
50 50

100 100
100 100 DPTAB
55
50

∆Pst ∆Pst 50
45
[Pa] 58 [Pa]

40 50 45
46
LpA dB(A)
LpA dB(A)
35
40
30 30
30
35
157 235
20 qv [l/s] 20 qv [l/s]
100 565 200 200 848 300
qv [m3/h] qv [m3/h]
300 500 500 1000
∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED ∆Lr = 4 dB MAXIMUM AIRFLOW
RECOMMENDED

Section 2000 Static pressure loss and sound data Section 2500 Static pressure loss and sound data
10 10
200
200
50
50
100
100

55
100 55
100
10 50
300 50
68 100 70 50
∆Pst ∆Pst 10 50
[Pa] [Pa] 300
200 100
50 45
45
50
200
40 LpA dB(A)
55 40
30
100
30
∆Pst 50
35 100
[Pa] 35 55392
314
20 45 qv [l/s] qv [l/s]
∆Pst
200 300 400
LpA dB(A) 20 200 300 500
[Pa] 50
50 qv [m3/h] qv [m3/h]
40
600 1000 1130 1600 1000 1412
LpA dB(A)
MAXIMUM AIRFLOW 50 45 MAXIMUM AIRFLOW
∆Lr = 4 dB 35 RECOMMENDED ∆Lr = 4 dB RECOMMENDED

30 38
30 40
146 30
20 qv [l/s]

KVF/I 300
Capture Jet™
100 525hood 200 300
qv [m/3/h]
With (F) or without (I) makeup air on the front
500 1000
M.A.R.V.E.L. compatible
20
35
219
qv [l/s]
10 50 200 300 500
300
∆Lr = 4 dB MAXIMUM AIRFLOW qv [m3/h]
RECOMMENDED 100 20
500 788 1000 2000
KVIF/1908/UK
Section 3000 Static pressure loss and sound data
10 50
200

© Halton
100

100

55
∆Pst
[Pa] 50
50
45
45
LpA dB(A)
40
30

35
471
20 qv [l/s]
300 500
qv [m3/h]
1000 1695 2000
MAXIMUM AIRFLOW
RECOMMENDED

Supply airflow rate measurement with T.A.B.TM ports


Recommended pressure T.A.B.TM 35 Pa

100

00 00 00 00 00
10 15 20 25 30
10 50
300
50 100
Maximum
35
200 Value
30 Recommended

20
∆PTAB 100
[Pa]
∆Pst
[Pa] 55
10
50
50
45
40
5 LpA dB(A) 157 235 314 392 471
qv [l/s]
70 80 90 40
100 120 140 160 180 200 300 400 500 600 700 800
30
qv [m3/h]
260 30035 400 500 600 700 1000 1500 2000 3000
438 565 848 1130 1412 1695
20 qv [l/s]
300 500 1000
qv [m3/h]
1000 1575 2000 3000
Supply airflow
∆Lr = 4 dBrate measurement using k factors
MAXIMUM AIRFLOW
RECOMMENDED
Supply airflow rate measurement using MSM
With the T.A.B. TM
pressure measurement, it is also The supply airflow is balanced with MSM modules
possible to check the supply airflow with the following installed on each supply connection. Therefore, it is
formula: qs = k x ÏwDPTAB [Pa] also possible to check the supply airflow by adding up
100
the airflow of each MSM using the following formula.
0 00 00 00 00
L1 (Length of section) mm k factor [m 3/h] 00
k factor [l/s]
1 15 20 25 30
1000 95,5 26,5 qs [l/s] = 51 x ÏwDPm [Pa]
1500 50 143,3 39,7
2000 191,0 53,1 qs [m3/h] = 183,6 x ÏwDPm [Pa]
35
2500 238,7 66,3
30
3000 286,5 79,6

20
∆PTAB
[Pa]

KVF/I 10 Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

21
156 238 303 380 478
5 qv [l/s]
Specifications

KVIF/1908/UK
KVF / KVI Hood • Any modification of the hood installation height together

© Halton
The hood shall be Halton Brand, KVIF range. This hood type with the input power, type and dimensions of the cooking
is equipped with the Capture Jet™. The models shall be appliances shall be brought to the attention of the
according to the projected exhaust devices list. KVI is the manufacturer as they all significantly impact the exhaust
exhaust only type model when the KVF is equipped with an airflow rates.
integrated makeup air system on the front. • The makeup air design, especially the diffuser type, size,
location and the balance between exhaust and supply, shall
The hood shall be supplied completed and ready to be be entrusted to the hood manufacturer as it also impacts the
installed with all embedded technologies fully pre-wired exhaust airflow rates and capture efficiency. It is also key to
from the factory. The following specifications shall be fully preventing cross-contamination between the kitchen areas.
observed.
Exhaust plenum
Hood outer casing • The exhaust plenum shall be constructed from 1.0 mm
• Constructed from 1.0 mm AISI 304 stainless-steel in a AISI 304 stainless steel in a brushed satin finish. The lower
brushed satin finish. The joints of the lower edges shall be part of the sides shall be welded for a durable tightness
fully welded for better robustness, cleanability and a better against condensates. All exposed welds are ground and
aesthetic. All exposed welds are ground and polished to the polished to the metal’s original finish. Its bottom edge shall
metal’s original finish. be aerodynamically designed (no flat surface) thus helping the
• Hood sides shall be of double-wall construction to enable smoke and steam to freely rise toward the exhaust plenum,
the air supply of the side Capture Jets while reducing the preventing steam spillage or stagnation leading to harmful
condensation risk on the internal face. dripping of condensation.
• It shall be equipped with KSA multi-cyclone grease filters,
Capture Jet™ technology constructed from stainless steel. Their efficiency shall be at
• The hood shall be equipped with the Capture Jet™ least 95% on 10 microns particles or larger, as tested by an
technology. Based on the use of two sets of nozzles on the independent laboratory. The filters shall also be NSF and UL
lower part of both the front fascia and sides, the Capture Jets classified. Baffle or slot type filters shall not be used.
improve the hood capture and containment efficiency. The • The exhaust connections shall be supplied with sliding
exhaust airflow rates are thus reduced by up to 30 to 40% balancing dampers. The exhaust plenum shall be equipped
to remove the same heat load compared to the traditional with T.A.B.™ pressure tap for quick airflow measurement.
hoods, thus leading to huge energy savings.
• The air used for the Capture Jets shall not represent more [Option] Integrated makeup air (KVF)
than 5% of the calculated exhaust airflow and the airspeed at • To improve the staff comfort but also to optimise the
nozzles outlet shall be a minimum of 8 m/s. Slot- or grille-type capture and containment efficiency of the hoods (thus
discharge shall not be used. contributing to the exhaust airflow rates reduction), the
• The hood shall be supplied with an integrated fan to provide makeup air shall be introduced into space from the hood front
the required airflow and static pressure for the Capture fascia and at a very low velocity (less than 0.5 m/s).
Jet™ nozzles operation. A specific duct is thus not required • The hood shall be equipped with a perforated stainless-
whatever the model, unless contrary specification of a local steel front panel, combined with a honeycomb structure on
code. the back. This draught free diffusion complex shall be easy to
remove for cleaning and maintenance operations. The internal
Exhaust and supply airflow rates face of the supply plenum shall be insulated to avoid any risk
• The exhaust airflow rates shall be determined with an EN of condensation on the hood containment volume side.
16282-1(1) based calculation method. Hence, they shall be • The supply connections shall be supplied with MSM
calculated based on the convective loads released by the balancing dampers. The supply plenum shall be equipped with
cooking appliances, whether the loads are characterised by T.A.B.™ pressure tap for quick airflow measurement.
the standard, the manufacturer or third parties’ tests, and
the installation configuration of the hood(s). The method [Option] M.A.R.V.E.L. Demand Controlled Ventilation
shall, also, in addition, consider the hood capture efficiency • The hood shall be equipped with M.A.R.V.E.L. Demand
according to ASTM 1704-12 standard. Both the exhaust Controlled Ventilation system to automatically adjust, in real
airflow rates and capture efficiency shall be justified by a time, the exhaust airflow rates and this, hood section per
calculation note. hood section, in an independent manner and depending on
the real cooking activity.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

22
KVIF/1908/UK
• To that purpose, each hood section shall be equipped with •  [Option] A specific DALI user interfaces with an advanced
one or several IRIS Infrared Radiation Index Sensor(s). They scenario and zoning functions, equipped with an LCD screen,
are used to scan the cooking appliances’ surface and monitor shall be used to control the light fittings installed both in

© Halton
real-time variations in cooking activity. the hoods and/or ventilated ceilings and in the rest of the
• The reliability and sharpness of the airflow adjustment are kitchens and related areas. Check the additional lighting
reinforced by temperature sensors installed in each hood requirements described in the present document.
exhaust plenum. An additional room temperature sensor
installed in the kitchen provides the required reference to the [Option] Fire Suppression System
plenum temperature sensors. • The fire extinguishing system shall be from Ansul®
• Each hood section is also equipped with an ABD damper R-102™ type and be pre-installed from the factory for better
used for real-time exhaust airflow adjustment. integration, at least for the plenum and exhaust connection(s)
• All hood section specific components are connected to a protection. The detection chain and fusible link(s) shall be fully
hood controller. This controller shall have the ability to make integrated inside the exhaust plenum to not be visible at all.
the hood section behave in a totally independent manner • The cooking appliances nozzles shall, as much as possible,
while communicating with all the other sections. These drop from the hood roof, without horizontal pipes visible
communication capabilities are a must for an efficient and inside the containment volume of the hood.
required adjustment of the fan(s) speed. • The site complementary installation shall be carried out
• M.A.R.V.E.L. system shall be controlled by a tactile LCD by the hood manufacturer or a certified partner. In all cases,
screen. It shall allow a fast and simple use of the systems, it shall be an authorised representative of Ansul and the
even by non-professional personnel. installation shall comply with UL 300 requirements and local
•  [Option] The LCD screen shall also manage all the other codes.
technologies delivered by the manufacturer as part of the
kitchen ventilation system. Check the additional requirements
specific to these technologies. (1) The European Standards published by CEN are developed by experts,
established by consensus and adopted by the Members of CEN. It is important
• The additional requirements specific to M.A.R.V.E.L., to note that the use of standards is voluntary, and so there is no legal
especially concerning the balance between exhaust and obligation to apply them (source: CEN).
supply together with the fan’s speed control, will also be
observed.

Halton Skyline light fitting


• Each hood shall be equipped with Halton Skyline Culinary
Light. Constructed from stainless steel, the light fitting
comprises flush-mounted broad beam spots with a diffusion
angle of at least 80°. Each spot is composed of a patented
mixing chamber and a specific reflector. Both shall provide a
good balance between direct and diffuse light components
without dazzling the staff. Especially, the shielding angle shall
exceed DIN 12464-1 requirement and be at least 30°.
• The illuminance on the working surfaces shall be 750 lx with
a CRI Colour Rendering Index of at least 83.
• The LEDs lifetime shall be 50,000 hours. The power supplies
shall have at least the same lifetime and be DALI compatible.
They shall enable switching on/off or dim the light (0-100%)
with one or several switches.
•  [Option] The power supplies shall also have a Constant
Light Output feature, adjusting the output to keep the 750-lx
illuminance required over LEDs lifetime.
•  [Option] A specific DALI user interface with a simple
scenario and zoning functions shall be used to control the
light fittings installed in the hoods and/or ventilated ceilings
and – if applicable – in the rest of the kitchen. Check the
additional lighting requirements described in the present
document.

KVF/I Capture Jet™ hood


With (F) or without (I) makeup air on the front / M.A.R.V.E.L. compatible

23
KVIF/1908/UK
© Halton
www.halton.com/foodservice

Halton Manufacturing Facilities

France Germany United Kingdom


Halton Foodservice Halton Foodservice Halton Foodservice
Zone Technoparc Futura Tiroler Str. 60 11 Laker Road
CS 80102 83242 Reit im Winkl Airport Industrial Estate
62402 Béthune Cedex Tel. +49 8640 8080 Rochester, Kent ME1 3QX
Tel. +33 (0)1 80 51 64 00 Fax +49 8640 80888 Tel. +44 1634 666 111
Fax +33 (0)3 21 64 55 10 info.de@halton.com Fax +44 1634 666 333
foodservice@halton.fr www.halton.de foodservice.uk@halton.com
www.halton.fr www.halton.com

USA Canada Brazil


Halton Halton Indoor Climate Systems Halton Refrin
101 Industrial Drive 1021 Brevik Place Rua Antonio de Napoli
Scottsville, KY 42164 Mississauga, Ontario 539 Parada de Taipas
Tel. +1 270 2375600 L4W 3R7 CEP 02987-030
Fax + 1 270 2375700 Tel. + 905 624 0301 São Paulo - SP
sales.us@halton.com Fax + 905 624 5547 Tel. +55 11 3942 7090
www.halton.com sales.ca@halton.com vendas@haltonrefrin.com.br
www.halton.com www.haltonrefrin.com.br

Asia Pacific China


Halton Group Asia Sdn Bhd Halton Ventilation
PT 26064 浩盾通风设备(上海)有限公司
Persiaran Teknologi Subang Room 701, No.2277 Longyang Road,
Subang Hi-Tech Industrial Park Pudong New District
47500 Subang Jaya, Selangor 201204 Shanghai
Tel. +60 3 5622 8800 Tel. +86 (0)21 6887 4388
Fax +60 3 5622 8888 Fax +86 (0)21 6887 4568
sales@halton.com.my halton.cn@halton.com
www.halton.com www.halton.cn

Halton has a policy of continuous product development, therefore we reserve the right to modify design and specifications without
notice. For more information, please contact your nearest Halton agency.
All rights reserved. No part of this publication may be reproduced, distributed, or transmitted in any form or by any means, including
photocopying, recording, or other electronic or mechanical methods, without the prior written permission of the publisher, except in the
case of brief quotations embodied in critical reviews and certain other non commercial uses permitted by copyright law.