200MM Ø HUME PIPE

FOR ELEC. CABLE 100MM Ø HUME PIPE


FOR LV CABLE

450x450x500 MM
P/R1

G
DEEP MAIN HOLE P/B4 P/R5
P/B2
P/R2

G
2000X500mm
ELEC.PANEL

D
TOILET TOILET TOILET
2000 X 2400 1715 X 2400
P/Y2 G
P/Y6 P/Y5
WIDE P/B1
P/R1 P/R1 P/R1
BH
LIFT PASS- P/B1
1815X1975 AGE
LIFT

D
Cassette AC
2000X2750 2000X500mm Cassette AC
P/Y5

D
BH
(15 PERSONS)
DG.PANEL
CABLE RISER

G
300x300x500 MM

B5
1000x405MM

P/
DEEP MAIN HOLE
CUTOUT FOR MV
600x405MM
ROOM ROOM CUTOUT FOR LV LPDB PDB
3800 X 2975 3800 X 2975 3800 X 2975 TOILET
3510 X 3825

R6
P/
R3

R3
P/

P/

150MM WIDE CABLE TRAY MULTIPURPOSE 150MM WIDE CABLE TRAY


HALL
13185 X 13210
P/Y6
Y3
P/

ROOM ROOM

D
3800 X 2975 3800 X 2975
1800 WIDE P/Y1 P/B1
COVERED SERVICE P/Y1 P/Y1
BALCONY 5835 X 7605 P/B1
Cassette AC Cassette AC
TOILET TOILET TOILET
1600 X 2400 1600 X 2400 1715 X 2400

D
P/Y4
G

G
P/B3 P/R4

P/Y1 P/R5

ISSUES
NO. DATE BY DESCRIPTION PRINTS
01 20-01-2023 PC GFC DRAWING -------

ELECT.LEGENDS
L-DB- GROUND FLOOR PDB- GROUND FLOOR
SYM. DESCRIPTION HEAGHT TYPE:-2+8 WAY TPN DB
TYPE:-2+6 WAY TPN DB
INCOMING :- .40A FP MCB INCOMING :- .40A FP MCB REVISIONS
6A ONE WAY SWITCH BOARD 1050MM AFFL.
SUBMAIN SIZE:-4X10Sq mm (CU) CABLE+2X10 Sq mm(E) SUBMAIN SIZE:-4X16Sq mm (CU) CABLE+2X10 Sq mm(E) No. DATE

EACH PHASE WITH 40A DP ELCB (100 mA) AS INCOMER EACH PHASE WITH 40A DP ELCB (100 mA) AS INCOMER
6A TWO WAY SWITCH BOARD 1050MM AFFL.
OUTGOING:- OUTGOING:-
NO OF LOAD IN MCB WIRE NO OF LOAD IN MCB WIRE
20W LED WALL TUBE LIGHT 2100MM AFFL. CKT NO. LOCATION CKT NO. LOCATION
POINT WATT RATING SIZE POINT WATT RATING SIZE
L/R1 16 680 ROOM FOR DISABLED 10 A 2X1.5+1X1.5 P/R1 04 600 ROOM & OFFICE (AC) 10 A 2X1.5+1X1.5
10W LED MIRROR LIGHT ABOVE MIRROR L/R2 14 600 ROOM & LOUNDGE 10 A 2X1.5+1X1.5 P/R2 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4
L/R3 14 170 ROOM & LOUNDGE 10 A 2X1.5+1X1.5 P/R3 02 1000 LAUNDRY (P) 16 A 2X2.5+1X2.5
20W LED CEILING LIGHT CEILING GFC DRAWING
L/R4 16 240 STAIRCASE-2 10 A 2X1.5+1X1.5 P/R4 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4
Project :
R5 - - SPARE - P/R5 02 1000 MULTIPURPOSE HALL (P) 16 A 2X2.5+1X2.5 J.K. LAKSHMIPAT
CEILING FAN (1400Ø) SWEEP CEILING - - - P/R6 01 TOILET (P) 2X2.5+1X2.5
R6 SPARE 500 16 A UNIVERSITY, JAIPUR
R PHASE LOAD= 1690 W R7 - - SPARE -
L/Y1 - - - Client:
12W LED CEILING LIGHT 13 660 ROOM & OFFICE 10 A 2X1.5+1X1.5 R8 SPARE
CEILING
L/Y2 06 115 STORE & PANTRY 10 A 2X1.5+1X1.5 R PHASE LOAD= 6100 W
15W LED CEILING LIGHT CEILING L/Y3 16 240 STAIRCASE-1 P/Y1 04 600 ROOM & LOUNDGE (AC) 10 A 2X1.5+1X1.5 Architects:

L/Y4 08 120 STAIRCASE-1 P/Y2 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4


6A SOCKET WITH SWITCH(ROOM) 300MM AFFL. Malhotra & Associates
Y5 - - SPARE - P/Y3 01 500 LAUNDRY (P) 16 A 2X4.0+1X2.5
Y6 - - - P/Y4 01 1500 TOILET (GEYSER) 2X4.0+1X4 Architects - Engineers - Interiors Designers
BH BULK HEAD LIGHT CEILING SPARE 20 A
Y PHASE LOAD= 1135 W P/Y5 02 1000 DRINKING WATER (P) 16 A 2X4.0+1X2.5 IInd floor,
C-86B, Nand Kishor Pareek Marg
DATA OUTLET 300MM AFFL. L/B1 16 680 ROOM 10 A 2X1.5+1X1.5 P/Y6 02 1000 LOUNGE & OFFICE (P) 16 A 2X4.0+1X2.5 J.L.N. Marg, Bapu Nagar, Jaipur
L/B2 Y7 - - - Ph: 0141-2700661,2706431
16 300 MULTIPURPOSE HALL 10 A 2X1.5+1X1.5 SPARE
TELEPHONE OUTLET 300MM AFFL. email:ashokar_malhotra@yahoo.com
L/B3 06 120 MULTIPURPOSE HALL 10 A 2X1.5+1X1.5 Y8 - - SPARE - MEP CONSULTANTS:

6A SOCKET WITH SWITCH 300MM AFFL. L/B4 16 240 STAIRCASE-2 Y PHASE LOAD= 6100 W PARADISE CONSULTANTS
Plot No. 129, Basement, Pocket 2
B5 - - SPARE - P/B1 04 600 MULTIPURPOSE HALL (AC) 10 A 2X1.5+1X1.5 Near Sanjivani Hospital, Jasola Vihar
CONDUIT LEGEND:- 6A SOCKET FOR AC 2650MM AFFL. B6 - - SPARE - P/B2 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4 New Delhi - 110025
Landline : +91-11-46132800, 41030619
G B PHASE LOAD= 1340 W P/B3 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4 E-mail: paradiseconsultants@gmail.com
16A SOCKET FOR GEYSER 2400MM AFFL.
TOTAL LOAD= 4165 W MAX DEMAND= 2.91 KW L/B4 01 500 ELECTRICAL ROOM (P) 16 A 2X2.5+1X2.5 DRAWING TITLE :
S.NO. SYMBOL DESCRIPTION SIZE OF CONDUIT
16A SOCKET WITH SWITCH 300MM AFFL. P/B5 01 1500 TOILET (GEYSER) 20 A 2X4.0+1X4 HOSTEL BLOCK
GROUND FLOOR PLAN
1. MV MV MV LIGHT CONDUIT 20mmØ H.D B6 - - SPARE - POWER CONDUIT LAYOUT
16A SOCKET FOR HANDRAYER 1050MM AFFL. - -
2. MV MV MV LIGHT CONDUIT 25mmØ B7 SPARE - scale : 1:75 (A1) drawn by : SR
date : 20/01/2023 checked by : ATIQ
B8 - - SPARE -
3. P P P P POWER CONDUIT 25mmØ DISTRIBUTION BOARD 1500MM AFFL. project no : - - - - - - approved by : NAFEES
B PHASE LOAD= 5600 W drawing no :
4. TEL TEL TEL TELEPHONE CONDUIT 25mmØ EL/PC/JK-HOS-101a
32Amp.4P 3PHASE ISOLATOR NEAR VRF UNIT TOTAL LOAD= 17800 W MAX DEMAND= 12.46 KW
REVISION R0